Electrical Notes
Electrical Notes
1. ALL ELECTRICAL INSTALLATION WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH THESE PLANS
& SPECS, AND THE APPLICABLE PROVISIONS OF THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL
CODE, ITS RULES & REGULATIONS, OF THE LOCAL ENFORCING AUTHORITY & THE REQUIREMENTS OF
THE LOCAL POWER COMPANY. THE ELECTRICAL WORK SHALL BE UNDER THE IMMEDIATE
SUPERVISION OF A DULY LICENSED PROFESSIONAL ELECTRICAL ENGINEER.
2. THE ELECTRICAL SERVICE VOLTAGE SHALL BE 2 WIRES,
3. THE ELECTRICAL WIRING INSTALLATION SHALL BE DONE IN PVC PIPES. IF NOT INDICATED OR
SPECIFIED, IT SHALL BE DONE AS
a) SERVICE ENTRANCE RIGID STEEL COUNDUIT (RSC) OR INTERMEDIATE METTALIC CONDUIT
(IMC).
b) UNDERGROUND & EMBEDDED IN CONCRETE SLAB & WALLS PVC CONDUITS OR PE
PIPESSCHEDULE 40. FLEXIBLE CONDUITS SHALL BE USED WHERE REQUIRED.
4. ALL WIRES SHALL BE COPPER & THERMOPLASTIC HEAT AND WATER RESISTANT INSULATED TYPE
THW UNLESS OTHERWISE INDICATED. USE PHELPS DODGE OR COLUMBIA BRAND.
5. THE CONTRACTOR SHALL VERIFY & ORIENT THE ACTUAL LOCATION OF SERVICE ENTRANCE FOR
CONNECTION TO THE POWER SUPPLY.
6. ALL SERVICE ENTRANCE EQUIPMENT, SWITCHES, PANELBOARDS, LIGHTNING FIXTURES & ALL NON-
CURRENT CARRYING METAL PARTS SHALL BE PROPERLY GROUNDED.
7. ALL FEEDERS & BRANCH CIRCUIT HOMERUNS SHALL BE INSTALLED AS INDICATED ON THE PLANS.
BRANCH CIRCUIT HOMERUN WIRES SHALL BE INSTALLED IN INDIVIDUAL HOMERUN CONDUITS.
8. ANY DISCREPANCY IN LOCATION & RATINGS OF EQUIPMENT AND/OR APPARATUS TO BE INSTALLED
SHALL BE VERIFIED WITH THE OWNER OR HIS AUTHORIZED REPRESENTATIVE, & CHANGES SHALL BE
MADE ACCORDINGLY.
9. ALL MATERIALS & EQUIPMENT TO BE USED & INSTALLED SHALL BE BRAND NEW, OF THE APPROVED
TYPE FOR THE LOCATION AND PURPOSE INTENDED.
10. ALL POWER & CONVINIENCE OUTLETS SHALL BE GROUNDING TYPE.
11. THE MOUNTING HEIGHTS OF WIRING DEVICES SHALL BE AS FF:
a. LIGHT SWITHCHES 1.40 M. ABOVE FINISH FLOOR LINE
b. CONVINIENCE OUTLETS 0.30 M. ABOVE FINISH FLOOR LINE
c. TELEPHONE OUTLETS 0.30 M. ABOVE FINISH FLOOR LINE
d. PANELBOARDS & CABINETS 1.40 M. ABOVE FINISH FLOOR LINE