AGS0260D: Diesel Generator Set 250/275 kVA
AGS0260D: Diesel Generator Set 250/275 kVA
Engine Data
Genset Rating
Crankcase made of gray cast iron
Prime Power (PRP)1 250 kVA / 200 kWe
Closed crankcase ventilation
Limited Time Power (LTP)2 275 kVA
Piston cooling with oil spray nozzle
Power Factor (cos phi) 0.8 pf
Dropforged crankshaft
Nominal Voltage 400 V / 230 V
Steel camshaft
Nominal Current 361 A
Dropforged connecting rod shanks
Frequency 50 Hz
Speed 1 500 min-1
Electronically controlled high-pressure injection system with single
injection pumps
Load Acceptance approx. 60 %
Hand primer for first fill and ventilation (low-pressure system)
Forced feed lubrication and piston cooling
Lube oil filter
Lube oil cooler
Fuel Consumption and Fuel Tank Capacity 3
All servicing points on one side
Without engine alternator
Fuel Consumption at 100 % Load 49.9 l/h 200 g/kWh
75 % Load 39.9 l/h 213 g/kWh
50 % Load 28.7 l/h 229 g/kWh
25 % Load 14.6 l/h 233 g/kWh Manufacturer DEUTZ
Capacity of base frame fuel tank Type TCD 2013 L06 4V
(Open Set) 240 l Gross Output (PRP/LTP) 227 kW / 250 kW
Capacity of base frame fuel tank Speed 1 500 min-1
(Sound Proof) 240 l
No. of cylinders / Configuration 6 / in-line
Bore / Stroke 108 mm / 130 mm
Displacement 7.15 l
Compression ratio 17 : 1
Weight incl. cooling system approx. 954 kg
Injection system Common-Rail- fuel injec-
Noise Emission (Sound Proof)4 tion system
Standard of cooling system water
Sound pressure LPA @ 7 m approx. 70 dB(A) Flywheel housing SAE 2
Flywheel connection -
Aspiration turbo charged with charge
air cooler
Govenor type electronic
Average piston speed 6.5 m/s
Brake mean effective pressure 28 bar
Noise Emission (Open Set) 4
Electric starter 24 V / 5 kW
Sound power level LWA 112.1 dB(A) Exhaust emission standard EU Stage2 (COM 2)
Sound pressure LPA @ 1 m 97.6 dB(A)
Manufacturer Aggretech
Type ACG0250-4-400
Lubrication System Output (PRP) 250 kVA
Voltage control electronic, self- regulating,
Oil capacity (sump) min. / max. 24 l +/- 1%
Lube oil consumption (in % of fuel cons.) 2 Short circuit capability 3 x Nominal current
Oil pressure min. (Warning) 1.50 bar AC wavefactor total harmonic distorsion <2%
Oil pressure min. (Shut-down) 1.35 bar No. of poles 4
Max. oil temperature 130 C Radio interference EN 55011 Class B, Group 1
Efficiency at cos phi 0.8 / 1.0
100 % Load 0.926 / 0.950
75 % Load 0.926 / -
50 % Load 0.916 / -
Cooling System 25 % Load 0.870 / -
Mechanical protection (IP class) IP 23
Voltage of water jacket heater 230 V Insulation class H
Output of water jacket heater 1.2 kW Cooling air volume 2 322 m3/h
Preheating temperature min. / max. 32 C / 70 C Moment of inertia 2.433 kgm2
Max. ambient temperature 54 C Weight approx. 735 kg
Antifreezing compound for radiator to -25 C
Fan power 11.6 kW
Cooling air flow 16 200 m3/h
Max. air pressure loss approx. 1.5 mbar
Max. permanent flow resistance
(cooling system and piping) 0.33 bar
Dimensions of cooling system approx. B 708 x H 907 mm
Max. coolant temperature (at engine outlet
in front of cooling equipment) 103 C
Max. coolant temp. after engine (Alarm) 108 C
Max. coolant temp. after engine (Stop) 110 C
Coolant flow rate 14.7 m3/h
Coolant pump inlet pressure min. 0.3 bar
Exhaust System
Quality Standards:
Exhaust gas flow 2 547 m3/h VDE 0530, DIN 6280, ISO 8528, IEC 34, BS 4999, BS 5000, BS 5514
Exhaust gas temp. after turbocharger 530 C Performance figures according to ISO standard ambient conditions as follows:
Exhaust back pressure max. 50 mbar ambient temperature 25 C, 100 m above sea level, rel. humidity 30 %;
We reserve the right to change specifications without notice.
Legend:
1
PRP (Prime Power) is the variable load with an average load factor < 75%. 10% overload
capabilty for governing purposes for 1 hour in every 12 hours.
Heat Rejection PRP according to ISO 8528. 10% overload capability according to ISO 3046, AS 2789;
DIN 6271 and BS 5514.
Heat rejection to coolant approx. 122.3 kW 2
LTP (Limited Time Power) is limited to 300 hours annual usage with an average load factor
Heat rejection to charge air cooler approx. 48.0 kW < 75%. No overload is permitted on Limited Time Power. LTP according to ISO 8528.
Engine radiation and convection approx. 25.0 kW 3
Fuel consumption according to Deutz datasheet.
Heat rejection of alternator approx. 15.9 kW 4
At 75% load, according to EU guideline 2000/14/EG
Diesel Generator Set
Type AGS0260D
250/275 kVA
1130
3820 1100
1922
2112
2004
2960 1060
156 2672 708
907
1770
195
350
990
120
2960 230.5
Weights refer to the dry weights and represent a set with standard features. Accesso-
ries and loose parts are not accounted. Drawings are for illustrative purposes only and
might include special accessories.
We reserve the right to change specifications without notice.
A 3 / AGS0260D 27/06/2011 E