PCS7 Web Option V8.0 Mobile

This document provides instructions for visualizing PCS 7 process control systems on mobile devices. It discusses the required hardware and software, how to configure resolutions and scaling for different devices, and how to initialize remote access. The user first installs a remote app on the mobile device and initializes it. They can then establish a secure connection to a Web server to remotely view and interact with PCS 7 processes. Proper internet settings and a holistic security concept are also recommended.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
252 views

PCS7 Web Option V8.0 Mobile

This document provides instructions for visualizing PCS 7 process control systems on mobile devices. It discusses the required hardware and software, how to configure resolutions and scaling for different devices, and how to initialize remote access. The user first installs a remote app on the mobile device and initializes it. They can then establish a secure connection to a Web server to remotely view and interact with PCS 7 processes. Proper internet settings and a holistic security concept are also recommended.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 40

i

Application Example 10/2014

PCS 7 Process visualization


on mobile devices
SIMATIC PCS 7 V8.0

http://support.automation.siemens.com/WW/view/en/102843424
Warranty and liability

Warranty and liability


Note The Application Examples are not binding and do not claim to be complete
regarding the circuits shown, equipping and any eventuality. The Application
Examples do not represent customer-specific solutions. They are only intended
to provide support for typical applications. You are responsible for ensuring that
the described products are used correctly. These application examples do not
relieve you of the responsibility to use safe practices in application, installation,
operation and maintenance. When using these Application Examples, you
recognize that we cannot be made liable for any damage/claims beyond the
liability clause described. We reserve the right to make changes to these
Application Examples at any time without prior notice. If there are any deviations
between the recommendations provided in these application examples and other
Siemens publications e.g. Catalogs the contents of the other documents
have priority.

We do not accept any liability for the information contained in this document.
Any claims against us based on whatever legal reason resulting from the use
of the examples, information, programs, engineering and performance data etc.,
described in this Application Example shall be excluded. Such an exclusion shall
not apply in the case of mandatory liability, e.g. under the German Product Liability
Act (Produkthaftungsgesetz), in case of intent, gross negligence, or injury of life,
body or health, guarantee for the quality of a product, fraudulent concealment of
a deficiency or breach of a condition which goes to the root of the contract
Siemens AG 2014 All rights reserved

(wesentliche Vertragspflichten). The damages for a breach of a substantial


contractual obligation are, however, limited to the foreseeable damage, typical for
the type of contract, except in the event of intent or gross negligence or injury to
life, body or health. The above provisions do not imply a change of the burden of
proof to your detriment.
Any form of duplication or distribution of these Application Examples or excerpts
hereof is prohibited without the expressed consent of Siemens Industry Sector.

Security Siemens provides products and solutions with industrial security functions that
infor- support the secure operation of plants, solutions, machines, equipment and/or
mation networks. They are important components of a holistic industrial security
concept. With this in mind, Siemens products and solutions undergo continuous
development. Siemens recommends strongly that you regularly check for
product updates.
For the secure operation of Siemens products and solutions, it is necessary to
take suitable preventive action (e.g. cell protection concept) and integrate each
component into a holistic, state-of-the-art industrial security concept. Third-party
products that may be in use should also be considered. For further information
about industrial security, visit http://www.siemens.com/industrialsecurity.
To stay informed about product updates as they occur, sign up for a product-
specific newsletter. For further information, visit
http://support.automation.siemens.com.

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 2
Table of contents

Table of contents

Warranty and liability ............................................................................................... 2


1 Task................................................................................................................. 4
2 Solution........................................................................................................... 5
2.1 PCS 7 Process visualization on mobile terminal devices .................... 5
2.2 Range of functions............................................................................. 6
2.3 Required hardware and software components ................................... 7
3 Resolution and scaling .................................................................................. 8
3.1 Aspect ratio ....................................................................................... 8
3.2 Configuring the OS project editor ....................................................... 9
3.3 Configuring the graphics runtime ..................................................... 10
3.4 Scaling process pictures .................................................................. 11
3.5 Publishing changes.......................................................................... 14
4 Initializing remote access ............................................................................ 18
4.1 Initializing the mobile terminal device ............................................... 18
4.1.1 Installing the remote app.................................................................. 18
4.1.2 Initializing the remote app ................................................................ 21
4.2 Operation ........................................................................................ 27
Siemens AG 2014 All rights reserved

