Digital Temperature Controller: E5 @C/E5@C-T

The document describes a new digital temperature controller product line. It has a large, easy-to-read display and is designed for simple setup and use. The controllers are available in different sizes and I/O configurations to handle a wide range of applications.

Uploaded by

Muresan Sandu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
66 views

Digital Temperature Controller: E5 @C/E5@C-T

The document describes a new digital temperature controller product line. It has a large, easy-to-read display and is designed for simple setup and use. The controllers are available in different sizes and I/O configurations to handle a wide range of applications.

Uploaded by

Muresan Sandu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 98

New Product

Digital Temperature Controller


E5@C/E5@C-T
Large White PV Display That's Easier to Read.
Easy to Use, from Model Selection to Setup and Operation.
New Plug-in Models That Are Convenient for Maintenance and
Replacement as replacing temperature controllers is possible without
changing wiring.
New Models That Mount to DIN Track and Are Ideal for HMI/PLC
Connections.
And Programmable Models to Support a Wider Range of Applications.

E5CC DIN 48 48 mm
page 2
E5CC-U
Digital Temperature Controller

E5C DIN 48 96 mm
E5EC page 20
Series

DIN 96 96 mm
E5AC page 20

22.5 mm wide
E5DC Mounts to DIN
Track page 36

DIN 48 48 mm
Programmable E5CC-T page 50
Temperature Controller
(Digital Controller)

E5@C-T DIN 48 96 mm
E5EC-T page 66
Series

DIN 96 96 mm
E5AC-T page 66

1
Digital Temperature Controller

E5CC/E5CC-U (48 48 mm)

Large White PV Display Thats Easier to Read.


Easy to Use, from Model Selection to
Setup and Operation.
A Complete Range of I/O Capacities,
Functions, and Performance.
Handles More Applications.
The white PV display with a height of 15.2 mm improves visibility.
High-speed sampling at 50 ms. 48 48 mm 48 48 mm
E5CC E5CC-U
Models are available with up to 3 auxiliary outputs, up to 4 event
inputs, a transfer output, and a remote SP input to cover a wide Refer to your OMRON website for the most recent information on
range of applications. applicable safety standards.

E5CC: Short body with depth of only 60 mm.


Set up the Controller without wiring the power supply by Refer to Safety Precautions on page 90.
connecting to the computer with a Communications Conversion
Cable (sold separately). Setup is easy with the CX-Thermo (sold
separately).
Easy connections to a PLC with programless communications. Use component communications to link
Temperature Controllers to each other.

Main I/O Functions

Sensor Input E5CC/E5CC-U


Universal input
Thermocouple
Dual displays: PV/SV 4-digit displays
Pt
Analog current/voltage

Control Output 1
Indication Accuracy
Relay output
Thermocouple input:
Voltage output (for driving SSR)
0.3% of PV
Linear current output
Pt input: 0.2% of PV
Analog input:
0.2% of FS Control Output 2
None
Sampling Period Voltage output (for driving SSR)
50 ms
Auxiliary Outputs
None
Event Inputs 1
None PF (shift) Key 2
2 Temperature status display 3
4 Simple programming
Independent heating and Transfer Output
cooling PID control
Remote SP Input Changed parameter display None
Display brightness setting 1
None
1

Serial Communications
None
RS-485

This datasheet is provided as a guideline for selecting products.


Be sure to refer to the following manuals for application precautions and other information required for operation before attempting
to use the product.
E5@C Digital Temperature Controllers Users Manual (Cat. No. H174)
E5@C Digital Temperature Controllers Communications Manual (Cat. No. H175)

2
E5CC/E5CC-U
Model Number Legend and Standard Models
Model Number Legend
Models with Screw Terminals
E5CC-@@ 3 @ 5 M -@@@ (Example: E5CC-RX3A5M-000)

A B C D E F

A B C D E F
Model No. of Power Meaning
Control outputs Terminal Input
auxiliary supply Options
1 and 2 type type
outputs voltage
E5CC 48 48 mm
Control output 1 Control output 2
RX Relay output None
Voltage output
QX None
(for driving SSR)
*1 *3 CX Linear current output *2 None
Voltage output Voltage output
QQ
(for driving SSR) (for driving SSR)
Voltage output
CQ Linear current output *2
(for driving SSR)
3 3 (one common)
A 100 to 240 VAC
D 24 VAC/DC
5 Screw terminals (with cover)
M Universal input
HB alarm and Event Remote Transfer
Communications
HS alarm inputs SP Input output
000 --- --- --- --- ---
*1 001 1 --- 2 --- ---
2
*1 003 (for 3-phase RS-485 --- --- ---
heaters)
*3 004 --- RS-485 2 --- ---
005 --- --- 4 --- ---
006 --- --- 2 Provided.
007 --- --- 2 Provided. ---
*1. Options with HB and HS alarms (001 and 003) cannot be selected if a linear current output is selected for the control output.
*2. The control output cannot be used as a transfer output.
*3. Option 004 can be selected only when "CX" is selected for the control outputs.

Heating and Cooling Control


Using Heating and Cooling Control
A Control Output Assignment
If there is no control output 2, an auxiliary output is used as the cooling control output.
If there is a control output 2, the two control outputs are used for heating and cooling.
(It does not matter which output is used for heating and which output is used for cooling.)
B Control
If PID control is used, you can set PID control separately for heating and cooling.
This allows you to handle control systems with different heating and cooling response characteristics.

3
E5CC/E5CC-U

Model Number Legend


Plug-in Models
E5CC-@@ @ @ U M -@@@ (Example: E5CC-RW0AUM-000)

A B C D E F

A B C D E F
Model Control No. of Power Meaning
Terminal Input
outputs auxiliary supply Options
type type
1 and 2 outputs voltage
E5CC 48 48 mm
Control output 1 Control output 2
RW Relay output (SPDT) None
QX Voltage output (for driving SSR) None
CX Linear current output* None
0 None
1 1
2 2 (one common)
A 100 to 240 VAC
D 24 VAC/DC
U Plug-in model
M Universal input
HB alarm and HS Communi- Remote SP Transfer out-
Event inputs
alarm cations Input put
000 --- --- --- --- ---
* The control output cannot be used as a transfer output.

