Dust Papers 1
Dust Papers 1
com
tion differ from those for the published data for the
same material, producing different combustible dust re-
About 40 percent of combustible dust explosions re- sults. The only way to determine your dusts combustibil-
ported in the US and Europe over the last 25 years ity is to have a qualified laboratory run explosion tests on a
have involved dust collectors. Dust collection sys- representative sample of the dust. Then, to meet NFPA re-
tems are now a primary focus of inspections re- quirements, youll need to commission a hazard analysis
quired by OSHAs National Emphasis Program on of your dust collection system to document that its design
safely handling combustible dusts.1 OSHA also has mitigates the explosion risk posed by your dust. (For more
information, see reference 4.)
the authority to enforce National Fire Protection As-
sociation (NFPA) standards for preventing or pro-
tecting against dust explosions. This two-part article Some dust explosion basics
focuses on how you can design your dust collection The five elements required for a dust explosion can be pic-
systems dust collector, ductwork, and exhaust fan tured as a pentagon, as shown in Figure 1. The three ele-
to meet the intent of these NFPA requirements. Part ments labeled in black are those in the familiar fire
II will appear in January. triangle: fuel (combustible dust), an ignition source, and
Figure 1
T
he explosion hazards posed by dusts commonly han-
dled in bulk solids plants can be surprising. In fact, Ignition
most natural or synthetic organic dusts and some source
metal dusts can explode under the right conditions. You can
find a limited list of combustible dusts and their explosion
data in the appendix to the NFPA standard focusing on dust Confinement
explosion hazards, NFPA 68: Standard on Explosion Pro- Dust dispersion of dust cloud
at or greater
tection by Deflagration Venting (2007),2 and in Rolf K. Eck- than dusts MEC
in equipment
hoffs book Dust Explosions in the Process Industries.3 or building
While such published data can give you some idea of your
dusts explosion hazards, using this data for designing ex-
plosion prevention or protection equipment for your dust Fuel Oxygen
isnt recommended. Your processing conditions and your (combustible
dust)
dusts characteristics such as its particle size distribu-
oxygen. For a dust explosion, two more elements (labeled vention of Fire and Dust Explosions from the Manufactur-
in red) are required: dust dispersion at or greater than the ing, Processing, and Handling of Combustible Particulate
dusts minimum explosible concentration (the lowest dust Solids (2006).2 First, the conveying air velocity must be
concentration that will propagate a combustible dust defla- adequate throughout the duct. Second, at points where two
gration or explosion; MEC) and confinement of the dust airstreams merge, the duct sections must join in a way that
cloud within equipment or a building. maintains this velocity.
Put simply, a dust explosion occurs when an ignition If your plant handles a combustible dust, a visiting OSHA
source touches a dust cloud with a concentration at or inspector will ask whether the conveying air velocity
greater than the dusts MEC. A dust cloud with this con- through your dust collection system is adequate and
centration can result when a layer of dust thicker than 132 will ask you to prove it. Why is this velocity important?
inch on equipment, piping, overhead conduit, or similar Keeping the conveying air velocity in every part of the duct
components is pushed into the air by some event, such as within a reasonable range will prevent two problems: Too
the pressure wave from a relief devices operation. When low an air velocity will cause the dust to drop out of the air
an ignition source such as a spark or the flame front and build up inside the duct, and, depending on the dusts
from an equipment explosion touches the cloud, the characteristics, too high an air velocity will waste energy,
dust can explode with devastating impact, as evidenced by erode the duct, or, if the dust is moist or sticky, cause the
the fatal results of the sugar refinery explosion in Georgia dust to smear on the duct wall.
last February. To mitigate your dust collection systems
explosion risk, you need to focus on preventing dust accu-
mulation in the system, preventing ignition, and providing
explosion prevention or protection at the collector all
covered by NFPA standards. If your plant handles a combustible dust, a visiting
OSHA inspector will ask whether the conveying air
Even when a dust collector is equipped with an explosion velocity through your dust collection system is
vent that works properly, the ductwork in the dust collec- adequate and will ask you to prove it.
tion system can propagate a collector dust explosion
throughout a process area. An investigation into one such
case revealed that a contributing factor was the ignition
and explosion of dust that had accumulated in the duct- A conveying air velocity between 3,500 and 4,000 fpm
work because of the systems inadequate conveying veloc- (17.5 and 20 m/s) is a reasonable starting point for design-
ity. 5 Another contributing factor was the lack of ing your system. Then, based on supporting data about
flame-front-isolation devices in the collectors dirty-air your application, you can speed or slow the conveying air
inlet and the clean-air outlet for recirculating air to the to the systems optimal velocity. For instance, if your sys-
building. Such devices could have prevented the flame tem handles an extremely fine, lightweight material that
front in the collector from entering the inlet duct and re-en- wont clump together, like cotton dust, you can slow the
tering the building through the outlet duct. velocity to 3,000 fpm; if you handle a very heavy material,
like lead dust, you may need to increase the velocity to
In this case as in many others, following the requirements 4,500 to 5,000 fpm. For guidance in determining the opti-
in NFPA standards for mitigating explosion risks in a dust mal velocity for your application, see Table 5-1 in the
collection system could have prevented the dust explosion American Conference of Governmental Industrial Hy-
from propagating beyond the dust collector. In the follow- gienists Industrial Ventilation: A Manual of Recom-
ing sections, well look at how you can design your dust mended Practice for Design (26th edition, 2007),6 which
collection system to meet the NFPA standards. Informa- lists minimum duct design air velocities for many dusts.
tion covers preventing dust accumulation in ductwork,
eliminating ignition sources, and using explosion preven- How duct sections are joined in your system also affects
tion and protection methods at the collector. [Editors the conveying air velocity. If incorrectly designed, the
note: Capture hood design, another important factor in de- point where ducts join to merge two airstreams can slow
signing a safe dust collection system, is beyond this arti- the air velocity, in turn causing the dust to drop out and ac-
cles scope; for more information, see the later section cumulate in the duct. You can prevent this problem by con-
For further reading or contact the author.] necting each branch duct to a 15-degree tapered expansion
on the main duct, which enlarges the main duct diameter
to a size appropriate for the merged airstreams. A related
Preventing dust accumulation in ductwork problem is that dust particles can drop out of the airstream
To prevent dust from accumulating in your dust collection when a branch duct joins the main duct at too great an
systems ductwork and becoming fuel for an explosion, angle. The momentum of the conveyed dust particles
you must design all ducts in the system with two principles causes them to want to move in a straight line, so when one
in mind, as described in NFPA 654: Standard for the Pre- duct joins another at a sharp angle, the particles have to
change direction and slow down. Avoid this problem by larges from 8 to 9 inches, and the downstream main duct,
designing the branch duct entry with no more than a 30- C, is 9 inches in diameter. Before the blank flange was in-
degree angle to the main duct. stalled, the systems design airflow met the air velocity re-
quirements at A (4,200 fpm [1,500-cfm airflow]), B
(3,900 fpm [350-cfm airflow]), and C (4,100 fpm [1,850-
Failing to practice these duct design principles can lead to cfm airflow]). But with A blanked off, the required air ve-
any of several problems that produce a slower-than-re- locity through the 4-inch-diameter duct (B) is now 3,900
quired conveying air velocity in your ducts. Following are fpm (350-cfm airflow). The exhaust fan might be able to
some visual clues that indicate the air velocity in the ducts pull an airflow of no more than 600 cfm through B and C,
isnt high enough to prevent dust from dropping out of the which would drop the air velocity at C from the required
air. Under each clue, ways to remedy the problem and get 4,100 fpm to 270 fpm.
adequate conveying air velocity though the ducts are de-
scribed.
Solutions: Two solutions are possible: You can replace all
the duct between B and the systems dust collector with
Clue 1: Main duct diameter doesnt enlarge after branch smaller duct to achieve an adequate conveying velocity.
junctions. In Figure 2a, two 8-inch-diameter branch ducts Or, as a much cheaper alternative, you can remove the
join an 8-inch-diameter main duct, and the main ducts blank flange and replace it with an orifice plate that deliv-
downstream diameter is the same after each junction. At ers 1,500-cfm airflow at the systems available static pres-
A, before the first branch junction, the 4,200-fpm air ve- sure; the orifice plate has a hole at its center thats sized to
locity required to convey the dust is reasonable and can be meet the systems airflow and pressure drop requirements.
achieved by the systems design airflow of 1,500 cfm. But
because the duct diameter doesnt enlarge after the branch
junctions, the required air velocity increases exponen- Clue 3: Poor duct junctions dont maintain conveying ve-
tially: Its 8,400 fpm at B, after the first branch junction, locity. Lets look at two examples of this problem. In the
which would require a 3,000-cfm airflow, and its 16,800 first, shown in Figure 2c, an 8-inch-diameter duct section
fpm at C, after the second junction, which would require a abruptly joins a 20-inch-diameter section. At the systems
4,500-cfm airflow. However, 5,500 fpm is the practical 1,400-cfm design airflow, the conveying air velocity is
upper limit for air velocity in system ductwork. To meet 4,000 fpm in the 8-inch section, but it drops abruptly to 650
the velocity requirements in this duct arrangement, the fpm in the 20-inch section, which will cause the dust to drop
system would require a major upgrade of the exhaust fan out of the air. Solution: In this case, the solution is to replace
and electric power, which is impractical. the 20-inch duct section with 8-inch duct. The duct diameter
should stay at 8 inches until the next branch junction; after
that junction, the duct should be enlarged to maintain the air
Solution: The more economical solution is to enlarge the velocity, following the rule of thumb under Clue 1.
downstream duct. This will solve the problem that results
from not upgrading the exhaust fan that is, that C gets
most of the airflow, B gets some, and A gets very little. To Another poor duct junction is shown in Figure 2d. Here, an
ensure that the ducts diameter is large enough after a 8-inch-diameter branch duct, A, joins an 8-inch-diameter
branch duct joins it, follow this rule of thumb: The sum of main duct at a 90-degree angle, forming a T junction. The
the areas of the upstream branch ducts should roughly systems 1,400-cfm design airflow can produce the re-
equal the area of the downstream duct. Based on the equa- quired 4,000-fpm conveying air velocity through A and
tion duct area = (diameter/2)2, this rule can be re- and section B upstream from the junction without a prob-
stated as: the sum of the squares of the upstream branch lem. But section C downstream from the junction would
duct diameters should roughly approximate the square of require 8,000 fpm (at an airflow of 2,800 cfm) to convey
the downstream main duct diameter. Thus, at B: the dust through the duct and past the T junction. Meeting
this impossibly high air velocity requirement would de-
82 + 82 = 128 112 or 121
mand an unreasonably high fan energy, and the duct at
so the main duct diameter at B should be changed to 11 both B and C would probably plug with dust. Solution: In
inches. Then, at C, two solutions are possible: this case, replacing the T junction with a 30-degree Y junc-
112 + 82 = 185 132 or 169 tion that enlarges to a downstream diameter of 11 inches
(again following the rule of thumb in Clue 1) will maintain
112 + 82 = 185 142 or 196
the systems 4,000-fpm conveying air velocity.
so the main duct diameter at C should be changed to 13 or
14 inches, depending on your applications conveying ve-
locity requirements. Clue 4: Ductwork includes too much flexible hose. In
Figure 2e, flexible hose has been used in place of metal
duct as a quick way to connect two duct sections. How-
Clue 2: Main duct is blanked off. In Figure 2b, an 8-inch- ever, dust builds up more easily on the hoses corrugated
diameter main duct, A, is blanked off. A 4-inch-diameter inside surface than on smooth metal duct. The hoses inter-
branch duct, B, joins the main duct at a Y junction that en- nal resistance also is more than twice that of smooth metal
duct, so with the hose bends acting as elbows, the hoses vide the speed necessary to overcome this additional air-
equivalent length is much greater than its actual length. flow resistance, and the result is low air velocity that
The systems exhaust fan may not be large enough to pro- causes dust to drop out of the air and plug the ducts.
Figure 2
A C
B B
C
Branch
junctions 30-degree
T junction
Y junction
Blank
flange
8 inches
A
C B 4 inches
9 inches
A
8 inches
Solution: Replace the flexible hose with sections of metal per minute divided by the square feet of filter media sur-
duct that are clamped together. You should use flexible face area) for your dust collector, properly starting up the
hose in the system only with equipment that must move, collector when the new filters are installed will provide the
such as connecting metal duct to the capture hood for a best long-term performance. Once the new filters are in-
loss-in-weight feeder that rests on load cells; see NFPA
654 for more information.