4.2.1 Establishing a connection to the Web Server ................................... 27


4.2.2 Cursor functions .............................................................................. 28
4.2.3 Keyboard functions .......................................................................... 31
4.2.4 Displaying the menu bar .................................................................. 33
4.2.5 Disconnect ...................................................................................... 33
4.3 Internet Explorer Settings ................................................................ 34
4.3.1 Setting up the target computer as a start page ................................. 34
4.3.2 Setting to full screen ........................................................................ 36
4.3.3 Using the plug-in function ................................................................ 37
4.3.4 Process control on the mobile terminal device.................................. 39
5 References .................................................................................................... 40
6 History .......................................................................................................... 40

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 3
1 Task

1 Task
The process visualization is an essential part of a system. The larger and more
complex a system is, the more information must be processed and visualized.
Stationary operating stations are localized over Ethernet cables and are matched
to the visualization of specific units. The central control room together with its
process operating stations is located far away from the sensors and actuators.
To increase flexibility, one would wish to be able to move freely with a mobile
operating unit inside the system next to the process level components.
Siemens AG 2014 All rights reserved

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 4
2 Solution

2 Solution
2.1 PCS 7 Process visualization on mobile terminal
devices
The use of mobile terminal devices enables one to get close to all the process-
specific information.
Thanks to the portability, weight and computing power, smartphones and tablets
offer the best conditions for a comfortable and process-oriented operation of the
system. Currently, there is no standardized app for smartphones and tablets, which
connects them directly to a plant. However, there are many apps are available that
can establish a remote connection to a terminal server, which in turn is connected
to the system.
When using mobile devices, process pictures must be scaled as required by the
particular device resolution. The Application Example will help you achieve the best
possible display results.
Siemens AG 2014 All rights reserved

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 5
2 Solution

2.2 Range of functions


Terminal server
A terminal server with installed "PCS 7 Web Server" software serves as the
interface between the mobile terminal devices and the system. If a mobile terminal
device connects to the terminal server, a session will be assigned to it. Sessions
are limited depending on the server operating system. Therefore, the number of
mobile terminal devices that can be connected concurrently to the terminal server
is limited.

Remote Desktop Protocol


The communication between the mobile terminal devices and the terminal server
is done via Remote Desktop Protocol.
Internet Explorer is opened via the terminal server. Plug-ins allow you to receive
graphical information via Internet Explorer while the terminal server takes over the
computing power. This allows you to control and monitor process pictures and to
get a complete process control.

Object properties of process pictures


Changes to the object properties of the process pictures allow you to fit the process
pictures to any screen size and to hide the bulky scrollbars.
Siemens AG 2014 All rights reserved

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 6
2 Solution

2.3 Required hardware and software components


This is implemented via the PCS 7 Web Option. The type of hardware and software
components required can be found in the following manual:
SIMATIC Process Control System PCS 7 Web Option for OS (V8.0 SP1)
http://support.automation.siemens.com/WW/view/en/68154057

This document only deals with the representation and scaling of process pictures
as well as the establishment of the remote connection between the mobile terminal
devices and the terminal server.

Mobile terminal devices


The mobile terminal devices must meet the minimum requirements of the remote
app. It's up to you to decide which model you use.
In this case, the larger the screen, the clearer and easier the process pictures are
displayed. A smartphone with a 5-inch screen is enough for pure observation
purposes and is easier to carry than a tablet with a 10-inch screen. If you place
more emphasis on controlling process objects or want a better overview of the
process pictures, it is recommended to have a larger model (from 7 inches).
Siemens AG 2014 All rights reserved

NOTE Please note that when applying this example in hazardous areas, the mobile
devices used must be certified accordingly.

Remote app
To enable remote access, there are various apps available from
different providers for Android, iOS and Windows Phone.
Some apps like TeamViewer require additional software on the desired target
computer and a commercial license, while others are based on Remote Desktop
Protocol but are available for free. The remote app "2X RDP Client" has been used
in this Application Example.
This provides the following advantages:

Free of charge
There is no separate software needed on the target computer because"2X
RDP Client" is based on Microsoft's already existing "Remote Desktop"
operating system function and its RDP (Remote Desktop Protocol).
Simple and clear operation
Available for:
- Android smartphones (from V1.5), Android tablets (from V3.0)
- From iOS 3.1.3 for Apple iPad, iPhone und iPod Touch
- Windows Phone 8

Note For more information about the remote app, see the manufacturer's website.
http://www.2x.com/en/rdp-client/devices/

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 7
3 Resolution and scaling

3 Resolution and scaling


3.1 Aspect ratio
Process pictures are scaled linearly. Devices with an aspect ratio of 4:3 will not
display correctly or will be distorted if your monitor resolution corresponds to an
aspect ratio of 16:9. This also applies the other way around. The following figure
shows this problem:
Siemens AG 2014 All rights reserved

For this reason, it is recommended to use a mobile terminal device having the
same aspect ratio as that of the monitor.