List of Models
Options Model Model
No. of auxiliary Power supply voltage Power supply voltage
Control output HB alarm and No. of event
outputs Communications
HS alarm inputs
100 to 240 VAC 24 VAC/DC

--- E5CC-RW0AUM-000 E5CC-RW0DUM-000


Relay output 1 --- --- --- E5CC-RW1AUM-000 E5CC-RW1DUM-000
2 E5CC-RW2AUM-000 E5CC-RW2DUM-000
--- E5CC-QX0AUM-000 E5CC-QX0DUM-000
Voltage output
1 --- --- --- E5CC-QX1AUM-000 E5CC-QX1DUM-000
(for driving SSR)
2 E5CC-QX2AUM-000 E5CC-QX2DUM-000
--- E5CC-CX0AUM-000 E5CC-CX0DUM-000
Linear current
1 --- --- --- E5CC-CX1AUM-000 E5CC-CX1DUM-000
output
2 E5CC-CX2AUM-000 E5CC-CX2DUM-000

Heating and Cooling Control


Using Heating and Cooling Control
A Control Output Assignment
An auxiliary output is used as the cooling control output.
B Control
If PID control is used, you can set PID control separately for heating and cooling.
This allows you to handle control systems with different heating and cooling response characteristics.

4
E5CC/E5CC-U

Optional Products (Order Separately)


USB-Serial Conversion Cable Front Covers
Model Type Model
E58-CIFQ2 Hard Front Cover Y92A-48H
Soft Front Cover Y92A-48D
Terminal Covers (for E5CC)
Model CX-Thermo Support Software
E53-COV17 Model
E53-COV23 EST2-2C-MV4
Note: The Terminal Covers E53-COV23 are provided only with Note: CX-Thermo version 4.5 or higher is required for the E5CC.
E5CC. The E53-COV10 cannot be used. CX-Thermo version 4.61 or higher is required for the E5CC-U.
Refer to page 14 for the mounted dimensions. For the system requirements for the CX-Thermo, refer to
information on the EST2-2C-MV4 on the OMRON website
Waterproof Packing (www.ia.omron.com).
Model
Y92S-P8
Note: The Waterproof Packing is provided only with E5CC
Controllers.
The E5CC-U cannot be waterproofed even if the Waterproof
Packing is attached.

Current Transformers (CTs)


Hole diameter Model
5.8 mm E54-CT1
12.0 mm E54-CT3

Adapter
Model
Y92F-45
Note: Use this Adapter when the panel has already been prepared for
an E5B@ Controller.

Waterproof Cover
Model
Y92A-48N

Mounting Adapter
Model
Y92F-49
Note: This Mounting Adapter is provided with the Digital Temperature
Controller.

DIN Track Mounting Adapter


Model
Y92F-52

Sockets (for E5CC-U)


Type Model
Front-connecting Socket P2CF-11
Front-connecting Socket with Finger Protection P2CF-11-E
Back-connecting Socket P3GA-11
Terminal Cover for Back-connecting socket
Y92A-48G
with Finger Protection

5
E5CC/E5CC-U
Specifications
Ratings
A in model number: 100 to 240 VAC, 50/60 Hz
Power supply voltage
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Models with option selection of 000: 5.2 VA max. at 100 to 240 VAC, and 3.1 VA max. at 24 VAC or
Power consumption 1.6 W max. at 24 VDC
All other models: 6.5 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC
Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Sensor input Infrared temperature sensor (ES1B): 10 to 70C, 60 to 120C, 115 to 165C, or 140 to 260C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 max., Voltage input: 1 M min.
Input impedance
(Use a 1:1 connection when connecting the ES2-HB/THB.)
Control method ON/OFF control or 2-PID control (with auto-tuning)
E5CC: SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum ap-
plicable load: 5 V, 10 mA (reference value) *
Relay output
E5CC-U: SPDT, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applica-
Control ble load: 5 V, 10 mA (reference value)
output
Voltage output
Output voltage: 12 VDC 20% (PNP), max. load current: 21 mA, with short-circuit protection circuit
(for driving SSR)
Linear current output 4 to 20 mA DC/0 to 20 mA DC, load: 500 max., resolution: approx. 10,000*
E5CC: 3
Number of outputs
E5CC-U: 1 or 2 (depends on model)
Auxiliary
output SPST-NO relay outputs, 250 VAC, Models with 1 or 2 outputs: 3 A (resistive load), or Models with 3
Output specifications outputs: 2 A (resistive load), Electrical life: 100,000 operations, Minimum applicable load: 10 mA at
5 V (reference value)
Number of inputs 2 or 4 (depends on model)
Contact input: ON: 1 k max., OFF: 100 k min.
Event input External contact input
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
specifications
Current flow: Approx. 7 mA per contact
Number of outputs 1 (only on models with a transfer output)
Transfer
output Current output: 4 to 20 mA DC, load: 500 max., resolution: approx. 10,000
Output specifications
Linear voltage output: 1 to 5 VDC, load: 1 k min., resolution: Approx. 10,000
Setting method Digital setting using front panel keys
Current input: 4 to 20 mA DC or 0 to 20 mA DC (input impedance: 150 max.)
Remote SP input
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V (input impedance: 1 M min.)
11-segment digital display and individual indicators
Indication method
Character height: PV: 15.2 mm, SV: 7.1 mm
Up to eight set points (SP0 to SP7) can be saved and selected using event inputs, key operations, or
Multi SP
serial communications.
Bank switching None
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater
burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital
Other functions filter, self tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root,
MV change rate limit, logic operations, temperature status display, simple programming, moving
average of input value, and display brightness setting
-10 to 55C (with no condensation or icing),
Ambient operating temperature
for 3-year warranty: -10 to 50C (with no condensation or icing)
Ambient operating humidity 25% to 85%
Storage temperature -25 to 65C (with no condensation or icing)
Altitude 2,000 m max.
Recommended fuse T2A, 250 VAC, time-lag, low-breaking capacity
Installation environment Installation Category II, Pollution Degree 2 (IEC 61010-1 compliant)
* You cannot select a relay output or linear current output for control output 2.
Note: There are no optional functions for the E5CC-U. Refer to Model Number Legend and List of Models on page 4.