Figure 3
Clue 5: Duct blast gate isnt locked in position. Blast
gates in ducts add artificial airflow resistance to balance Effect on airflow of high pressure drop
the airflow in individual duct branches. For each blast gate, across the filter media
only one position is correct to balance the airflow in all
Design High pressure
branches. In Figure 2f, the blast gate has been adjusted to static pressure drop shifts
send more airflow into this branch, which steals airflow fan operation
from other branches. curve to left
References
1. The OSHA National Emphasis Program (NEP) directive on safely
handling combustible dusts is available at http://www.osha.gov
/OshDoc/Directive_pdf/CPL_03-00-008.pdf.
2. Available from National Fire Protection Association (NFPA), 1
Batterymarch Park, Quincy, MA 02169-7471; 800-244-3555, fax
617-770-0700 (www.nfpa.org).
Gary Q. Johnson is principal consultant with Workplace
3. Rolf K. Eckhoff, Dust Explosions in the Process Industries, Elsevier
Publishing, third edition, 2003; available from the PBE Bookstore at
Exposure Solutions, 7172 Willowood Drive, Cincinnati,
www.powderbulk.com. OH 45241; phone/fax 513-777-4626 (gary@workexpo
4. Lee Morgan and Terry Supine, Five ways the new explosion venting soln.com, www.workexposoln.com). He holds a masters
requirements for dust collectors affect you, Powder and Bulk degree in business administration from the University of
Engineering, July 2008, pages 42-49; see For further reading for Scranton, Scranton, Pa., and a bachelors degree in chemi-
information on purchasing a copy of this article.
cal engineering from Ohio State University in Columbus.
As appeared in PBE January 2009 www.powderbulk.com
Figure 1
Duct grounding
wires clearly
visible to
operators
Ground exhaust fan
and fan motor
Ground each section Ground
of conductive duct dust collector
for carbonaceous dusts, and Group G is for all other dusts. Standard on Explosion Protection Systems (2008).2 You
To determine the right hazardous area classification for your can see a dust collector equipped with various explosion
systems electrical components, consider your dust type, prevention and protection devices in Figure 2.
dust quantity, whether the systems dust collector is inside
or outside, and related factors. Of the several ways to meet NFPA 68 requirements for pro-
Protecting the exhaust fan. If your exhaust fan fails me- tecting your dust collector from an explosion, explosion
chanically, the fan impeller can shift and rub or hit the venting is the most common. NFPA 68 venting require-
housing. A spark from such metal-to-metal contact has ments are described in detail in the PBE article Five ways
enough energy to ignite a combustible dust. To avoid this the new explosion venting requirements for dust collectors
hazard, you should do two things: First, place the exhaust affect you.3 As the article states: The purpose of explo-
fan on the dust collectors clean side, where it cant contact sion venting is to save lives, not property. A well-designed
dust under normal conditions, as detailed in NFPA 654: explosion vent functions as a weak element in the equip-
Standard for the Prevention of Fire and Dust Explosions ments pressure envelope, relieving internal combustion
from the Manufacturing, Processing, and Handling of pressure to keep the collector from blowing up into pieces.
Combustible Particulate Solids (2006).2 Second, train and ...Typically, the collector is located outside and designed to
equip your operators to practice good dust collector main- vent away from buildings and populated locations. Addi-
tenance so they can spot filter leaks early and replace the tional venting information in the article highlights NFPA
affected filters before dust can escape the system. One tool 68 areas that have changed or are of most importance to
available from multiple suppliers for helping the operators bulk solids processors, including the performance-based
spot filter leaks before they cause a problem is a filter-leak design option and sizing vents and discharge ducts.
detection system; the system uses an inductive or tribo-
electric probe inserted into the system ductwork to sense If your dust collector is indoors and cant be vented outside
particles escaped from a leaking filter. through an exterior wall or ceiling, you must equip it with
an explosion prevention method, such as a suppression
system, that can prevent a dust explosion from propagat-
Using explosion prevention and protection methods ing to connected equipment. You can use any of several
at the collector systems described in NFPA 69. One common example is a
To meet NFPA requirements for protecting your dust col- chemical suppression system, which senses a developing
lector from a dust explosion, you must use one (or more) explosion in the dust collector and rapidly injects a chemi-
cal powder into the developing fireball to stop the flame lates cleaned air to the workplace. Placed on the dust col-
front; this can be a useful retrofit for a collector located in- lectors clean-air side between the fan and collector or
doors and too far from an outside wall to allow explosion after the fan, the float valve works like a ball check valve
Figure 2
venting. Another suppression system injects a hot-water that is, its pushed shut by the pressure and airflow
mist into the collector to stop the flame front from travel- changes caused by an explosion in the collector.
ing to upstream equipment. For a dust collection system
thats part of a closed-circuit process, you may consider an Meeting additional NFPA requirements
explosion prevention method that uses nitrogen to inert the
According to our industrys current interpretation of the
dust collection system; using nitrogen inerting in a closed-
NFPA standards covering dust collection system design,
circuit application minimizes nitrogen consumption,
you dont have to update equipment in your system each
which otherwise would be prohibitively expensive.
time a particular standard is updated unless your locations
authority having jurisdiction (an organization, office, or
NFPA 69 also describes methods for isolating upstream individual responsible for enforcing the requirements of a
and downstream equipment from an explosion in the dust code or standard [NFPA 68]) decides otherwise. How-
collector. One common example is a flame-front diverter, ever, the standards require you to follow certain proce-
which is an explosion vent in the duct (Figure 2). The di- dures related to maintenance, housekeeping, explosion
verter is typically placed at the dust collectors dirty-air protection, and managing system changes, and you must
inlet when the collector is located near the dust collection implement the procedures retroactively.
systems exhaust fan and ductwork. When an explosion
occurs in the collector, the flame-front diverters vent Here are some of the key retroactive requirements in
opens and releases the explosion to the atmosphere, thus NFPA 68, 69, and 654:
isolating other equipment from the flame front. Another You must provide both initial training and refresher train-
isolation device is a high-speed isolation valve, which is ing to employees on the established operating and main-
located in the dirty-air duct and wired to an explosion de- tenance procedures for your dust collection system and
tector in the collector. The valves location on the duct is explosion prevention and protection equipment.
far enough from the explosion detector to allow the detec-
tor to respond to an explosion and close the valve before You must provide housekeeping and cleaning for the dust
the flame front can reach upstream equipment. A float collection system and surrounding area using procedures
valve (Figure 2) is another isolation device that protects (such as vacuum cleaning) that minimize dust-cloud gen-
the exhaust fan or the ventilation equipment that recircu- eration and at a frequency that minimizes dust accumula-
tion in your workplace. The portable vacuum cleaners References
you use must meet Class II hazardous location require- 1. The OSHA National Emphasis Program (NEP) directive on safely
ments when operated in a combustible dust hazard area. handling combustible dusts is available at http://www.osha.gov
/OshDoc/Directive_pdf/CPL_03-00-008.pdf.
You must ensure that all dust collection system compo- 2. Available from National Fire Protection Association (NFPA), 1
nents are conductive, bonded (to protect workers from Batterymarch Park, Quincy, MA 02169-7471; 800-244-3555, fax
electric shock), and grounded to a resistance of less than 617-770-0700 (www.nfpa.org).
106 ohms. 3. Lee Morgan and Terry Supine, Five ways the new explosion venting
requirements for dust collectors affect you, Powder and Bulk
You must inspect, test, and maintain the dust collection Engineering, July 2008, pages 42-49; see For further reading for
system and its explosion prevention and protection information on purchasing a copy of this article.
equipment according to the manufacturers recommen-
dations. You also must keep records of these inspections
and tests and sign off on them. For further reading
You need to establish change management procedures Find more information on designing dust collection sys-
for the dust collection system and its explosion preven- tems and preventing dust explosions in articles listed
tion and protection equipment and address related tech- under Dust collection and dust control and Safety in
nical issues before making any system changes; after a Powder and Bulk Engineerings comprehensive article
system change, you must update the systems design index (later in this issue and at PBEs Web site,
documentation to reflect the change. www.powderbulk.com) and in books available on the Web
site at the PBE Bookstore. You can also purchase copies of
past PBE articles at www.powderbulk.com.
Also be aware that if equipment in your dust collection sys-
tem has changed or the dust collected by your system has
changed since you initially tested the dust for combustible
properties and conducted a hazard analysis of your system, Gary Q. Johnson is principal consultant with Workplace
you must revisit the hazard analysis to see if you need to Exposure Solutions, 7172 Willowood Drive, Cincinnati,
change any of the systems explosion risk mitigation strate- OH 45241; phone/fax 513-777-4626 (gary@work
gies, such as explosion vent size and location. Dont forget exposoln.com, www.workexposoln.com). He holds a mas-
that NFPA requires that you keep the hazard analysis up to ters degree in business administration from the University
date for the life of the process it protects and that you review of Scranton, Scranton, Pa., and a bachelors degree in
and update the analysis at least once every 5 years. PBE chemical engineering from Ohio State University in
Columbus.
115
A publication of
CHEMICAL ENGINEERINGTRANSACTIONS
The Italian Association
VOL. 31, 2013 of Chemical Engineering
Online at: www.aidic.it/cet
Guest Editors: Eddy De Rademaeker, Bruno Fabiano, Simberto Senni Buratti
Copyright 2013, AIDIC ServiziS.r.l.,
ISBN 978-88-95608-22-8; ISSN 1974-9791
The current paper describes an approach for dust explosion quantitative risk management of the following
nontraditional particulate fuel systems: (i) nanomaterials having particles with dimensions between 1 and
100 nm, (ii) flocculent (fibrous) materials characterized by a length-to-diameter ratio rather than a particle
diameter, and (iii) hybrid mixtures consisting of a combustible dust and a flammable gas (or a combustible
dust wetted with a flammable solvent). Experimental results are considered as input to a quantitative risk
management framework so as to provide a comprehensive procedure to analyze, assess and control the
likelihood and consequences of explosions of nontraditional dusts. Using concepts drawn from previous
studies, the framework consists of three main components: (i) a new combined safety management
protocol, (ii) use of the CFD (computational fluid dynamics) software DESC (Dust Explosion Simulation
Code) and FTA (Fault Tree Analysis) to determine explosion consequences and likelihood, respectively,
and (iii) application of the hierarchy of controls (inherent, engineered and procedural safety) to achieve
residual risk reduction.
1. Introduction
Dust explosion risk reduction has been the subject of intensive research for several decades. There
remains, however, a strong need for continued research on dust explosions especially for dusts that may
be termed nontraditional when compared with the more common and often-tested micron-size, spherical
particles comprising a single-fuel powder (Worsfold et al., 2012). The specific fuel/air systems studied here
fall in three nontraditional categories as follows: (i) micron- and nano-size titanium powders, (ii) flocculent
polyamide 6.6 and polyester, and (iii) hybrid mixtures of lactose and microcrystalline cellulose dusts
admixed with methanol, ethanol and isopropanol solvents. Relevant industrial applications are the handling
of metallic nano-powders, fabric and textile processing, and pharmaceutical manufacturing, respectively.
A generalized Quantitative Risk Management Framework (QRMF) for dust explosions has been modified
in the current work to integrate the above three nontraditional categories of dust explosions. The
modifications were developed through a synthesis of experimental findings and a comprehensive literature
review. Use of the QRMF for the three nontraditional fuel/air systems is proceeding in parallel, with each
system being considered from the key perspectives of hazard characterization, risk (consequence and
likelihood) assessment, and residual risk control (along with other aspects of the quantitative risk
management sequence). Here we present a summary of hazard characterization findings and residual risk
control measures for the nanomaterials, flocculent materials and hybrid mixtures being studied, along with
a representative look at consequence assessment for flocculent materials and likelihood assessment for
nanomaterials.
116
with the corresponding experimental results (as expected). As shown in Figures 2(b) and 2(d), the peak
overpressure in a 1-m3 chamber is similar to the 20-L case for each fuel dust, but with a longer time to
attainment of Pmax. Polyester (Figures 2(c) and 2 (d)) is seen to take less time to reach its maximum
pressure than polyamide 6.6 (Figures 2(a) and 2(b)) because of the higher experimental rate of pressure
rise for polyester (Iarossi et al., 2012). Work is ongoing to extend the flocculent material simulations to
industrial-scale geometries, and to investigate the applicability of DESC to other nontraditional particulate
fuel/air systems.
