Safe Load Tables

High strength precast &


prestressed concrete lintels

June 2003
corporate

Policy
Cast-Crete lintels and sills have been incorporated into structures throughout Florida and other south-

eastern states for over 45 years to the complete satisfaction of all concerned. We produced in excess

of 17 million lintels representing over 100 million lineal feet of product during that period of time.

Probably every concrete products producer in America claims to sell quality products at competitive

prices, and to back up all orders with superior service.

Cast-Crete also has these policies. But we say it this way:

1. QUALITY: Cast-Crete guarantees that every lintel and sill it sells meets or exceeds all known

federal, state, and local strength and quality specifications. Should tests prove any failure to meet such

specifications, Cast-Crete, at its own expense, will replace IN THE WALL all units supplied to the job.

2. SERVICE: Cast-Crete guarantees delivery as promised on every lintel and sill order on the agreed

delivery date. If we fail to perform on any guaranteed delivery, Cast-Crete will pay the customer for

any resulting unproductive labor charges. Money talks. We dont claim to be perfect. But if you lose

through our failure, you can look to us to pay the bill.

3. GUARANTEE: Cast-Cretes lintels and sills are guaranteed against any and all defects in work-

manship and/or materials for the lifetime of the structure into which they are properly installed.

PAGE 1
Engineering

product description
specifications
High strength precast and prestressed concrete lintels designed to be used unfilled or filled with grout to form a composite reinforced beam using concrete
masonry units.

Materials
fc 8" precast lintels = 3500 psi Concrete masonry units (CMU) per ASTM C90 with
f'c 8" prestressed, 6" and 12" precast lintels = 6000 psi minimum net area compressive strength = 1900 psi
f'c 4" precast lintels = 3000 psi Rebar per ASTM A615 Grade 60
Grout per ASTM C476 f'g = 3000 psi w/maximum 3/8 inch aggregate Prestressing strand per ASTM A416 Grade 270 low relaxation
and 8 to 11 inch slump. 7/32 inch wire per ASTM A510
Mortar per ASTM C270 Type M or S
General Notes
1. Provide full mortar head and bed joints. 9. Safe load ratings based on rational design analysis per ACI 318 and
2. Shore filled lintels as required. ACI 530
3. Installation of lintel must comply with architectural 10. Product Approvals: Miami-Dade County, Florida Nos. 03-0605.05
and/or structural drawings. and 03-0605.04. Florida Certificate of Product Approval No. FL158.
4. U-Lintels are manufactured with 5-1/2 inch long notches at 11. The exterior surface of lintels installed in exterior concrete masonry
ends to accommodate vertical cell reinforcing and grouting. walls shall have a coating of stucco applied in accordance with ASTM
C-926 or other approved coating.
5. All lintels meet or exceed L/360 vertical deflection, except
lintels 17'-4" and longer with a nominal height of 8" meet 12. Lintels loaded simultaneously with vertical (gravity or uplift) and
or exceed L/180. horizontal (lateral) loads should be checked for the combined loading
with the following equation:
6. Bottom field added rebar to be located at the bottom of lintel cavity. Applied vertical load + Applied horizontal load < 1.0
7. 7/32 inch diameter wire stirrups are welded to the bottom steel for Safe vertical load Safe horizontal load
mechanical anchorage.
8. Cast-in-place concrete may be provided in composite lintel in lieu of
concrete masonry units.

Safe load table notes


1. All values based on minimum 4 inch nominal bearing. Exception: Safe 8. For composite lintel heights not shown, use safe load from next
loads for unfilled lintels must be reduced by 20% if bearing length is lower height.
less than 6-1/2 inches. 9. For lintel lengths not shown, use safe load from the next longest
2. N.R. = Not Rated. length shown.
3. Safe loads are superimposed allowable load. 10. All safe loads in units of pounds per linear foot.
4. Safe loads based on Grade 40 or Grade 60 field rebar. 11. All safe loads based on simply supported span.
5. Additional lateral load capacity can be obtained by the designer by 12. The number in the parenthesis indicates the percent reduction for
providing additional reinforced masonry above the precast lintel. See grade 40 field added rebar.
Reinforced CMU on Page 4. Example: 7'6" lintel Type 8F32-1B safe gravity load =6472 (15)
6. One #7 rebar may be substituted for two #5 rebars in 8" lintels only. w/15% reduction => 6472 (.85) = 5501 plf
7. The designer may evaluate concentrated loads from the safe load
tables by calculating the maximum resisting moment and shear at
d-away from the face of support.
PAGE 2
reinforcing

