Manual Comap
Manual Comap
InteliLite NT MRS
Modular Gen-set Controller
User guide
!! Warnings !!
Remote control
InteliLiteNT controller can be remotely controlled. In case of the work on the gen-set check, that
nobody can remotely start the engine.
To be sure:
Disconnect remote control via RS232 line
Disconnect input REM START/STOP
or
Disconnect output STARTER and outputs GCB CLOSE/OPEN
Because of large variety of InteliLiteNT parameters settings, it is not possible to describe any
combination. Some of InteliLiteNT functions are subject of changes depend on SW version.
The data in this manual only describes the product and are not warranty of performance or
characteristic.
Text
PAGE (Capital letters in the frame) buttons on the front panel
Break Return (Italic) set points
Generator protections (Bold) Set point group
REMOTE START/STOP (Capital letters) binary inputs and outputs
*Something (Symbol * before text) valid only for IL-NT MRS15/16
^Something (Symbol ^ before text) valid only for IL-NT MRS11/16
Note:
ComAp believes that all information provided herein is correct and reliable and reserves the right to
update at any time. ComAp does not assume any responsibility for its use unless otherwise expressly
undertaken.
Note:
SW and HW must be compatible (e.g. IL-NT-MRS10 firmware and IL-NT MRS10 HW) otherwise the
function wil be disabled. If wrong software is downloaded, message HARDWARE INCOMPATIBLE
appears on controller screen. In this case use Boot load (jumper) programming close Boot jumper
and follow instructions in LiteEdit, download correct software.
The following instructions are for qualified personnel only. To avoid personal injury do
not perform any action not specified in this User guide !!!
IL-NT RS232 is optional plug-in card to enable InteliLiteNT for RS232 communication. This is required
for computer or Modbus connectin. Card inserts into expansion slot back on the controller.
IL-NT AOUT8 is optional plug-in card. Through this card controller can drive up to 8 VDO style
industrial/automotive gauges. Gauge type and value are configured in LiteEdit software. Any analog
value from controller may be shown in that way.
IL-NT RD is remote display for controller. Remote display provides the same control and monitoring
functions as controller itself . No programing of the display is required unit is self configurable from
main controller. It is connected with controller via RS232 line. Longer distances (up to 1200m) are
possible when RS232/RS485 converters are used.
106 (4,2)
120 (4,7)
125 (4,9)
~ 25 (1,0)
165 (6,5)
Cutout
~ 75 (3,0)
167 x 108 mm
180 (7,1) (6,6 x 4,3)
185 (7,3)
IG IOM/PTM module
IG-IOM and IGS-PTM modules are I/O extension modules equipped with 8 binary inputs, 8 binary
outputs, 4 analogue inputs and one analogue output. The module can be used for AMF25 only.
Binary inputs and outputs are configurable the same way like inputs and outputs on iL.
Analogue inputs are configurable like iL with the limitation that the binary and tristate mode
can not be used on PTM module.
The protection of analogue IOM/PTM inputs is activated by overcrossing the limits, active only
when the engine is running.
IG-IOM analogue inputs are resistive (the same parameters like IL-NT) 0 -2,4 k. The
module IOM is designed for especially VDO resistive sensors.
IGS-PTM analogue inputs are configurable by jumpers to ranges 0-250, 0-100mV, 0-20mA.
The module can be used especially for Pt100 sensors and current sensors. The module PTM
is not suitable for VDO temperature sensor.
See the documentation of IGS-PTM for the technical and function description.
Modem or PC
Interface
RS-232C
NOT USED
SPRINKLER
REMOTE OFF
LOAD
+24 V
EMERGENCY STOP
ACCESS LOCK
REMOTE S/S
CONTROL
SIGNALS
ALARM
READY TO LOAD
BINARY OUTPUTS
PRESTART
GEN C.B.
FUEL SOLENOID
Generator C.B.
STARTER
L1
L2
L3
RPM
GENERATOR
OIL PRESSURE
WATER TEMP
FUEL LEVEL
DIESEL/GAS ENGINE
ECU
FUEL SOLENOID
STARTER
- +
D+
BATTERY
Hint:
It is possible to start Volvo and Scania engines via CAN bus. See Engines started via CAN bus.
Power supply
To ensure proper function:
Use min. power supply cable of 1.5mm2
Maximum continuous DC power supply voltage is 36VDC. Maximum allowable power supply voltage
is 39VDC. The InteliLites power supply terminals are protected against large pulse power
disturbances. When there is a potential risk of the controller being subjected to conditions outside its
capabilities, an outside protection devise should be used.
Hint:
The InteliLiteNT controller should be grounded properly in order to protect against lighting strikes!!
The maximum allowable current through the controllers negative terminal is 4A (this is dependent on
binary output load).
For the connections with 12VDC power supply, the InteliLiteNT includes internal capacitors that allow
the controller to continue operation during cranking if the battery voltage dip occurs. If the voltage
before dip is 10V, after 100ms the voltage recovers to 7 V, the controller continues operating. During
this voltage dip the controller screen backlight can turn off and on but the controller keeps operating.
It is possible to further support the controller by connecting the external capacitor and separating
diode:
Relays
D controller
T2A
+ +
-
C
- +
12VDC Battery
The capacitor size depends on required time. It shall be approximately thousands of microFarads.
The capacitor size should be
5 000 microFarad to withstand 150ms voltage dip under following conditions:
Voltage before dip is 12V, after 150ms the voltage recovers to min. allowed voltage, i.e. 8V
controller
T2A
+ + +
I-LBA
- - -
- +
12VDC Battery
Note:
I-LBA may not eliminate voltage drop when used with low temperature (-40C) version of controller
and display heating element is on (below 5C). Current drain of heating element exhausts LBA
capacitors very fast .
