This document provides a wind analysis for an open structure (solar panels) based on ASCE 7-2010 standards. It includes input data on the exposure category, importance factor, basic wind speed, topographic factor, and dimensions of the roof. The analysis calculates the maximum horizontal and vertical forces on the main wind-force resisting system, as well as the maximum inward and outward pressures on component and cladding elements. It summarizes the design requirements for the structural system and components to withstand the wind loads calculated according to the specified code.

Uploaded by

jamal
Copyright
© © All Rights Reserved
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
301 views

Open Structure Wind

This document provides a wind analysis for an open structure (solar panels) based on ASCE 7-2010 standards. It includes input data on the exposure category, importance factor, basic wind speed, topographic factor, and dimensions of the roof. The analysis calculates the maximum horizontal and vertical forces on the main wind-force resisting system, as well as the maximum inward and outward pressures on component and cladding elements. It summarizes the design requirements for the structural system and components to withstand the wind loads calculated according to the specified code.

Uploaded by

jamal
Copyright
© © All Rights Reserved
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 6

PROJECT : PAGE :

CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Wind Analysis for Open Structure (Solar Panels) Based on ASCE 7-2010

INPUT DATA
Exposure category (B, C or D) = C
Importance factor, 1.0 only, (Table 1.5-2) Iw = 1.00
Basic wind speed (ASCE 7-10 26.5.1) V = 136 mph
Topographic factor (26.8 & Table 26.8-1) Kzt = 1 Flat
Height of mean roof h = 10.5 ft
Roof slope 0 : 12
Roof length L = 16 ft
Roof horizontal projected width B = 11.33 ft
Effective area of component / cladding A = 10 ft2

DESIGN SUMMARY
1. Main Wind-Force Resisting System
Max horizontal force / base shear from roof = 0.00 kips
+ 0.00 kips (eave & columns increasing)
S 0.00 kips

Max vertical download force = 3.95 kips


Max vertical uplift force = 4.48 kips

Max moment at centroid of base from roof = 7.47 ft-kips


+ 0.75 ft-kips (eave & columns increasing)
S 8.21 ft-kips

2. Component and Cladding Elements


Max inward pressure = 69 psf
Max net outward pressure = 103 psf

ANALYSIS
Velocity pressure
qh = 0.00256 Kh Kzt Kd V2 = 34.21 psf
where: qh = velocity pressure at mean roof height, h. (Eq. 28.3-1 page 298 & Eq. 30.3-1 page 316)
Kh = velocity pressure exposure coefficient evaluated at height, h, (Tab. 28.3-1, pg 299) = 0.85
Kd = wind directionality factor. (Tab. 26.6-1, for building, page 250) = 0.85
h = height of mean roof = 10.50 ft

Main Wind-Force Resisting System (Sec. 27.4.3)


p = qh G CN
F = p Af
where: G = gust effect factor. (Sec. 26.9) = 0.85
q = roof angle = 0.00 degree
< 45 deg. [Satisfactory]
Af = roof actual area. = 90.6 ft2, windward
= 90.6 ft2, leeward
CN = net force coefficients. (Fig. 27.4-4, page 267)
Check Fig. 27.4-4 limitation h/B= 0.93 within [0.25 , 1.0] [Satisfactory]

WIND TO BOTTOM, g = 0o WIND TO TOP, g = 180o


CLEAR FLOW OBSTRUCTED CLEAR FLOW OBSTRUCTED
q CASE CNW CNL CNW CNL CNW CNL CNW CNL
A 1.20 0.30 -0.50 -1.20 1.20 0.30 -0.50 -1.20
p (psf) 34.89 8.72 -14.54 -34.89 34.89 8.72 -14.54 -34.89
F (kips) 3.16 0.79 -1.32 -3.16 3.16 0.79 -1.32 -3.16
0.00
B -1.10 -0.10 -1.10 -0.60 -1.10 -0.10 -1.10 -0.60
p (psf) -31.99 -2.91 -31.99 -17.45 -31.99 -2.91 -31.99 -17.45
F (kips) -2.90 -0.26 -2.90 -1.58 -2.90 -0.26 -2.90 -1.58
(cont'd)

WIND TO BOTTOM, g = 0o WIND TO TOP, g = 180o


CLEAR FLOW OBSTRUCTED CLEAR FLOW OBSTRUCTED
CASE A CASE B CASE A CASE B CASE A CASE B CASE A CASE B
Horizontal force / base shear H (kips) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Vertical download force V (kips) 3.95 0.00 0.00 0.00 3.95 0.00 0.00 0.00
Vertical uplift force V (kips) 0.00 3.16 4.48 4.48 0.00 3.16 4.48 4.48
Bending moment at centroid of base M (ft-kips) -6.719035 7.465594 -5.22592 3.732797 -6.719 7.465594 -5.2259 3.732797

Component and Cladding Elements (Sec. 30.8.2)


p = qh G CN
where: CN = net force coefficients. (Fig. 30.8-1, page 351)
a = Max[ Min( 0.1L , 0.1B , 0.4h ) , 0.04L , 0.04B , 3ft ] , (Fig. 30.8-1, footnote 6) = 3.0 ft