(a) (b)
(c) (d)
Figure 2: DESC simulation of polyamide 6.6 (dtex 1.7 and length 0.5 mm) explosions in (a) a 20-L
3
spherical chamber and (b) a 1-m spherical chamber; similarly for polyester (dtex 1.7 and length 0.5 mm)
3
explosions in (c) a 20-L spherical chamber and (d) a 1-m spherical chamber
2.4.1 Nanomaterials
Coating of particles with a less hazardous substance is a possible approach to manage the risk of a given
nanomaterial (Williams et al., 2010); this is an example of inherent safety. Surface modification, change-of-
form and other approaches to alter the physical state of nanoparticles could also be acceptable safety
measures in nano-risk reduction. Control of hazards at their source with containment is a possible
engineering safety measure for nano-dust explosions (Williams et al., 2010). Isolation of workers, local
ventilation, specially designed dust collectors, and process changes are some other engineering/
procedural controls to manage the risk of dust explosions associated with nanoparticles. Inerting with
admixed solids could be applied to avoid pre-ignition and associated risks. Moreover, discharge control
measures, special organizational measures, and personal protective equipment designed for nano-dusts
are further important safety measures for nanomaterials.
3. Conclusion
The concepts of a modified risk management framework presented in this paper have been established to
assess and manage the risks of nontraditional dust explosions in relevant industrial applications involving
metallic nano-powders, flocculent textile materials, and pharmaceutical base powders and solvents.
Quantitative analysis of explosion likelihood and consequences, as well as implementation of the hierarchy
of safety controls, can provide guidance and establish measures to prevent and mitigate nontraditional
dust explosions. Appropriate case studies as well as validation of the abovementioned comprehensive
framework have been planned for further analysis of various aspects of nontraditional dust explosions.
Acknowledgement
The authors gratefully acknowledge the financial support of the Natural Sciences and Engineering
Research Council (NSERC) of Canada in the form of a strategic grant.
References
Abuswer M., Amyotte P., Khan F., 2012, A quantitative risk management framework for dust and hybrid
mixture explosions, Journal of Loss Prevention in the Process Industries, DOI: 10.1016/j.jlp.2011.08.
010.
Amyotte P.R., 2011, Are classical process safety concepts relevant to nanotechnology applications?
Journal of Physics: Conference Series (Nanosafe2010: International Conference on Safe Production
and Use of Nanomaterials) 304, 012071.
Amyotte P., Lindsay M., Domaratzki R., Marchand N., Di Benedetto A., Russo P., 2010, Prevention and
mitigation of dust and hybrid mixture explosions, Process Safety Progress 29, 17-21.
Amyotte P., Khan F., Boilard S., Iarossi I., Cloney C., Dastidar A., Eckhoff R., Marmo L., Ripley R., 2012,
Explosibility of nontraditional dusts: experimental and modeling challenges, Hazards XXIII, IChemE,
Southport, UK (November 12-15, 2012), pp. 83-90.
Amyotte P.R., Dastidar A.G., Khan F.I., Eckhoff R.K., Hossain M.N., Symington K., Boilard V., Abuswer M.,
2013, Influence of liquid and vapourized solvents on explosibility of pharmaceutical excipient dusts,
th
Accepted for 9 Global Congress on Process Safety, San Antonio, TX, USA.
Boilard S.P., Amyotte P.R., Khan F.I., Dastidar A.G., Eckhoff R.K., 2012, Explosibility of micron- and nano-
size titanium powders, Paper No. 009, Proceedings of Ninth International Symposium on Hazards,
Prevention, and Mitigation of Industrial Explosions, Krakow, Poland (July 22-27, 2012).
Iarossi I., Amyotte P.R., Khan F.I., Marmo L., Dastidar A.G., Eckhoff R.K., 2012, Explosibility parameters
of polyamide and polyester fibers, Paper No. 004, Proceedings of Ninth International Symposium on
Hazards, Prevention, and Mitigation of Industrial Explosions, Krakow, Poland (July 22-27, 2012).
Shell, 1995, Quantitative Risk Assessment, vol. 3. Shell International Exploration and Production B.V., The
Hague, The Netherlands.
Skjold, T., 2007, Review of the DESC project, Journal of Loss Prevention in the Process Industries, 20,
291-302.
von Pidoll U., 2002, Avoidance of the ignition of textile fiber/air mixtures during the electrostatic flocking
process, IEEE Transactions on Industry Applications 38, 401-405.
Williams A.R., Kulinowski M.K., White R., Louis G., 2010, Risk characterization for nanotechnology, Risk
Analysis, 30, 1671-1679.
Worsfold S.M., Amyotte P.R., Khan F.I., Dastidar A.G., Eckhoff R.K., 2012, Review of the explosibility of
nontraditional dusts, Industrial & Engineering Chemistry Research, 51, 7651-7655.
Risk Logic Inc. Page 1 of 5
Risk Logic Inc. . 48 Dimmig Road, Upper Saddle River, NJ 07458 . Phone: (201) 930-0700 . Fax: (201) 930-8795 . www.risklogic.com
For the purposes of this article, we are going to specifically address the equipment explosion hazard.
The fire protection engineering industry treats all equipment that handles combustible dusts as
having a dust explosion hazard. The first recommendation is locate all such equipment outdoors. If
this is not practical, then it is recommended to eliminate the explosion hazard or to mitigate the
explosion hazard.
Elimination of an equipment explosion hazard through inerting or liquid misting is not easily
accomplished in many cases and explosion hazard mitigation features are then recommended for the
equipment/system design. These typically involve the use of explosion venting, suppression,
containment, or vacuum operation. In many situations involving a complex system/arrangement (i.e.,
storage, handling and conveyance system with several bins, vessels and lengths of ductwork), a
combination of these may be required for best protection. The most common methods of equipment
explosion hazard mitigation are venting and suppression.
Explosion venting is a passive safety approach and is usually the first choice. When dealing with a
vessel, it may be easiest to locate it next to an exterior wall and vent the explosion to the outdoors via
a short vent duct; however, this may not be practical for existing installations surrounded by other
important process and manufacturing equipment. An alternative would be to vent the explosion to
the surrounding area indoors through an explosion quench pipe, again if practical. Vents should be
sized based on the properties of the dust being handled/collected and the design strength of the
equipment/vessel involved. Vent sizes and properties should be designed in accordance with NFPA
68, Standard on Explosion Protection by Deflagration Venting, or FM Global Standards (using by
FM Global DustCalc software if you are an insured of FM Global).
It is recommended to provide explosion suppression for high valued equipment, equipment that
exposes high valued processes, or equipment that has frequent explosions, when explosion venting,
pressure containment, or inerting is impractical or cannot be provided. It should be noted that
explosion suppression systems are generally less reliable than explosion venting or explosion
resistant construction.
Explosion suppression relies on detecting the start of an explosion and delivering an extinguishing
agent as quickly as possible (within milliseconds) to quench the explosion and reduce the maximum
explosion pressure to a substantially lower amount. The lower pressure is called the reduced
explosion pressure (or suppressed pressure), which must be lower than the vessel design strength for
an explosion to be successfully suppressed.
http://www.risklogic.com/articles/sep2012.html 10/15/2015
Risk Logic Inc. Page 2 of 5
System Design:
The first step in the design of an effective explosion suppression system for a specific application or
piece of equipment is to quantify the potential explosion hazard. The minimum required information
is as follows:
As recommended by FM Global Property Loss Prevention Data Sheet 7-17, Explosion Protection
Systems, use caution when installing explosion suppression systems on enclosures larger than those
used in the verification testing of the suppression systems. It is technically possible to suppress
explosions in vessels with volumes of up to 1,000 cu. m (35,300 cu. ft). In practice, dust explosions
have been successfully suppressed in vessel sizes of 0.2 cu. m (7.1 cu. ft) up to 250 cu. m (8,825 cu.
ft). The appropriate system should be selected and designed as noted above.
In addition, do not install explosion suppression systems where ST3 dusts (Kst > 300; e.g.,
aluminum) are used unless proven by full-scale tests. In general, ST3 dusts cannot be effectively
suppressed due to their extremely fast rate of pressure rise.
System Components:
Detectors - to be effective, the detector chosen must be capable of recognizing the existence of an
explosion very early after ignition. There are three types of detectors: thermoelectric, optical and
pressure.
For dust explosion hazards, use pressure detectors; thermoelectric sensors (activated by direct heat
transfer from hot gases) and optical detectors should not be used since they only work effectively if
located close to the heat source.
Pressure detectors continuously measure pressure and monitor the rate of pressure rise and threshold
pressure.
To minimize false trips of the explosion suppression system, it is recommended to position two
detectors in two planes (i.e., cross-zoned). This is especially important for pressure detectors.
In general, locate pressure detectors a maximum distance of 20 ft. from the suspected ignition source
(s).
Wire detectors actuating explosion suppression systems to a Class A initiating device circuit, as
defined by NFPA.
Suppressant Material - the suitability of a particular extinguishing agent for a given application
should be determined by explosion suppression tests.
Control/Monitoring Systems - control systems detect changes in the explosion sensor output or
mechanical condition; they determine whether a hazard exists, and activate the suppressors
accordingly.
http://www.risklogic.com/articles/sep2012.html 10/15/2015
Risk Logic Inc. Page 3 of 5
The control system should be interlocked to shut down the equipment involved (safely) upon
detector activation and should prevent the process equipment from restarting without re-arming the
suppression system.
Monitor the electrical system of the detector and suppressor activation circuits at a constantly
attended location. Any component failure should sound an alarm and automatically shut down the
process.
Provide a standby battery that engages automatically when the electrical power fails.
Install the control system in a safe, dust-free area or within enclosures approved for explosive
atmospheres.
De-activate the control system, shut down the process and purge any combustible dusts before
entering the vessel or performing any activity that could accidentally trip the suppression system.
Explosion isolation is a means of preventing flame front and ignition (primarily through the use of
mechanical valves or chemical suppressants) from being conveyed past a predefined point (i.e., to
other process equipment through ducting or piping). The detection and control functions are identical
to explosion suppression. Examples of explosion isolation are as follows:
These systems are typically used with explosion suppression systems. A chemical blocking system
should be activated by optical or pressure detectors at the same time as an explosion suppression
system. These systems are generally activated using the same control equipment as the explosion
suppression system, but they can also be installed/activated separately.
In general, gaseous clean agents and dry chemical powders (based on ammonium phosphate) are
used as suppressants. As with explosion suppression systems, the vessel or ductwork should be
designed to withstand the expected local pressure that would result from the blocking system.
Flame Arrestors:
A flame arrestor is a device that prevents the transmission of a flame through a flammable gas/air
mixture by quenching the flame on the surfaces of a series of small passages (or heat sinks) through
which the flame must pass. The emerging gases are sufficiently cooled to prevent re-ignition. The
arrestor must be placed in the flame path between the source of ignition and the system to be
protected.
Deflagration and detonation arrestors should be used in accordance with their approval/listing. These
types of arrestors are not interchangeable (i.e., do not use in-line arrestors as end-of-line and vice
versa) and must be used in the proper arrangement. The vendor or manufacturer should supply the
necessary details regarding the specific arrestor.
Inspect arrestors at least annually, and after each incident in which they have functioned.
http://www.risklogic.com/articles/sep2012.html 10/15/2015
Risk Logic Inc. Page 4 of 5
The flame front diverter (also known as explosion diverters, back-blast dampers, back-flash
interrupters or backflow preventers) incorporates the need to vent deflagration pressures with the
need to direct the flame front in such a way that it does not ignite material in the process
downstream. The main advantages are low initial cost and maintenance costs.
Flame front diverters that are either commercially manufactured and distributed, or fabricated in-
house according to design guidelines from VDI (Germany) are acceptable (see FM Global Property
Loss Prevention Data Sheet 7-76, Prevention and Mitigation of Combustible Dust Explosions and
Fires, for guidelines). Using prefabricated rupture disks for the rupture membrane will eliminate the
need to test or calculate the rupture pressure.
Do not use explosion diverters in air streams that have a significant loading of abrasive dust. Such
dust would eventually erode through the pressure relieving diverter cover.