+ IL-NT
T1A -
+ -
Battery HUGE
LOADS
STARTER
Fuse
Fuse
K1 K2
K1 K2
controller
T1A
+
-
DC relays
- +
24VDC Battery
Grounding
To ensure proper function:
Use as short as possible cable to the grounding point on the switchboard
Use cable min. 2,5mm2
The - terminal of the battery has to be properly grounded
MAGNETIC
PICK-UP
iL Signal b
D C
Signal
GAC
Speed Control Unit
ESD 5500
+ -
Power
Supply
- Power
+
Supply
+ -
Battery
Be aware of interference signal from Speed governor when one speed pick-up is used.
If engine will not start:
- Check ground connection from pick-up to controllers, eventually disconnect ground connection
to one of them
- Galvanically separate InteliLite RPM input using ComAp separation transformer RPM-ISO
(1:1)
- Use separate pick-up for Speed governor and InteliLiteNT
Hint:
In some cases the controller will measure a RPM value even though the gen-set is not running:
RPM is measured from the generator voltage (Gear teeth = 0)
IL-NT is measuring some voltage value on input terminals due to open fusing.
If RPM > 0 the controller will be put into a Not ready state and the engine will not be allowed to start.
Current measurement
To ensure proper function
Use cables of 2,5mm2
Use transformers to 5A
Connect CT according to following drawings
K L
L1
k l K L
G L2
k l K L L3
k l
N
N L1 L2 L3
GENERATOR
L1
L2
G
L3
BUS
N L1 L2 L3
GENERATOR
Hint:
No separation transformers for three wires voltage connection (without N) are needed.
Switchboard lighting strikes protection according standard regulation is expected !!!
Recommended wirings
Generator (and mains) single-phase voltage has to be connected to all three-voltage terminals L1, L2
and L3. Generator current has to be connected to L1l and COM terminals only.
Voltage measurement
L
G N
N L1 L2 L3 N L1 L2 L3
GENERATOR MAINS
Hint:
Switchboard lighting strikes protection according standard regulation is expected !!!
Current measurement
To ensure proper function
Use cables of 2,5mm2
Use transformers to 5A
Connect CT according to following drawings. Terminals L2l and L3l are opened.
Analog inputs
Three analog inputs are available on the IL-NT
Configuration
Each analog input can be configured by LiteEdit software following way.
3x RESISTIVE
SENSOR
AI1
AI2
AI3
Set jumpers for current measurement
GND 3x SENSOR
4 - 20 mA
+24V
- POWER
AI3
Analog inputs are designed for resistive sensors with resistance in range of 0 to 2,4k.
To ensure a proper function use shielded cables, especially for length over >3m.
As binary input
Open, close state are detected, threshold level is 750 .
Hint:
Protections on binary and three state inputs are following:
IL-NT: AI1 Shutdown IG-IOM: AI1 Shutdown
AI2 Shutdown AI2 Shutdown
AI3 Warning AI3 Shutdown
AI4 Shutdown
Dim: Physical dimension of measured value (C, %, Bar, ..) Maximal dimension length is three
characters.
Set to: Bar
Contact type: selection of polarity only when analog input is configured as Binary or Tri-state. When
is analog input configured as analog this setting has no sense.
NC polarity of binary or tri-state input
NO polarity of binary or tri-state input
When Analog input configuration is finished set the setpoints Wrn Oil press, Sd Oil press, Oil press del
in Engine protection group.
Each Analog input has separate triplet of setpoints: Wrn level, Sd level, Anl Inp del. Names of these
setpoints are fix defined
Number of decimal points of Wrn level1 and Sd level is the same as the configured number of
decimal points of measured value.
4k7
iL
+ -
Power
Supply
+ -
Battery
Binary outputs
LOAD
iL
+ -
Power
Supply
+ -
Battery
120 ohm
CAN LO
120 ohm
IL-NT L
10 ohm
CAN H
CAN L
CAN H
CAN L
COM
15nF
COM
Engine ECU
EXTENSION
IGS-PTM (optional) IGL-RA15 (optional)
MODULES or
COM (optional)
CAN H
CAN L
9 5
120 ohm
IG-IOM (optional)
Connection rules
CAN bus line must be connected in series, from one unit to the next (no star, no cable stubs, no
branches) both ends must by the 120-ohm (internal or external) resistor terminated. Maximal CAN bus
length is up to 200 meters.
For CAN data cables details see chapter Technical data Communication interface. CAN cable
shielding connect to IL-NT COM terminal.
IL-NT contains internal fix 120-ohm resistor and must be located on the CAN bus end.
New IG-IOM and IGS-PTM units contain internal jumper removable 120-ohm resistor (in older IOM
types are fix resistors). To be sure check resistor presence by ohmmeter. Unit with internal resistor
connect to the end of CAN line.
Following connections are supported (IOM, PTM, ECU order is not important).
It is possible to connect only one IG-IOM or IGS-PTM and one IGL-RA15 to IL-NT.
Analog outputs
Optional plug in card IL-NT AOU8 provides eigth Pulse-With-Modulation (PWM) outputs. These are
intended to drive VDO style analog gauges. This is to provide visual indication of typically ECU values
without installing aditional sensors on the engine. PWM signal emulates sensor which would be
typically mounted on the engine.
Any value from controler may be configured to the outputs. Use LiteEdit PC SW to configure
coresponding sensor/gauge curve and value selection.
Alarm
If the input is closed (or opened) selected alarm is activated.
Binary Alarm configuration items
Name 14 chararcters ASCII string
Contact type NC Normally closed
NO Normally opened
Alarm type Warning
Shut down
Alarm active All the time
Engine running only
Rem start/stop
External request for engine run. AUT mode only.
