How To Find The Suitable Size of Cable & Wire - Examples
How To Find The Suitable Size of Cable & Wire - Examples
How to Find The Suitable Size of Cable & Wire for Electrical Wiring
Installation (Solved Examples in British and SI System)
Electrical Technology 10/18/2013
Basic/Important Electrical Formulas, Electrical Wiring (Basic for Home), How To, Questions/Answers (Electrical)
503,609 Views
How to determine the suitable size of cable for Electrical Wiring Installation
We know that all conductors and cables (except Super conductor) have some amount of resistance.
This resistance is directly proportional to the length and inversely proportional to the diameter of conductor
R L/a [Laws of resistance R = (L/a)]
http://www.electricaltechnology.org/2013/10/how-to-determine-the-suitable-size-of-cable-for-electrical-wiring-installation-with-solved-examples-in-both-british-and-si-system.html 1/17
7/8/2017 How to Find The Suitable Size of Cable & Wire | Examples
Whenever current flows through a conductor, a voltage drop occurs in that conductor. Generally, voltage
drop may neglect for low length conductors but in a lower diameter and long length conductors, we cannot
neglect that voltage drops.
According to IEEE rule B-23, at any point between power supply terminal and installation, Voltage drop
should not increase above 2.5% of provided (supply) voltage.
Also must read: How to calculate the Cable size for LT & HT Motors?
Example: if the Supply voltage is 220V, then the value of allowable voltage drop should be;
http://www.electricaltechnology.org/2013/10/how-to-determine-the-suitable-size-of-cable-for-electrical-wiring-installation-with-solved-examples-in-both-british-and-si-system.html 2/17
7/8/2017 How to Find The Suitable Size of Cable & Wire | Examples
In electrical wiring circuits, voltage drops also occur from the distribution board to the different sub circuit
and final sub circuits, but for sub circuits and final sub circuits, the value of voltage drop should be half of
that allowable voltage drops (i.e. 2.75V of 5.5V in the above case)
Normally, Voltage drop in tables is described in Ampere per meter (A/m) e.g. what would be the voltage drop
in a one meter cable which carrying one Ampere current?
There are two methods to define the voltage drop in a cable which we will follow.
In SI (System international and metric system) voltage drop is described by ampere per meter.
Update: Now you can also use the following Calculators to find Voltage drop & the wire size in American
wire gauge.
http://www.electricaltechnology.org/2013/10/how-to-determine-the-suitable-size-of-cable-for-electrical-wiring-installation-with-solved-examples-in-both-british-and-si-system.html 3/17
7/8/2017 How to Find The Suitable Size of Cable & Wire | Examples
Below are the important Tables which you should follow for determining the proper size of cable for
Electrical Wiring Installation.
http://www.electricaltechnology.org/2013/10/how-to-determine-the-suitable-size-of-cable-for-electrical-wiring-installation-with-solved-examples-in-both-british-and-si-system.html 5/17
7/8/2017 How to Find The Suitable Size of Cable & Wire | Examples
Now, according to load current, select a proper cable (which current rating should be nearest to the
calculated load current) from table 1
From Table 1, find the voltage drop in meter or 100feet (what system you prefer) according its rated
current
(Stay cool we will follow both methods and system for finding voltage drops (in meter and 100feet) in our
solved example for whole electrical installation wiring).
http://www.electricaltechnology.org/2013/10/how-to-determine-the-suitable-size-of-cable-for-electrical-wiring-installation-with-solved-examples-in-both-british-and-si-system.html 6/17
7/8/2017 How to Find The Suitable Size of Cable & Wire | Examples
Now, calculate the voltage drop for the actual length of wiring circuit according to its rated current with the
(Actual length of circuit x volt drop for 1m) /100 -> to find Volt drop in per meter.
(Actual length of circuit x volt drop for 100ft) /100> to find volt drop in 100feet.
Now multiply this calculated value of volt drop by load factor where;
Load factor = Load Current to be taken by Cable/ Rated Current of Cable given in the table.
This is the value of Volt drop in the cables when load current flow through it.
If the calculated value of voltage drop is less than the value calculated in step (1) (Maximum allowable
voltage drop), than the size of selected cable is proper
If the calculated value of voltage drop is greater than the value calculated in step (1) (Maximum allowable
voltage drop), than calculate voltage drop for the next (greater in size) cable and so on until the calculated
value of voltage drop became less than the maximum allowable voltage drop calculated in step (1)
How to determine the proper Cable Size for Given Load (with Examples)
For a given load, cable size may be found with the help of different tables but we should keep in mind and
follow the rules about voltage drop.
