Step & Touch Potentials
Step & Touch Potentials
A. Design Parameter
1 Soil Resistivity 600
2 Surface Layer Resistivity s 50000
3 Fault Current If 101
4 Calculated Grid Current Ig 67.33333333
5 Duration of fault current t 1
C. Earthing Layout
Km= 0.333947659
kh= 1.14
na= 28.38
E touch(estimated)= 8756.067117
E step(estimated)= 26985.98371
As,
Etouch (permissible) > Etouch(estimated) Design is safe
Estep (permissible) > Estep(estimated) Design is safe
& L shaped grids)
121.9702 4.803777
0.877058 -2.70659 2.097191 0.333948
0.045685 -3.08598
Earthing calculation of Step & Touch Potentials of Transformer Hall
A. Design Parameter
1 Soil Resistivity 430
2 Surface Layer Resistivity s 50000
3 Fault Current If 50
4 Calculated Grid Current Ig 33.33333
5 Duration of fault current t 1
6 Duration of shock determining
allowable body current ts 0.5
C. Earthing Layout
Km= 0.458816
kh= 1.140175
na= 11.90
E touch(estimated)= 5803.851
E step(estimated)= 13016.98
As,
Etouch (permissible) > Etouch(estimated) Design is safe
Estep (permissible) > Estep(estimated) Design is safe
r Hall
ngular grids)
ngular grids & L shaped grids)
(1-0.5^(n-2)))
/(Lx^2+Ly^2)))*Lr