Emergency stop
If the input is opened, shut down is immediately activated. Input is inverted (normally closed) in default
configuration.
Hint:
In case of controller hardware or software fail, safe stop of the engine doesnt have to be ensured. To
back-up the Emergency stop function it is recommended to connect separate circuit for disconnection
of Fuel solenoid and Starter signals.
Sprinkler
If the input is closed all alarms are disabled except the binary input EMERGENCY STOP and "engine
overspeed protection".
Hint:
Warning SprinklActive is indicated in the AlarmList if sprinkler mode active to inform the operator that
the engine is not protected.
Access lock
If the input is closed, no setpoints can be adjusted from controller front panel and gen-set mode (OFF-
MAN-AUT) cannot be changed.
Hint:
Access lock does not protect setpoints and mode changing from LiteEdit. To avoid unqualified
changes the selected setpoints can be password protected.
Remote OFF
If closed, iL is switched to OFF mode (there are four modes OFF-MAN-AUT-TEST). When opens
controller is switched back to previous mode.
Hint:
This binary input should be connected to schedule timer switch, to avoid start of engine.
Remote MAN
If the input is active, MAN mode is forced to the controller independently on the position of the MODE
selector.
Remote AUT
If the input is active, AUT mode is forced to the controller independently on the position of the MODE
selector. If another of remote inputs is active, then the REMOTE AUT input has the lowest priority.
RemControlLock
If the input is active, setpoints writing or command sending from the external terminal is disabled.
Emergency manual
If the input is activated the controller behaves like when switched to OFF mode. Opens all binary
outputs. There is one exception STOP SOLENOID doesnt activate on this transition.
Detection of "running" engine and subsequent alarm message "Sd Stop fail" is blocked.
The controller shows Emerg Man state and the engine can not be started.
Generator current and power measurement is active in this mode, regardless of the actual state of the
engine.
After the input is open again, the controller recovers to previous state and behaves according to the
actual situation .
Function is active in any controller mode.
StartButton
Binary input has the same function as Start button on the InteliLite front panel. It is active in MAN
mode only.
StopButton
Binary input has the same function as Stop button on the InteliLite front panel. It is active in MAN
mode only.
HornResButton
Binary input has the same function as Horn reset button on the InteliLite front panel.
^GCB button
Binary input has the same function as GCB button on the InteliLite front panel. It is active in MAN
mode only.
Starter
The closed relay energizes the starter motor.
The relay opens if:
the firing speed is reached or
maximum time of cranking is exceeded or
request to stop comes up
Fuel solenoid
Closed output opens the fuel solenoid and enables the engine start.
The output opens if:
EMERGENCY STOP comes or
Cooled gen-set is stopped or
in pause between repeated starts
Stop solenoid
The closed output energizes stop solenoid to stop the engine.
The output is active at least for Stop time, if the stop lasts longer, it stays active until all symptoms say
the engine is stopped.
The engine is stopped if:
RPM < 2 and
Generator voltage < 10V and
Oil pressure < Engine params: StartingPoil.
Hint:
Stop Pulse
Output is active for 1 second after Stop solenoid output activation. This signal is sent to ECU in case
of engine stop request.
Ignition
The output closes after reaching value of CrankRPM, fixed 30RPM. Opens after stopping of the
engine or in pause during repeated start.
Prestart
The output closes prior to the engine start (Prestart) and opens when Starting RPM speed is reached.
During repeated crank attempts the output is closed too.
The output could be used for pre-glow, pre-heat or prelubrication.
Cooling pump
The output closes when gen-set starts and opens Engine params:AfterCool time after stop of the
engine.
Idle/Nominal
The output Idle/Nominal closes after the timer Idle time elapses. The Idle time counter starts to
countdown when Start speed reached. The Underspeed protection is not evaluated during idle period.
A Start fail protection occurs if the RPM drop below 2RPM during idle.
Air valves
Closes together with Prestart. Opens after the engine is stopped.
Stopped engine conditions: RPM = 0, Engine params: Starting Poil, D+ (when enabled).
Alarm
The output closes if :
any warning or shutdown comes up or
the gen-set malfunctions
The output opens if
FAULT RESET is pressed
The output closes again if a new fault comes up.
Horn
The output closes if:
any warning or shutdown comes up or
the gen-set malfunctions
The output opens if:
FAULT RESET is pressed or
HORN RESET is pressed or
Max time of HORN is exceeded (Horn timeout)
The output closes again if a new fault comes up.
GCB Close/Open
MRS11, 16: The output controls the generator circuit breaker.
MRS10 and 15 (GCB no GCB button):
The output closes automatically (in MAN or AUT mode) after engine is started,
MinStabtime elapsed, and generator voltage and frequency is in limits.
GCB on coil
The output activates Generator Circuit Breaker coil.
GCB UV coil
The output controls Generator Circuit Breaker coil after voltage drop-out.
*AnInIOM1..4 Wrn
Output closes if warning alarm on the appropriate IOM/PTM analog input activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
*AnInIOM1..4 Sd
Output closes if shutdown alarm on the appropriate IOM/PTM analog input activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Ready
The output is closed if following conditions are fulfilled:
Gen-set is not running and
No Shut down or Slow stop alarm is active
Controller is not in OFF mode
Ready to load
The output is closed if genset is running and all electric values are in limits no alarm is active - it is
possible to close GCB or it is already closed. The output opens during cooling state.
Running
Output closes if the engine is in Running state.
Cooling
The output closes when gen-set is in Cooling state.
Supplying load
Closed when the generator current is > 0,5% of the CT ratio.