6
E5CC/E5CC-U

Input Ranges
Thermocouple/Platinum Resistance Thermometer (Universal inputs)
Sensor Platinum resistance Infrared temperature
Thermocouple
type thermometer sensor
Sensor
10 to 60 to 115 to 140 to
specifica- Pt100 JPt100 K J T E L U N R S B W PLII 70C 120C 165C 260C
tion
2300
2300
1800
1800
1700 1700
1700
1600
1500
Temperature range (C)

1400
1300 1300 1300
1300
1200
1100
1000
850 850 850
900
800
700
600
600
500.0 500.0 500.0
500
400.0 400 400.0 400 400.0
400
260
300
120 165
200
100.0 100.0 90
100
100
0
0.0 0.0 0 0 0 0 0 0 0 0
-100
-20.0 -100 -20.0 -100
-200
-200 -199.9 199.9 -200 -200 -199.9 -200 -200 -199.9 -200
Set value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Shaded settings are the default settings.

The applicable standards for the input types are as follows:


K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 60584-1 JPt100: JIS C 1604-1989, JIS C 1606-1989
L: Fe-CuNi, DIN 43710-1985 Pt100: JIS C 1604-1997, IEC 60751
U: Cu-CuNi, DIN 43710-1985 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)
W: W5Re/W26Re, ASTM E988-1990

Analog input
Input type Current Voltage
Input
4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V
specification
Usable in the following ranges by scaling:
Setting range -1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
Set value 25 26 27 28 29

7
E5CC/E5CC-U

Alarm Types
Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.)
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
To use alarm 1, set the output assignment to alarm 1.

Alarm output operation


Set Alarm type Description of function
value When alarm value X When alarm value X
is positive is negative
0 Alarm function OFF Output OFF No alarm
Set the upward deviation in the set point for the alarm upper
L H
ON limit (H) and the lower deviation in the set point for the alarm
1 Upper- and lower-limit *1 OFF PV
*2
SP lower limit (L). The alarm is ON when the PV is outside this
deviation range.
X X Set the upward deviation in the set point by setting the alarm
2 ON ON
Upper-limit OFF PV OFF PV value (X). The alarm is ON when the PV is higher than the
(default) SP SP
SP by the deviation or more.
X X Set the downward deviation in the set point by setting the
ON ON
3 Lower-limit OFF PV OFF PV alarm value (X). The alarm is ON when the PV is lower than
SP SP
the SP by the deviation or more.
Set the upward deviation in the set point for the alarm upper
L H
Upper- and lower-limit ON limit (H) and the lower deviation in the set point for the alarm
4 OFF PV *3
range *1 SP lower limit (L). The alarm is ON when the PV is inside this de-
viation range.
L H
Upper- and lower-limit ON A standby sequence is added to the upper- and lower-limit
5 OFF PV *4
with standby sequence *1 *5 SP alarm (1). *6
X X
Upper-limit with standby ON ON
6 OFF PV OFF PV A standby sequence is added to the upper-limit alarm (2). *6
sequence SP SP

X X
Lower-limit with standby ON ON
7 OFF PV OFF PV A standby sequence is added to the lower-limit alarm (3). *6
sequence SP SP

X X
Absolute-value upper-lim- ON ON The alarm will turn ON if the process value is larger than the
8 OFF PV OFF PV
it 0 0 alarm value (X) regardless of the set point.
X X
ON ON The alarm will turn ON if the process value is smaller than the
9 Absolute-value lower-limit OFF PV OFF PV
0 0 alarm value (X) regardless of the set point.
X X
Absolute-value upper-lim- ON ON A standby sequence is added to the absolute-value upper-
10 OFF PV OFF PV
it with standby sequence 0 0 limit alarm (8). *6
X X
Absolute-value lower-limit ON ON A standby sequence is added to the absolute-value lower-
11 OFF PV OFF PV
with standby sequence 0 0 limit alarm (9). *6
12 LBA (alarm 1 type only) - *7
13 PV change rate alarm - *8
X X
SP absolute-value ON ON This alarm type turns ON the alarm when the set point (SP)
14 OFF SP OFF SP
upper-limit alarm 0 0 is higher than the alarm value (X).
X X
SP absolute-value ON ON This alarm type turns ON the alarm when the set point (SP)
15 OFF SP OFF SP
lower-limit alarm 0 0 is lower than the alarm value (X).
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
16 Heating/Cooling
upper-limit alarm *9 Heating/Cooling variable (MV) is higher than the alarm value (X).
Control (Heating MV) Control (Heating MV)
X
ON
OFF
0
MV Always ON
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
17 Heating/Cooling Heating/Cooling
lower-limit alarm *9 variable (MV) is lower than the alarm value (X).
Control (Cooling MV) Control (Cooling MV)
X
ON
OFF
0
MV Always ON
X X
RSP absolute-value ON ON This alarm type turns ON the alarm when the remote SP
18 OFF RSP OFF RSP
upper-limit alarm *10 0 0 (RSP) is higher than the alarm value (X).
X X
RSP absolute-value ON ON This alarm type turns ON the alarm when the remote SP
19 OFF RSP OFF RSP
lower-limit alarm *10 0 0 (RSP) is lower than the alarm value (X).

