Monitoring and Supervision Devices

The central power supply system includes facilities for monitoring the system function and measuring battery voltage, current, load current, and charger output. The monitoring equipment provides devices to simulate a normal supply failure, isolate the AC supply for checks, indicate the current power source, and indicate faults such as voltages or currents outside permissible ranges, interruptions in circuits, failure of charging equipment, incorrect supply sources, and warnings before and indications of deep discharge protection initiation.

Uploaded by

Alex Mociran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
32 views

Monitoring and Supervision Devices

The central power supply system includes facilities for monitoring the system function and measuring battery voltage, current, load current, and charger output. The monitoring equipment provides devices to simulate a normal supply failure, isolate the AC supply for checks, indicate the current power source, and indicate faults such as voltages or currents outside permissible ranges, interruptions in circuits, failure of charging equipment, incorrect supply sources, and warnings before and indications of deep discharge protection initiation.

Uploaded by

Alex Mociran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 1

Monitoring and supervision devices

6.7.1 The central power supply system shall include facilities for monitoring the system function. The
following shall be measured:
- battery voltage;
- battery/charger/discharge current;
- load current (in parallel standby-mode operation)
- output current of the charger (in parallel standby-mode operation).
6.7.2 The following test and monitoring equipment shall be provided:
a) devices with automatic reset, e.g push button, to simulate a normal supply failure;
b) isolating devices to isolate the AC supply for checking the duration of the system;
c) indication of the actual power supply source (normal supply or battery);
d) indication of the following faults & system condition;
- float charge voltage (trickle charge current for Nickel/cadmium battery) out of the permissible range:
- interruption of the battery charging circuit
- failure in charge equipment; no charge current, although normal supply is available;
- supply from the battery, although normal supply is available;
- warning to be given at least ten minutes before deep discharge protection is initiated (CPs systems
only);
- deep discharge protection initiated
When fitted, the following devices shall also provide indication of their o