FC302 PI Example
FC302 PI Example
All the above settings are in addition to the basic set-up of the unit that can normally be carried
out using the Quick Menu.
During set-up of the PID Controller it can be useful to indicate several data values in the display
at the same time, e.g. Set point, Feedback, Frequency, Current, by using both the large
and small display readouts.
These are displayed by using the STATUS key and are configured using Parameters 0.20 0.24
The parameter displayed in the centre of the keypad can also be selected to suit the application
e.g. Bar flow rates etc. in parameter 0-23
NB. The minimum requirement to operate the FC302 in remote control is to have both terminals
18 and 27 ON to enable the unit. This is usually carried out by connecting 24 Volts DC from
terminal 12.
Terminal 37 (safe stop) must always be connected to T12 (24volts)