8
E5CC/E5CC-U

*1 With set values 1, 4 and 5, the upper and lower limit values can be set *4 Set value: 5, Upper- and lower-limit with standby sequence
independently for each alarm type, and are expressed as L and H. For Upper- and Lower-Limit Alarm Described Above *2
*2 Set value: 1, Upper- and lower-limit alarm
Case 1 and 2
Case 1 Case 2 Case 3 (Always ON)
Always OFF when the upper-limit and lower-limit hysteresis overlaps.
H<0, L<0
L H SP SP L H H SP L Case 3: Always OFF
H<0, L>0 *5. Set value: 5, Upper- and lower-limit with standby sequence
H<0, L>0 H>0, L<0
H L SP |H| |L| Always OFF when the upper-limit and lower-limit hysteresis overlaps.
|H| < |L| |H| > |L|
*6 Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No.
H>0, L<0
H174) for information on the operation of the standby sequence.
SP H L |H| |L|
*7 Refer to the E5@C Digital Temperature Controllers User's Manual (Cat.
*3 Set value: 4, Upper- and lower-limit range No.H174) for information on the loop burnout alarm (LBA).
Case 1 Case 2 Case 3 (Always OFF) *8 Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No.
H<0, L<0 H174) for information on the PV change rate alarm.
L H SP SP L H H SP L *9 When heating/cooling control is performed, the MV absolute upper limit
H<0, L>0 H>0, L<0 H<0, L>0 alarm functions only for the heating operation and the MV absolute lower
|H| < |L| |H| > |L| H L SP |H| |L| limit alarm functions only for the cooling operation.
*10 This value is displayed only when a remote SP input is used. It functions in
H>0, L<0
both Local SP Mode and Remote SP Mode.
SP H L |H| |L|
Remote SP input is supported only for the E5CC.

9
E5CC/E5CC-U

Characteristics
E5CC
Thermocouple: (0.3% of indication value or 1C, whichever is greater) 1 digit max. *1
Platinum resistance thermometer: (0.2% of indication value or 0.8C, whichever is greater) 1 digit
Analog input: 0.2% FS 1 digit max.
Indication accuracy
CT input: 5% FS 1 digit max.
(at the ambient temperature of 23C)
E5CC-U
Thermocouple: (1% of indication value or 2C, whichever is greater) 1 digit max. *1
Platinum resistance thermometer: (0.2% of indication value or 0.8C, whichever is greater) 1 digit
Analog input: 0.2% FS 1 digit max.
Transfer output accuracy 0.3% FS max.
Remote SP Input Type 0.2% FS 1 digit max.
Influence of temperature *2 Thermocouple input (R, S, B, W, PL II): (1% of indication value or 10C, whichever is greater) 1 digit
max.
Other thermocouple input: (1% of indication value or 4C, whichever is greater) 1 digit max. *3
Platinum resistance thermometer: (1% of indication value or 2C, whichever is greater) 1 digit max.
Influence of voltage *2 Analog input: 1%FS 1 digit max.
CT input: 5% FS 1 digit max.
Remote SP input: 1% FS 1 digit max.
Input sampling period 50 ms
Temperature input: 0.1 to 999.9C or F (in units of 0.1C or F)
Hysteresis
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9C or F (in units of 0.1C or F)
Proportional band (P)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Temperature input: 0.1 to 999.9C or F (in units of 0.1C or F)
Proportional band (P) for cooling Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value 0.0 to 100.0% (in units of 0.1%)
Alarm setting range -1999 to 9999 (decimal point position depends on input type)
Influence of signal source resistance Thermocouple: 0.1C/ max. (100 max.)
Platinum resistance thermometer: 0.1C/ max. (10 max.)
Insulation resistance 20 M min. (at 500 VDC)
Dielectric strength 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Vibration
Resistance 10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions
Malfunction 100 m/s2, 3 times each in X, Y, and Z directions
Shock
Resistance 300 m/s2, 3 times each in X, Y, and Z directions
E5CC: Controller: Approx. 120 g, Adapter: Approx. 10 g
Weight
E5CC-U: Controller: Approx. 100 g, Adapter: Approx. 10 g
E5CC: Front panel: IP66, Rear case: IP20, Terminals: IP00
Degree of protection
E5CC-U: Front panel: IP50, Rear case: IP20, Terminals: IP00
Memory protection Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool E5CC: CX-Thermo version 4.5 or higher
E5CC-U: CX-Thermo version 4.61 or higher
E5CC/E5CC-U top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect to a USB
Setup Tool port
port on the computer. *5
Approved standards UL 61010-1*6, KOSHA certified (some models) *7, Korean Radio Waves Act (Act 10564)
Standards
Conformed standards EN 61010-1 (IEC 61010-1): Pollution Degree 2, overvoltage category II, Lloyd's standards *8
EMI: EN61326
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage: EN 55011 Group 1, class A
EMS: EN 61326
ESD Immunity: EN 61000-4-2
EMC
Electromagnetic Field Immunity: EN 61000-4-3
Burst Noise Immunity: EN 61000-4-4
Conducted Disturbance Immunity: EN 61000-4-6
Surge Immunity: EN 61000-4-5
Voltage Dip/Interrupting Immunity: EN 61000-4-11
*1 The indication accuracy of K thermocouples in the -200 to 1300C range, T and N thermocouples at a temperature of -100C max., and U and
L thermocouples at any temperatures is 2C 1 digit max. The indication accuracy of the B thermocouple at a temperature of 400C max. is
not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800C is 3C max. The indication accuracy of the R and
S thermocouples at a temperature of 200C max. is 3C 1 digit max. The indication accuracy of W thermocouples is (0.3% of PV or 3C,
whichever is greater) 1 digit max. The indication accuracy of PL II thermocouples is 0.3% of PV or 2C, whichever is greater, 1 digit max.
*2 Ambient temperature: -10C to 23C to 55C, Voltage range: -15% to 10% of rated voltage
*3 K thermocouple at -100C max.: 10C max.
*4 The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*5 External communications (RS-485) and USB-serial conversion cable communications can be used at the same time.
*6 The E5CC-U plug-in model is certified for UL listing only when used together with the OMRON P2CF-11 or P2CF-11-E Socket. The P3GA-11
is not certified for UL listing.
*7 Access the following website for information on certified models. http://www.ia.omron.com/support/models/index.html
*8 Refer to information on maritime standards in Shipping Standards on page 92 for compliance with Lloyd's Standards.
The E5CC-U is scheduled to obtain certification in January, 2014.