Exact formulas:
Output is closed when the current at least in one phase is for 1 sec over CT ratio/200+2
Output is opened when the current in all three phases is for 1 sec below CT ratio/200+2
Hint:
Values are truncated after division, not rounded.
Vgen failed
The output closes if the generator over/under voltage shutdown alarm or voltage asymmetry shutdown
alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
fgen failed
Output closes if the generator over/under frequency shutdown alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Stop failed
Output closes when the engine has to be stopped, but speed or frequency or voltage or oil pressure is
detected. This protection goes active 60s after stop command.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Overspeed
Output closes if the gen-set over speed alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Underspeed
Output closes if the gen-set under speed alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Start failed
Output closes after the gen-set start-up fails.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Overcurrent
Output closes if the generator
*IDMT over current or
current unbalance or
short current alarm activates.
The output opens, if
Alarm is not active and
FAULT RESET is pressed
Battery flat
Output closes when iL performs reset during start procedure (probably due to weak battery).
The output opens, if
alarm is not active and
FAULT RESET is pressed
V batt failed
Output closes when battery over/under voltage warning appears.
The output opens, if
alarm is not active and
FAULT RESET is pressed
Oil Press
Output closes if the oil pressure shutdown alarm activates.
The output opens, if
Water Temp
Output closes if the water temperature shutdown alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
FuelLevel
Output closes if the Fuel level shutdown alarm activates.
FuelLevelWrn
Output closes if the Fuel level warning alarm activates.
Common Wrn
Output closes when any warning alarm appears.
The output opens, if
No warning alarm is active and
FAULT RESET is pressed
Common Sd
Output closes when any shut-down alarm appears.
The output opens, if
No sd alarm is active and
FAULT RESET is pressed
Common Fls
Output closes when any sensor fail alarm appears.
The output opens, if
No warning alarm is active and
FAULT RESET is pressed
OFF mode
The output is closed, if OFF mode is selected.
MAN mode
The output is closed, if MAN mode is selected.
AUT mode
The output is closed, if AUT mode is selected.
ServiceTime
Output closes if the ServiceTime alarm activates.
The output opens, if
alarm is not active and
FAULT RESET is pressed
ECU CommOK
If the ECU is not communicating and all values from ECU show #### the output is not active. If the
ECU communicates the output is active.
ECU PwrRelay
The output closes at the beginning of prestart and opens if the engine shall be stopped.
ECU YellowLamp
The output copies warning information from ECU.
ECU RedLamp
The output copies shutdown information from ECU.
CtrlHeartBeat
Output signalizes watchdog reset. In a healthy state it blinks at 500ms : 500ms rate. When watchdog
reset occurs, it stops blinking.
ECU CommError
The output is an inversion of binary output ECU CommOK, i.e. the output is closed when ECU is not
communicating and all values from ECU show #####. Communication error causes stop of the engine.
BI1..6 stat
*BI1..8IOM - stat
The outputs give an information about the assigned binary input.
In case the assigned binary input is configured to alarm type, then the output closes when the alarm
activates. It opens if
alarm is not active and
FAULT RESET is pressed
In case the assigned binary input is configured to any control function, the output propagates the state
of the input.
Timer1
Output activates when Timer1 is active. Simultaneously, gen-set is started when is in AUT mode.
Timer2
Output activates when Timer2 is active
Glow plugs
The output closes prior to the engine start (Prestart) and opens when Starting RPM speed is reached.
During repeated crank attempts the output is opened.
Supplying load
Closed when the generator current is > 0,5% of the CT ratio.
Exact formulas:
Output is closed when the current at least in one phase is for 1 sec over CT ratio/200+2
Output is opened when the current in all three phases is for 1 sec below CT ratio/200+2
Hint:
Values are truncated after division, not rounded.
Analog inputs
Three analog inputs are jumper configurable for resistive(default), voltage or current sensor.
Oil press
Oil pressure analog input. Default VDO sensor in range 0 to 10.0 bars.
Water temp
Water temperature analog input. Default VDO sensor in range 0 to 100 C.
Fuel level
Fuel level analog input. Default VDO sensor 0-180R = 0-100%
Hint:
For further information about analog inputs configuration see Analog inputs.
ChangePassword
Use or keys to set and ENTER key to change the password.
Hint:
At first the Password has to be entered before the new Password can be changed.
Basic settings
Gen-set name
User defined name, used for InteliLite identification at remote phone or mobile connection.
Gen-set name is max 14 characters long and have to be entered using LiteEdit software.
CT Ratio [/5A]
Gen-set phases current transformers ratio.
Step: 1A
Range: 1 5000 A / 5A
PT ratio [/1]
Gen-set potential transformers ratio.
Step: 0,1 V / V
Range: 0,1 500,0 V / V
FltResGoToMAN [ENABLED/DISABLED]
DISABLED: Controller stays in AUT mode after Fault reset .
ENABLED: Automatic switch from AUT (or TEST) to MAN mode after Fault reset to avoid
automatic engine start. This function is active for Shut down protection only.
DispBaklightTO [min]
Timeout after which the display backlight is switched off.
Step: 1 min
Range: 0 60 min
Default value: 0 means that the display lights all the time
Hint:
For detail description see chapter Modbus protocol.
Engine params
Starting RPM [%]
Firing speed when IL controller stops cranking (starter goes OFF).
Step: 1% of nominal RPM
Range: 5 50 %
M
RP
Start RPM
RP
M
RPM = 2
BO Starter
BO IDLE/RATED
Idle time Min stab time
Electric protections
activ e
Start Fail
Hint:
If the IDLE function not supported on the governor, set the Idle time nevertheless to minimum 5s to
avoid Underspeed possibly caused by instability of the engine short after start.