OVERALL LENGTH TOP STEEL BOTTOM STEEL OVERALL LENGTH TOP STEEL BOTTOM STEEL
8" WIDE PRECAST U-LINTEL 6" WIDE PRECAST U-LINTEL
2'-10" Thru 5'-10" 2 - 7/32" wire 2 - #3 rebar 3'-6" Thru 5'-10" 2 - 7/32" wire 2 - #3 rebar
5'-11" Thru 7'-6" 2 - 7/32" wire 2 - #4 rebar 5'-11" Thru 7'-6" 2 - 7/32" wire 2 - #4 rebar
7'-7" Thru 10'-6" 2 - #3 rebar 2 - #4 rebar 7'-7" Thru 10'-6" 2 - #3 rebar 2 - #4 rebar
10'-7" Thru 14'-0" 2 - #3 rebar 2 - #5 rebar 10'-7" Thru 17'-4" 2 - #3 rebar 2 - #5 rebar
8" WIDE PRESTRESSED U-LINTEL 12" WIDE PRECAST U-LINTEL
14'-1" Thru 19'-4" 2 - 7/32" wire 2 - 7/16 strand 3'-6" Thru 7'-6" 2 - 7/32" wire 2 - #5 rebar
19'-5" Thru 24'-0" 2 - 7/32" wire 2 - 7/16 strand 7'-7" Thru 19'-4" 2 - #3 rebar 2 - #5 rebar
and 2 - #4 rebar
8" WIDE PRECAST RECESS U-LINTEL 4" WIDE PRECAST SOLID LINTEL
4'-4" Thru 5'-10" 2 - 7/32" wire 2 - #3 rebar 3'-6" Thru 10'-6" 1 - #3 rebar 1 - #3 rebar
5'-11" Thru 9'-8" 2 - #3 rebar 2 - #4 rebar

Cross Sections

8" PRECAST 8" RECESS 8" PRESTRESSED

4" SOLID 6" PRECAST 12" PRECAST

INSTALLATION OF COMPOSITE U LINTELS


Set precast lintel in full joints of mortar and shore as required. Place bottom field rebar on the floor of the lintel cavity, if required. Set additional courses of
concrete masonry units to obtain composite height. Place top field rebar. Fill composite lintel with grout.

PAGE 3
How to read safe load tables

TYPE DESIGNATION

For a 5'-10 overall length lintel type 8F161B/IT:


Safe superimposed gravity load = 4360 PLF
Safe superimposed uplift load = 2093 PLF
Safe superimposed lateral load = 339 PLF

Example composite lintel types Reinforced CMU

Note: See Safe Load Table


Notes #5 for Application

PAGE 4
8 inch Lintel

Safe Loads (Lbs/FT)