An explosion isolation valve such as a fast-acting valve provides a mechanical barrier against the
flame front of an explosion. The intent is to isolate the explosion and protect the area beyond the
valve. The valve must be activated upon detection of the explosion. An explosion suppression
system or explosion venting is required on the ignition side of the valve because, when the isolation
valve closes, the ducting or vessels are subject to over-pressurization. The primary advantage of this
isolation method is the certainty of preventing flame propagation to other equipment or processes.
The distance between the valve and the explosion detection device should be far enough to allow the
valve to fully close before the arrival of the flame front. The valve should be activated
simultaneously with the explosion suppression system (by using pressure detection).
They stop an explosion before the developing pressure can damage the process equipment
They control any ensuing fire and reduce flame front propagation to other process equipment
They do not vent flame or other material, therefore are useful when toxic and other hazardous
materials are being handled, equipment is located indoors, or venting exposes personnel to discharge
of pressure and combustion products
They are maintained in an active condition with continuous electrical supervision of components
If you would like further information regarding explosion protection systems for combustible dusts,
please contact Risk Logic Inc.
http://www.risklogic.com/articles/sep2012.html 10/15/2015
Risk Logic Inc. Page 5 of 5
References:
FM Global Property Loss Prevention Data Sheet 7-17, Explosion Protection Systems
FM Global Property Loss Prevention Data Sheet 7-76, Prevention and Mitigation of Combustible
Dust Explosions and Fires
http://www.risklogic.com/articles/sep2012.html 10/15/2015
Explosive atmospheres
risk assessment:
a case study
EMULSIFIER l MDG 90 (kerry) 1 152 <10 280 <10 8,5 530 100-150
PROTEIN l ANI MAL l MILK l WHEY 44oc self ing te m p 25 glm3 650-800
PROTEIN l ANI MAL l MILK l WHEY 60 1 39 440 30 glm3 7.0 < 1000
R=P*C*D
w h ere:
R is the risk,
P is the hazard factor, that is the probability of
existence of the hazard,
C is the contact factor, that is the probability that the
hazard can cause damage,
D is the damage factor, that is the entity of
any damage that might occur.
STEP 1. Identification of explosion hazardous and determination
of occurrence of a hazardous explosive atmosphere
The probability of occurrence of a hazardous explosive atmosphere
is evaluated through Area Classification methods, according to EN
60079-10-1 and 61241-10. The correlation between hazard factor P
and area classification is represented in the following table:
- Hot surfaces
- Flames and hot gases
- Mechanically generated sparks
- Electrical apparatus
- Stray electric currents, cathodic corrosion protection
- Static electricity
- Lightning
- Radio frequency (RF) electromagnetic waves from 104 Hz to 3 *
1011Hz
- Electromagnetic waves from 3*1011 Hz to 3 * 1015 Hz
- lonizing radiation
- Ultrasonics
- Adiabatic compression and shock waves
- Exothermic reactions, including self - ignition of dusts.
The correlation between the factor C and likelihood of occurrence
of effective ignition sources is represented in the following table:
lndex
Parameters
0,00 0,25 0,50
l
Workers presence {W p) ever Occasionai Continuous
Dust explosion index (KST) s 200 bar* m/s 200 < KsTS 300 bar* m/s > 300 bar*m/s
Gas explosion index (Kd s 500 bar* m/s 500 < ~ s 1.000 bar*m/s > 1.000 bar*m/s
l
Dust layer depth ('-d) ssmm 5 < ~...cts 50 mm 250mm
l
Cloud Confinement (Cc) ot confined Partly confined Completely confined
Dust explosion index (KsT) s 200 ba r*m/s 200 < KsTS 300 bar*m/s > 300 bar*m/s
Gas explosion index (~) s 500 bar*m/s 500 < ~ s 1.000 bar*m/s > 1.000 bar*m/s
a) Prevention:
avoid or reduce explosive atmospheres; this objective can mainly be
achieved by modifying either the concentration of the flammable
substance to a value outside the explosion range or the concentration
of oxygen to a value below the limiting oxygen concentration (LOC);
avoid any possible effective ignition source;
h) Protection:
halting the explosion and/ or limiting the range to a sufficient level by
protection methods, e.g. isolation, venting, suppression and
containment; in contrast to the two measures described above, here the
occurrence of an explosion is accepted.
Area classification
Sources of release in
Production unit (dust):
- A,BeC
Natural gas line (gas)
Charging trucks unit (gas)
Production unitA
The basic elements for establishing the hazardous zone types are:
1. the source of release - a point or location !rom which a
gas/liquid/dust may be released into the atmosphere so that an
explosive atmosphere could be formed;
2. the grade of release - there three basic grades of release, as listed
below in order of decreasing frequency and likelihood of the
explosive atmosphere being present: continuous, primary and
secondary grade.
Internai : 20 The only source of release could be the door that is always closed . During cleaning
Sieve SV2 Secondary
External: 2NE (Non hazardous area) operations, the sieve is electrically disconnected and suction system is activated .
The only source of release could be a drap door that is opened only during cleaning
Internai : 20
Storage tank S4 Secondary and maintenance operations. In these cases, the storage tank is electrically
External: 2NE (Non hazardous area)
disconnected and suction system is activated.
Internai : 20
Packaging Secondary Closed room.
External: 2NE (Non hazardous area)
Hopper and typical
equipment: suction system,
shelf for bags, ecc.
Internai: 20 /
,.-
External: 22, extension area, a= 1,05 m /
~~~~~~~~~~~~
Air
i l l
Dust/ Air
This a scheme of cartridge
filter. In Hopper fter GV1,
the dust collected is sent to
the production line
Ho erTCl
gnition sources Presence Effictive
Reasons Reasons
(EN 1127-1) (Yes/No) (Yes/No)
Not present. The temperature conclitions inside and outside of
o the hopper are of an order of magnitude lower than the ignitionNever
temperature of the dust treated.
The hopper is subject to perioclic maintenance
quarterly.
However, one can not exclude the presence of high temperature The source of initiation occurs in case of failure (eg
Never
surfaces for the moving parts due to friction in case of failure. seizure of a bearing), but with the adequate
maintenance such event is not relevant, which is
deemed no t effective for the source of ignition.
The possible presence of flames and hot gases could be due to
lames and ho ho t work during maintenance operations.
No Never
ases However, it excludes this occurrence beacuse "Hot work permit"
procedure are adopted.
Possible mechanical sparks may be generateci outside due to the
use of unsuitable tools. In this regard, we adopt suitable tools
o Never
will be drawn up and operating procedure for this purpose.
The risk assessment approach described taken into account the main
requirement steps indicated by EN 1127:1 standard and by law no. 81 of
Apr. 9th, 2008; moreover, this approach allows to quantify the effectiveness
of prevention and protection measures in order to reduce the risk.
A similar approach can also be used for workplaces where there may be
flammable gases, vapors and flammable liquid.
Dust Explosion Fundamentals: Ignition Criteria and Pressure
Development
Robert Zalosh
Firexplo
Wellesley, MA 02481
Basic Concepts
The five ingredients required for a dust explosion are:
Combustible particulates sufficiently small to burn rapidly when ignited
A suspended cloud of these combustible particulates at a concentration above the
Minimum Explosible Concentration (MEC)
Confinement of the dust cloud by an enclosure or partial enclosure
Oxygen concentration greater than the Limiting Oxygen Concentration (LOC) for the
suspended dust cloud
Delayed ignition source of adequate energy or temperature to ignite the suspended cloud.
The National Fire Protection Association (NFPA) has had several definitions of combustible
dusts over the years. The current definition in NFPA 654 is a combustible particulate solid that
presents a fire or deflagration hazard when suspended in air or some other oxidizing medium
over a range of concentrations, regardless of particle size or shape. Previous editions of NFPA
654 and the 2004 edition of the NFPA Glossary of Terms define a combustible dust as any
finely divided solid material that is 420 microns or smaller in diameter (material passing a U.S.
No. 40 Standard Sieve) and presents a fire or explosion hazard when dispersed in air. The
reason for the revision is that many combustible fiber segments, flat platelets, and agglomerates
do not readily pass through a No. 40 sieve, but they can be dispersed to form a combustible dust
cloud.
In practice, questions of combustibility as well as particle size often arise when evaluating the
potential explosion hazard of marginally small particles or mixtures of combustible and
noncombustible particulates. Many laboratories doing dust explosibility tests have developed
dust explosibility screening tests, also called Go/No Go tests, to deal with these questions.
Chapter 4 of the CCPS Guidelines for Safe Handling of Powders and Bulk Solids describes some
of these tests. The ASTM E27.05 Subcommittee is currently working on a revision to the
ASTM E1226-05 Standard Test Method for Pressure and Rate of Pressure Rise for Combustible
Dusts to provide a standardized Go/No Go test for potentially combustible particulates.
MEC values are determined in the U.S. per the ASTM E1515 test procedure involving tests with
various dust concentrations and a pyrotechnic igniter in a 20-liter sphere. The MEC corresponds
to the smallest concentration that produces a pressure at least twice as large as the initial pressure
at ignition. Eckhoff (2003) reports that MEC values are not very sensitive to particle diameter for
diameters less than about 60 m, but increase significantly with increasing diameter above this
approximate threshold. The majority of the materials listed in Eckhoff Table A.1 (2003) have MEC
values in the range 30 to 125 g/m3. These concentrations are sufficiently high that a 2 m thick cloud can
prevent seeing a 25 watt bulb on the other side of the cloud (Eckhoff, 2003, p.9).
The confinement needed for a dust explosion is usually from the process equipment or storage
vessel for the powder or dust. In the case of fugitive dust released from equipment and
containers, the room or building itself can represent the confinement. Often, the dust cloud
occupies only a fraction of the equipment or building volume, and the resulting explosion hazard
is called a partial volume deflagration hazard. Pressures produced from partial volume
deflagrations and the corresponding deflagration venting design bases are described in NFPA 68.
Example applications include dust collectors and spray driers.
LOC values for combustible dusts are also determined via tests in a 20-liter vessel, and the
ASTM E27 Technical Committee is drafting an ASTM standard for LOC values. LOC values
for various combustible powders and dusts listed in NFPA 69 Table C.1(b) are mostly in the
range 9 v% to 12 v% O2. Paragraph 7.7.2.5 of NFPA 69 requires that the oxygen concentration
for an inerted process system should be less than the measured LOC by at least 2 volume percent
for systems in which the oxygen concentration is continually monitored and no greater than 60%
of the LOC if the oxygen concentration is not monitored.
Ignition Criteria
Hot Temperatures
One hot temperature ignition scenario entails a dust cloud accidentally entering a hot oven or
furnace. This occurred in the CTA Acoustics phenolic resin dust explosion incident investigated
by the U.S. Chemical Safety Board (CSB, 2005). The resin dust cloud in that incident was
generated during cleaning of fugitive dust from the area around the oven.
The minimum dust cloud oven ignition temperature is determined by oven tests described in
ASTM E1491. These include a vertical oven called the Godbert-Greenwald furnace and a
horizontal oven called the BAM furnace. BAM furnace minimum Auto-Ignition Temperatures
(AITs) are usually 20oC to 60oC lower than the corresponding dust cloud ignition temperatures
measured in the Godbert-Greenwald furnace. Most of the Godbert-Greenwald dust cloud
ignition temperatures listed in Eckhoffs Table A.1 are in the range 420oC to 660oC.
When the high temperature is on a hot surface of limited area, the required surface ignition
temperature is higher than the standard furnace tests. Figure 1 shows some test data for surface
areas in the range 20 mm2 to 1000 mm2, and comparison with the BAM furnace data.
Figure 1 Hot surface ignition temperature versus surface area (Eckhoff Figure 5.25)
Examples of hot surface ignitions in dust explosion incidents include overheated failed bearings
and driers. Clearly, the former would require a surface temperature much higher than the
ignition temperature measured in the standard oven tests, but the latter might require a lower
temperature than the standardized tests because of the possibility of a dust layer remaining in the
drier for a long time. An aerated cell test described by Abbot (1990) and the CCPS Guidelines
reference (2005) has been developed for drier hot layer ignition scenarios. The aerated cell test
produces an exotherm onset temperature at which oxidation reactions leading to layer fires first
occur. Most of the exotherm onset data reported by Abbot (1990) were in the range 125oC to
175oC. These temperatures are lower than the dust layer minimum hot surface ignition
temperatures measured in the more common tests conducted in ambient air (ASTM E2021).
