100% found this document useful (1 vote)
220 views19 pages

3458 1

The document discusses power system protection zones. It explains that zones of protection overlap to ensure all elements are covered by at least one zone, with more important elements covered by two zones. A zone boundary is defined by a circuit breaker and current transformer. Primary protection zones clear faults quickly, while backup protection zones operate more slowly if primary protection fails. Backup protection can be local, within the same substation, or remote, from other substations. Examples demonstrate local and remote backup protection clearing faults when primary protection fails.

Uploaded by

Belayneh Tadesse
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
220 views19 pages

3458 1

The document discusses power system protection zones. It explains that zones of protection overlap to ensure all elements are covered by at least one zone, with more important elements covered by two zones. A zone boundary is defined by a circuit breaker and current transformer. Primary protection zones clear faults quickly, while backup protection zones operate more slowly if primary protection fails. Backup protection can be local, within the same substation, or remote, from other substations. Examples demonstrate local and remote backup protection clearing faults when primary protection fails.

Uploaded by

Belayneh Tadesse
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 19

Power system

protection
Zones of Protection

1
Zones of protection
Zone of protection of a relay is the place or the distance
that the relay can protect easily.Fig.1 shows an example
of protection zones for three circuit breakers. It is to be
noted that the protection zones are overlapped.

Fig.1
2
In power systems, all power system elements must be
encompassed by at least one zone
The more important elements must be included in at
least two zones.
Zones must overlap to prevent any element from being
unprotected.
The overlap must be finite but small to minimize the
likelihood of a fault inside this region.
A zone boundary is usually defined by a CT and a CB.
The CT provides the ability to detect a fault inside the
zone
The CBs provide the ability to isolate the fault.

3
CLOSED AND OPEN PROTECTION ZONES

4
Primary Zones of protection

5
Primary protection in power systems

6
Backup protection

It is essential that provision be made to clear the fault by


some alternative protection system in case of the
primary protection fails to operate. These are referred to
as backup protection systems.
Ideally primary and backup are independent ( relay,
breaker , CT,PT).
Slower than primary.
Sometimes backup protection opens more circuit
breakers than absolutely necessary to clear the fault.
Provide primary protection when usual primary
equipment out of service.

7
Two Types of Backup Protection:

Back up relaying may be installed locally, in the same


substation, or remote in other substations or places:

Local backup : Clears fault in the same station where the


failure has occurred
Remote backup : Clears fault on station away from where
the failure has occurred

8
Primary and Back up protection at the same location
( Local Backup)

9
Local backup protection at differente locations

10
Remote back up protection

Selectivity and zones of protection


Selectivity is defined in terms of regions of a power
system (zones of protection) for which a given relay is
responsible.
The relay will be considered secure if it responds only to
faults within its zone of protection.
11
Examples of Backup Protection:

Example .1:

The figure shows the one-line diagram of a power system and helps
illustrate the concept of backup protection. The tie circuit breaker (T)
is assumed to work normally closed. For a fault at CD, Line Breakers
5 and 6 should operate as the primary protection. If Protection 5 fails
to operate, with existing technology, we have two possibilities for
cutting the fault current contribution from A, B, and F: open Breakers
1, 3 and 8; or open
Breakers 2 and T. In any case, backup protection needs time delay.
The primary protection needs to be given an opportunity to operate
before using the decision of a backup operation
12
Remote Backup

Breakers 1, 3 and 8 are located in a remote substation. This is the remote


backup protection. An advantage of remote backup protection is low cost:
the remote backup protection comes from protection equipment that is
needed for primary protection functions of adjacent system elements.
Therefore, there is no need for additional investment.

13
Local Backup

Breakers 2 and T represent local backup protection, which is located


in the same substation as the primary protection. Local backup
protection is more expensive than remote backup because additional
equipment is needed. Advantages of local backup over remote
backup are greater sensitivity, greater selectivity, and faster
operation speed.

14
Example 2: Consider the following simple power system:

Discuss the local and remote backup protection for two fault locations
as follows:
15
Case 1: Local Backup

For fault at F1: Suppose that breaker J operate and breaker H failed
to operate. Therefore:
G and I must operate as local backup protection
16
Case 2: Local Backup

For fault at F2: Suppose that breakers P and Q operate and breaker M failed
to operate. Therefore:
L must operate as local backup protection and I should tripped by
communication signal (Transfer Trip
17
Case 3: Remote Backup

For fault at F1: Suppose that breaker J operate and breaker H failed to
operate. Therefore:
E, F, L and M must operate as Remot backup protection

18
Case 4: Remote Backup

For fault at F1: Suppose that breakers P & Q operate and breaker M failed to
operate. Therefore:
I, B, and C must operate as Remot backup protection
19

You might also like