gravity
8F8-0B 8F12-0B 8F16-0B 8F20-0B 8F24-0B 8F28-0B 8F32-0B
Type 8U8
Length* 8F8-1B 8F12-1B 8F16-1B 8F20-1B 8F24-1B 8F28-1B 8F32-1B
3069 4605 6113 7547 8974 10394 11809
2'10" (34") PRECAST 2231 3069 4605 6113 7547 8974 10394 11809
3069 3719 5163 6607 8054 9502 10951
3'-6" (42") PRECAST 2231 3069 4605 6113 7547 8974 10394 11809
2561 2751 3820 4890 5961 7034 8107
4'0" (48") PRECAST 1966 2693 4605 6113 7547 8974 10394 11809
1969 2110 2931 3753 4576 5400 6224
4'6" (54") PRECAST 1599 2189 4375 6113 7547 (7) 8672 10294 11809
1349 1438 1999 2560 3123 3686 4249
5'4" (64") PRECAST 1217 1663 3090 5365 7547 (36) 7342 (19) 8733 (19) 10127 (19)
1105 1173 1631 2090 2549 3009 3470
5'10" (70") PRECAST 1062 1451 2622 4360 7168 (45) 6036 (19) 7181 (19) 8328 (20)
1238 2177 3480 3031 3707 4383 5061
6'6" (78") PRECAST 908 1238 2177 3480 5381 8360 10394 (37) 8825 (14)
1011 1729 2632 2205 2698 3191 3685
7'6" (90") PRECAST 743 1011 1729 2661 3898 5681 8467 (44) 6472 (15)
699 1160 1625 2564 3486 2818 3302
9'4" (112") PRECAST 554 752 1245 1843 2564 3486 4705 (37) 6390 (47)
535 890 1247 2093 2777 2163 2536
10'6" (126") PRECAST 475 643 1052 1533 2093 2781 3643 (38) 4754 (45)
582 945 1366 1846 2423 3127 4006
11'4" (136") PRECAST 362 582 945 1366 1846 2423 3127 4006
540 873 1254 1684 2193 2805 3552
12'0" (144") PRECAST 337 540 873 1254 1684 2193 2805 3552
471 755 1075 1428 1838 2316 2883
13'4" (160") PRECAST 296 471 755 1075 1428 1838 2316 2883
424 706 1002 1326 1697 2127 2630
14'0" (168") PRECAST 279 442 706 1002 1326 1697 2127 2630
NR NR NR NR NR NR NR
14'8" (176") PRESTRESSED N.R. 458 783 1370 1902 2245 2517 2712
NR NR NR NR NR NR NR
15'4" (184") PRESTRESSED N.R. 412 710 1250 1733 2058 2320 2513
NR NR NR NR NR NR NR
17'4" (208") PRESTRESSED N.R. 300 548 950 1326 1609 1849 2047
NR NR NR NR NR NR NR
19'4" (232") PRESTRESSED N.R. 235 420 750 1037 1282 1515 1716
NR NR NR NR NR NR NR
21'4" (256") PRESTRESSED N.R. 180 340 598 845 1114 1359 1468
NR NR NR NR NR NR NR
22'0" (264") PRESTRESSED N.R. 165 315 550 784 1047 1285 1399
NR NR NR NR NR NR NR
24'0" (288") PRESTRESSED N.R. 129 250 450 654 884 1092 1222
PAGE 5 * LENGTH = OVERALL LENGTH OF LINTEL (X) = SEE SAFE LOAD TABLE NOTES #12
8 inch Lintel