10
E5CC/E5CC-U

USB-Serial Conversion Cable When Digital Temperature Controllers are con-


nected, set points and RUN/STOP commands
Applicable OS Windows XP, Vista, or 7 can be sent from the Digital Temperature Control-
Component ler that is set as the master to the Digital Temper-
CX-Thermo version 4.5 or higher (Version 4.61 or Communications*1 ature Controllers that are set as slaves.
Applicable software
higher is required for the E5CC-U.) Slope and offsets can be set for the set point.
Applicable models E5@C-T Series, E5@C Series, and E5CB Series Number of connected Digital Temperature Con-
trollers: 32 max. (including master)
USB interface standard Conforms to USB Specification 2.0.
When Digital Temperature Controllers are con-
DTE speed 38400 bps nected, the parameters can be copied from the
Computer: USB (type A plug) Copying*2 Digital Temperature Controller that is set as the
Connector master to the Digital Temperature Controllers that
Digital Temperature Controller:
specifications are set as slaves.
Special serial connector
Power supply Bus power (Supplied from USB host controller.)* MELSEC is a registered trademark of Mitsubishi Electric Corporation.
Power supply voltage 5 VDC KEYENCE is a registered trademark of Keyence Corporation.
Current consumption 450 mA max. *1 A Temperature Controller with version 1.1 or higher is required.
4.70.2 VDC
A Temperature Controller with version 2.1 or higher is required for
Output voltage (Supplied from USB-Serial Conversion Cable to the FX Series or the KV Series.
the Digital Temperature Controller.) *2 Both the programless communications and the component
communications support the copying.
250 mA max.
Output current (Supplied from USB-Serial Conversion Cable to
the Digital Temperature Controller.) Current Transformer (Order Separately)
Ambient operating
temperature
0 to 55C (with no condensation or icing) Ratings
Ambient operating
10% to 80%
Dielectric strength 1,000 VAC for 1 min
humidity
Vibration resistance 50 Hz, 98 m/s2
Storage temperature -20 to 60C (with no condensation or icing)
E54-CT1: Approx. 11.5 g,
Storage humidity 10% to 80% Weight
E54-CT3: Approx. 50 g
Altitude 2,000 m max.
Accessories Armatures (2)
Weight Approx. 120 g (E54-CT3 only) Plugs (2)
Windows is a registered trademark of Microsoft Corporation in the
United States and or other countries.
* Use a high-power port for the USB port.
Heater Burnout Alarms and SSR Failure
Note: A driver must be installed on the computer. Refer to the Alarms
Instruction Manual included with the Cable for the installation Models with detection for singlephase
procedure. CT input (for heater heaters: One input
current detection) Models with detection for singlephase or
Communications Specifications three-phase heaters: Two inputs
Transmission line Maximum heater
connection method
RS-485: Multidrop 50 A AC
current
Communications RS-485 (two-wire, half duplex) Input current
5% FS 1 digit max.
Synchronization
Start-stop synchronization indication accuracy
method
Heater burnout
Protocol CompoWay/F, or Modbus 0.1 to 49.9 A (in units of 0.1 A)
alarm setting range
Baud rate* 9600, 19200, 38400, or 57600 bps Minimum detection ON time: 100 ms *3
*1
Transmission code ASCII SSR failure alarm 0.1 to 49.9 A (in units of 0.1 A)
Data bit length* 7 or 8 bits setting range *2 Minimum detection OFF time: 100 ms *4
Stop bit length* 1 or 2 bits
*1 For heater burnout alarms, the heater current will be measured
Vertical parity (none, even, odd) when the control output is ON, and the output will turn ON if the
Error detection Block check character (BCC) with
CompoWay/F or CRC-16 Modbus heater current is lower than the set value (i.e., heater burnout
Flow control None
detection current value).
*2 For SSR failure alarms, the heater current will be measured when
Interface RS-485 the control output is OFF, and the output will turn ON if the heater
Retry function None current is higher than the set value (i.e., SSR failure detection
Communications buffer 217 bytes current value).
*3 The value is 30 ms for a control period of 0.1 s or 0.2 s.
Communications 0 to 99 ms *4 The value is 35 ms for a control period of 0.1 s or 0.2 s.
response wait time Default: 20 ms
* The baud rate, data bit length, stop bit length, and vertical parity can
be individually set using the Communications Setting Level.
Electrical Life Expectancy Curve for
Relays (Reference Values)
Communications Functions 500
Life ( 104 operations)

You can use the memory in the PLC to read and 300
write E5@C parameters, start and stop operation,
etc. The E5@C automatically performs communi-
cations with PLCs. No communications program- 100
ming is required.
Number of connected Temperature Controllers: 50
32 max. (Up to 16 for the FX Series) 30
Applicable PLCs
Programless
OMRON PLCs
communications*1
CS Series, CJ Series, or 10
CP Series
Mitsubishi Electric PLCs 5
E5CC
MELSEC Q Series, L Series, or FX Series 3 250 VAC, 30 VDC
(compatible with the FX2 or FX3 (excluding (resistive load)
the FX1S)) cos = 1
KEYENCE PLCs 1
KEYENCE KV Series 0 1 2 3 4 5 6
Switching current (A)

11
E5CC/E5CC-U
External Connections
E5CC
Control output 1
Relay output E5CC-@@ 3 @ 5 M - @ @ @
250 VAC, 3A
(resistive load) (1) (2) (3) (4) (5) (6)
Voltage output
(for driving SSR) Auxiliary outputs 1 to 3 Terminal type
12 VDC, 21 mA Control output 2 Relay outputs
Linear current output Models with 3 auxiliary
0 to 20 mA DC Voltage output The E5CC is set for a K-type thermocouple (input type = 5) by
(for driving SSR) outputs: 250 VAC, 2 A default. An input error (s.err) will occur if the input type setting does
4 to 20 mA DC
Load: 500 max. 12 VDC, 21 mA (resistive load) not agree with the temperature sensor. Check the input type.