D+ function [ENABLED/CHRGFAIL/DISABLED]
ENABLED: The D+ terminal is used for both functions running engine detection and charge fail
detection.
CHRGFAIL: The D+ terminal is used for charge fail detection only
DISABLED: The D+ terminal is not used.
Hint:
Engine protect
Eng prot del [s]
During the start of the gen-set, some engine protections have to be blocked (e.g. Oil pressure).
The protections are unblocked after the Protection del time. The time starts after reaching Start RPM.
Step: 1s
Range: 0 300 s
AnlInp2 level1 []
Warning threshold level for ANALOG INPUT 2
Step: 1 C
Range: -100 10000
AnlInp2 level2 []
Shutdown threshold level for ANALOG INPUT 2
Step: 1 C
Range: -100 10000
AnlInp3 level1 []
Warning threshold level for ANALOG INPUT 3
Step: 1%
Range: -100 10000
AnlInp3 level2 []
Shutdown threshold level for ANALOG INPUT 3
Step: 1%
Range: -100 10000
NextServTime [h]
Counts down when engine running. If reaches zero, an alarm appears.
Step: 1h
Range: 0 65535h
Gener protect
Hint:
All electric protections when activated result in shutdown.
Overload [%]
Threshold for generator overload (in % of Nominal power)
Step: 1% of Nominal power
Range: 0 200%
Ishort [%]
Shutdown occurs when short circuit limit Ishort limit is reached.
Step: 1 % of Nominal current
Range: 100 - 500 %
Hint:
EXAMPLE of Reaction time for different over current levels. Values in column 200% are 2Inom del.
Overcurrent
200 % = 100 % 101 % 110 %
2Inom del
0,2 s No action 20 s 2s
Reaction time 2s No action 200 s 20 s
20 s No action No action 200 s
(time > 900 s)
2Inom del
Igen
Nominal current Ishort
Date/Time
Time stamp per [min]
Time interval for periodic history records.
Step: 1 min
Range: 0 200min
#Time [HHMMSS]
Actual real time
#Date [DDMMYYYY]
Actual date.
Timer1..2 ON time
Day time when Timer output activates.
Timer1..2Duration
Duration of Timer output is active.
Step: 1 min
Range: 1 1440 s
Sensor spec
Calibr AI1,AI2,AI3 []
Calibrating constant to adjust the measured value of IL analog inputs. Physical dimension of
calibrating constant is corresponding to Analog input.
Step: 1
Range: -1000 +1000
Hint:
Calibration constants have to be adjusted when measured value is near the alarm level.
User curves A, B, C can be defined by LiteEdit software.
CalibrAInIOM 1..4 []
Calibrating constant to adjust the measured value of IOM/PTM analog inputs. Physical dimension of
calibrating constant is corresponding to Analog input.
Step: 1
Range: -1000 +1000
*IOM/PTM module
AnlInIOM1..4 lev1 []
The level for IOM ANALOG INPUT 1..4 alarm detection.
Step: 1
Range: -100 - +10000
AnlInIOM1..4 lev2 []
The level for IOM ANALOG INPUT 1..4 alarm detection.
Step: 1
Range: -100 - +10000
Presence of the ECU on the CAN bus/RS232 is configured via LiteEdit like other peripheries (IG-IOM,
IGL-RA15). Pressing the button in Configuration window of LiteEdit (version 2.0 and higher),
opens ECU dialog window where the appropriate engine/ECU type should be selected. There are
three groups of engine/ECU types:
Hint:
Import latest ECU list Gensets.iwe for up to date engine ECU specification.
Loss of communication causes shutdown of the running engine. On the contrary, the ECU can be
switched off at quiescent engine, that means not-communicating ECU is in that moment normal
situation. All values from ECU shall show ####, but no alarm is displayed. The output ECU CommOK
follows the real situation, that means it is not active anytime when the ECU does not communicate.
The output ECU PwrRelay closes at the beginning of prestart and opens if the engine shall be
stopped.
The engine is started via standard contact output or via CAN bus (for Volvo and Scania engines). For
other engines J1939 is used for monitoring only.
Cummins MODBUS
When Cummins-Modbus option is selected, following values are read from Modbus Register Data
(for QSX15,QSK45, QSK60):
Engine Speed (Register Address:30001)
Oil Pressure (Register Address:30003)
Coolant Temperature (Register Address:30002)
Engine Running Time (Register Address:30008-30009)
Fuel Consumption Rate (Register Address:30018)
Intake Manifold Absolute Pressure (Register Address:30530 (QSK45, QSK60 only))
Intake Manifold Temperature (Register Address:30531 (QSK45, QSK60 only))
Hint:
InteliLite controller doesnt support J1587 diagnostic line on Volvo engines. This can cause in some
cases a J1939 alarm message FC:000608 due to missing J1587 bus. Contact your Volvo distributor to
update ECU firmware.
Analog inputs
Reading of mentioned values from ECU enables to use analog inputs of the unit for other purposes,
e.g. measuring, displaying and alarm activation related to various quantities. The configuration thus
allows to use three analog inputs on the central unit and four analog inputs on IG-IOM/IGS-PTM
module if connected.
If the engine without ECU is controlled by InteliLite, the first analog input is permanently configured to
Oil pressure, other analog inputs remain freely configurable.
Modem or PC
Interface
RS-232C
NOT USED
SPRINKLER
REMOTE OFF
LOAD
+24 V
EMERGENCY STOP
ACCESS LOCK
REMOTE S/S
CONTROL
SIGNALS
BINARY OUTPUTS
ALARM
READY TO LOAD
PRESTART
GEN C.B.
Generator C.B.