(Lbs/FT) Safe Loads


Uplift lateral
8F8-1T 8F12-1T 8F16-1T 8F20-1T 8F24-1T 8F28-1T 8F32-1T REINF.
Type 8U8 8F8 CMU**
Length* 8F8-2T 8F12-2T 8F16-2T 8F20-2T 8F24-2T 8F28-2T 8F32-2T
1972 3173 4460 5747 7034 8321 9608
2'10" (34") PRECAST 1972 3173 4460 5747 7034 8321 9608
1293 1642 2135
1569 2524 3547 4569 5591 6613 7636
3'-6" (42") PRECAST 1569 2524 3547 4569 5591 6613 7636
1025 1024 1830
1363 2192 3079 3966 4853 5740 6627
4'0" (48") PRECAST 1363 2192 3079 3966 4853 5740 6627
765 763 1365
1207 1940 2724 3508 4292 5077 5861
4'6" (54") PRECAST 1207 1940 2724 3508 4292 5077 5861
592 591 1057
1016 1632 2290 2949 3607 4265 4924
5'4" (64") PRECAST 1016 1632 2290 2949 3607 4265 4924
411 411 734
909 1492 2093 2694 3295 3897 4498
5'10" (70") PRECAST 929 1492 2093 2694 3295 3897 4498
340 339 607
835 (12) 1340 1880 2419 2959 3498 4038
6'6" (78") PRECAST 835 1340 1880 2419 2959 3498 4038
507 721 483
727 (23) 1021 1634 (12) 2102 (11) 2571 (10) 3039 (10) 3508 (9)
7'6" (90") PRECAST 727 1166 1634 2102 2571 3039 3508
424 534 357
591 680 1133 (15) 1471 (15) 1811 (15) 2152 (16) 2494 (15)
9'4" (112") PRECAST 591 851 1326 1705 2084 2463 2842
326 512 227
530 552 914 (15) 1185 (15) 1458 (15) 1732 (15) 2007 (15)
10'6" (126") PRECAST 530 686 1183 1526 1865 2204 2544
284 401 178
474 485 798 (15) 1034 (15) 1272 (15) 1510 (15) 1749 (15)
11'4" (136") PRECAST 494 599 1028 1422 1738 2053 2369
260 452 152
470 (9) 441 723 (14) 936 (14) 1151 (15) 1366 (15) 1582 (15)
12'0" (144") PRECAST 470 543 928 1349 1649 1948 2247
244 402 135
418 (15) 373 606 (14) 783 (14) 962 (14) 1141 (14) 1321 (14)
13'4" (160") PRECAST 428 455 770 1145 1444 1718 1993
217 324 109
384 (15) 346 559 (14) 723 (14) 887 (14) 1052 (14) 1218 (14)
14'0" (168") PRECAST 410 420 709 1050 1434 (8) 1694 (8) 1954 (7)
205 293 98
239 323 519 (13) 671 (13) 823 (13) 976 (14) 1129 (14)
14'8" (176") PRESTRESSED 246 390 655 968 1324 (8) 1625 (11) 1874 (11)
N.R. 284 89
224 302 485 (13) 626 (13) 767 (13) 909 (13) 1052 (13)
15'4" (184") PRESTRESSED 230 364 609 897 1224 (8) 1562 (14) 1801 (14)
N.R. 259 82
187 255 404 (12) 520 (12) 637 (12) 754 (12) 872 (12)
17'4" (208") PRESTRESSED 192 303 500 732 993 (8) 1268 (14) 1470 (14)
N.R. 194 63
162 222 347 (11) 446 (11) 546 (12) 646 (12) 746 (12)
19'4" (232") PRESTRESSED 166 261 424 616 831 (8) 1057 (14) 1225 (14)
N.R. 148 51
142 198 306 (11) 393 (11) 480 (11) 567 (11) 654 (11)
21'4" (256") PRESTRESSED 142 230 369 531 713 (7) 903 (13) 1046 (13)
N.R. 125 42
137 192 295 (10) 378 (11) 461 (10) 545 (11) 629 (11)
22'0" (264") PRESTRESSED 137 221 354 508 681 (7) 861 (13) 997 (13)
N.R. 116 39
124 175 267 (10) 341 (10) 416 (10) 491 (10) 566 (10)
24'0" (288") PRESTRESSED 124 200 316 450 600 (7) 756 (12) 875 (13)
N.R. 91 33
* LENGTH = OVERALL LENGTH OF LINTEL (X) = SEE SAFE LOAD TABLE NOTES #12 ** = SEE SAFE LOAD TABLE NOTES #5 PAGE 6
8 inch Recess Lintel

Safe Loads (Lbs/FT)


gravity
8RF6-0B 8RF10-0B 8RF14-0B 8RF18-0B 8RF22-0B 8RF26-0B 8RF30-0B
Type 8RU6
Length* 8RF6-1B 8RF10-1B 8RF14-1B 8RF18-1B 8RF22-1B 8RF26-1B 8RF30-1B
1749 3355 3280 4349 5421 6493 7567
4'4" (52") PRECAST 1635 1891 3699 5206 6639 8060 9479 10893
1596 3063 2992 3968 4946 5924 6904
4'6" (54") PRECAST 1494 1756 3699 5206 6639 8060 9479 10893
920 1770 1716 2277 2839 3402 3966
5'8" (68") PRECAST 866 1167 2481 4567 6389 8060 (34) 7917 (19) 9311 (19)

859 1653 1600 2124 2649 3174 3700


5'10" (70") PRECAST 810 1113 2342 4242 6639 (10) 8060 (39) 7402 (19) 8706 (19)

901 1825 3120 5048 7747 9448 7360


6'8" (80") PRECAST 797 901 1825 3120 5048 7915 9479 10893 (32)

