CT Sizing For Malawi

This document contains calculations for knee point voltage for busbar and transformer differential protection and burden calculations for metering and protection cores for the Bangwe substation. It provides inputs like relay type, cable length and resistance, transformer parameters, and fault currents. The knee point voltage requirements are calculated based on internal faults of 25kA and external faults of 3280A. The maximum knee point voltage requirement is 20(RCT + 10) volts. Burden calculations show the metering and protection cores can handle the lead and relay burdens within their available VA ratings.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
2K views2 pages

CT Sizing For Malawi

This document contains calculations for knee point voltage for busbar and transformer differential protection and burden calculations for metering and protection cores for the Bangwe substation. It provides inputs like relay type, cable length and resistance, transformer parameters, and fault currents. The knee point voltage requirements are calculated based on internal faults of 25kA and external faults of 3280A. The maximum knee point voltage requirement is 20(RCT + 10) volts. Burden calculations show the metering and protection cores can handle the lead and relay burdens within their available VA ratings.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

KNEE POINT VOLTAGE CALCULATION FOR PS CLASS (BUSBAR DIFFERNTIAL & TRANSFORMER DIFFERNTIAL)

A - PARAMETER & DESIGN INPUT FOR BUSBAR

A-1 Name of substation BANGWE SUBSTATION


A-2 Make of relay SIEMENS
A-3 Type of relay 7UT85
A-4 Total VA ( Rb) 5 APPROX
A-5 Maximum internal symmetrical fault current - kA ( I.int max ) 25
A-6 Transformer Rated Current -Iintr 262.43
A-7 Transformer impedence-Z 8
A-8 Maximum external symmetrical fault current - A ( I.extmax ) 3280.375
A-9 Factor of symmetrical fault current -Kssc 41.6666666667

B - PARAMETER & DESIGN INPUT FOR CURRENT TRANSFORMER

B-1 CT secondary core detail - PS class Primary Current - Amp(Ipr) Secondary Current - Amp(Isr)
B-2 600 1
B-3 300 1

C - PARAMETER & DESIGN INPUT FOR CONTROL CABLE

C-1 Cable size for CT 4C X 4 sq.mm.


C-2 Length of cable - KM. 0.07
C-3 Resistance of cable /KM at 70 C 4.61

D - PARAMETER & DESIGN INPUT FOR RELAY

D-1 TOTAL LEAD RESISTANCE ( Rl') =(RESISTANCE/KM)*LENGTH OF CABLE 0.3227

E - CT ADEQUACY CALCULATION - Vk REQUIRED= (If X 1000 / Primary Current ) X ( Rct + Rb + 2 Rl' )

E-1 MINIMUM = 20XIsrX(Rct+Rl'+Rb)


20XIsr= 20
Rl'+Rb= 5.6454

Minimum Requirement = 20(Rct+10)

E-2 Internal Fault, Vk REQUIRED= 0.4x(Iint max X 1000 / Primary Current ) X ( Rct + Rb + 2 Rl' )

Rb+2Rl'= 5.6454
0.4x(If X 1000 / Primary Current )= 16.6666666667
selected knee point voltage= 20 (RCT + 10) volt

E-3 Internal Fault, Vk REQUIRED=1.6x(Iext max X 1000 / Primary Current ) X ( Rct + Rb + 2 Rl' )

Rb+2Rl'= 5.6454
1.6xIextmax / Primary Current )= 8.7476666667
selected knee point voltage= 10 (RCT + 10) volt

final selection, the maximum requirement 20 (RCT + 10)


BURDEN CALCULATION FOR METERING & PROTECTION CORE

A - PARAMETER & DESIGN INPUT FOR TRANSMISSION LINE

A-1 Name of substation BANGWE SUBSTATION


A-2 Make of meter
A-3 Type of meter ..
A-4 Burden of meter - VA (Rm) 5 APPROX
A-5 BURDEN OF RELAY (Rr) 5 APPROX

B - PARAMETER & DESIGN INPUT FOR CURRENT TRANSFORMER

B-1 CT secondary core detail - Primary Current - Amp Secondary Current - Amp CLASS VA
B-2 METERING 600 1 0.2s 20
B-3 PROTECTION 600 1 5P20 20

C - PARAMETER & DESIGN INPUT FOR CONTROL CABLE

C-1 Cable size for CT 4C X 4 sq.mm.


C-2 Length of cable - KM. 0.07
C-3 Resistance of cable /KM at 70 C 4.61

D - PARAMETER & DESIGN INPUT FOR RELAY

D-1 LEAD RESISTANCE ( Rl') =(RESISTANCE/KM)*LENGTH OF CABLE 0.3227

E - CT ADEQUACY CALCULATION - VA REQUIRED = Meter Burden + Lead Burden = Meter Burden + (2 * Rl') Available Required
E-1 = Rm + ( 2 X Rl') VA VA
20 5.6454

E - CT ADEQUACY CALCULATION - VA REQUIRED = RELAY Burden + Lead Burden = RELAY Burden + (2 * Rl') Available Required
E-1 = Rr + ( 2 X Rl') VA VA
20 5.6454

REMARKS:The required burden is within 25% to 100% of available burden hence CT is suitable