Note When purchasing the mobile terminal device/monitor pay particular attention to
the aspect ratio.
To calculate the aspect ratio, divide the horizontal pixel width by the vertical pixel
width.
Example:
1920 1080 =

1024 768 =

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 8
3 Resolution and scaling

3.2 Configuring the OS project editor


Procedure
1. Right-click on "OS project editor" in WinCC Explorer.
2. Click "Open" in the shortcut menu. The "OS project editor" dialog box opens.

1 2

3. Choose the screen resolution that applies to your monitor in the "layout" tab.
4. Click on the "Apply" button to apply the change.
Siemens AG 2014 All rights reserved

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 9
3 Resolution and scaling

3.3 Configuring the graphics runtime


Procedure
1. Click on "Computer" using the left mouse button. A list with the configured
computer name appears in the right pane.
2. Right click on the configured computer name in the list.
3. Click on "Properties" in the context menu.
This opens the "Computer properties" dialog box.

4. Switch to the "Graphics runtime" tab. Select the "Adjust Image" radio button
Siemens AG 2014 All rights reserved

in the window attributes and confirm the change with "OK".

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 10
3 Resolution and scaling

3.4 Scaling process pictures


Procedure
1. In WinCC Explorer, left click on "Graphics Designer". A list with the available
process pictures appears in the right pane.

2. Open the process picture "@screen.pdl" by double clicking or right clicking


on "Open picture(s)".

3
Siemens AG 2014 All rights reserved

3. Select the picture window "@win12" from the drop-down list.

4. Click on "Other" in the object properties of the picture window.

5. Change the values of the attributes "Scroll bar" and "Scale to window" by
double clicking on "no" in each case and on "yes" for the value of the attribute
Scale to window.

Note Note the value of the attributes, as the changes must be reversed again at a later
stage.

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 11
3 Resolution and scaling

6. Open the process picture "@1001.PDL" by double clicking or right clicking


on "Open picture(s)".
Siemens AG 2014 All rights reserved

7. Select the picture window "@Desk" from the drop-down list.

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 12
3 Resolution and scaling

8. Click on "Other" in the object properties of the picture window.

9. Change the values of the attributes "Scroll bar" and "Scale to window" by
double clicking on "no" in each case and on "yes" for the value of the attribute
Scale to window.

10. In the Graphics Designer, run "File> Save All" to save the changes in both process
Siemens AG 2014 All rights reserved

pictures and exit the Graphics Designer.

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 13
3 Resolution and scaling

3.5 Publishing changes


Procedure
1. Open the Web View Publisher in WinCC Explorer
Right click > "Web View Publisher".

1
2

2. This opens the dialog box "WinCC Web Publishing Wizard Select files and
folders":
Siemens AG 2014 All rights reserved

Click on the "Next >" button

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 14
3 Resolution and scaling

3. Select the file "@1001.pdl" and click the ">" button to add it to the list of
selected files.

2
Siemens AG 2014 All rights reserved

4. Repeat step 3 with the file "@screen.pdl" and click the "Next >" button.

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 15
3 Resolution and scaling

CAUTION If you have not yet published all process pictures in this way, click the ">>"
button to add all process pictures to the list of selected files.

5. If the list of selected files contains functions, click on the "<<" button to remove
them.

6. Click on the "Next >" button.

CAUTION If you have not yet published all functions in this way, click the ">>" button to
add all functions to the list of selected files.

7. If the list of selected files contains referenced graphics, click on the "<<" button
to remove them.
Siemens AG 2014 All rights reserved

8. Click on the "Next >" button.

CAUTION If you have not yet published all referenced graphics in this way, click the ">>"
button to add all referenced graphics to the list of selected files.

9. Click on the "Finish" button to publish all files.

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 16
3 Resolution and scaling

10. When the process is completed, another dialog box opens. Click the "OK"
button, and then exit the WinCC Web Publishing Wizard.

1
Siemens AG 2014 All rights reserved

11. Repeat all the steps in chapter 3.4 and reverse the changes made to the object
properties of the process pictures.

Note This process is necessary because the changes will affect only the published
process pictures and not the OS station.

12. Activate the OS runtime.

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 17
4 Initializing remote access

4 Initializing remote access


Requirements

The Web server is on the same IP address range as the mobile terminal
device.

The OS runtime is activated.

Note For more information about installing and configuring the Web Navigator,
Web Server and Web Client, see Chapter 7 "Related Links".