(1) Control outputs 1, 2


RX QX CX QQ CQ
Models with Models with 1 Models with Models with 2 Models with 2 Outputs: Linear Current (2) Auxiliary Outputs
1 Relay Voltage Output 1 Linear Voltage Outputs Output and Voltage (for Driving SSR) Auxiliary outputs 1, 2, 3
Output (for Driving SSR) Current Output (for Driving SSR)
OUT1 1 OUT1 OUT1 1 OUT1 1 OUT1 7
1 + 1 + +Q +C Auxiliary output 3
R - Q - C 2 2 8
2 2 2 - Q - Q Auxiliary output 2
3 3 3 3 + OUT2 3 + OUT2 9
Auxiliary output 1
10

1 13 7
2 14 8
3 15 9
(5) Sensor (Temperature/Analog) Input (3) Input Power Supply
4 16 10
TC Pt I V 100 to 240 VAC 24 VAC/DC
A + 4 5 17 11
4 4 4
B mA 6 18 12 11 11
- 5 5 5 - 5
B - V 12 12
+ 6 6 6
+
6
(no polarity)
(6) Options
001 003 004 005 006 007
Event Inputs 1 Communications Communications Event Inputs Event Inputs Event Inputs
and 2, and CT1 (RS-485), CT1, (RS-485), and 1 to 4 1 and 2, and 1 and 2, and
and CT2 Event Inputs 3 and 4 Transfer Output Remote SP Input
B(+) B(+)
13 13 13 13 13 13
RS-485 RS-485
EV1
14 14 14 14 14 14
A(-) A(-) EV1 EV1 EV1
EV2 15 15 15 EV2
15 EV2
15 EV2
15
16 16 16 16 16 + + 16
CT1 CT1
+V V +
17 COM 17 EV3
17 17 17 mA 17
CT2 EV3 I
18 18 EV4 18 EV4
18 18 - - 18

E5CC-U

The E5CC-U is set for a K-type thermocouple (input type =


E5CC-UM-000
5) by default. An input error (s.err) will occur if the input Control output 1
type setting does not agree with the temperature sensor.
Check the input type. Auxiliary outputs 1 and 2
Relay output
250 VAC, 3 A (resistive load)

Control output 1
Auxiliary output 1
I Auxiliary output 2:
Pt
+ A Control output (cooling side)
mA V TC
B
V
+ + Input power supply
B

Sensor (temperature/analog) input 100 to 240 VAC


24 VAC/DC (no polarity)
Control output 1
Voltage output (for driving SSR) Control output 1:
12 VDC, 21 mA QX CX RW
Linear current output Models with 1 Models with 1 Models with 1
4 to 20 mA DC Voltage Output Linear Current Relay Output
0 to 20 mA DC (for Driving SSR) Output
Load: 500 max. Output 1
Relay output (three terminals used) Output 1 Output 1 R
SPDT, 250 VAC, 3 A Q C
(resistive load) + +

Note: 1. The application of the terminals depends on the model.


2. Do not wire the terminals that are shown with a gray background.
3. When complying with EMC standards, the cable that connects the sensor must be 30 m or less.
If the cable length exceeds 30 m, compliance with EMC standards will not be possible.
4. Connect M3 crimped terminals.
Connect M3.5 crimped terminals for the E5CC-U.

12
E5CC/E5CC-U

Isolation/Insulation Block Diagrams


E5CC
Models with 3 Auxiliary Outputs

Sensor input, CT inputs, and remote SP input

Communications and event inputs

Power Voltage output (for driving SSR),


supply linear current output, and transfer output

Relay output

Auxiliary outputs 1, 2, 3

: Reinforced insulation

: Functional isolation

Note: Auxiliary outputs 1 to 3 are not insulated.

E5CC-U
Models with 2 Auxiliary Outputs

Sensor input

Voltage output (for driving SSR) and linear current output


Power
supply
Relay output

Auxiliary outputs 1 and 2

: Reinforced insulation

: Functional isolation

Nomenclature
E5CC Front panel
Temperature unit Top View of E5CC Top View of E5CC-U
E5CC-U
Operation indicators No. 1 display

PV or specified parameter

No. 2 display

SP or specified parameter value

Use the U D Keys to set the


parameter.

Top-panel Setup Tool port


Press O Key once to go to Adjustment Level.
Use S Key to change the digit (default setting).
Press O Key for at least 3 seconds to go to Initial Setting Level.
Use the M Key to change to another parameter.

13
E5CC/E5CC-U
Dimensions (Unit: mm)

Controllers
E5CC
73.1
4
60
48 48 1 48 48

44.8 44.8 48.8 58

Waterproof Packing Mounting Adapter


(Accessory) (Accessory)
Terminal Cover
(E53-COV17)
(Sold separately)
The Setup Tool port is on the top of the Temperature Controller.
It is used to connect the Temperature Controller to the computer to use the Setup Tool.
The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection.
Refer to the instructions that are provided with the USB-Serial Conversion Cable for the connection procedure.
Note: Do not leave the USB-Serial Conversion Cable connected when you use the Temperature Controller.

Panel Cutout
Mounted Separately Group Mounted
(48 number of units - 2.5)+1.0
0

Recommended panel thickness is 1 to 5 mm.


45+0.6
0 Group mounting is not possible in the vertical direction. (Maintain
the specified mounting space between Controllers.)
60 min. To mount the Controller so that it is waterproof, insert the
waterproof packing onto the Controller.
When two or more Controllers are mounted, make sure that the
45+0.6
0
surrounding temperature does not exceed the allowable operating
temperature specified in the specifications.
45+0.6
To attach the USB-Serial Conversion Cable to the control panel,
0
use a panel thickness of 1 to 2.5 mm.

E5CC-U 76.8
4 14.2
48 48 58.6 48 48

58

Mounting Adapter
(Accessory)

The Setup Tool port is on the top of the Temperature Controller.