755 1490 2459 3776 5743 7239 5623


7'6" (90") PRECAST 669 755 1490 2459 3776 5743 8998 (19) 10893 (48)

466 999 1568 2253 3129 4091 3146


9'8" (116") PRECAST 411 526 999 1568 2253 3129 4150 5891 (47)

uplift Lateral
8RF6-1T 8RF10-1T 8RF14-1T 8RF18-1T 8RF22-1T 8RF26-1T 8RF30-1T REINF.
Type 8RU6 8RF6 CMU**
Length* 8RF6-2T 8RF10-2T 8RF14-2T 8RF18-2T 8RF22-2T 8RF26-2T 8RF30-2T
905 1748 2635 3522 4409 5296 6183
4'4" (52") PRECAST 905 1748 2635 3522 4409 5296 6183
758 757 1365
867 1675 2525 3374 4224 5074 5924
4'6" (54") PRECAST 867 1675 2525 3374 4224 5074 5924
694 693 1249
675 1301 1960 2618 3277 3935 4594
5'8" (68") PRECAST 675 1301 1960 2618 3277 3935 4594
408 407 734
655 1262 1900 2538 3176 3815 4453
5'10" (70") PRECAST 655 1262 1900 2538 3176 3815 4453
382 381 687
570 1012 1651 2204 2758 3312 3865
6'8" (80") PRECAST 570 1097 1651 2204 2758 3312 3865
595 788 510
506 797 1462 (8) 1952 (7) 2442 (6) 2931 (6) 3257
7'6" (90") PRECAST 506 967 1462 1952 2442 2931 3421
509 674 393
395 491 931 (12) 1301(15) 1640(15) 1980(15) 2322(16)
9'8" (116") PRECAST 395 589 1135 1514 1893 2272 2652
370 490 227
* LENGTH = OVERALL LENGTH OF LINTEL (X) = SEE SAFE LOAD TABLE NOTES #12
** = SEE SAFE LOAD TABLE NOTES #5

PAGE 7
6 inch lintel

(Lbs/FT) Safe Loads


gravity
Length* Type 6U8 6F8-1B 6F12-1B 6F16-1B 6F20-1B 6F24-1B 6F28-1B 6F32-1B
3'6" (42") PRECAST 2332 2676 3892 5050 6148 7227 8297 9357
4'0" (48") PRECAST 2025 2313 3892 5050 6148 7227 8297 9357
4'6" (54") PRECAST 1654 1887 3633 5050 6148 7227 8297 9357
5'10" (70") PRECAST 1067 1260 2198 3557 5734 7227 8297 (31) 8225 (19)
6'6" (78") PRECAST 949 1078 1831 2850 4328 6737 8297 9357
7'6" (90") PRECAST 779 883 1459 2188 3151 4524 6654 9357 (11)
9'4" (112") PRECAST 584 660 1056 1523 2084 2795 3731 5017
10'6" (126") PRECAST 503 566 895 1270 1706 2236 2898 3747
11'4" (136") PRECAST 457 513 805 1133 1507 1952 2492 3163
12'0" (144") PRECAST 425 477 744 1042 1377 1769 2238 2808
13'4" (160") PRECAST 373 417 646 895 1170 1485 1852 2285
14'0" (168") PRECAST 351 392 605 835 1087 1373 1703 2087
17'4" (208") PRECAST N.R. 299 455 620 794 985 1198 1437

uplift Lateral
REINF.
Length* Type 6F8-1T 6F12-1T 6F16-1T 6F20-1T 6F24-1T 6F28-1T 6F32-1T 6U8 6F8 CMU**