4.1 Initializing the mobile terminal device


The following figures were taken with a Nexus 5 and Android v4.4. The display and
operation under other versions of Android and other operating systems like iOS
and Windows Phone may vary slightly. The functionality is retained.

4.1.1 Installing the remote app


Siemens AG 2 014 All rights reserved

Procedure
1. Open according to the operating system:

Android iOS Windows Phone

2. Open the Search window. This is generally represented with a magnifying


glass icon.

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 18
4 Initializing remote access

3. Enter "2X RDP Client" in the search field and confirm your entry to start
searching.

4. Tap the app shown above called "2X Client RDP" to learn more about the app
and install it.

5. Tap on "Install" to download the app and install it.


Siemens AG 2 014 All rights reserved

6. The progress of the installation is displayed on your screen.

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 19
4 Initializing remote access

Note Some apps may require particular permissions to have, for example, access to
the network. Tap on "Accept" to grant these rights to the app.

To download and install apps you require a valid account. You might be
requested to enter your password before downloading.
Siemens AG 2 014 All rights reserved

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 20
4 Initializing remote access

4.1.2 Initializing the remote app

To enable access to your remote computer via "Microsoft Remote Desktop",


you will first have to adjust some settings within the remote app.

Procedure
1. Tap the "2X Client" remote app icon to start it.

2. To establish a remote connection, tap either on "Add connection" or the small


plus icon.
Siemens AG 2 014 All rights reserved

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 21
4 Initializing remote access

3. Select "Standard RDP (free)" as the connection type.

4. Click the relative button to edit the information.


Siemens AG 2 014 All rights reserved

5. Under "Alias", enter the connection name and confirm your entry.

Note This connection appears later in the list of possible connections, with the name
specified here.
The connection name doesn't have to be related to the actual name or the
Internet address of the target computer.

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 22
4 Initializing remote access

6. Under "Server", enter the name or the IP address of the target computer and
confirm your entry.

7. Under "Port", enter the port number and confirm your entry.

1
Siemens AG 2 014 All rights reserved

Note The port number of the firewall on the target computer is set to 3389 by default.
If this port number changed, add the changed port number over here.

8. Enter the name of the required Windows user under "Username" and the
corresponding password under "Password", and confirm your entry.

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 23
4 Initializing remote access

9. Then, tap on "Connection" to get to the other options.


Siemens AG 2 014 All rights reserved

10. Tap on "Display" to get to the display options.

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 24
4 Initializing remote access

11. Tap on "Layout".

12. Choose "horizontal".


Siemens AG 2 014 All rights reserved

13. Tap on "Resolution".

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 25
4 Initializing remote access

14. Select the resolution you have selected for the OS server in the previous step,
in the OS Project Editor.

Note If your mobile terminal device has a lower resolution, you can still select a high
resolution. The resolution you select here refers to the virtual screen that the
Windows operating system shows you when you connect via RDP.
Siemens AG 2 014 All rights reserved

15. Tap on "Back" to complete the setup.

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 26
4 Initializing remote access

4.2 Operation
4.2.1 Establishing a connection to the Web Server

Tap on the name of the established connection to connect to the Web Server.

Tap the three vertically aligned dots to view more options and to edit the
connection settings.
Siemens AG 2 014 All rights reserved

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 27
4 Initializing remote access

4.2.2 Cursor functions

The remote app supports touch screen operation. This allows you to left-click with
a single tap. You can display a cursor and mouse buttons from the menu bar.

2
Siemens AG 2 014 All rights reserved

Moving the cursor


You can move the cursor by pulling and holding the middle mouse button.

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 28
4 Initializing remote access

Left-click
To perform a left-click, tap with a finger on the desired area on the screen.
Alternatively, you can use the on-screen mouse button by moving the cursor over
the desired area and tapping the left mouse button.
Siemens AG 2 014 All rights reserved

Right-click
To perform a right-click, tap one finger on the desired area, then tap another finger
anywhere else on the screen.
Alternatively, you can use the on-screen mouse button by moving the cursor over
the desired area and tapping the left mouse button.

Scrolling
Tap and hold two fingers on the area you want to scroll, and move your fingers in
the desired direction.

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 29
4 Initializing remote access

Zooming
Tap and hold two fingers on the area you want to zoom, and move your fingers
away from each other to zoom into the area. Move your fingers towards each other
to zoom out of the area.
Siemens AG 2 014 All rights reserved

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 30
4 Initializing remote access

4.2.3 Keyboard functions

To show or hide the keyboard, tap on the keyboard icon in the menu bar.
Siemens AG 2 014 All rights reserved

Numeric keypad
To show numbers and other symbols, tap on the button with the three dots and
then on the "&123" button.

