Step & Touch Potentials

This document provides an earthing calculation for the step and touch potentials of a power house. It includes the design parameters such as soil resistivity, fault current duration, conductor size and electrode length. It then calculates the permissible step and touch potentials. The earthing layout details such as earth mat dimensions and total grid length are provided. Finally, the actual estimated step and touch voltages are calculated and found to be lower than the permissible values, indicating the design is safe.

Uploaded by

nicrajesh
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
374 views

Step & Touch Potentials

This document provides an earthing calculation for the step and touch potentials of a power house. It includes the design parameters such as soil resistivity, fault current duration, conductor size and electrode length. It then calculates the permissible step and touch potentials. The earthing layout details such as earth mat dimensions and total grid length are provided. Finally, the actual estimated step and touch voltages are calculated and found to be lower than the permissible values, indicating the design is safe.

Uploaded by

nicrajesh
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 9

Earthing calculation of Step & Touch Potentials of Power House

A. Design Parameter
1 Soil Resistivity 600
2 Surface Layer Resistivity s 50000
3 Fault Current If 101
4 Calculated Grid Current Ig 67.33333333
5 Duration of fault current t 1

Duration of shock determining


6 allowable body current ts 0.5
Conductor size selected , Steel
7 1020 flat 63x10
Diameter of conductor
8 choosen d 0.014
9 Ground Electrode Selected 0
10 Length of each electrode Lr 0

11 Depth of earth mat conductor h 0.3


12 Surface Layer Thickness hs 0.3
13 Grid Area S 5514
14 Weight of person W 70

Empirical constant for average


15 weight of a man 70/50 kg k 0.157
16 Maximum Grid Current IG 67.33
17 Current Divison factor Sf 0.67

B. Permissible Step & Touch


Potential
1 Permissible step potential Estep (1000+6Css)(k/ts)
2
Permissible touch potential Etouch (1000+6Css)(k/ts)

Reduction factor for derating


3 the normal value of surface Cs (1-0.09*(1-/s)/(2*hs+0.09)) 0.87113
layer of resistivity

Permissible Step Potential 58247.56


Permissible Touch Potential 14728.41

C. Earthing Layout

1 Length of earth mat L 240


2 Width of earth mat B 23
3 Spacing between parallel 2.5
conductor D
4 7465
Total length of horizontal grid Lc
5 Peripheral length of grid Lp 526
6 Correction factor ki 4.84
7 Maximum length of the grid in
x-direction Lx 240
8 Maximum length of the grid in
y-direction Ly 23
9 Length of each earthpit rod Lr 0
10 Total length of ground rod LR 0
11 Symmetrical grid current IG 67.33
12 Geometric factor composed of
factors n 28.38
13 nb= 1 (for square grid)
14 nc= 1 (for square & rectangular grids)
15 nd= 1 (for square & rectangular grids & L shaped grids)
16 Grid reference depth= 1

D. Estimation of actual step & touch voltages

Sapcing factor for mesh km= 1/2[Ln(A+B-C)+D*Ln(E)]


voltage
A= D^2/(16*h*d)
B= (D+2*h)^2/(8*D*d)
C= h/(4*d)
D= (kii/kh)
E= 8/(*(2n-1))
Corrective factor that for adjust
for the effects of inner conductor kii= 1
on the corner mesh

Corrective factor that emphasizes kh= (1+h/h0)


the effects the grid depth
Mesh voltage Emesh= P*km*ki*IG*1000/L

Km= 0.333947659
kh= 1.14
na= 28.38

Hepmetrical factor for


obtaining step voltage values 1/3.14(1/(2*h)+1/(D+h)+(1/D(1-0.5^(n-2)))
ks= 0.77191386
Calculate tocuh potential km*ki**IG/(Lc+(1.55+1.22(Lr/(Lx^2+Ly^2)))*Lr
& Calculated step potential *ks*ki*IG/(0.75*Lc+0.85*Lr)

E touch(estimated)= 8756.067117
E step(estimated)= 26985.98371
As,
Etouch (permissible) > Etouch(estimated) Design is safe
Estep (permissible) > Estep(estimated) Design is safe
& L shaped grids)

121.9702 4.803777
0.877058 -2.70659 2.097191 0.333948
0.045685 -3.08598
Earthing calculation of Step & Touch Potentials of Transformer Hall
A. Design Parameter
1 Soil Resistivity 430
2 Surface Layer Resistivity s 50000
3 Fault Current If 50
4 Calculated Grid Current Ig 33.33333
5 Duration of fault current t 1
6 Duration of shock determining
allowable body current ts 0.5

Conductor size selected , Steel 1020


7 flat 63x10

8 Diameter of conductor choosen d 0.014


9 Ground Electrode Selected 92
10 Length of each electrode Lr 3
11 Depth of earth mat conductor h 0.3
12 Surface Layer Thickness hs 0.3
13 Grid Area S 5514
14 Weight of person W 70
15 Empirical constant for average
weight of a man 70/50 kg k 0.157
16 Maximum Grid Current IG 33.33333
17 Current Divison factor Sf 0.666667

B. Permissible Step & Touch Potential

1 Permissible step potential Estep (1000+6Css)(k/ts)


2 Permissible touch potential Etouch (1000+6Css)(k/ts)

3 Reduction factor for derating the Cs (1-0.09*(1-/s)/(2*hs+0.09)) 0.870687


normal value of surface layer of
resistivity

Permissible Step Potential 58218.02


Permissible Touch Potential 14721.03

C. Earthing Layout

1 Length of earth mat L 215


2 Width of earth mat B 14

3 Spacing between parallel conductor D 2.5


4 Total length of horizontal grid Lc 2726
5 Peripheral length of grid Lp 458
6 Correction factor ki 2.405782
Maximum length of the grid in x-
7 direction Lx 240
Maximum length of the grid in y-
8 direction Ly 23
9 Length of each earthpit rod Lr 3
10 Total length of ground rod LR 276
11 Symmetrical grid current IG 33.33333
Geometric factor composed of
12 factors n 11.90393
13 nb= 1 (for square grid)
14 nc= 1 (for square & rectangular grids)
15 nd= 1 (for square & rectangular grids & L shaped grids)
16 Grid reference depth= 1

D. Estimation of actual step & touch voltages


Sapcing factor for mesh voltage km= 1/2[Ln(A+B-C)+D*Ln(E)]
A= D^2/(16*h*d)
B= (D+2*h)^2/(8*D*d)
C= h/(4*d)
D= (kii/kh)
E= 8/(*(2n-1))
Corrective factor that for adjust for kii= 1
Corrective factor that emphasizes the kh= (1+h/h0)
Mesh voltage Emesh= P*km*ki*IG*1000/L

Km= 0.458816
kh= 1.140175
na= 11.90

Hepmetrical factor for obtaining step voltage va 1/3.14(1/(2*h)+1/(D+h)+(1/D(1-0.5^(n-2)))


ks= 0.771781
Calculate tocuh potential km*ki**IG/(Lc+(1.55+1.22(Lr/(Lx^2+Ly^2)))*Lr
& Calculated step potential *ks*ki*IG/(0.75*Lc+0.85*Lr)

E touch(estimated)= 5803.851
E step(estimated)= 13016.98

As,
Etouch (permissible) > Etouch(estimated) Design is safe
Estep (permissible) > Estep(estimated) Design is safe
r Hall
ngular grids)
ngular grids & L shaped grids)

(1-0.5^(n-2)))

/(Lx^2+Ly^2)))*Lr