Determining the size of cable for a given load, take into account the following rules.
http://www.electricaltechnology.org/2013/10/how-to-determine-the-suitable-size-of-cable-for-electrical-wiring-installation-with-solved-examples-in-both-british-and-si-system.html 7/17
7/8/2017 How to Find The Suitable Size of Cable & Wire | Examples
For a given load except the known value of current, there should be 20% extra scope of current for
additional, future or emergency needs.
From Energy meter to Distribution board, Voltage drop should be 1.25% and for final sub circuit, voltage
Consider the change in temperature, when needed, use temperature factor (Table 3)
Also, consider the load factor when finding the size of cable
When determining the cable size, consider the wiring system i.e. in open wiring system, temperature would
be low but in conduit wiring, temperature increases due to the absence of air.
Note: Keep in mind Diversity Factor in Electrical Wring Installation while selecting the proper size of cable
Following are the examples of determining the proper Size of cables for electrical wiring installation which
will make it easy to understand the method of how to determine the proper size of cable for a given load.
For Electrical wiring installation in a building, Total load is 4.5kW and total length of cable from energy meter
to sub circuit distribution board is 35 feet. Supply voltages are 220V and temperature is 40C (104F). Find
http://www.electricaltechnology.org/2013/10/how-to-determine-the-suitable-size-of-cable-for-electrical-wiring-installation-with-solved-examples-in-both-british-and-si-system.html 8/17
7/8/2017 How to Find The Suitable Size of Cable & Wire | Examples
the most suitable size of cable from energy meter to sub circuit if wiring is installed in conduits.
Solution:-
Now select the size of cable for load current of 24.5A (from Table 1) which is 7/0.036 (28 Amperes) it means
we can use 7/0.036 cable according table 1.
Now check the selected (7/0.036) cable with temperature factor in Table 3, so the temperature factor is 0.94
(in table 3) at 40C (104F) and current carrying capacity of (7/0.036) is 28A, therefore, current carrying
Since the calculated value (26.32 Amp) at 40C (104F) is less than that of current carrying capacity of
(7/0.036) cable which is 28A, therefore this size of cable (7/0.036) is also suitable with respect to
temperature.
Now find the voltage drop for 100feet for this (7/0.036) cable from Table 4 which is 7V, But in our case, the
length of cable is 35 feet. Therefore, the voltage drop for 35feet cable would be;
http://www.electricaltechnology.org/2013/10/how-to-determine-the-suitable-size-of-cable-for-electrical-wiring-installation-with-solved-examples-in-both-british-and-si-system.html 9/17
7/8/2017 How to Find The Suitable Size of Cable & Wire | Examples
Here The Actual Voltage Drop (2.1V) is less than that of maximum allowable voltage drop of 5.5V.
Therefore, the appropriate and most suitable cable size is (7/0.036) for that given load for Electrical Wiring
Installation.
Load = 5.8kW
Volts = 230V
Solution:-
Voltage = 230V
http://www.electricaltechnology.org/2013/10/how-to-determine-the-suitable-size-of-cable-for-electrical-wiring-installation-with-solved-examples-in-both-british-and-si-system.html 10/17
7/8/2017 How to Find The Suitable Size of Cable & Wire | Examples
Now select the size of cable for load current of 30.2A (from Table 1) which is 7/1.04 (31 Amperes) it means
we can use 7/0.036 cable according table 1.
Now check the selected (7/1.04) cable with temperature factor in Table 3, so the temperature factor is 0.97
(in table 3) at 35C (95F) and current carrying capacity of (7/1.04) is 31A, therefore, current carrying
capacity of this cable at 40C (104F) would be;
Since the calculated value (30 Amp) at 35C (95F) is less than that of current carrying capacity of (7/1.04)
cable which is 31A, therefore this size of cable (7/1.04) is also suitable with respect to temperature.
Now find the voltage drop for per ampere meter for this (7/1.04) cable from (Table 5) which is 7mV, But in
our case, the length of cable is 35 meter. Therefore, the voltage drop for 35 meter cable would be:
= mV x I x L
http://www.electricaltechnology.org/2013/10/how-to-determine-the-suitable-size-of-cable-for-electrical-wiring-installation-with-solved-examples-in-both-british-and-si-system.html 11/17
7/8/2017 How to Find The Suitable Size of Cable & Wire | Examples
Here the actual Voltage drop (7.35V) is greater than that of maximum allowable voltage drop of 5.75V.