For effective area, 10 sq.ft. as given


CLEAR WIND FLOW OBSTRUCTED WIND FLOW
ZONE 3 ZONE 2 ZONE 1 ZONE 3 ZONE 2 ZONE 1
CN 2.38 -3.24 1.80 -1.70 1.20 -1.10 0.99 -3.53 0.80 -1.80 0.50 -1.20
p (psf) 69.14 -94.24 52.34 -49.43 34.89 -31.99 28.86 -102.74 23.26 -52.34 14.54 -34.89
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Wind Analysis for Open Structure (Solar Panels) Based on ASCE 7-05 / IBC 2009 / CBC 2010

INPUT DATA
Exposure category (B, C or D) = C
Importance factor, pg 73, (0.87, 1.0 or 1.15) I = 1.00 Category II
Basic wind speed (3 sec. gust wind) V = 85 mph
Topographic factor (Sec.6.5.7.2, pg 26 & 45) Kzt = 1 Flat
Height of mean roof h = 10.5 ft
Roof slope 0 : 12
Roof length L = 16 ft
Roof horizontal projected width B = 11.33 ft
Effective area of component / cladding A = 10 ft2

DESIGN SUMMARY
1. Main Wind-Force Resisting System
Max horizontal force / base shear from roof = 0.00 kips
+ 0.00 kips (eave & columns increasing)
S 0.00 kips

Max vertical download force = 1.54 kips


Max vertical uplift force = 1.75 kips

Max moment at centroid of base from roof = 2.92 ft-kips


+ 0.29 ft-kips (eave & columns increasing)
S 3.21 ft-kips

2. Component and Cladding Elements


Max inward pressure = 27 psf
Max net outward pressure = 40 psf

ANALYSIS
Velocity pressure
qh = 0.00256 Kh Kzt Kd V2 I = 13.36 psf
where: qh = velocity pressure at mean roof height, h. (Eq. 6-15, page 27)
Kh = velocity pressure exposure coefficient evaluated at height, h, (Tab. 6-3, Case 1,pg 79) = 0.85
Kd = wind directionality factor. (Tab. 6-4, for building, page 80) = 0.85
h = height of mean roof = 10.50 ft

Main Wind-Force Resisting System (Sec. 6.5.13.2)


p = qh G CN
F = p Af
where: G = gust effect factor. (Sec. 6.5.8, page 26). = 0.85
q = roof angle = 0.00 degree
< 45 deg. [Satisfactory]
Af = roof actual area. = 90.6 ft2, windward
= 90.6 ft2, leeward
CN = net force coefficients. (Fig. 6-18A, page 66)
Check Fig. 6-18A limitation h/B= 0.93 within [0.25 , 1.0] [Satisfactory]

WIND TO BOTTOM, g = 0o WIND TO TOP, g = 180o


CLEAR FLOW OBSTRUCTED CLEAR FLOW OBSTRUCTED
q CASE CNW CNL CNW CNL CNW CNL CNW CNL
A 1.20 0.30 -0.50 -1.20 1.20 0.30 -0.50 -1.20
p (psf) 13.63 3.41 -5.68 -13.63 13.63 3.41 -5.68 -13.63
F (kips) 1.24 0.31 -0.51 -1.24 1.24 0.31 -0.51 -1.24
0.00
B -1.10 -0.10 -1.10 -0.60 -1.10 -0.10 -1.10 -0.60
p (psf) -12.49 -1.14 -12.49 -6.82 -12.49 -1.14 -12.49 -6.82
F (kips) -1.13 -0.10 -1.13 -0.62 -1.13 -0.10 -1.13 -0.62
(cont'd)

WIND TO BOTTOM, g = 0o WIND TO TOP, g = 180o


CLEAR FLOW OBSTRUCTED CLEAR FLOW OBSTRUCTED
CASE A CASE B CASE A CASE B CASE A CASE B CASE A CASE B
Horizontal force / base shear H (kips) 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
Vertical download force V (kips) 1.54 0.00 0.00 0.00 1.54 0.00 0.00 0.00
Vertical uplift force V (kips) 0.00 1.24 1.75 1.75 0.00 1.24 1.75 1.75
Bending moment at centroid of base M (ft-kips) -2.624623 2.916248 -2.04137 1.458124 -2.6246 2.916248 -2.0414 1.458124

Component and Cladding Elements (Sec. 6.5.13.3)


p = qh G CN
where: CN = net force coefficients. (Fig. 6-19A, page 70)
a = Max[ Min( 0.1L , 0.1B , 0.4h ) , 0.04L , 0.04B , 3ft ] , (Fig. 6-19A, footnote 6) = 3.0 ft

For effective area, 10 sq.ft. as given


CLEAR WIND FLOW OBSTRUCTED WIND FLOW
ZONE 3 ZONE 2 ZONE 1 ZONE 3 ZONE 2 ZONE 1
CN 2.38 -3.24 1.80 -1.70 1.20 -1.10 0.99 -3.53 0.80 -1.80 0.50 -1.20
p (psf) 27.01 -36.81 20.45 -19.31 13.63 -12.49 11.27 -40.13 9.09 -20.45 5.68 -13.63
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Wind Analysis for Open Structure Based on ASCE 7-02

