0% found this document useful (0 votes)
485 views

Generator Protection Relay VAMP 210i

This document provides specifications for a generator protection relay and the generator it protects. It lists the current transformer and voltage transformer scaling values. It then lists the nameplate ratings for the generator, including its power output, direction of rotation, duty, voltage, weight, current, and other parameters. The remainder of the document outlines the pickup and time delay settings for the various stages of the protection relay, including overcurrent, reverse power, underfrequency, overvoltage, and others.

Uploaded by

Yandri Paulus
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
485 views

Generator Protection Relay VAMP 210i

This document provides specifications for a generator protection relay and the generator it protects. It lists the current transformer and voltage transformer scaling values. It then lists the nameplate ratings for the generator, including its power output, direction of rotation, duty, voltage, weight, current, and other parameters. The remainder of the document outlines the pickup and time delay settings for the various stages of the protection relay, including overcurrent, reverse power, underfrequency, overvoltage, and others.

Uploaded by

Yandri Paulus
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 3

Generator Protection Relay VAMP 210i

PLTMG Balai Pungut


Scaling
CT
CT primary 1000A
CT secondary 1A
Nominal input 1A
VT
VT primary 15000 V
VT secondary 110 V

Generator Ratings
Output 20798 kVA
Direction of rotation(Facing drive end) CCW
Duty S1
Voltage 15000 V
Weight 57000 kg
Current 801 A
Inertia 12000 kgm^2
Power factor 0,80
Protection by enclosure IP23
Frequency 50 Hz
Cooling method IC0A1
Speed 500 rpm
Mounting arrangement IM7303
Overspeed 600 rpm

Overcurrent Stage I> 50/51


Pick up setting 897 A
Pick up setting 1.12 xIgn
Delay curve family IEC
Delay Type NI
Inv. Time coefficient k 0.20
Inverse delay (20x) 0.45 s
Inverse delay (4x) 0.99 s
Inverse delay (1x) 141.07 s

Overcurrent Stage I>> 50/51


Pick up setting 2001 A
Pick up setting 2.50 xIgn
Operation delay 0.60 s

Reverse Power Stage P< 32


Pick up setting -682 kW
Pick up setting -4.0 %Pm
Operation delay 2.0 s

UnderExcitation Stage Q< 40


Q1 limit in P=0% -6240 kvar
Q1 limit in P=0% -30 %Sgn
Q2 limit in P=80% -6240 kvar
Q2 limit in P=80% -30 %Sgn
Operation delay 2.00 s
Release delay 0.50 s

Unbalance Stage I2> 46


Pick Up setting K2 8%
Delay type INV
Operation delay 10.0 s
Inverse delay K1 20 s

Earth Fault Stage I> 50/51 N


Pick up setting 2A
Pick up setting 0.040 pu
Delay curve family DT
Delay Type DT
Operation delay 1.0 s
Inverse delay (20x) -
Inverse delay (4x) -
Inverse delay (1x) -

Earth Fault Stage I>> 50/51 N


Pick up setting 3A
Pick up setting 0.06 pu
Operation delay 0.60 s

Overvoltage Stage U> 59


Pick up setting 15750 V
Pick up setting 105 %Ugn
Operation delay 30.0 s
Release relay 0.06 s
Hysteresis 3.0 %

Overvoltage Stage U>> 59


Pick up setting 16800 V
Pick up setting 112 %Ugn
Operation delay 4.0 s
Hysteresis 3.0 %
Overvoltage Stage U>>> 59
Pick up setting 21000 V
Pick up setting 140 %Ugn
Operation delay 2.0 s
Hysteresis 3.0 %

Undervoltage Stage U1< 27


Pick up setting 95 %Ugn
Operating delay 30.0 s
Low voltage blocking 40 %Ugn
Block time by U<1% 10.0 s

Undervoltage Stage U1< 27


Pick up setting 88 %Ugn
Operating delay 20.0 s
Low voltage blocking 40 %Ugn
Block time by U<1% 10.0 s

Zero Seq. Voltage stage Uo> 59N


Pick up setting 10 %
Operating delay 2.0 s

Zero Seq. Voltage stage Uo>> 59N


Pick up setting 20 %
Operating delay 1.2 s

Frequency Stage fX 81
Pick up setting 51 Hz
Operating delay 30.0 s
Low voltage blocking 85 %Ugn

Frequency Stage fXX 81


Pick up setting 55 Hz
Operating delay 4.0 s
Low voltage blocking 85 %Ugn

UnderFrequency Stage fX 81L


Pick up setting 49 Hz
Operating delay 30.0 s
Low voltage blocking 85 %Ugn

UnderFrequency Stage fXX 81L


Pick up setting 47.5 Hz
Operating delay 4.0 s
Low voltage blocking 85 %Ugn