Self-Heating
Certain particulate materials are prone to self-heating that can potentially lead to spontaneous
ignition. The predominant chemical reaction is low level oxidation. Examples of materials that
can self-heat by oxidation at relatively low temperatures include ABS resin powder, activated
carbon, coal (particularly Powder River Basin coal), and various chemical intermediates.
Materials such as freshly manufactured/dried wood chips, anhydrous calcium hypochlorite, and
hops are subject to self-heating by moisture absorption/condensation. Organic peroxides and
other potentially unstable chemicals can self-heat by exothermic decomposition. Various
agricultural materials, such as bagasse and soybeans, start self-heating by microbiological
processes. In many of these and other materials, multiple self-heating mechanisms overlap and it
is difficult to distinguish the dominant mechanism at a given temperature.
Self-heating is typically manifested as smoldering in the interior of a large storage pile of
particulates or in an accumulated layer in a dryer. If the smoldering particulates in the pile or
dryer are subsequently disturbed and exposed to air, the smoldering can evolve into flaming.
When the flaming nest or agglomerate is then transported to a hopper or dust collector, it can
ignite the suspended dust cloud as discussed in the preceding section.
Various laboratory tests have been developed to determine self-heating onset temperatures for
different sample sizes and configurations. These include particulate basket tests in an isothermal
oven, heated air flow tests with a slow rate of air temperature rise, and material in a package test
to determine the Self-Accelerating Decomposition Temperature. Application of laboratory self-
heating data to plant conditions requires use of appropriate volume scaling methods described in
handbook references including Babrauskas (2003), the CCPS Guidelines (2005), and Gray
(2002). In addition to showing how the self-heating onset temperature decreases with increasing
size of the particulate pile or layer, the scaling relationships also can be used to assess how the
expected time-to-ignition increases with the pile or layer size. The combination of laboratory
data and the scaling equations can then be used to establish appropriate plant level precautions to
prevent self-heating and spontaneous ignition.
Impact/Friction
Impact and frictional heating during combustible powder processing and during
maintenance/repairs involving cutting and grinding have been responsible for igniting many dust
explosions. Grinders, hammermills, and other size reduction equipment are particularly prone to
ignitions during operation. Blenders with rotating element tip speeds greater than 1 m/s are also
vulnerable to this scenario. Tramp metal stuck in a screw conveyor or a particle classifier
represents another frictional ignition scenario.
Figure 2 Boundaries for steel surface frictional and impact ignition of dust clouds (from Babrauskas, 2003)
One common friction ignition scenario is a blender with a rotating helical screw impeller. Jaeger
(2001) provided guidance on how the mixing speed and blender fill level can be used to control
frictional ignition hazards. He states that there is a negligible chance of ignition when the fill
level is greater than 70%, no matter what the impeller tip speed is. When the tip speed is greater
than 10 m/s and the fill level is less than 70%, there is a high probability of dust cloud ignition.
At tip speeds between 1 m/s and 10 m/s and fill levels less than 70%, Jaeger provides a MIE
versus AIT relationship analogous to that in Figure 2, to show which combustible dusts can be
blended without any likelihood of ignition.
Single impact spark ignition experiments described by Eckhoff (2003) have shown that the
probability of igniting a corn starch dust cloud increased with increasing impact energy, and that
it also depended on the impact velocity. Lower speed impacts produced a much greater
probability of ignition than higher speed impacts for a given impact energy. The metal
combinations involved in the impact also play an important role in the probability of ignition.
Steel-steel impacts and aluminum-steel impacts did not ignite corn starch dust clouds, whereas
titanium impacts against rusty steel did ignite dusts with MIE values below roughly 10 mJ. The
titanium-rusty steel impacts produced thermite reaction sparks, while the aluminum-rusty steel
impacts did not.
Electrical Equipment
Electrical equipment and wiring can potentially ignition dust clouds by sparks, arcs, or heated
surfaces. Dust Ignitionproof equipment is enclosed in a manner that excludes dusts and does not
permit arcs, sparks, or heat otherwise generated or liberated inside of the enclosure to cause
ignition of exterior accumulations or atmospheric suspensions of a specified dust on or in the
vicinity of the enclosure. UL 1203 describes the design, fabrication, and testing required to
certify electrical equipment as Dust Ignitionproof.
When electrical equipment and wiring is used in locations in which combustible dusts can be
present, there is a need to establish the Class II hazardous location classification of the area. Per
NFPA 70, a Class II Division 1 location is one in which combustible dust is in the air under
normal operating conditions in quantities to produce explosive or ignitable mixtures, or where
mechanical failure or abnormal operation of machinery or equipment might cause such explosive
or ignatible mixtures to be produced, and might also provide a source of ignition through
simultaneous failure of electrical equipment (NFPA 70 definition). There are three possible
conditions for the existence of a Class II Division 2 location. The first condition is a location in
which combustible dust due to abnormal operations may be present in the air in quantities
sufficient to produce explosive or ignitable mixtures. The second and third conditions refer to
dust accumulations that could be either suspended or ignited during equipment malfunctions or
abnormal operations. Class II locations are further classified as Group E, F, or G depending on
the type of dust material. NFPA 499 provides guidance and examples for the assignment of
appropriate Class II Division 1 and 2 classifications for combustible powder and dust processing
and handling operations.
NFPA 70 Article 500.7 permits Dust Ignitionproof electrical equipment in Class II Division 1
and 2 areas. Similarly, intrinsically safe electrical equipment (in which all circuits cannot
produce a spark or thermal effect capable of igniting a dust cloud per UL 913) is also allowed in
these areas. Dusttight equipment is permitted in Class II Division 2 areas. Article 502 of NFPA
70 describes the types of acceptable wiring in Class II Division 1 and 2 locations. Threaded
metal conduit together with dusttight boxes and fittings is one acceptable method commonly
used. The use of electrical sealing putty at boundaries of Class II areas is also described in
Article 502.
Electrostatic Discharges
Electrostatic discharges occur are preceded by charge accumulation on insulated surfaces,
ungrounded conductors (including human bodies), or particulate materials with high resistivities.
The subsequent electrostatic discharge is only an ignition threat if it is sufficiently energetic in
comparison to the Minimum Ignition Energy of the pertinent dust cloud. Different types of
electrostatic discharges have correspondingly different maximum discharge energy capacities as
listed in Table 1.
Table 1 Types of Electrostatic Discharge
Type of Discharge Maximum Energy1 (mJ) Examples
Corona 0.1 Wires, Type D Bulk Bags
Brush 1-3 Flexible boots and socks
Bulking Brush 1 - 10 Piles of powders with resistivities > 109
-m in hopper or silo
Propagating Brush 1000 - 3000 Boots, plastic pipe or duct
Spark > 10,000 Ungrounded conductor, e.g. baghouse
cage, or person, e.g. packager
1. Maximum energies are from Figure 5.3.1 of NFPA 77-2006.
Since combustible dust MIE values are substantially greater than 0.1 mJ, corona discharges are
not an ignition threat. In fact, Type D bulk bags are deliberately designed and fabricated to
safely dissipate accumulated charges via corona discharges. A recent study by Glor and
Schwenzfeuer (2005) has shown that brush discharges were not able to ignite clouds of dusts
with MIE values less than 1 mJ, thus correcting a different impression obtained from earlier
studies. Since brush discharges do ignite flammable vapors, they are an ignition threat for hybrid
dust-vapor mixtures such as occur in processes with flammable solvents.
The most hazardous situation for a bulking brush discharge ignition is filling a hopper with a
high resistance material combination of large particles with diameters over 1 mm together with
fines with a MIE less than 10 mJ. Some of the dusts listed in Eckhoffs Table A.1 (2003) with
MIE values less than 10 mJ include certain wood dusts (with 39 weight % < 20 m), naphthalene
with a median diameter of 95 m, zinc stearate with a 13 m median diameter, and toner with
median diameter of 23 m and less. Transport and processing of these easily ignitable dusts
require special precautions to prevent brush and bulking brush discharges. Precautions provided
in NFPA 77 Chapter 9 and in Brittons (1999) chapter 6 are especially important for these dusts.
A propagating brush discharge can occur when a charged non-conductor is in direct contact with
a conductive surface, such as a metal surface coated with a plastic film or a layer of high
resistivity powder (Glor, 2005). The Propagating brush discharge occurs when the surface
charge density is sufficiently large to cause electrostatic breakdown at the nonconductor surface.
Streamers carry the surface charge to a central region where it intensifies as shown in Figure 4.
Propagating brush discharges can ignite dusts with MIE values less than about 3 J.
The most commonly used dust explosion protection method is deflagration venting. The
effectiveness of deflagration vents depends on the level of turbulence in the process vessel and
the vessel size and shape as well as the vent design and the dust characteristics cited above.
NFPA 68 Chapter 7 provides dust deflagration design requirements.
Inter-vessel deflagration propagation and pressure piling does not always occur. Lunn et al.
(1996) did not observe deflagration propagation in tests with a 15 cm diameter pipe, and later
vented explosion tests using a pipe with a sharp 90 degree elbow produced pressure enhancement
in only one of many tests conducted (Skjold, 2007). However, when the deflagration does
propagate into the interconnected vessels, the jet flame ignition of the dust cloud in the second
vessel produces a much more rapid rate of burning and associated pressure rise. The more rapid
burning and pressure rise can render explosion venting or explosion suppression systems
ineffective in the second vessel. Hence, there is often a need for explosion isolation systems to
supplement the installed explosion protection for an individual vessel. NFPA 69 provides the
requirements for various types of passive and active explosion isolation systems.
Secondary Dust Explosions
Most of the casualties from dust explosions occur when the initiating explosion within some
equipment or enclosure breaches the equipment/enclosure and causes a secondary explosion in
the surrounding building. The secondary explosion occurs when dust deposits on exposed
surfaces in the building are lifted by the blast wave emanating from the breached
equipment/enclosure, and then are ignited by the flame vented from the breached
equipment/enclosure. Figure 4 shows a dust cloud formed when an air blast wave propagated
over a corn starch layer in experiments conducted by Scherpa (2002). Air blast velocities of 12
to 48 m/s lifted 13% to 44% of the deposited cornstarch.
Figure 4. Corn starch dust cloud produced from air blast over dust layer (from Scherpa, 2002)
These secondary dust explosions are particularly devastating because they produce large burning
dust clouds and pressures beyond the strength of most buildings. The two critical prevention
measures are the installation of effective explosion protection for the combustible powder/dust
processing and handling equipment (including explosion isolation), and minimizing combustible
dust layer accumulations on equipment and building surfaces. NFPA 654 provides requirements
for maximum allowable dust layer thicknesses and surface areas with dust accumulations. Some
of the other papers at this Symposium offer guidance on how different types of industrial
facilities are attempting to meet these requirements, and possibly improve them.
References
Abbot, J. Prevention of Fires and Explosions in Dryers, Institute Chem Engrs, 1990.
ASTM E1226-05, Standard Test Method for Pressure and Rate of Pressure Rise for
Combustible Dusts, American Society for Testing and Materials, 2005.
ASTM E1491-06, Standard Test Method for Minimum Autoignition Temperature of Dust Clouds,
American Society for Testing and Materials, 2006.
ASTM E1515-07, Standard Test Method for Minimum Explosible Concentrations of Combustible
Dusts, American Society for Testing and Materials, 2007.
ASTM E 2019-03 Standard Test Method for Minimum Ignition Energy of a Dust Cloud in Air,
American Society for Testing and Materials, 2003.
ASTM E 2021-01 Standard Test for Hot Surface Ignition Temperature of Dust Layers, American
Society for Testing and Materials, 2001.
Babrauskas, V., Ignition Handbook, Fire Science Publishers, 2003.
Britton, L., Avoiding Static Ignition Hazards in Chemical Operations, AIChE CCPS, 1999.
CCPS, Guidelines for Safe Handling of Powders and Bulk Solids, AIChE Center for Chemical
Process Safety, 2005.
CSB, 2005. Investigation Report. Combustible Dust Fire and Explosions, CTA Acoustics, Inc., Chemical
Safety Board, February 2005.
Eckhoff, R., Dust Explosions in the Process Industries, 3rd Edition, Gulf Professional Publishing, 2003.
Gray, B., Spontaneous Combustion and Self-Heating, SFPE Handbook of Fire Protection
Engineering, 3rd Edition, pp. 2-211-228, SFPE, NFPA, 2002.