It is used to connect the Temperature Controller to the computer to use the Setup Tool.
The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection.
Refer to the instructions that are provided with the USB-Serial Conversion Cable for the connection procedure.
Note: Do not leave the USB-Serial Conversion Cable connected when you use the Temperature Controller.

Panel Cutout
Mounted Separately Group Mounted
(48 number of units - 2.5)+1.0
0

Recommended panel thickness is 1 to 5 mm.


45+0.6
0 Group mounting is not possible in the vertical direction. (Maintain
the specified mounting space between Controllers.)
60 min.
When two or more Controllers are mounted, make sure that the
surrounding temperature does not exceed the allowable operating
temperature specified in the specifications.
45+0.6
0 To attach the USB-Serial Conversion Cable to the control panel,
use a panel thickness of 1 to 2.5 mm.

45+0.6
0

14
E5CC/E5CC-U
Accessories (Order Separately)
USB-Serial Conversion Cable
E58-CIFQ2 (2110)
250 263 1510

LED (RD)

USB connector
(type A plug)
LED (PWR) Serial connector

LED (SD)

Terminal Covers 48 Terminal Covers


E53-COV17 E53-COV23 (Three Covers provided.)
2 3.8
48.8

10

Terminal Cover
(E53-COV23)
22 44.8

9.1

Terminal Cover (for the P3GA-11 Back-connecting Socket)


Y92A-48G
Twelve, 6.4-dia.

34 Y92A-48G
UP 47.747.7 4848

P C

16.5
24.6 27.6

47.4

Note: You can attach the P3GA-11 Back-connecting Socket for finger protection.

Waterproof Packing The Waterproof Packing is provided only with the E5CC.
Y92S-P8 (for DIN 48 48) Order the Waterproof Packing separately if it becomes lost or damaged.
The Waterproof Packing can be used to achieve an IP66 degree of protection.
(Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the
operating environment. Therefore, periodic replacement is recommended to ensure the level of
waterproofing specified in IP66. The time for periodic replacement depends on the operating
environment. Be sure to confirm this point at your site.
Consider three years as a rough standard.)
The Waterproof Packing does not need to be attached if a waterproof structure is not required.
The E5CC-U cannot be waterproofed even if the Waterproof Packing is attached.

15
E5CC/E5CC-U

Current Transformers
E54-CT1 Thru-current (Io) vs. Output Voltage (Eo)
21
2.8
15 (Reference Values)
5.8 dia.
E54-CT1
7.5
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 4002
25 3
Winding resistance: 182
10.5
100V

Output voltage (Eo) V (r.m.s.)


Frequency: 50 Hz
40
10 Distortion
Two, 3.5 dia. factor
1k
10%
10 1
3%
1%
30 100mV

10 100
E54-CT3
2.36 dia.
30 RL=10
1
12 dia.
9
100V

10
40 40 1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)

Thru-current (Io) vs. Output Voltage (Eo)


Two, M3 (depth: 4) (Reference Values)
15
E54-CT3
Maximum continuous heater current: 120 A (50/60 Hz)
30 (Maximum continuous heater current for an OMRON
Digital Temperature Controller is 50 A.)
Number of windings: 4002
E54-CT3 Accessories
Winding resistance: 80.8
Armature Connection Example
100V
Output voltage (Eo) V (r.m.s.)

Frequency: 50 Hz
Armature Distortion
Approx. 3 dia. Plug
10 factor
1k
10%
Lead 500 3%
1 1%

100mV
18
100
50
Plug 10
RL=10

1
Approx. 6 dia.

100V
(22)
10
1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)

16
E5CC/E5CC-U

Adapter
Y92F-45 Note: 1. Use this Adapter when the Front Panel has already been prepared for the E5B@.
2. Only black is available.
3. You cannot use the E58-CIFQ2 USB-Serial Conversion Cable if you use the Y92F-45 Adapter. To use the USB-Serial
Conversion Cable to make the settings, do so before you mount the Temperature Controller in the panel.
Fixture (Accessory)
4.7 76
69.6 to 77.6
72 72

67 67 87

Mounted to E5CC Panel (1 to 8 mm) Mounting Adapter


72 72 Y92F-30
(Accessory)

48 48

2.2 4.7
62.8
To back of the E5CC

DIN Track Mounting Adapter


Y92F-52 Note: This Adapter cannot be used together with the Terminal Cover.
Remove the Terminal Cover to use the Adapter.

This Adapter is used to mount the


E5CC to a DIN Track.
61
If you use the Adapter, there is no
need for a plate to mount in the
panel or to drill mounting holes in
3.5 the panel.
50 38

Mounted to E5CC

48

80.5

17
E5CC/E5CC-U

Watertight Cover Mounting Adapter


Y92A-48N Y92F-49
21.9 14
The Mounting Adapter is provided with the
(2)
Temperature Controller.
Order this Adapter separately if it becomes
lost or damaged.

87.7 69
79.2

12

67.6

Protective Cover Protective Cover


Y92A-48D Note: This Protective Cover cannot be used Y92A-48H
if the Waterproof Packing is installed. This Protective Cover is hard type.
Please use it for the mis-operation
This Protective Cover is soft type.
prevention etc.
It is able to operate the controller with using
this cover.

E5CC-U Wiring Socket


Front-connecting Socket
P2CF-11
Eleven, M3.5 7.5 3 4.5 Terminal Layout/Internal Connections
sems screws 7.8 (Top View)

8 7 6 5 Mounting Holes
4
Two, 4.5 dia. mounting holes
70 max. 35.4
Two,
4.5-dia. 9 3 400.2
holes
10 11 1 2 Note: Can also be mounted
to a DIN track
4 50 max. 31.2 max.
Note: 1. A model with finger protection (P2CF-11-E) is also available.
2. You cannot use the P2CF-11 or P2CF-11-E together with the Y92F-45.

Back-connecting Socket
P3GA-11
Eleven, M3.5 Terminal Layout/Internal Connections
sems screws
27dia. 4 7 3 (Bottom View)
5 6 7 8
4
45 25.6
3 9
2 1 11 10

45
4.5 16.3 6.2
6
8.7

Note: 1. Using any other sockets will adversely affect accuracy. Use only the specified sockets.
2. A Protective Cover for finger protection (Y92A-48G) is also available.
3. You cannot use the P3GA-11 together with the Y92F-45.