L1
L2
L3
N
GENERATOR
RPM
G
8-pole Deutsch
8 7 6 5 4 3 2 1
DIESEL/GAS ENGINE
connector
ECU
BO ECU PwrRelay
BO ECU CommOK (EDCIII) / ECU CommError (EMSII)
FUEL LEVEL
Modem or PC
Interface
RS-232C
NOT USED
SPRINKLER
REMOTE OFF
LOAD
+24 V
EMERGENCY STOP
ACCESS LOCK
REMOTE S/S
CONTROL
SIGNALS
BINARY OUTPUTS
ALARM
READY TO LOAD
PRESTART
GEN C.B.
Generator C.B.
L1
L2
L3
N
GENERATOR
RPM
G
1 2 3 4 5 6 7 8 9 10
10 -pin EMS B1
DIESEL/GAS ENGINE
connector
ECU
GND
+24 V DC
FUEL LEVEL
JOHN DEERE
IL-NT binary output description John Deere 21 pin Deutsch connector
Start output D
Fuel output G (switched ECU power),J (ignition)
CUMMINS ISB/ISBE
IL-NT binary output description Cummins ISB OEM Harness connector B
Start output connects directly to engine starter solenoid
Fuel output 39
10-30
VDC RS485
NOT USED
SPRINKLER
REMOTE OFF
LOAD
+24 V
EMERGENCY STOP
ACCESS LOCK
REMOTE S/S
CONTROL
SIGNALS
ALARM
BINARY OUTPUTS
READY TO LOAD
PRESTART.
GEN C.B.
FUEL SOLENOID
Generator C.B.
STARTER
L1
L2
L3
RPM
GENERATOR
ECU
FUEL SOLENOID
STARTER
- +
D+
BATTERY
200
2000
Resistance [ohm]
Resistance [ohm]
150
1500
1000 100
500 50
0 0
0 20 30 40 50 60 70 80 90 110 0 2 4 6 8 10
Temperature [ C] Pressure [bar]
Hint:
When measured value is 6% out of range the Sensor fail FLS is detected.
15
9
10
16
11
12 8 17
1. MODE Cyclic forward selection the gen-set operation mode (OFF -> MAN -> AUT )
2. MODE Cyclic backward selection the gen-set operation mode (AUT -> MAN ->OFF )
3. HORN RESET Deactivates the HORN
4. FAULT RESET Acknowledges faults and alarms
5. START Start of the gen-set
6. STOP Stop of the gen-set
7.
8. GCB ON/OFF ^Manual open/close of the Generator circuit breaker
9. PAGE Cyclic selection of the display mode(MEASUREMENT->ADJUSTEMENT)
10. Select the set point, select the screen or increase set point value
11. Select the set point, select the screen or decrease set point value
12. ENTER Confirm set point value
LEDs
13.
14.
15. GEN VOLTAGE PRESENT: GREEN LED is on, if gen. voltage is present and within limits
16. GEN-SET FAILURE: RED LED starts flashing when gen-set failure occurs. After FAULT RESET
button is pressed, goes to steady light (if an alarm is still active) or is off (if no alarm is active)
17. ^GCB ON: GREEN LED is on, if GCB is closed. Driven by GCB CLOSE/OPEN output.
Display menus
There are 2 display menus available: MEASUREMENT and ADJUSTMENT
Each menu consists of several screens. Press repeatedly PAGE button to select requested menu.
Description
* Wrn Water temp Active not accepted alarm
Wrn water temp Active accepted alarm
* Wrn Water temp Inactive not accepted alarm
Inactive accepted alarm
Press FAULT RESET accepts all alarms. Non-active alarms immediately disappear from the list.
Active alarm list appears on the screen when a new alarm comes up and Main MEASUREMENT
screen is active.
Hint:
Alarm list does not activate when you are reviewing the values or setpoints.
Second alarm list for ECU alarms is also available. It is displayed one screen above the standard
alarm list on the controller display or under the standard alarm list in Control window of LiteEdit. If an
alarm appears in this alarm list, it is signalized in the standard alarm list and by exclamation mark on
the main measure screen.
Control from the front panel:
3
OFF MAN AUT TEST L
Ready 4
Mains Oper
cos 0.00 7
RPM 0
Timer 0
5
8
6
Generator screen
Gen freq
*ECU state
ECU YellowLamp
ECU RedLamp
WaitToStart
Hint:
This screen is shown/hidden depending on whether the ECU is configured or not.
*ECUValues
Oil press
Water temp
PercLoadAtCS
Boost pressure
ManifoldTemp
Fuel rate
Hint:
This screen is shown/hidden depending on whether the ECU is configured or not.
Statistic
Run hours
Number of starts
NextServTime
Hint:
Running time is measured in complete minutes, displayed in complete hours. Values are stored in
nonvolatile memory.
*ECU AlarmList
Diagnostic messages are read from ECU and displayed in this second alarm list. For Standard J1939
engines SPN (Suspect Parameter Number), FMI (Failure Mode Identifier) and OC (Occurrence
Counter) are shown together with verbal description if available.
EngOilPress WRN
BoostPress FLS
EngOilTemp FLS
629(275h) FLS
Controller#1
EngCoolTemp WRN
_____________________
SPN:110 OC:7 FMI:3
Hint:
For FMI = 0 and 1, WRN is displayed. For other FMI codes, FLS is displayed.
Alarm list
PAGE
PAGE
PAGE ENTER
GEAR TEETH
150 150 -
Screen 30
CRANK TIME
10
30%
10s
Parameter setting:
2. Press ENTER
to editing mode
MAN mode
START. - starts the gen-set.
^GCB ON/OFF
The controller closes GCB.
The controller opens GCB when closed.
If the generator voltage is out of the limits, the controller does not to respond to the GCB
ON/OFF
Hint:
The engine can run without load unlimited time.
