Sec - Eoa Contract No: 4400003814 Sheet No: 1 of 5

This 3-page document summarizes the results of testing an energy meter. It includes: 1. Visual and mechanical inspections of the meter. 2. Tests of voltage, current injection, frequency response, watt, VAR and VA metering at 10% and 100% loads with different phase angles. 3. Measurements of MWh over 5 minutes at 10% and 100% loads and voltage with a 0 degree phase angle. The tests confirmed the meter was functioning accurately within a 0.53% error range.

Uploaded by

Humayun Ahsan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
133 views4 pages

Sec - Eoa Contract No: 4400003814 Sheet No: 1 of 5

This 3-page document summarizes the results of testing an energy meter. It includes: 1. Visual and mechanical inspections of the meter. 2. Tests of voltage, current injection, frequency response, watt, VAR and VA metering at 10% and 100% loads with different phase angles. 3. Measurements of MWh over 5 minutes at 10% and 100% loads and voltage with a 0 degree phase angle. The tests confirmed the meter was functioning accurately within a 0.53% error range.

Uploaded by

Humayun Ahsan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 4

Responsi

bilities
Legend SITE TEST REPORT DATE : 1 /14 /2017
CSD
NATIONAL CONTRACTING CO. LTD

SEC EOA CONTRACT NO :


AIN DAR WIP - 1 4400003814
ENERGY METER TEST ( RM 1 ) SHEET NO: 1 OF 5

1. GENERAL DATA AND INFORMATION :


PANEL NAME : AMI-1
METER DETAILS:
MAKE: Elster MODEL: A 1884 RA LNC s200
CT RATIO: 1200/5 A (as in drawing) VT RATIO: 115 KV/
3 /115 V/ 3 - 115V * 115V/ 3 -115 V ( as in
drawing) S.NO: 02829853 TYPE: A1800
2. VISUAL INSPECTION & MECHANICAL CHECKS:

Item Description Checked


1 Physical Inspection (For Damages & Defects) OK
2 Verify if meter connections are as per app. Drawings OK
3 Check tightness of all connections OK
4 Case earthing Checked OK
5 All energy and demand readings made zero after testing. OK
6 Date and Time updated. OK
7 Meter is tested for energy in energy mode. OK

3 PHASE VOLTAGE TEST

SCALE APPLIED MEASURED VOLTAGE (Primary ERR0R %


VOLTAGE IN KV)
SECONDARY VA VB VC VA VB VC
25% 16.6 16.6 16.6 16.6 0 0 0
50% 33.2 33.2 33.2 33.2 0 0 0
100% 66.4 66.4 66.4 66.4 0 0 0

4 MINIMUM OPERATING CURRENT

Applied Voltage
Minimum Current For Pulse Count Check Pulse Indication
3 Phase VL-N
66.4 0.15 OK

TESTING ENGINEER CSD- ENGINEER

Signature: ________________ Signature: ________________


Name Hasan Islam / Xer 89 Name : Khalid Al-Jebreen
SITE TEST REPORT DATE : 1 /14 /2017

NATIONAL CONTRACTING CO. LTD

SEC EOA CONTRACT NO :


AIN DAR WIP - 1 4400003814
ENERGY METER TEST ( RM 1 ) SHEET NO: 2 OF 5

5 CURRENT INJECTION TEST

SCALE APPLIED EXPECTED MEASURED CURRENT ERR0R %


CURRENT IN CURRENT IN IA IB IC IA IB IC
SECONDARY PRIMARY
(A) (A)
25% 1.250 300 299 299 299 0.33 0.33 0.33
50% 2.500 600 599 599 599 0.17 0.17 0.17
100% 5.000 1200 1199 1198 1199 0.17 0.08 0.17

6 FREQUENCY MEASUREMENT TEST:

INJECTED
% Error
Voltage METER READ
FREQUENCY
VL-N
66.40 59 58.99 0.02
66.40 60 59.99 0.02
66.40 61 60.99 0.02

7 WATT METERING TEST

AT 10% of Current
Phase Applied Voltage Injected Current Calculated Meter Under Test
MW % Error
Angle 3 Phase VL-N 3Phase(A) MW
0 66.4 0.5 23.904 23.91 0.00
45 66.4 0.5 16.9 16.85 0.01
180 66.4 0.5 -23.904 -23.91 0.00

