GAS system
Series 4000 natural gas
400V / 50 Hz
NOx < 500 mg/Nm3
System Ratings
Gas genset with optional heat recovery module
Genset Engine Output Energy Efficiency Methane
Type Type Elect.1) Therm.2) Exhaust3) Low Temp. input4) Electr. Total number5)
kWel. kWth. kWth. (C) kWth. (C) kW nel. (%) ntot (%)
MTU 8V4000 GS L33 776 401 422 (120) 47 (40) 1832 42.4 87.3 70
MTU 8V4000 GS L33 854 443 448 (120) 49 (40) 1993 42.8 87.5 80
MTU 8V4000 GS L64 1012 475 461 (120) 69 (43) 2298 44.0 84.8 80
MTU 12V4000 GS L33 1286 664 659 (120) 88 (40) 2974 43.2 87.7 80
MTU 12V4000 GS L64 1523 712 691 (120) 104 (43) 3438 44.3 85.1 80
MTU 16V4000 GS L33 1718 974 821 (120) 113 (40) 3991 43.0 88.0 80
MTU 16V4000 GS L64 1999 950 928 (120) 125 (43) 4511 44.3 85.9 80
MTU 16V4000 GS L64 2028 965 936 (120) 127 (43) 4573 44.3 85.9 80
MTU 20V4000 GS L33 2145 1161 1078 (120) 142 (40) 4990 43.0 87.9 80
MTU 20V4000 GS L64 2535 1186 1212 (120) 176 (43) 5751 44.1 85.8 80
Hot ambient conditions
MTU 8V4000 GS L32 776 446 420 (120) 32 (53) 1853 41.9 88.6 80
MTU 12V4000 GS L32 1169 632 638 (120) 43 (53) 2747 42.5 88.8 80
MTU 16V4000 GS L32 1560 863 805 (120) 76 (53) 3651 42.7 88.4 80
MTU 20V4000 GS L32 1948 1035 1101 (120) 78 (53) 4577 42.6 89.2 80
Low methane number
MTU 16V4000 GS L32 ER 1560 921 937 (120) 84 (53) 3848 40.5 88.8 60
MTU 20V4000 GS L32 ER 1948 1143 1181 (120) 99 (53) 4812 40.5 88.8 60
1) Rated power at nominal voltage, power factor = 1,0 and nominal frequency 2) Heat output from engine cooling with tolerance of 8%
3) Heat output from exhaust (exhaust cooling to 120C) with tolerance of 8% 4) Performance data in accordance with ISO 3046/I-2002 with tolerance of 5%
5) Referenced methane number
Project specific data on request:
- different alternator voltage
- different flow-/return-temperatures, hot cooling, methane number, installation conditions etc.
- Container
Drawings and dimensions
Note: This drawing is provided for reference only and should not be used for installation planning.
Genset Type Dimensions Genset (LxWxH) Heat recovery module (LhxWxH)
MTU 8V4000 GS 4200 x 2000 x 2400 mm 1500 x 1900 x 2000 mm
MTU 12V4000 GS 5000 x 2000 x 2400 mm 1500 x 1900 x 2000 mm
MTU 16V4000 GS 5500 x 2000 x 2600 mm 1500 x 1900 x 2000 mm
MTU 20V4000 GS 6000 x 2000 x 2600 mm 1500 x 1900 x 2000 mm
Engine Data
4000
Configuration 90 V
Subject to change. | 3234731 | Edition 01/15 | ENC 2015-04 | Printed in Germany on chlorine-free bleached papaer.
No. of cylinders 8/12/16/20
Bore/Stroke 170/210 mm
Cyl. displacement 4.77 lit.
design and equipment (extract)
// Sliding gear starter 24V
// Gas supply with electronically controlled gas metering valve
// Electronic high-voltage capacitor ignition system with one ignition coil
per cylinder
// Electronic speed governor for speed and power output control with
automatic knocking control
Any specifications, descriptions, values, data or other information related to dimensions, power or other technical performance criteria of the goods as provided in
this general productinformation are to be understood as non-binding and may be subject to further changes such as but not limited to technical evolution at any time.
Version: 01.08.2014, materials and specifications subject to change without notice due to technical advances.
MTU Onsite Energy
A Rolls-Royce Power Systems Brand
www.mtuonsiteenergy.com