The controller does not automatically stop the running gen-set in MAN mode.
The controller does not start the gen-set when binary input REM START/STOP is closed.
1
if all generator parameters OK and MinStab Time elapsed, indicates that GCB is possible to close.
In AUT mode closes in this moment GCB automatically.
2
If GCB output used GCB opens automatically
3
The start-up sequence can be interrupted in any time by comming stop request
4
Fuel solenoid is switched on with time advance of 1s fixed before starter motor is switched on.
Hint:
Treshhold level for D+ input is 80% supply voltage, activation delay is 1s (to override short firings
during during cranking for example in cold conditions).
AUT mode
The controller does not respond to buttons START, STOP, GCB ON/OFF. Engine start/stop request
is given by binary input REM START/STOP.
Warning (WRN)
When warning comes up, only alarm outputs and common warning output are closed.
Possible warnings:
See List of possible events
5 sec Underspeed
"All the time" configured protections, I >, I >>, RPM >>, mains failure detection
nominal speed
GCB opened
Switched to
GCB closed
Starter OFF
Stop
Hint:
Phase sequence detection is active when voltage in all three phases is >50VAC and all phases angles
are in the range 120 20.
Phase sequence alarm detection is 1 sec delayed to avoid transient effects.
R1
R2
R3
R4
R5
Information on binary
Protection
Events specification output available (See Description
type
list of Binary outputs)
Oil Press Wrn WRN YES Oil pressure is smaller than Wrn Oil
press setpoint.
Oil Press Sd SD NO Oil pressure is smaller than Sd Oil
press setpoint.
Engine Temp Wrn WRN YES Water temperature is greater than
Wrn Water temp setpoint.
Engine Temp Sd SD NO Water temperature is greater than Sd
Water temp setpoint.
Fuel Level Wrn WRN YES Fuel level is smaller than Wrn Fuel
Level setpoint.
Fuel Level Sd SD NO Fuel level is smaller than Sd Fuel
Level setpoint.
Ubat WRN YES Battery voltage is out of limits given by
Batt overvolt and Batt undervolt
setpoints.
AnInIOM Wrn WRN YES Warning alarm configurable on the
input of IG-IOM/IGS-PTM.
History file
InteliLite NT stores a record of each important event into the history file. The history file seats 117
records. When the history file is full, the oldest records are removed.
Hint:
To force history download in LiteEdit (direct,,modem or Internet) open History window and select
History | Read history command.
Record structure
Abbreviation Historical value
Num Number of historical event
Reason Event specification
Date Date of historical event in format DD/MM/YY
Time Time of historical event in format HH:MM:SS
RPM Engine speed
Pwr Generator active power
PF Generator PF
LChr Character of the load
Gfrq Generator frequency
Vg1 Generator voltage L1
Vg2 Generator voltage L2
Vg3 Generator voltage L3
Ig1 Generator current L1
Ig2 Generator current L2
Ig3 Generator current L3
UBat Battery voltage
OilP IL-NT Analog input 1 value ( default Oil pressure)
EngT IL-NT Analog input 2 value ( default Water temperature)
FLvl IL-NT Analog input 3 value ( default Fuel level)
AIM1 IG-IOM, IGS-PTM Analog input 1 value (when configured IG-IOM, IGS-PTM)
AIM2 IG-IOM, IGS-PTM Analog input 2 value (when configured IG-IOM, IGS-PTM)
AIM3 IG-IOM, IGS-PTM Analog input 3 value (when configured IG-IOM, IGS-PTM)
AIM4 IG-IOM, IGS-PTM Analog input 4 value (when configured IG-IOM, IGS-PTM)
BIN Binary inputs IL-NT
BIM IG-IOM, IGS-PTM Binary inputs (when configured IG-IOM, IGS-PTM)
BOUT Binary inputs IL-NT
BOM IG-IOM, IGS-PTM Binary outputs (when configured IG-IOM, IGS-PTM)
FC ECU alarm FailureCode
FMI ECUalarm Failure Mode Identifier
Hint:
Make sure the grounding system on controller and PC COM port (negative of the PC DC supply) are
identical before the first direct connection. There must not be any voltage between these two points
otherwise the internal reversible fuse in controller burns out. The simple solution is to assure, that the
PC supply 240/20V is ground free (GND terminal is not connected).
PC CONTROLLER
2 - RxD 2 - RxD
RS232
RS 232
RS232
3 - TxD 3 - TxD
230 VAC 5 - GND 5 - GND
0 VDC
- +
Battery
PC software - LiteEdit
On the PC (for direct or modem connection) has to be installed the ComAps software package
LiteEdit. (based on Windows 95 or newer platform)
LiteEdit enables:
read the quantities
adjust all set points
control the engine
configure the controller
select software configuration
modify alarm inputs and outputs
modify password, commands protections
direct, modem or Internet communication
Modbus protocol
The selection of the function of IL serial port is done via the setpoint RS232 mode in Basic settings
The complete description of Modbus communication protocol can be found in Modbus Protocol
Reference Guide PI-MBUS-300 and Open Modbus Specification Release 1.0. Both documents are
available from web site at http://www.modicon.com/openmbus/ .
Hint:
To obtain communication object numbers it is possible to download the actual controller description
on-line from controller or from (ail) archive and use export data function from LiteEdit software.
Setpoints (MRS16):
Ser.