AT 100% of Current
Phase Applied Voltage Injected Current Calculated Meter Under Test
% Error
Angle 3 Phase VL-N 3Phase(A) MWATT MWATT
0 66.4 5 239.04 239.21 0.41
45 66.4 5 169 169.34 0.57
180 66.4 5 -239.04 -239.26 0.53

TESTING ENGINEER CSD- ENGINEER

Signature: ________________ Signature: ________________


Name Hasan Islam / Xer 89 Name : Khalid Al-Jebreen
SITE TEST REPORT DATE : 1 /14 /2017

NATIONAL CONTRACTING CO. LTD

SEC EOA CONTRACT NO :


AIN DAR WIP - 1 4400003814
ENERGY METER TEST ( RM 1 ) SHEET NO: 3 OF 5

8 VAR METERING TEST


AT 10% of Current
Phase Applied Voltage Injected Current Calculated Meter Under Test
% Error
Angle 3 Phase VL-N 3Phase(A) MVAR MVAR
0 66.4 0.5 0 0.12 0.00
45 66.4 0.5 16.9 16.99 0.02
90 66.4 0.5 23.904 23.94 0.01

AT 100% of Current
Phase Applied Voltage Injected Current Calculated Meter Under Test
% Error
Angle 3 Phase VL-N 3Phase(A) MVAR MVAR
0 66.4 5 0 0.45 0.00
45 66.4 5 169 169 0.00
90 66.4 5 239.04 239.26 0.53

9 VA METERING TEST

AT 25% of Current
Phase Applied Voltage Injected Current Calculated Meter Under Test
% Error
Angle 3 Phase VL-N 3Phase(A) MVA MVA
0 66.4 1.25 59.76 59.79 0.02
45 66.4 1.25 59.76 59.81 0.03
180 66.4 1.25 59.76 59.80 0.02

AT 100% of Current
Phase Applied Voltage Injected Current Calculated Meter Under Test
% Error
Angle 3 Phase VL-N 3Phase(A) MVA MVA
0 66.4 5 239.04 239.21 0.41
45 66.4 5 239.04 239.24 0.48
180 66.4 5 239.04 239.24 0.48

10 MWh MEASUREMENTS FOR 5 MINS @(10% &100% LOAD,RATED VGE,ANGLE 0 DEG)


TESTING ENGINEER CSD- ENGINEER

Signature: ________________ Signature: ________________


Name Hasan Islam / Xer 89 Name : Khalid Al-Jebreen
SITE TEST REPORT DATE : 1 /14 /2017

NATIONAL CONTRACTING CO. LTD

SEC EOA CONTRACT NO :


AIN DAR WIP - 1 4400003814
ENERGY METER TEST ( RM 1 ) SHEET NO: 4 OF 5

Applied Injected Current MEASURED


Calculated
SCALE Voltage 3 MWh % Error
MWh
3 Phase VL-N Phase(A)

10% 66.40 0.500 1.992 1.98 0.25


100% 66.40 5.000 19.92 19.90 0.01

11 MVARh MEASUREMENTS FOR 5 MINS @(10% &100% LOAD,RATED VGE,ANGLE 90 DEG)

Applied Injected Current MEASURED


Calculated
SCALE Voltage 3 MVARh % Error
MVARh
3 Phase VL-N Phase(A)

10% 66.40 0.500 1.992 1.98 0.25


100% 66.40 5.000 19.92 19.90 0.01

Formulae used for calculations:


REAL POWER/ACTIVE POWER (P) : [3*V*PTR*I*CTR*cos() * T KWh

REACTIVE POWER (Q) : [3*V*PTR*I*CTR*sin() * T KVARh

APPARENT POWER (S) : ( P*2 + Q*2)

MAXIMUM DEMAND : [3*V*PTR*I*CTR

Where: V(Secondary voltage)


I (Secondary Current)
PTR ( Potential Transformer Ratio)
CTR ( Current Transformer Ratio)
T( Time in Hours)
Equipment Used

CALIBRATION DUE
EQUIPMENT NAME SERIAL NUMBER CALIBRATION DATE DATE
FREJA 7501802 09.10.2016 09.01.2017

TESTING ENGINEER CSD- ENGINEER

Signature: ________________ Signature: ________________


Name Hasan Islam / Xer 89 Name : Khalid Al-Jebreen