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 31
4 Initializing remote access

Num keyboard
To display the depicted buttons, tap on the button with the three dots and then on
the "Num" button.

1
Siemens AG 2 014 All rights reserved

Fn keyboard
To display F buttons (Function buttons) and other symbols, tap on the button with
the three dots and then on the "Fn" button.

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 32
4 Initializing remote access

4.2.4 Displaying the menu bar

To use the entire surface of your touch screen, you can hide the top menu bar.
When you hide the menu bar you get the message saying that the menu bar can
be shown again by swiping it down with three fingers.

2
Siemens AG 2 014 All rights reserved

4.2.5 Disconnect

To log off the user and disconnect, proceed as if you were using a normal Windows
computer. Click on Start and log off.
Alternatively, you can disconnect from the menu bar.

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 33
4 Initializing remote access

4.3 Internet Explorer Settings


4.3.1 Setting up the target computer as a start page

It is awkward having to enter the name or IP address of the target computer in the
URL field each time you open Internet Explorer. It is suggested to set the address
of the target computer as a start page.

Procedure

1. Open Internet Explorer.

Note To get a faster access to Internet Explorer, we recommend that you create
a shortcut on the desktop or to add a link to Internet Explorer on the task bar.
Siemens AG 2 014 All rights reserved

2. Click on "Extra > Internet options".

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 34
4 Initializing remote access

3. Enter the name or IP address of the target computer in the "Start page" text
box.

4. Click on the "Apply" button.

1
Siemens AG 2 014 All rights reserved

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 35
4 Initializing remote access

4.3.2 Setting to full screen

The URL, Search, Favorites bar, etc, take space unnecessarily on the screen.
To make use of the complete screen size, they should be hidden.

Procedure
1. Open Internet Explorer.

2. First click on "Extra > Full screen (F11)". This hides superfluous toolbars and
the address bar of Internet Explorer.

1
Siemens AG 2 014 All rights reserved

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 36
4 Initializing remote access

4.3.3 Using the plug-in function

The Web Navigator provides plug-ins for Internet Explorer. A plug-in provides
a function which adapts the process pictures to Internet Explorer.

Preparation
You can find out how to install the plug-ins in Chapter 9.5 of the manual "SIMATIC
Process Control System PCS 7 Web Option for OS (V8.0 SP1)" from the following
link:
http://support.automation.siemens.com/WW/view/en/68154057

Procedure
You are logged on to your Web Server and have connected via the Internet
Explorer.

1. Move the mouse pointer to the left edge of the screen to display the options
bar of the Web Navigator.

2. Click on "Settings" in the options bar.


Siemens AG 2 014 All rights reserved

3. Click on "WebClient properties" to open the properties of the WinCC Web


Navigator client.

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 37
4 Initializing remote access

4. Select the "Adjust size" radio button in the "Process pictures" area.

5. By clicking on the "Process pictures" link (below in the settings), you will be
redirected to the process pictures.

3
2
Siemens AG 2 014 All rights reserved

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 38
4 Initializing remote access

4.3.4 Process control on the mobile terminal device

Requirement
Connection to the Web Server is established from the Remote app
Web Client is installed.
Plug-ins are installed. (see Chapter 4.3.2).
WinCC Runtime of the Web Server is activated.

Procedure
1. Start the Internet Explorer.

2. Enter your server address or IP address in the input field "Address".

3. Enter your WinCC user name and password in the dialog box "Enter network
password". If you want to save your password, activate the "Remember
password" option button.

Note You can find more information about project management in Chapter 9.6 of
the manual "SIMATIC Process Control System PCS 7 Web Option for OS
(V8.0 SP1)" from the following link:
Siemens AG 2 014 All rights reserved

http://support.automation.siemens.com/WW/view/en/68154057

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 39
5 References

5 References
Table 5-1
Subject area Title
\1\ Siemens Industry http://support.automation.siemens.com
Online Support
\2\ Download page http://support.automation.siemens.com/WW/view/en/102843424
of this entry
\3\ WinCC / http://support.automation.siemens.com/WW/view/en/78468929
WebNavigator
\4\ Web Server / Web http://support.automation.siemens.com/WW/view/en/68154057
Client / Web Option
\5\ OS Project Editor http://support.automation.siemens.com/WW/view/en/73527672

6 History
Table 6-1
Siemens AG 2 014 All rights reserved

Version Date Change


V1.0 09/2014 First edition

PCS 7 Process visualization on mobile terminal devices


Entry ID: 102843424, V1.0, 10/2014 40