Name Firmware ver. Application Date App. ver. num. Filename
IL-NT-
IL-NT-1.0 MRS16-
IL-NT R:26.07.2007 MRS16 14.8.2007 1,0 1234567 1.0.AIL
Com. High
Group Name Value Dimension Password obj. Low limit limit Data type
IOM/PTM
module AnlInIOM1 lev1 0 U4 0 8762 -100 10000 Integer 16
IOM/PTM
module AnlInIOM1 lev2 0 U4 0 8766 -100 10000 Integer 16
IOM/PTM
module AnlInIOM1 del 5 s 0 8770 0 180 Unsigned 16
IOM/PTM
module AnlInIOM2 lev1 0 U5 0 8763 -100 10000 Integer 16
IOM/PTM
module AnlInIOM2 lev2 0 U5 0 8767 -100 10000 Integer 16
IOM/PTM
module AnlInIOM2 del 5 s 0 8771 0 180 Unsigned 16
IOM/PTM
module AnlInIOM3 lev1 0 U6 0 8764 -100 10000 Integer 16
IOM/PTM
module AnlInIOM3 lev2 0 U6 0 8768 -100 10000 Integer 16
IOM/PTM
module AnlInIOM3 del 5 s 0 8772 0 180 Unsigned 16
IOM/PTM
module AnlInIOM4 lev1 0 U7 0 8765 -100 10000 Integer 16
IOM/PTM
module AnlInIOM4 lev2 0 U7 0 8769 -100 10000 Integer 16
IOM/PTM
module AnlInIOM4 del 5 s 0 8773 0 180 Unsigned 16
Values (MRS16):
Name Firmware ver. Application Date App. ver. Ser. num.
IL-NT IL-NT-1.0 R:26.07.2007 MRS16 14.8.2007 1,0 12345678
Internet connection
IL-NT controllers can be monitored from LiteEdit 3.0 over the Internet using Internet Bridge (IG-IB)
connected to the controller RS232 port.
Hint:
It is strongly recommended to use the same type of modem on the both sides (IL and PC) of
connection.
Allowed supply voltage drop-out: 100ms from min. 10V, return to min. 8V
Battery voltage measurement tolerance 2 % at 24V
Hint:
For the supply voltage less than 7V the backlight of the display is switched off.
Short-term voltage drops (e.g. during the engine cranking) do not affect the operation at all.
Operating conditions
Operating temperature IL-NT -20..+70oC
Operating temperature IL-NT LT# -40..+70oC
Storage temperature -30..+80oC
Protection front panel IP65
Humidity 95% without condensation
Standard conformity
Low Voltage Directive EN 61010-1:95 +A1:97
Electromagnetic Compatibility EN 50081-1:94, EN 50081-2:96
EN 50082-1:99, EN 50082-2:97
Vibration 5 - 25 Hz, 1,6mm
25 - 100 Hz, a = 4 g
Shocks a = 200 m/s2
#
Low Temperature modification
LCD display limits controller operating temperature range to 20 oC - + 70 oC even if the other
electronic components work in wider temperature range.
Internal preheating foil is mounted in InteliLiteNT LT to extend display operational temperature range.
Preheating starts at temperature below 5 oC and preheating power depends on temperature and
power supply voltage.
Technical data
IL-NT Standard Order code:IL-NT-xxxxx LT
Operating temperature -20 oC..+70oC -40 oC..+70oC
Storage temperature -30 oC..+80oC -30 oC..+80oC
Generator
Nominal frequency 50-60Hz
Frequency measurement tolerance 0,2Hz
Current inputs
Nominal input current (from CT) 5A
Load (CT output impedance) < 0,1
CT input burden < 0,2 VA per phase (In=5A)
Max. measured current from CT 10 A
Current measurement tolerance 2% from the Nominal current
Max. peak current from CT 150 A / 1s
Max. continuous current 12 A
Voltage inputs
Measuring voltage range 0 277 VAC phase to neutral
0 480 VAC phase to phase
Maximal measured voltage 340 VAC phase to neutral
600 VAC phase to phase
Input resistance 0.6 M phase to phase
0.3 M phase to neutral
Voltage measurement tolerance 2 % from the Nominal voltage
Overvoltage class III / 2 (EN61010)
Analog inputs
Not electrically separated
Number of inputs 3
Resolution 10 bits
Jumper selectable range V, Ohm(default), mA
Maximal resistance range 2500
Maximal voltage range 2.5 V
Current range 0 20 mA
Input impedance 180 for mA measuring
Input impedance > 100 k for V measuring
Resistance measurement tolerance 2 % 2 out of measured value
Voltage measurement tolerance 1 % 1mV out of measured value
D+ function
Max. D+ output current 300 mA
Guaranteed level for signal Charging OK 80% of supply voltage
Following dynamic cable parameters are important especially for maximal 200 meters CAN bus length
and 32 iS-COM units connected:
Nominal Velocity of Propagation min. 75% (max. 4,4 ns/m)
Wire crosscut min.0,25 mm2
Maximal attenuation (at 1 MHz) 2 dB / 100m
IGS-PTM
Voltage supply 8-36V DC
Consumption 0,1A depend on supply voltage
Mechanical dimensions: 40 x 95 x 45 mm , DIN rail (35 mm) mounted
Interface to controller CAN
Binary inputs and outputs see IG-IOM
Analog output see IG-IOM
Analog inputs
Not electrically separated
Number of inputs 4
Resolution 10 bits
Maximal resistance range 0 250
Maximal voltage range 0 100 mV
Maximal current range 0 20 mA
Resistance measurement tolerance 1 % 2 out of measured value
Voltage measurement tolerance 1,5 % 1mV out of measured value
Current measurement tolerance 2,5 % 0,5mA out of measured value
IGL-RA15
Power supply
Voltage supply 8-36V DC
Consumption 0,35-0,1A (+1A max horn output)
Depend on supply voltage
Operating conditions
Operating temperature -20..+70oC
Storage temperature -40..+80oC
Protection front panel IP65
Horn output
Maximum current 1A
Maximum switching voltage 36 VDC