LV Capacitor Sizing:: Thus APFC Capacitor Bank Size Selected As 925 KVAR

The document details the sizing of a low voltage capacitor bank. It determines that a 925 KVAR capacitor bank with 12 steps is needed based on an operating load of 1233 KW, 0.8 power factor, and 924.75 KVAR of capacity required. Non-linear loads account for over 30% of the total load, so detuned filters at 7% of the capacitor rating are also required.

Uploaded by

Sonu Desai
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
187 views

LV Capacitor Sizing:: Thus APFC Capacitor Bank Size Selected As 925 KVAR

The document details the sizing of a low voltage capacitor bank. It determines that a 925 KVAR capacitor bank with 12 steps is needed based on an operating load of 1233 KW, 0.8 power factor, and 924.75 KVAR of capacity required. Non-linear loads account for over 30% of the total load, so detuned filters at 7% of the capacitor rating are also required.

Uploaded by

Sonu Desai
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 10

LV CAPACITOR

30.06.15
SIZING

LV Capacitor Sizing:

Operating load in KW (refer load list) 1233 KW

Operating load in KVA (refer load list) 1419 KVA

Power factor 0.80

To improve power factor to near unity 1

Initial power factor cos 1 0.8

Final power factor cos 2 1

Tan 1 0.75

tan 2 0

KVAR Required: KW (Tan 1-tan 2 ) 924.75 KVAR

Thus APFC capacitor bank size selected as 925 KVAR


No. of steps-12 nos.
step-1 100
step-2 100
step-3 100
step-4 100
step-5 100
step-6 100
step-7 100
step-8 50
step-9 50
step-10 50

step-11 50
step-12 25

Heavy duty capacitor bank 925KVAR is selected.


Non linear loads
UPS 10 KVA
DC Load 1.1583 KVA
Transformer leakage reactance @4% 80 KVA
Computers 3
Lighting load(CFL) 3
VFD Load with a load factor of 0.8, since all VFD shall be loaded upto a max. of 839
Total non linear loads 936.1583 KVA
Transformer rated KVA 2000
46.80792 %
Thus total non linear loads are >30%.
Thus filters are required.
Detuned Filters at 7% of capacitor rating is considered.

Conclusion: 925KVAR Capacitor Bank with 12 steps.


Detuned Filters at 7%.

1
LV CAPACITOR
30.06.15
SIZING

2
LV CAPACITOR
30.06.15
SIZING

3
LV CAPACITOR
30.06.15
SIZING

4
LV CAPACITOR
30.06.15
SIZING

5
LV CAPACITOR
30.06.15
SIZING

6
LV CAPACITOR
30.06.15
SIZING

7
LV CAPACITOR
30.06.15
SIZING

8
LV CAPACITOR
30.06.15
SIZING

9
LV CAPACITOR
30.06.15
SIZING

10

You might also like