Transformer Sizing & Tentative Load List: Power Consumption Sl. No. Description Installed Power

The document provides a tentative load list for sizing a transformer. It lists 15 equipment items with their installed power in kW, running hours, demand factor, and calculated running kW. The total installed power is 1063 kW, total running power is 425.76 kW, and maximum demand is 1017.059 kVA. Based on the loads, transformer size is calculated as 2000 kVA to meet the future margin of 25% and loading of 80%. The nearest standard transformer size is 2000 kVA.

Uploaded by

mathan_ae
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
268 views

Transformer Sizing & Tentative Load List: Power Consumption Sl. No. Description Installed Power

The document provides a tentative load list for sizing a transformer. It lists 15 equipment items with their installed power in kW, running hours, demand factor, and calculated running kW. The total installed power is 1063 kW, total running power is 425.76 kW, and maximum demand is 1017.059 kVA. Based on the loads, transformer size is calculated as 2000 kVA to meet the future margin of 25% and loading of 80%. The nearest standard transformer size is 2000 kVA.

Uploaded by

mathan_ae
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Date:

TRANSFORMER SIZING & TENTATIVE LOAD LIST


Sl. Installed Power Power Consumption
Description
No. Qty KW/ Unit Rpm Total KW Working Demand kW D.Factor U. Factor Running kW

1a Mobile conveyor -Belt Feeder MBC1 1 132.00 1440 132.00 1 132 0.60 0.85 67.32
1b Mobile conveyor -Belt Feeder MBC2 1 132.00 1440 132.00 1 132 0.60 0.85 67.32
2a BC01A 1 37.00 1440 37.00 1 37 0.80 0.85 25.16
2b BC01B 1 30.00 1440 30.00 1 30 0.80 0.85 20.40
3a BC02A 1 55.00 1440 55.00 1 55 0.80 0.85 37.40
3b BC02B 1 45.00 1440 45.00 1 45 0.80 0.85 30.60
4a BC03A 1 75.00 1440 75.00 1 75 0.80 0.85 51.00
4b Actuator for Plough 6 1.50 730 9.00 1 1.5 0.80 0.85 1.02
5 BC3 A1-A6 6 18.50 1440 111.00 1 37 0.80 0.85 12.58
6 Motorized Gate-(chute) 2 1.50 1440 3.00 1 3 0.80 0.85 1.02
7 BC3B 1 22.00 1440 22.00 1 22 0.80 0.85 14.96
8a BC4B 1 37.00 1440 37.00 1 37 0.80 0.85 25.16
8b Actuator for Plough 2 1.50 730 3.00 1 1.5 0.40 0.85 0.51
9 Hoist 3 5.50 1440 16.50 0 0 0.30 0.85 0.00
10 Dust Suppression System 2 75.00 1440 150.00 1 150 0.50 0.70 26.25
11 Unit Dust collector 3 45.00 1440 135.00 1 45 0.50 0.70 15.75
12 Motorized plough 2 1.50 1440 3.00 1 1.50 0.40 0.85 0.51
13 Fire Fighting system 1 7.50 1440 7.50 0 0 0.80 0.85 0.00
14 Lighting and Utility Power 1 35.00 1440 35.00 1 35 0.80 0.60 16.80
15 Control Supply & UPS Power 1 25.00 1440 25.00 1 25 0.80 0.60 12.00
Total Installed 1063.00 864.5
Total Running 425.76 12.10 15.00
Maximum Demand (kVA) 1017.059
Installed (kW) 1063.00
Running (kW) 425.76
Future Margin (25%) 1328.75
Transformer Loading (80%) 1660.94
Transformer Efficiency (95%) 1748.36
Transformer Size in KVA 2056.89
Nearby Transformer Size (kVA) 2000.00

1 of 2
Date:
TRANSFORMER SIZING & TENTATIVE LOAD LIST
Sl. Installed Power Power Consumption
Description
No. Qty KW/ Unit Rpm Total KW Working Demand kW D.Factor U. Factor Running kW

Note: The above are indiactive only. Actual kw rating c/w e&I related changes will be submitted upon finalize design.

2 of 2