CH 1 - Introduction Electrical Installation Design 2010-2011 A4
CH 1 - Introduction Electrical Installation Design 2010-2011 A4
CHAPTER 1
INTRODUCTION TO ELECTRICAL INSTALLATION DESIGN
The best distribution system is one that will, cost effectively and safely, supply
adequate electric service to both present and future probable loads - this book is
included to aid in selecting, designing and installing such a system.
The function of the electric power distribution system in a building or installation site
is to receive power at one or more supply points and deliver it to the individual lamps,
motors, and all other electrically operated devices. The importance of the distribution
system to the function of a building makes it almost imperative that the best system be
designed and installed.
In order to design the best distribution system, the system design engineer must have
information concerning the loads and a knowledge of the various types of distribution
systems that are applicable. The various categories of buildings have many specific
design challenges, but certain basic principles are common to all. Such principles, if
followed, will provide a soundly executed design.
The basic principles or factors requiring consideration during design of the power
distribution system include:
1. Safety:
The No. 1 goal is to design a power system which will not present any
electrical hazard to the people who utilize the facility, and/or the utilization
equipment fed from the electrical system. It is also important to design a
Authors: 1
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
system which is inherently safe for the people who are responsible for
electrical equipment maintenance and upkeep.
Authors: 2
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
1.1.1 Summary
It is to be expected that the engineer will never have complete load information
available when the system is designed. The engineer will have to expand the
information made available to him on the basis of experience with similar problems.
Of course, it is desirable that the engineer has as much definite information as
possible concerning the function, requirements, and characteristics of the utilization
devices. The engineer should know whether certain loads function separately or
together as a unit, the magnitude of the demand of the loads viewed separately and as
units, the rated voltage and frequency of the devices, their physical location with
Authors: 3
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
respect to each other and with respect to the source and the probability and possibility
of the relocation of load devices and addition of loads in the future. Coupled with this
information, a knowledge of the major types of electric power distribution systems
equips the engineers to arrive at the best system design for the particular building.
It is beyond the scope of this guide to present a detailed discussion of loads that might
be found in each of several types of buildings. Assuming that the design engineer has
assembled the necessary load data, the following pages discuss some of the various
types of electrical distribution systems that can be utilized. The description of types of
systems, and the diagrams used to explain the types of systems on the following pages
omits the location of utility revenue metering equipment for clarity. A discussion of
short circuit calculations, coordination, voltage selection, voltage drop, ground fault
protection, motor protection, and other specific equipment protection is also
presented.
For medium to large sites, three distribution levels as shown in Figure 1.1 are
generally used to supply LV power to all loads:
Distribution from the Main Switchboard (MSB)
At this level, power from one or more MV/LV transformers connected to the
MV network of the electrical utility is distributed to:
- Different areas of the sites: shops in a factory, homogeneous production areas
in industrial premises, floor in the office buildings, etc.
- Centralised high power loads such as air compressors and water cooling units
in industrial processes or air conditioners and lifts in office buildings.
Sub distribution used to distribute electricity within each area
Final distribution, used to supply the various loads
Authors: 4
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
D B
SSB 1 D B
D B
D B
D B
M SB
SSB 2
D B
D B
SSB 3 D B
D B
M a in D is t r ib u t io n L e v e l S u b D is t r ib u t io n L e v e l S u b D i s t r ib u t io n L e v e l
Authors: 5
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
All distribution systems are combinations of two basic topologies (see Figure 1.2):
Star topologies: Radial (or centralized) distribution
Bus topology: Distribution using busduct/busways (also referred to as busbar
trunking systems)
a) b)
Figure 1.2: Two basic topologies of distribution systems:
a) Star b) Bus
Authors: 6
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
The electricity supply and installation practice in Peninsular Malaysia are governed
by the following:
1. Electricity Supply Act 1990 Act 447
2. Licensee Supply Regulation 1990
3. Electricity Regulation 1994
4. OSHA 1994 Occupational, Safety & Health Act
5. Malaysia Standard MS IEC 60364 Electrical Installation of Buildings
6. The current edition of the IEE Wiring Regulations for Electrical Installations,
where necessary (IEE Wiring Regulation 16th Edition)
7. Electricity Supply (Successor Company) Act 1990 Act 448
Authors: 7
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
Table 1.1: Standard voltages between 100V and 1000V (IEC 60038 Edition 6.2 2002-
07)
Three phase four wire or three wire Single phase three wire systems
systems Nominal voltage (V)
Nominal voltage (V)
50Hz 60Hz 60Hz
- 120/208 120/240
- 240 -
(1)
230/400 277/480 -
400/690 (1) 480 -
- 347/600 -
1000 600 -
1) The nominal voltage of existing 220/380 V and 240/415 V systems shall evolve
towards the recommended value of 230/400 V. The transition period should be as
short as possible, and should not exceed 20 years after the issue of this IEC
publication. During this period, as a first step, the electricity supply authorities of
countries having 220/380 V systems should bring the voltage within the range
230/400 V +6% -10% and those of countries having 240/415 V systems should bring
the voltage within the range 230/400 V +10% -6%. At the end of this transition period
the tolerance of 230/400 V 10% should have been achieved; after this the reduction
of this range will be considered. All the above considerations apply also to the present
380/660 V value with respect to the recommended value 400/690 V.