3'6" (42") PRECAST 1412 1860 2613 3366 4120 4873 5626 587 1055 587
4'0" (48") PRECAST 1225 1615 2269 2923 3576 4230 4883 487 787 438
4'6" (54") PRECAST 1083 1430 2008 2585 3163 3741 4319 416 609 339
5'10" (70") PRECAST 831 1100 1543 1987 2430 2874 3317 300 350 195
6'6" (78") PRECAST 723 988 1385 1783 2181 2578 2976 263 496 155
7'6" (90") PRECAST 648 (16) 850 1204 1550 1895 2240 2586 222 367 115
9'4" (112") PRECAST 575 564 967 (5) 1257 (5) 1537 (5) 1816 (4) 2096 (3) 173 352 73
10'6" (126") PRECAST 514 456 776 (5) 1125 (15) 1375(14) 1625(14) 1875(13) 151 276 57
11'4" (136") PRECAST 474 399 676 (5) 983(15) 1210(15) 1439(15) 1669(15) 139 311 49
12'0" (144") PRECAST 454 (7) 362 611 (5) 885(15) 1090(15) 1296(15) 1502(15) 131 277 43
13'4" (160") PRECAST 402(13) 305 509 (5) 735(15) 904(15) 1074(15) 1245(15) 117 223 35
14'0" (168") PRECAST 368(13) 282 469 (5) 675(14) 830(14) 986(15) 1143(15) 111 202 32
17'4" (208") PRECAST 253(12) 205 334 (4) 475(13) 583(13) 692(13) 801(13) N.R. 130 20
* LENGTH = OVERALL LENGTH OF LINTEL (X) = SEE SAFE LOAD TABLE NOTES #12 ** = SEE SAFE LOAD TABLE NOTES #5 PAGE 8
12 inch Lintel

Safe Loads (Lbs/FT)


gravity
Length* Type 12U8 12F8-2B 12F12-2B 12F16-2B 12F20-2B 12F24-2B 12F28-2B 12F32-2B
3'6" (42") PRECAST 3428 5000 5838 7619 9352 11060 12755 14438
4'0" (48") PRECAST 2923 4232 5838 7619 9352 11060 12755 14438
4'6" (54") PRECAST 2396 3464 5304 7619 9352 11060 12755 14438
5'10" (70") PRECAST 1612 2320 3218 5234 8487 11060 12755 14438 (11)
6'6" (78") PRECAST 1383 1986 2679 4196 6421 10032 12755 14438 (30)
7'6" (90") PRECAST 1138 1628 2131 3218 4676 6756 9763 13528 (46)
9'4" (112") PRECAST 795 1216 1535 2230 3083 4167 5593 7552 (40)
10'6" (126") PRECAST 614 1043 1295 1853 2516 3323 4334 5632 (38)
11'4" (136") PRECAST 518 945 1162 1649 2216 2893 3719 4746 (38)
12'0" (144") PRECAST 456 878 1073 1513 2020 2617 3333 4206 (39)
13'4" (160") PRECAST 359 767 (8) 926 1294 1709 2188 2743 3409 (42)
14'0" (168") PRECAST 321 720 (12) 865 1204 1584 2017 2451 3106 (43)
17'4" (208") PRECAST N.R. 451 (17) 631 (18) 881 (15) 1141 (14) 1428 (14) 1750 (16) 2102 (52)
19'4" (232") PRECAST N.R. 343 (17) 477 (19) 700 (19) 925 (20) 1152 (20) 1380 (20) 1609 (54)

uplift Lateral
REINF.
Length* Type 12F8-2T 12F12-2T 12F16-2T 12F20-2T 12F24-1T 12F28-2T 12F32-2T 12U8 12F8 CMU**