Therefore, this is not suitable size of cable for that given load. So we will select the next size of selected
cable (7/1.04) which is 7/1.35 and find the voltage drop again. According to Table (5) the current rating of
7/1.35 is 40Amperes and the voltage drop in per ampere meter is 4.1 mV (See table (5)). Therefore, the
= mV x I x L
This drop is less than that of maximum allowable voltage drop. So this is the most appropriate and
Example 3
Sub-Circuit 1
http://www.electricaltechnology.org/2013/10/how-to-determine-the-suitable-size-of-cable-for-electrical-wiring-installation-with-solved-examples-in-both-british-and-si-system.html 12/17
7/8/2017 How to Find The Suitable Size of Cable & Wire | Examples
Sub-Circuit 2
If supply voltages are 230V then calculate circuit current and Cable size for each Sub-Circuit?
Solution:-
http://www.electricaltechnology.org/2013/10/how-to-determine-the-suitable-size-of-cable-for-electrical-wiring-installation-with-solved-examples-in-both-british-and-si-system.html 13/17
7/8/2017 How to Find The Suitable Size of Cable & Wire | Examples
Therefore, Cable suggested for sub circuit 1 = 3/.029 (13Amp) or 1/1.38mm (13Amp)
Example 4
A 10H.P (7.46kW) three phase squirrel cage induction motor of continuous rating using Star-Delta starting is
connected through 400V supply by three single core PVC cables run in conduit from 250feet (76.2m) away
from multi-way distribution fuse board. Its full load current is 19A. Average summer temperature in Electrical
installation wiring is 35C (95F). Calculate the size of the cable for motor?
Solution:-
http://www.electricaltechnology.org/2013/10/how-to-determine-the-suitable-size-of-cable-for-electrical-wiring-installation-with-solved-examples-in-both-british-and-si-system.html 14/17
7/8/2017 How to Find The Suitable Size of Cable & Wire | Examples
Now select the size of cable for full load motor current of 19A (from Table 4) which is 7/0.36 (23 Amperes) *
(Remember that this is a 3-phase system i.e. 3-core cable) and the voltage drop is 5.3V for 100Feet. It
means we can use 7/0.036 cable according Table (4).
Now check the selected (7/0.036) cable with temperature factor in table (3), so the temperature factor is
0.97 (in table 3) at 35C (95F) and current carrying capacity of (7/0.036) is 23 Amperes, therefore, current
carrying capacity of this cable at 40C (104F) would be:
Since the calculated value (22.31 Amp) at 35C (95F) is less than that of current carrying capacity of
(7/0.036) cable which is 23A, therefore this size of cable (7/0.036) is also suitable with respect to
temperature.
Now find the voltage drop for 100feet for this (7/0.036) cable from table (4) which is 5.3V, But in our case,
the length of cable is 250 feet. Therefore, the voltage drop for 250 feet cable would be;
http://www.electricaltechnology.org/2013/10/how-to-determine-the-suitable-size-of-cable-for-electrical-wiring-installation-with-solved-examples-in-both-british-and-si-system.html 15/17
7/8/2017 How to Find The Suitable Size of Cable & Wire | Examples
Here the actual Voltage drop (10.94V) is greater than that of maximum allowable voltage drop of 10V.
Therefore, this is not suitable size of cable for that given load. So we will select the next size of selected
cable (7/0.036) which is 7/0.044 and find the voltage drop again. According to Table (4) the current rating of
7/0.044 is 28Amperes and the volt drop in per 100feet is 4.1V (see Table 4). Therefore, the actual voltage
The actual voltage drop is less than that of maximum allowable voltage drop. So this is the most appropriate
and suitable cable size for Electrical wiring Installation of given situation.
How to Calculate the Suitable Capacitor Size in Farads & kVAR for Power factor Improvement
(Easiest way ever)
How to Convert Capacitor Farads into kVAR & Vice Versa (For Power factor improvement)
How To check a Capacitor with Digital & Analog Multimeter. 4 Methos
How to Check the Value of Burnt Resistor. 3 Handy methods
How To: Electrical & Electronics Tutorials
http://www.electricaltechnology.org/2013/10/how-to-determine-the-suitable-size-of-cable-for-electrical-wiring-installation-with-solved-examples-in-both-british-and-si-system.html 16/17
7/8/2017 How to Find The Suitable Size of Cable & Wire | Examples
Cheapest PCB Prototype: Only $2 for 10pcs, 24 hours Quick Turn, DHL Delivery in 3 days
6288 63 21 6
24
Share
42 56 100K
Advertise Here
Like Share 588 people like this. Be the first of your friends.
http://www.electricaltechnology.org/2013/10/how-to-determine-the-suitable-size-of-cable-for-electrical-wiring-installation-with-solved-examples-in-both-british-and-si-system.html 17/17