Table 1.2: Standard voltages above 1kV and not exceeding 35kV (IEC 60038 Edition
6.2 2002-07)
Series 1 Series II
Highest voltage for Nominal system Highest voltage for Nominal system
equipment (kV) voltage (kV) equipment (kV) voltage (kV)
(1) (1) (1) (1)
3.6 3.3 3 4.40 4.16(1)
(1) (1) (1)
7.2 6.6 6 - -
12 11 10 - -
(2)
- - - 13.2 12.47(2)
- - - 13.97(2) 13.2(2)
- - - 14.52(1) 13.8(1)
(17.5) - (15) - -
24 22 20 - -
- - - 26.4(2) 24.94(2)
36(3) 33(3) - - -
- - - 36.5 34.5
40.5(3) - 35(3) - -
These systems are generally three-wire systems unless otherwise indicated. The
values indicated are voltages between phases.
The values indicated in parentheses should be considered as non-preferred values. It is
recommended that these values should not be used for new systems to be constructed
in future.
Note 1: It is recommended that in any one country the ratio between two adjacent
nominal voltages should be not less than two.
Authors: 8
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
Note 2: In a normal system of Series 1, the highest voltage and the lowest voltage do
not differ by more than approximately 10 % from the nominal voltage of the system.
In a normal system of Series II, the highest voltage does not differ by more then +5%
and the lowest voltage by more than 10% from the nominal voltage of the system.
In Malaysia, the design criteria are developed by Tenaga Nasional Berhad (TNB) for
steady state supply voltage level fluctuation of the low voltage system can be divided
into:
1. Steady state voltage level fluctuation under normal condition: 415V/240V
10% to +5%.
2. Steady state voltage level fluctuation under contingency condition:
415V/240V 10%.
1.5 TNB Supply Schemes and Maximum Demand Level for Low Voltage System
Table 1.3 shows the typical supply schemes for maximum demand (MD) level of
individual customer for low voltage system provided by TNB.
Table 1.3: Typical supply schemes for various Maximum Demand (MD) levels
MD Ranges of Individual Supply Voltage Typical Supply Scheme
Customer
Up to 12kVA 240V Overhead services from LV
mains
12kVA to 100kVA 415V Three phase overhead or
underground cable service from
existing LV mains
100kVA to 1000kVA 415V Direct cable services from LV
board from a substation
Table 1.4 and 1.5 indicates the typical ranges of maximum demand for domestic and
shop lots or shop houses respectively. These values shall be subjected to revisions
based upon the latest results of load profiling studies.
Table 1.4: Range of Maximum Demand (MD) for domestic customer subclasses or
premises
No Type of Premises Maximum Average Maximum
(kW) (kW) (kW)
1 Low cost flats, single storey terrace 1.5 2.0 3.0
2 Double storey terrace or apartment 3.0 4.0 5.0
3 Single storey, semidetached 3.0 5.0 7.0
4 Single storey bungalow & three 5.0 7.0 10.0
room condominium
5 Double storey bungalow & luxury 8.0 12.0 15.0
condominium
Authors: 9
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis
Electrical Installation Design
Authors: 10
Hasnizam Hanafi & Rafi Azman
Universiti Malaysia Perlis