3'6" (42") PRECAST 2752 3849 5408 6967 8526 10084 11643 1295 4841 3707
4'0" (48") PRECAST 2389 3343 4696 6048 7401 8753 10106 1295 4841 3412
4'6" (54") PRECAST 2113 2959 4154 5350 6546 7741 8937 1049 3922 2642
5'10" (70") PRECAST 1623 2275 3192 4109 5026 5943 6860 681 2547 1516
6'6" (78") PRECAST 1444 2044 2867 3689 4512 5335 6158 579 2167 1206
7'6" (90") PRECAST 1267(14) 1743 2492 3207 3921 4636 5350 474 1771 893
9'4" (112") PRECAST 1028 (9) 1156 1980 (7) 2600 (8) 3179 (7) 3757 (7) 4335 (6) 355 1326 566
10'6" (126") PRECAST 920 (18) 935 1591 (7) 2276(15) 2804(15) 3335(16) 3867(16) 306 1143 444
11'4" (136") PRECAST 858 (24) 819 1386 (7) 1978(15) 2436(15) 2896(15) 3357(15) 278 1041 379
12'0" (144") PRECAST 814 (27) 744 1253 (7) 1784(15) 2196(15) 2610(15) 3025(15) 260 971 337
13'4" (160") PRECAST 678 (27) 626 1045 (6) 1482(15) 1822(15) 2165(15) 2508(15) 229 857 271
14'0" (168") PRECAST 622 (27) 579 963 (6) 1362(14) 1675(14) 1989(14) 2304(14) 216 809 246
17'4" (208") PRECAST 434 (25) 423 687 (6) 962 (13) 1180(13) 1400(13) 1619(13) N.R. 633 (12) 159
19'4" (232") PRECAST 366 (23) 366 587 (5) 816 (12) 1000(12) 1185(12) 1370(12) N.R. 534 (17) 127
PAGE 9 * LENGTH = OVERALL LENGTH OF LINTEL (X) = SEE SAFE LOAD TABLE NOTES #12 ** = SEE SAFE LOAD TABLE NOTES #5
12 inch recess Lintel

(Lbs/FT) Safe Loads gravity


Length* Type 12RU6 12RF6-2B 12F10-2B 12RF14-2B 12RF18-2B 12RF22-2B 12RF26-2B 12RF30-2B
4'4" (52") PRECAST 2538 2942 5468 7584 9640 11669 13679 15679
4'6" (54") PRECAST 2319 2740 5468 7584 9640 11669 13679 15679
5'8" (68") PRECAST 1347 1841 3555 6395 9640 11669 13679 15679 (24)
5'10" (70") PRECAST 1259 1758 3361 5954 9358 11669 13679 15679 (29)
6'8" (80") PRECAST 924 1430 2633 4415 6884 10353 (16) 12573 (16) 14800 (45)
7'6" (90") PRECAST 703 1203 2157 3494 5259 7922 (16) 9623 (17) 11329 (46)
9'8" (116") PRECAST 389 843 1451 (5) 2157 3203 (9) 4427 (16) 5417 (17) 6380 (47)

uplift Lateral
REINF.
Length* Type 12RF-2T 12RF10-2T 12RF14-2T 12RF18-2T 12RF22-2T 12RF26-2T 12RF30-2T 12RU6 12RF6 CMU**

4'4" (52") PRECAST 1626 2668 4022 5377 6731 8086 9440 1295 3692 3412
4'6" (54") PRECAST 1558 2557 3855 5152 6450 7748 9045 1213 3458 3122
5'8" (68") PRECAST 1210 1987 2994 4000 5006 6012 7018 784 2236 1835
5'10" (70") PRECAST 1173 1927 2902 3877 4853 5828 6803 747 2129 1718
6'8" (80") PRECAST 1020 (4) 1676 2522 3368 4215 5061 5908 602 1716 1274
7'6" (90") PRECAST 904 (15) 1319 2234 2983 3732 4482 5231 504 1438 982
9'8" (116") PRECAST 703 (14) 810 1550 2316 (8) 2897 (8) 3477 (7) 4057 (6) 355 1011 566
* LENGTH = OVERALL LENGTH OF LINTEL (X) = SEE SAFE LOAD TABLE NOTES #12
** = SEE SAFE LOAD TABLE NOTES #5

4 inch solid Lintel

gravity uplift Lateral gravity uplift Lateral


Length* Type 4S8 4S8 4S8 Length* Type 4S8 4S8 4S8
3'6" (42") PRECAST 1180 687 371 6'6" (78") PRECAST 360 366 118
4'0" (48") PRECAST 959 597 320 7'6" (90") PRECAST 260 280 87
4'6" (54") PRECAST 789 529 258 9'4" (112") PRECAST 156 187 55
5'10" (70") PRECAST 460 407 148 10'6" (126") PRECAST 116 152 43
* LENGTH = OVERALL LENGTH OF LINTEL (X) = SEE SAFE LOAD TABLE NOTES #12 ** = SEE SAFE LOAD TABLE NOTES #5 PAGE 10