Glor, M., Electrostatic Ignition Hazards in the Process Industries, J. of Electrostatics, v 63, pp.
447-453, 2005.
Glor, M. and Schwenzfeuer, K., Direct Ignition Tests with Brush Discharges, J. of
Electrostatics, v 63, pp. 463-468, 2005.
Gummer, J. and Lunn, G., Ignitions of Explosive Dust Clouds by Smouldering and Flaming
Agglomerates, J. of Loss Prevention in the Process Industries, v. 16, pp 27-32, 2003.
Jaeger, N., Safety strategy against potential hazards due to the handling of powders in a
blending unit, J. Loss Prevention in the Process Industries, v. 14, pp 139-151, 2001.
Lunn, G., Holbrow, P., Andrews, S., and Gummer, J., Dust explosions in totally enclosed
interconnected vessel systems, J. Loss Prevention in the Process Industries, v. 9, pp. 45-
58, 1996.
NFPA 68, Explosion Protection by Deflagration Venting, National Fire Protection
Association, 2007.
NFPA 69, Standard on Explosion Prevention Systems, 2008.
NFPA 70, National Electrical Code, National Fire Protection Association, 2008.
NFPA 77, Recommended Practice on Static Electricity, 2007.
NFPA 499, Recommended Practice for the Classification of Combustible Dusts and of
Hazardous (Classified) Locations for Electrical Installations in Chemical Process Areas,
National Fire Protection Association, 2008.
NFPA 654, Standard for the Prevention of Fire and Dust Explosions from the Manufacturing,
Processing, and Handling of Combustible Particulate Solids, National Fire Protection
Association, 2006.
Scherpa, T., Secondary Dust Cloud Formation from an Initiating Blast Wave, WPI M.S.
Thesis, 2002.
Skjold, T., "Review of the DESC project," Journal of Loss Prevention in the Process Industries v.
20: 291-302, 2007.
UL 913, Standard for Safety, Intrinsically Safe Apparatus and Associated Apparatus for Use in
Class I, II, and III, Division 1, Hazardous (Classified) Locations, Underwriters
Laboratories, 1997.
UL 1203, Explosionproof and Dust-Ignitionproof Electrical Equipment for Hazardous
(Classified) Locations, Underwriters Laboratories, 1994.
Zalosh, R., Grossel, S., Kahn, R., and Sliva, D., Safely Handle Powdered Solids, Chemical
Engineering Progress, v. 101, pp. 23-30, 2005.
Combustible Dust
Hazard Recognition
an Insurers View
Visit Protocol
FM Global data sheets
Target hazards depending on occupancy
How do we target hazards?
INDUSTRY TYPE Number
Woodworking 64
Food 26
Metals 18
Chemical/Pharmaceutical 14
Pulp/Paper 12
Mineral 11
Utility 7
Plastics 5
Rubber 5
Various 4
EQUIPMENT TOTAL 166
How do we target hazards?
EQUIPMENT TYPE Number Gross Loss %
Dust Collector 67 12
Impact Equipment 22 11
Boiler 11 18
Storage Silo 8 4
Processing Equipment 7 2
Conveyor 5 3
Oven/Dryer 8 40
Grain Elevator 4 2
Spray Dryer 4 1
Various 30 7
EQUIPMENT TOTAL 166 100
Dust - questions to answer
Is there a combustible dust in use or created?
raw materials
intermediates
products
What is a Combustible Dust?
Organic material
Plastics, wood, solid fuels,
starch, flour, grain
Unoxidized metal
Aluminum, silicon
Other oxidizable materials
Zinc stearate, sulfur, iron
sulfides (pyrites)
What is a Combustible Dust?
500 microns (1/50th inch) or smaller
different materials have different size threshold
usually range of particle sizes
larger (non-explosible) particles stay mixed: helps
inert mixture
fines segregation = increased hazard
Might not burn in pile or solid form
Solid form combustibility = certain dust explosibility
What is a Combustible Dust?
Geir Pedersen
GexCon AS
Scott Davis
GexCon US Inc
Abstract
In this paper a semi-quantitative short-cut risk analysis method (SCRAM) is presented, allowing
for the assessment of dust explosion hazards. The method is first described and two application
examples are presented.
The consequences of dust explosions are described as consequences for personnel and
consequences for equipment. The method reviews the consequences of both primary and
secondary events. Factors determining the consequences of dust explosions include the how
frequently personnel are present, the equipment strength, housekeeping and implemented
consequence-reducing measures. Both the likelihood of dust explosions and consequences are
described by classes ranging from low probabilities and limited local damage, to high probability
of occurrence and catastrophic damage. Acceptance criteria are based on the likelihood and
consequence of the events.
The method allows for optimal choice of adequate preventive and protective measures.
To demonstrate the method an application of the method is presented: a milk powder production
facility.
Note: Do not add page numbers. Do not refer to page numbers when referencing different portions of the
paper
GCPS 2010 __________________________________________________________________________
1. Introduction
Dust explosions are a continuous threat in companies producing flammable powders and dust as
final and intermediate products. Sad recent examples include the serious accidents in Kinston,
North Carolina in 2003 (killing 6), Savannah, Georgia in 2008 (killing 14), and one year later the
explosion in a coal silo injuring 7 in Oak Creek, Wisconsin (2009). These serious accidents are
accompanied by many smaller dust explosion accidents in industry causing limited damage and
minor or no injuries. Some of them could however have led to more serious consequences.
Dust explosion risks prevailing in industrial facilities are dependent on a large variety of factors
that include process parameters, such as pressure and temperature, as well as equipment
properties, such as the presence of moving elements, the mechanical strength of such dust
handling equipment, dust explosion characteristics, and mitigating measures taken including
housekeeping and protective measures such as explosion venting.
The method is described and an application example presented. The example demonstrates the
strength of the method and the support it offers to industry for choosing appropriate risk
mitigating measures.
This chapter describes the methodology used to determine the risk for dust explosions in
industrial facilities. The risk for a dust explosion is the product of the probability of a dust
explosion occurring and the consequences of the dust explosion. The consequences can be
divided in primary consequences such as failure of the piece of equipment in which the dust
explosion occurs and secondary consequences such as a an ensuing fire and secondary
explosions in connected equipment or in the working area due to whirling up and subsequent
ignition of dust layers there.
For a dust explosion to occur a flammable atmosphere must be present and simultaneously a
sufficiently strong ignition source. The dust concentration in this atmosphere must exceed a
certain limits, typically 30 g/m3, and the particle size distribution must be sufficiently small. Dust
with particle size distribution from 10 to 40 micron and dust concentration range from 250 to
1500 g/m3 have shown to ignite easiest and produce the most severe explosions. Finer dust
might produce more severe explosions if the dispersion process has enough force to break up the
agglomerates and produce a dust cloud consisting of primary particles.
GCPS 2010 __________________________________________________________________________
To be able to quantify the probability for the occurrence of an explosive atmosphere, properties
of the combustible material should be considered, together with how likely it is that the
combustible material will be mixed with air.
The probability of a specific ignition source being able to ignite the explosive atmosphere is
considered based on different criteria, such as the energy released by the ignition source, the
period in which this energy is supplied, the surface temperature of the ignition source and its
size. For mechanically generated sparks, collision speed, friction, contact time and physical
properties of the colliding materials are included.
The factors mentioned above are considered individually and form the basis for estimating how
often an explosion can occur. It is not possible to give the exact frequencies for an explosion. In
a risk analysis the probability for an explosive atmosphere and the probability for an ignition
source are ranged from I to V, where I has the lowest probability and V has the highest
probability. Each range (I, II, III, IV and V) describes a range in probability or frequency.
The probability for a secondary event depends on the probability for the primary event and is
normally lower than that of the primary event.
The consequence for personnel (Dp) and equipment (De) is estimated based on the expected
effect of the explosion. This is estimated based on expected damage caused by the heat, pressure
or loose items after the definitions given below. The consequence for personnel and equipment
from an explosion depends on the explosion pressure and the heat intensity from the explosion.
Pressure build-up in enclosed units might cause the units to rupture resulting in heat radiation
from flames, dispersion of pressure waves and flying objects.
The strength of an explosion depends on several factors, for example the initial conditions of the
dust cloud, including the fuel concentration, initial turbulence and the position of the ignition
source. The properties of the combustible material are also important, including chemical
composition. The properties of the explosive atmosphere will change over time hence, the time
of the explosion is important for the explosion propagation.
Flames propagating out from a ruptured vessel release heat that might injure personnel or cause
damage to equipment. The convective heat transfer during an explosion causes the most severe
burns. Burns/damage might be the result if personnel or equipment are in direct contact with the
explosion flame.
GCPS 2010 __________________________________________________________________________
2.3 Definitions
The probability or the frequency of an explosion occurring and the potential consequences is
estimated from I to V, as described previously. The definition and description of the different
values are given below.
Table 1 Definition of the probability and consequence for explosions under normal
operation
The explosion risk is the product of the probability of an explosion occurring and its
consequences. In the present risk analysis a qualitative risk evaluation is completed for each
process unit. The risk level for explosions can be estimated from the matrix given in Figure 1
below, based on the probability and consequence, as described in the above section, and after the
definitions in Table 1 also above. The risk level increases from E to A.
V C B A A A
IV D C B A A
Consequence
III E D C B A
II E E D C B
I E E E D C
I II III IV V
Probability
The risk level and the recommended acceptance criteria are selected and based on the
probability for human and economical loss according to Table 1 above. The selected criteria are
given in Table 2 below. It should be emphasized that these acceptance criteria are a proposal
only and may be chosen differently.
GCPS 2010 __________________________________________________________________________
In the application example given in this document, the estimations of probabilities and
consequences are summarized in tables. These tables also include estimations of ignition source
probability and an estimate of the risk of secondary incidents/events.
Below, explanations to the different parts of the tables are given.
IV II I I I I II
EXPOSURE TO EXPLOSION
PRIMARY EXPLOSION
I II III III E D
I I V V C C
Comments:
EXAMPLE
GCPS 2010 __________________________________________________________________________
Consequence: The consequences for an event considering both personal injuries and
damage to equipment. Both primary and secondary consequences are given.
Definitions for explosion related probability, (and consequences) are given
in the above section.
Risk: The product of probability and consequence. Both the risk of primary and
secondary events is estimated. See Table 2 for acceptance criteria.
Ignition source: Probability for occurrence of the five most common ignition sources are
given.
3.1 Analysis
The analysis has been performed for the dryer only.
To perform the risk analysis the explosion properties of milk powder need to be known.
Although it is strongly preferred to have these properties determined for the milk powder in
question the present study was performed using literature data. This may lead to
overconservative preventive and protective measures resulting from the analysis since one would
normally base oneself on the most conservative values of published data. On the other hand an
underestimate of the hazards may also be possible, especially for dusts where only a limited set
of explosion properties is available. For milk powder the use of literature data is acceptable since
GCPS 2010 __________________________________________________________________________
there is a rather big number of well-described data available which are not varying much. The
data found for milk powder are presented in Table 4 (from Beck et al, 1997).
In addition to the properties presented in Table 4 it is known that milk powder stored in bulk
might self-ignite when exposed to a higher temperature over a longer period. Tests show that
storage at a temperature of 80-90 C during a period exceeding 20 hours results in self-ignition
(Le Maillard reaction).
Hazards identification
Under normal operating conditions the average dust concentration in the dryer is below the lower
explosion concentration. Locally in the cone however one can expect that flammable
concentrations can be reached though being it intermittently. An initial local explosion could
however whirl up dust present on the cone walls causing a stronger secondary explosion (Siwek
et al., 2004). Potential ignition sources include mechanical sparks due to the rotating spraying
GCPS 2010 __________________________________________________________________________
wheel in the top of the dryer coming loose and hitting the wall of the dryer (In the light of the
minimum ignition temperature and minimum ignition energy of milk powder this ignition source
is most likely not able to cause ignition) and self-heating of layers of milk powder. The latter
would especially be possible if the rotating spraying wheel, in case of an anomaly, is distributing
the milk slurry against the walls of the cylindrical part of the dryer. The hot drying air could
cause the resulting milk powder cake to self-ignite. The smoldering material could come loose
and fall into the cone of the dryer, causing either ignition of a flammable dust cloud there or
whirl up dust and causing this to ignite.
The probability of the latter is relatively high and based on historical evidence an explosion
should be expected with a frequency of between 10-1 and 10-2 per year (probability class III).