INPUT DATA
Exposure category (B, C or D) = C
Importance factor, pg 73, (0.87, 1.0 or 1.15) I = 1.00 Category II
Basic wind speed (3 sec. gust wind) V = 90 mph
Topographic factor (Sec.6.5.7.2, pg 30 & 47) Kzt = 1 Flat
Height of centroid of roof area h = 35 ft
Roof slope 1 : 12
Roof length L = 100 ft
Roof horizontal projected width B = 60 ft

DESIGN SUMMARY
Max horizontal force / base shear = 26.02 kips
Max vertical uplift / download force = 73.15 kips
Max bending moment at centroid of base = 910.64 ft-kips

ANALYSIS
Velocity pressure
qz = 0.00256 Kz Kzt Kd V2 I = 17.80 psf
where: qz = velocity pressure at mean roof height, h. (Eq. 6-15, page 31)
Kz = velocity pressure exposure coefficient evaluated at height, z, (Tab. 6-3, Case 1,pg 75) = 1.01
Kd = wind directionality factor. (Tab. 6-4, for building, page 76) = 0.85
z = height of centroid of roof area = 35.00 ft

Design pressures for wind force acting nomal to the roof


F = q z G C f Af = ( 12.19 psf ) Af = 73.40 kips, (inward and outward)
where: F = design wind load on open structural roof. (Eq. 6-25, page 34).
G = gust effect factor. (Sec. 6.5.8.1 & 6.5.8.3, page 30). = 0.85
q = roof angle = 4.76 degree
Cf = net force coefficients. (Fig. 6-18, page 68) = 0.81
Af = roof actual area. = 6020.8 ft2
X = F location from windward edge of roof. (Fig. 6-18 notes 3, page 68) = 18.06 ft

Horizontal force / base shear H = F Sin q = 6.10 kips


Vertical uplift / download force V = F Cos q = 73.15 kips
Bending moment at centroid of base M = H (0.5B Tan q - X Sin q) - H h + V (0.5B - X Cos q ) = 670.5 ft-kips

Design pressures for wind force acting to horizontal projected area


F = q z G C f Af = ( 49.73 psf ) Af = 26.02 kips, (horizontal)
where: F = design wind load on open structural roof. (Eq. 6-25, page 34).
G = gust effect factor. (Sec. 6.5.8.1 & 6.5.8.3, page 30). = 0.85
e = ratio of solid area to gross area. (Fig. 6-22 notes 7, page 72) = 0.13
Cf = net force coefficients. (Fig. 6-22, page 72) 4.0 e2 -5.9 e +4.0 = 3.29
Af = horizontal projected area normal to the wind, included columns area. = 523.2 ft2

Horizontal force / base shear H=F = 26.02 kips


Vertical uplift / download force V = 0.00 kips
Bending moment at centroid of base M=Fh = 910.6 ft-kips
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Wind Analysis for Open Structure Based on CBC 2001 / UBC 97

INPUT DATA
Exposure type (B, C or D) = C
Importance factor, (CBC Tab.16-K) Iw = 1.00
Basic wind speed (fastest mile wind) V = 75 mph
Height of centroid of roof area h = 35 ft
Roof slope 1 : 12
Roof length L = 100 ft
Roof horizontal projected width B = 60 ft

DESIGN SUMMARY
Max horizontal force / base shear from roof = 39.14 kips
Max vertical download force = 0.00 kips
Max vertical uplift force = 78.56 kips
Max bending moment at centroid of base from roof = 1370.00 ft-kips

ANALYSIS
Design pressures for wind force acting normal to the roof
F = C e C q q s Iw A f = ( 0.00 psf ) Af = 0.00 kips, (inward)
= ( 13.09 psf ) Af = 78.83 kips, (outward)
where: F = design wind load on open structural roof. (Sec. 1620).
q = roof angle = 4.76 degree
h = max top height for Ce calculation = 37.49 ft
Ce = exposure and gust factor. (Tab. 16-G) = 1.29
Cq = pressure coefficient. (Tab. 16-H, Item 1) = 0.00 inward
= 0.70 outward
qs = wind stagnation pressure. (Tab. 16-F) = 14.50 psf
Af = roof actual area. = 6020.8 ft2

Horizontal force / base shear H = F Sin q = 6.55 kips


Vertical download force V = Finward Cos q = 0.00 kips
Vertical uplift force V = Foutward Cos q = 78.56 kips
Bending moment at centroid of base M=Hh = 229.1 ft-kips

Design pressures for wind force acting to horizontal projected area


F = C e C q q s Iw A f = ( 74.82 psf ) Af = 39.14 kips, (horizontal)
where: Cq = pressure coefficient. (Tab. 16-H, Item 5) = 4.00 horizontal
Af = horizontal projected area normal to the wind, included columns area. = 523.2 ft2

Horizontal force / base shear H=F = 39.14 kips


Vertical uplift / download force V = 0.00 kips
Bending moment at centroid of base M=Fh = 1370.0 ft-kips