Here it is assumed that the ignition source also causes the dust cloud (a smoldering cake of milk
powder falling into the cone of the dryer).
A final ignition source could be an explosion occurring in other parts of the drying installation
running back into the dryer. This ignition source, although very realistic, is not considered here
since in a full risk analysis of the spray dryer installation it has to be considered in the analysis of
the other pieces of equipment of the installation. In this document it is assumed that sufficient
preventive and protective measures are taken to prevent this from happening, i.e. the likelihood
of this ignition source occurring is assumed to be sufficiently low.
The consequence of the explosion is most likely the failure of the dryer (explosion tests reported
by Siwek et al. (2004) show that pressure up to 1 bar are possible; it should be mentioned
however that these tests were performed under conservative conditions) potentially injuring
personnel or even causing fatalities if in the vicinity of the dryer at that very moment
(consequence classes III and IV respectively). Moreover there is a possibility that the explosion
propagates into the fluid bed or the cyclones and into the bag filter (secondary incident). This
probability is however lower than the probability of an explosion (probability class II). The
consequences are however more severe: loss of the plant (consequence class IV) and most likely
loss of one or several lives (consequence class V).
The analysis is summarized in Table 5. The table also determines the risk based on the various
probabilities and associated consequences.
Risk evaluation
The results of the analysis of the spray dryer as summarized in Table 5. The Table shows that the
risks are either medium (implying that risk reducing measures should be implemented) or high
(implying risk reducing measures must be implemented). Hence two alternatives are
investigated: one where a single preventive measure is introduced reducing the probability of
explosions and a second one where this preventive measure is combined with protective
measures.
smoldering before a hazardous situation arises (Steenbergen et al, 2007). Including this
preventive measure a new analysis has been performed of the explosion risks of the spray dryer.
EXPOSURE TO EXPLOSION
PRIMARY EXPLOSION
II III IV III C C
II II V IV B C
Comments:
Hazard identification
The introduction of a CO-detection system will reduce the probability of an explosion. An early
detection of smoldering combustion is assumed to reduce the probability of explosions by at least
a factor of 10 implying a probability of explosions of class II. The probability of equipment be
damaged and personnel being affected will be reduced accordingly both for primary and
secondary incidents. The consequences are however still similar. This results in risks as
summarized in Table 6.
Risk evaluation
Table 6 shows that risks have been reduced by introducing a CO-detection system compared to
Table 5 presenting the original risks without any preventive or protective measure. The
GCPS 2010 __________________________________________________________________________
EXPOSURE TO EXPLOSION
PRIMARY EXPLOSION
II II IV III C D
I I V IV C D
Comments: A CO-detection system has been included.
remaining risks for personnel which are described as medium according to the acceptance
criteria proposed in Table 2 should be addressed by introducing further risk reducing measures.
A described in section 3.1 an additional analysis is presented where the preventive measure of
CO-detection is combined with protective measures. A combination of explosion venting and
explosion isolation by extinguishing barriers between the dryer and fluidized bed and the dryer
and the cyclones is investigated.
3.3 New analysis investigating the introduction of preventive measures in combination with
protective measures
Reducing the probability of an explosion by introducing CO-detection still leaves personnel
exposed to a medium risk. Hence additional protective measures are proposed. The effects of
introducing a combination of explosion venting and explosion isolation (extinguishing barriers)
have been investigated.
GCPS 2010 __________________________________________________________________________
Hazard identification
The probability of explosions assuming an early detection of smoldering combustion is still as
described in section 3.2 equivalent to a probability class II. The consequences of possible
explosions are however reduced considerably. Assuming use of appropriate venting devices,
sufficient venting surface and taking into account the effect of vent ducts (which are necessary
since the spray dryer is installed inside a building) and adequate installation distances for the
extinguishing barriers (containing sufficient extinguishing powder to extinguish flames) the risk
of explosion in the spray dryer can be reduced considerably. The consequences of an explosion
are now reduced to limited or no damage both for the primary and secondary events
(consequence class I).
Risk evaluation
Introducing explosion protective measures as described reduces the risks both for the equipment
and personnel to acceptable levels. The reduction of consequences to consequence class I
(replacement of vent panels and refilling of extinguishing barriers (neglecting the costs of loss of
some produced milk powder)) results in risk levels E implying that no further measures would be
necessary. Results of the analysis have been presented in Table 7.
4. Conclusions
A semi-quantitative short-cut risk analysis method (SCRAM) has been presented, allowing for
the assessment of dust explosion risks and choosing adequate preventive and protective
measures. The performance of such an analysis makes industry aware of the most hazardous
areas in their facilities and associated consequences in case of an explosion.
The application example demonstrates the strength of the method and the support it offers to
industry for choosing appropriate risk mitigating measures.
GCPS 2010 __________________________________________________________________________
EXPOSURE TO EXPLOSION
PRIMARY EXPLOSION
II II I I E E
I I I I E E
Comments: A CO-detection system has been included combined with explosion venting
and isolation.
5. References
Beck H., Glinke N.and Mohlman C., BIA-Report: Combustion and explosion characteristics of
dust, HVBG, Berufsgenossenschaftliches Institut fr Arbeitssicherheit BIA 13/97, 1997.
Siwek, R., van Wingerden, K., Hansen, O.R., Sutter, G., Schwartzbach, Chr., Ginger, G., &
Meili, R., Dust explosion venting and suppression of conventional spray driers. Eleventh
International Symposium on Loss Prevention, Prague, May 31 June 3, 2004.
Steenbergen, A.E., Van Houwelingen, G. and Straatsma, J., System for early detection of fire in
a spray drier, International Journal of Dairy Technology, 44, no. 3, pp. 76-79, 2007.
staubEX_e_Nachdruck.qxd 30.10.2006 10:50 Uhr Seite 33
the basics of
dust-explosion protection
staubEX_e_Nachdruck.qxd 30.10.2006 10:49 Uhr Seite 2
Powders or dust like substances are processed or are byproducts of the production process in
many industries.
Whether the dust is useful (e.g. for the production of plastics, pigments or pharmaceuticals)
or waste, a large majority of dustlike substances pose the danger of fire or possibly even
explosions. Eighty percent of all industrial dusts are combustible, and even a dust layer of 1 mm
in a closed room is sufficient to result an explosion when the dust is swirled up and ignited.
These facts, combined with the fact that those affected are not sufficiently aware of the danger
(in contrast to the hazard of gas explosions) underlines the importance of preventing dust
explosions. This brochure is intended to help you analyse the risk of a dust explosion in your
facilities and to take the suitable technical and organisational steps to minimise this risk.
contents
1 Dust as a Risk Factor 4
77 Equipment Selection 22
9 Product Overview 30
dust-explosion protection
1 dust as a risk factor
4
Dust explosions have a different process of Figure 2 shows the results of statistical studies in
propagation than gas explosions and can in some North America, which examined the distribution
cases be much more devastating. If a gas/air of the ignition sources that caused dust explosions.
mixture is ignited, the force of the resulting ex- It shows that mechanically produced sparks
plosion causes the gas cloud to dissipate were responsible in almost one third of the cases.
rapidly and thus dilutes the gas/air mixture to a Add to that the 13 % of explosions caused by open
concentration lower than that necessary for further fire and welding, and it becomes obvious that
combustion. Thus, if no further gas is added, the many people are not aware of the danger of dust
explosion is over after several milliseconds. explosions. Figure 3 shows that a wide variety
of industries are affected, including branches of the
Figure 1: Explosion Risk Triangle
food and wood processing industries, paper and
plastics materials production, pharmaceuticals
production and others.
dust-explosion protection
2 definitions and characteristics
6
Explosive Dust Mixture with air, under atmospheric conditions, of flammable The condition is that the process
Atmosphere substances in form of dust or fibers in which, after ignition, ends only after one reactant has
combustion spreads throughout the unconsumed mixture been entirely consumed.
(IEV 426-02-4).
Hazardous Explosive atmosphere in hazardous amount. The presence A thickness of a dust layer less
Explosive of a hazardous explosive atmosphere must be assumed if than 1 mm on the floor of a normal
Atmosphere ignition causes an exothermal reaction that endangers people, room is sufficient to cause a
domestic animals and property. hazardous explosive atmosphere.
Size of particle Dust particles larger than 400 m are not explosive. Depending on friction, the transportation and processing of
Dust particles are explosive when they measure less coarse dust result in the formation of fine dust.
than 400 m and up to 20 m
Explosion limits As with gases, dust is explosive within certain These characteristics vary widely throughout the entire range.
concentration limits: Extreme dusts can form an explosive mixture in concentrations of
lower explosion limit: approx. 2060 g/m 3 air less than 15 g/m 3.
upper explosion limit: approx. 26 kg/m 3 air
Maximum explo- In enclosed containers of simple design, combustible dust In exceptional cases, such as with light metal dusts, explosive
sion pressure can reach an explosive pressure between 6 and 10 bar. pressure of up to 20 bar may develop.
KSt -value This is a classifying value expressing the shattering power This figure is the basis for calculating pressure relief areas.
of the combustion. Nummerically, it is equal to the value for
the maximum rate of explosion pressure rise during explosion
of a dust/air mixture in a 1 m 3 vessel.
Minimum igni- Lowest engery which is sufficient to effect ignition of Not every spark is capable of causing ignition. The decisive factor is
tion energy Emin the most easily ignitable explosive dust atmosphere under whether sufficient energy is introduced into the dust/air mixture to
speciefied test conditons ( EN 13237). initiate a self-substaining combustion of the entire mixture.
A modified Hartmann tube (Figure 5) is used to determine the minimum
ignition energy.
Ignition The lowest temperature of a hot inner wall of a furnace The shape of the vessel in which the ignition temperature is deter-
temperature of at which ignition occurs in a dust cloud in air contained mined has proved to be especially critical. It may be assumed that
a dust cloud Tic therein (EN 50281-2-1). ignition on differently shaped surfaces is, in practice, only possible
at much higher temperatures. In the case of dust from food products
and animal feed, this figure is between 410 and 500 degrees C,
depending on type.
Ignition The lowest temperature of a hot surface on which a This temperature describes the ignition behaviour of thin dust layers.
temperature of ignition occurs in a dust layer of specified thickness If the layer is thicker, or if the ignition source is completely inundated
a dust layer Til on a hot surface (EN 50281-2-1). by dust, the thermal insulation provided by the dust layer increases,
resulting in quite different, sometimes significantly lower temperatures,
which could trigger an exothermal reaction. Experiments have shown
that the ignition temperature decreases nearly linearly with an in-
crease in the layer thickness. The ignition temperature of a dust layer
is sometimes considerably lower than the ignition temperature of a
mixture of the same dust in air. The maximum permissible surface
temperature for electrical equipment may be higher, depending on the
dusts thermal conductivitiy. Unnoticed glowing spots can exist un-
noticed for long periods in thick layers of dust and can, if the dust is
swirled up, become effective ignition sources.
dust-explosion protection
2 definitions and characteristics
8
dust-explosion protection
3 legal basis and standards
10
11
After this, in Germany a certificate of conformity Table 5: Comparison of Old IEC 61241 Standards and New Suggestion
for electrical equipment to be used in Zone 10
Number of Proposed Subject Planned
became a legal requirement, based on the VDE Current Standard New Number Date
standard. VDE 0170/0171, Part 13 developed by
following the action of IEC. Based on this standard, IEC 61241-1-1 IEC 61241-0 General requirements 2003
Directive 94/9/EC provided a new regulation IEC 61241-2-2 IEC 61241-20-2 Test methods 2005
for explosion protection in Europe. This directive
formulates the requirements to be fulfilled by IEC 61241-2-3 IEC 61241-20-3 Test methods 2005
manufacturers of electrical and no electrical IEC 61241-3 IEC 61241-10 Classification of areas 2003
equipment. The Explosion Protection Regulation of
December 1996 (Explosionsschutzverordnung) IEC 61241-4 IEC 61241-2 Protection by pressurization pD 2005
transfers this directive into German law. In Annex I,
IEC 61241-5 IEC 61241-11 Protection by intrinsic safety iD 2002
Directive 94/9/EC mentions, in the course of an
explanation of Equipment Group 2, only the danger IEC 61241-18 Protection by encapsulation mD 2004
presented by an explosive atmosphere consisting
IEC 61241-17 Inspection & maintenance
of a dust/air mixture, which does not seem to in-
clude dust deposits. The special risk presented by IEC 61241-19 Repair & overhaul
these dust deposits as a source of release is only
taken into account in the zone classification
insofar as other circumstances, such as a swirling
up of the dust by air currents, could cause an 99/92/EC. As part of the consolidation of
explosive atmosphere. standards dealing with dust and gas, the goal at
the IEC level is to adapt the numbering of the
The questions of proper use are addressed by dust standards to the IEC 60079 standard series
Directive 1999/92/EC. The current treatment of (Table 5). This plan is laudable, because it
dust explosion protection in Directive 1999/92/EC would create analogous standards for gas and
is not very comprehensive and is limited to dust explosion protection.
a simple definition of zones and a reference to
deposits of combustible dust.
dust-explosion protection
4 dust explosion protection measures
12
13
4.3 Constructional Explosion Protection this ejection process from the relief apertures
associated with the explosion pressure relief
Constructional explosion protection is a method of also contains burnt and unburnt combustible
avoiding the hazardous effects of explosions substances. It must always be checked whether
and/or of limiting the effects of an explosion to a the consequences of the explosion in the loca-
safe level by the use of: tion in question can be controlled.
dust-explosion protection
5 zone classification
14
15
In the new version of the Standard Classification Figure 6: Example of the Classification into Dust Explosion Hazardous Areas
of areas where combustible dusts are or may be According to IEC 61241-10
dust-explosion protection
6 dust types of protection
16
17
6.1.1 Enclosures of Moulded Materials material to become brittle which would eliminate
the required IP protection.
Thermal Endurance
Plastic materials must certainly fulfil the most For electrical equipment of Category 3D, it is
complex requirements. For electrical equipments sufficient for the material to have a TI at least 10 K
of Categories 1D and 2D, the temperature index higher than the temperature at the hottest point
TI must be known, according to EN 50281. This of the enclosure. Proof of a continuous operating
figure allows conclusions about the long-term temperature (COT) which fulfils the same
mechanical performance of moulded materials to requirement as the TI is also sufficient. No thermal
be drawn. The temperature index corresponds to endurance test is carried out in this case.
the 20,000-h point on the thermal endurance
graph without loss of flexing strenght or tenside
strenght excluding 50 %. This figure must be
20 K higher than the temperature at the hottest
point of the enclosure. In addition, the moulded
material must be proven to have sufficient
thermal resistance for the intended application.
Enclosures or parts of enclosures made of moulded
materials for electrical equipment from the
Categories 1D and 2D must be subjected
to thermal endurance tests according to EN 50014
(artificial ageing). The ageing process caused by
extreme temperatures must not cause the moulded
Table 9: Types of Protection for Use in the Presence of Combustible Dust in the Current Standards
Symbol Principle Type of Protection Current Status at IEC Future Status at IEC Status at CLC
dust-explosion protection
6 dust types of protection
18
Seals
Type of protection protection by enclosures
depends on the elastomeric seals used. These are
evaluated in accordance with Annex B3.3 of
EN 50014. This is an ageing test using specially
shaped test objects (ISO 48/ ISO 1818) which tests
the increase in hardness of the material. This
figure must not exceed 20 % difference between
Table 10: Summary of Requirements for Electrical Equipment the initial and the final figure. Materials that
Requirements: Cat. 1 + 2 Zone 20+21 Cat. 3 Zone 22 have hardened to a greater degree may lose their
No dust infiltration in enclosure IP6X IP5X
sealing properties.
Conformity to standards
Surface temp. in C, T C T C
(not temperature class)
19
An example: Moulded materials in the pipes of Table 11: Summary of the Requirements for Rotating Electrical Machines,
pneumatic conveyor systems initially receives a Type of Protection tD
strong electrostatic charge from friction on the Requirements Cat. 2 Zone 21 Cat. 3 Zone 22
inside. This charge produces an influence-charge on
Dust tightness of enclosure IP6X IP5X
the external surface, which is coated with plastic
material and covered dust. This double layer of Magnesium content in enclosure material 6% 6%
charge may contain large amounts of energy. If
Thermal properties of non-metallic as in e as in n
one short-circuits both sides of the doubly charged enclosure materials
layer, all the stored energy is violently discharged.
This causes brightly lit discharge channels to Insulation resistance of enclosure, 10 9 10 9
fan guards
form on the surface of the plastic material. This
discharge may contain several joules of energy, so Insulation resistance of the fan wheel 10 9 10 9
that nearly all gases and vapours and the majority at all speeds
of dusts will be ignited. However, propagating
External connection for as in e as in n
brush discharges are relatively rare in practice.
equipotential bonding
The following measures can prevent this type of Dust tightness of entries IP6X IP5X
discharge process such as these :
Degree of protection of the external fan as in e as in e
> Adjusting the surface resistance to 10 9 and
grounding the plastic material. Protective cover for V1 (air inlet on top) as in e
> Limiting the breakdown voltage of the non-
Fan and cover construction and mounting as in e as in e /n
conductive material to 4 kV.
> Avoiding thicknesses < 8 mm for the non-conduc- Clearances in ventilation system as in e
tive material.
> Limiting isolated capacities to < 10 pF. Magnesium content in the material 6% 6%
of the fan
> Increasing humidity to > 65 % in order to reduce
the insulation resistance of non-conductive Clearance and creepage IEC 60664 IEC 60664
materials. distances of connecting parts
CE conformity
Conformity to standards
Surface temperature in C T C T C
(not temperature class)
dust-explosion protection
6 dust types of protection
20
22 Warning as in 7.5.1.2 Internal pressurization not required The measures to be taken when the pressurization
equipment fails are graduated according to
zone and the presence of operational ignition
sources (see Table 12).
21
dust-explosion protection
7 equipment selection
22
23
Figure 7: Correlation between the Maximum Permissible Surface Temperature and the Thickness of Dust Layers
The self-ignition of dust deposits is a critical other areas by way of transportation facilities.
problem. These processes are often caused by During this process, the flames swirl up unburned
exothermal reactions involving oxygen from dust, which in turn takes deposited dust with it.
the surrounding air. It could be a chemical reaction A sudden change in the volume of the dust cloud
(oxidation), a physical reaction (adsorbtion) or a as it enters a larger room (e.g. a silo) can produce
decomposition process (mainly in the case of a hazardous explosive atmosphere. The flames
organic dusts). Self-ignition is determined of the cause ignition.
temperature of the surrounding area, of the
geometric factors and of the volume of the dust. The ignition temperature of a dust layer is
The reaction heat produced during decomposition determined using the method from EN 50281-1-2.
of materials can produce carbonisation gas, which The determination of the maximum surface
in turn can lead to an explosive gas/air mixture. temperature that an electrical apparatus can
achieve must be done by the manufacturer, with
Not every case of dust ignition necessarily leads any possible faults taken into consideration.
to an explosion. Dusts with low rate of pressure Temperature limitation measures should be used
rise may first of all be a dust fire. Under certain to counter these faults (electrical/thermal fuse).
conditions, an explosion may occur, often in The maximum surface temperature is measured
a completely different location than the ignition. as specified in Clause 10 of EN 50281-1-1.
The fire can spread from the place of origin to
dust-explosion protection
7 equipment selection
24
Figure 8: Determining the Maximum Surface Temperature When determining the maximum permissible
TL Under a Dust Layer of Thickness L in mm surface temperature (in relation to the
surrounding dust), two figures should be noted:
1. Maximum permissible surface temperature
when a dust cloud is present (calculation in
L accordance with 6.1 of EN 50281-1-2).
L The ignition temperature of the dust cloud must
be taken into account.
2. Maximum permissible surface temperature
when a dust layer is present. When making
the determination, one must take the ignition
L L temperature of a dust layer (which is dependent
on the thickness of the dust layer) into account:
> For dust deposits up to 5 mm thick, the
calculation must be made in accordance with
L 6.2.1 of EN 50281-1-2.
> For dust deposits > 5 mm -- 50 mm, the curves
in Figure 7 may be applied.
The redutions in temperature plotted here were
determined empirically for dust layers of up
to 50 mm on top of electrical equipment. The
curves take into account both the reduction,
specific to dusts, of the ignition temperature
with increasing layer thickness, and also an ex-
pected increase of the temperature of the
electronic apparatus, due to the reduction of the
heat flow. In addition, the curves include the
usual safety reduction of 75 K.
Here it must be stated explicitly that this does
not take into account an electrical apparatus
submerged completely in dust.
> Determining a surface temperature for
dust deposits > 50 mm: According to the
currently valid requirements in Clause 6.3 of
EN 50281-1-1, if dust deposits of excessive
thickness are present, the equipment in
question must be tested in a laboratory using
the relevant dust (see Annex A of the above-
mentioned standard).
25
In the future, manufacturers will have the option, The following verification from 1 and 2 must
during the type testing, of determining a surface be made by the user!
temperature TL under a deposit of thickness
L (orientated toward the thickness of the layer The maximum permissible surface temperature,
during actual use), which may be stated on in relation to the ignition temperature of a dust
labels (Figure 8). Section 5.2 of IEC 61241-0 cloud Tic and/or the ignition temperature of a
states: In addition to the maximum surface dust layer Til of the surrounding dust is determined
temperature TL required in 5.1, the maximum as follows:
surface temperature may be stated for a given 1. Maximum permissible surface temperature in
depth of layer, TL, of dust surrounding all sides case of dust clouds Tmax = 2/3 Tic
of the apparatus, unless otherwise specified 2. Maximum permissible surface temperature in
in the documentation, and marked according to case of dust layers (5 mm thickness)
29.2(8). For the determination of the temperature Tmax = Til 75 K
TL, 23.4.5.2 requires: the electrical
apparatus to be tested shall be mounted and Example: flour
surrounded by a layer depth "L" as stated by the Tic 380C and Til 300C
manufacturers specification. The measurement Tmax (1) = 2/3 x 380C = 253C
for the maximum surface temperature shall Tmax (2) = 300C 75 K = 225C
be made using a dust having a thermal con-
ductivity of no more than 0.003 kcal/m C h. Accordingly, the surface temperature of the
The user must take note of Clause 6.3.3.4 of electrical equipment in this particular case must
the installation standard 61241-14: Where the not exceed the value of 225C; this must be
apparatus is marked TL for a layer depth the guaranteed by the manufacturer (see Determi-
ignition temperature of the combustible dust, at nation of the Maximum Surface Temperature
a layer depth L, must be applied in place of T5 mm. above).
Figure 9: Explosion Protected Luminaire 6600 Series for Use in Zone 21 (Category 2D) and Zone 22 (Category 3D).
dust-explosion protection
7 equipment selection
26
27
>
dust-explosion protection
8 installation and maintenance
28
29
Cable glands must be assembled and mounted so This task is in conformity with the requirement
that they do not compromise the equipments dust of the Directive 99/92/EC, which obligates
tightness. They can also be permanently the employer to draw up an explosion protection
connected to the equipment, in which case they document. The content of the document
are certified together with the equipment. should indicate:
> The explosion risk have been determined
8.2 Maintenance and Servicing and assessed.
> Adequate measures will be taken.
In addition to the protective measures already > Work equipment and warning device are
taken, an organisational plan must be drawn up design, operated and maintained with due
for the installation. regard for safety.
> Cleaning, removal of dust deposits. > Provisions to ensure that the equipment is
> Inspection and maintenance of equipment and used correctly.
protective systems.
> Testing of earthing, especially for the
parts of the equipment that could become
electrostatically charged.
dust-explosion protection
9 product overview
30
Some Examples of
9. Product Overview
Dust Explosion
Protected Products
R. STAHL has a fully certified product range for
ECOLUX 6608 dust hazardous areas in your installation.
Emergency Luminaire
We take dust explosion protection just as seriously
as gas explosion protection. We can offer you a
specially adapted solution for almost every
Optical Beacon 6161
Traffic Light 6091
application. At a minimum, all dust explosion
protection products comply with the regulations of
Group 3D; that is, they can be used in Zone 22
(non-conductive dusts).
31
www.dust-ex.stahl.de
www.visuell.de
R. STAHL
Am Bahnhof 30, 74638 Waldenburg, Germany
Phone +49 7942 943-0
Fax +49 7942 943-4333
www.stahl.de
ID-NR. 00 006 84 77 0
S-PB-dustex-01-en-05/2008 Printed in the Federal Republic of Germany