18
MEMO

19
Digital Temperature Controller

E5EC/E5AC (48 96 mm/96 96 mm)

Large White PV Display Thats Easier to Read.


Easy to Use, from Model Selection to
Setup and Operation.
A Complete Range of I/O Capacities,
Functions, and Performance.
Handles More Applications.
A white LCD PV display with a height of approx. 18 mm for the
E5EC and 25 mm for the E5AC improves visibility.
Tool ports are provided both on the top panel and the front panel.
Set up the Controller without wiring the power supply by 48 96 mm 96 96 mm
connecting to the computer with a Communications Conversion E5EC E5AC
Cable (sold separately). Setup is easy with the CX-Thermo (sold
separately). Refer to your OMRON website for the most recent
information on applicable safety standards.
High-speed sampling at 50 ms.
Models are available with up to 4 auxiliary outputs, up to 6 event
inputs, a transfer output, and a remote SP input to cover a wide Refer to Safety Precautions on page 90.
range of applications.
Short body with depth of only 60 mm.
Easy connections to a PLC with programless communications.
Use component communications to link Temperature Controllers to each other.
The new position-proportional control models allow you to control valves as well.

Main I/O Functions


Sensor Input
E5EC E5AC
Universal input
Thermocouple
Pt
Analog current/voltage Three-level Display
PV, SV, and MV displayed 4-digit
at the same time. displays
Indication Accuracy
Thermocouple input: Control Output 1
0.3% of PV
Relay output
Pt input: 0.2% of PV
Voltage output (for driving SSR)
Analog input: 0.2% of FS
Linear current output

Sampling Period
Control Output 2
50 ms
Voltage output (for driving SSR)
Relay output
Event Inputs Linear current output
None
PF (shift) Key
2 Auxiliary Outputs
Setup Tool port on front panel
4
Temperature status display 4
6
Simple programming
Remote SP Input Independent heating and
cooling PID control Transfer Output
None Changed parameter display None
1 Display brightness setting 1
Serial Communications
None
RS-485

This datasheet is provided as a guideline for selecting products.


Be sure to refer to the following manuals for application precautions and other information required for operation before attempting
to use the product.
E5@C Digital Temperature Controllers Users Manual (Cat. No. H174)
E5@C Digital Temperature Controllers Communications Manual (Cat. No. H175)

20
E5EC/E5AC
Model Number Legend and Standard Models
Model Number Legend
Models with Screw Terminals
E5EC-@@ 4 @ 5 M -@@@ (Example: E5EC-RX4A5M-000)

A B C D E F
E5AC-@@ 4 @ 5 M -@@@ (Example: E5AC-RX4A5M-000)

A B C D E F

A B C D E F
Model No. of auxil- Power Meaning
Control outputs Terminal Input
iary out- supply Options
1 and 2 type type
puts voltage
E5EC 48 96 mm
E5AC 96 96 mm
Control output 1 Control output 2
RX Relay output None
Voltage output
QX None
(for driving SSR)
*2 CX Linear current output None
Voltage output Voltage output
QQ
(for driving SSR) (for driving SSR)
Voltage output
QR Relay output
(for driving SSR)
RR Relay output Relay output
Linear current out-
*2 CC Linear current output
put
Voltage output
*2 CQ Linear current output
(for driving SSR)
Position-proportion-
PR Position-proportional relay output
al relay output
4 (auxiliary outputs 1 and 2 with same common and auxilia-
*3 4
ry outputs 3 and 4 with same common)
A 100 to 240 VAC
D 24 VAC/DC
5 Screw terminals (with cover)
Control outputs 1 and 2 M Universal input
For RX,
QX, QQ, For CX or HB alarm
For PR Event Remote Transfer
QR, RR, or CC and Communications
inputs SP Input output
CQ HS alarm
Selectable Selectable Selectable 000 --- --- --- --- ---
Option Selectable Selectable 004 --- RS-485 2 --- ---
selection Selectable 005 --- --- 4 --- ---
conditions 2
*1 Selectable 009 (for 3-phase RS-485 2 --- ---
heaters)
Selectable 010 1 --- 4 --- ---
Selectable 011 1 --- 6 Provided. Provided.
Selectable 013 --- --- 6 Provided. Provided.
Selectable Selectable 014 --- RS-485 4 Provided. Provided.
*1. The options that can be selected depend on the type of control output.
*2. The control output cannot be used as a transfer output.
*3. A model with four auxiliary outputs must be selected.

Heating and Cooling Control


l Using Heating and Cooling Control
A Control Output Assignment
If there is no control output 2, an auxiliary output is used as the cooling control output.
If there is a control output 2, the two control outputs are used for heating and cooling.
(It does not matter which output is used for heating and which output is used for cooling.)
B Control
If PID control is used, you can set PID control separately for heating and cooling.
This allows you to handle control systems with different heating and cooling response characteristics.

21
E5EC/E5AC

Optional Products (Order Separately)


USB-Serial Conversion Cable Current Transformers (CTs)
Model Hole diameter Model
E58-CIFQ2 5.8 mm E54-CT1
12.0 mm E54-CT3
Communications Conversion Cable
Model CX-Thermo Support Software
E58-CIFQ2-E Model
Note: Always use this product together with the E58-CIFQ2. EST2-2C-MV4
This Cable is used to connect to the front-panel Setup Tool Note: CX-Thermo version 4.5 or higher is required for the E5EC.
port. For the system requirements for the CX-Thermo, refer to
information on the EST2-2C-MV4 on the OMRON website
Terminal Covers (www.ia.omron.com).
Model
E53-COV24
Note: The Terminal Covers E53-COV24 are provided with the Digital
Temperature Controller.
Waterproof Packing
Applicable Controller Model
E5EC Y92S-P9
E5AC Y92S-P10
Note: This Waterproof Packing is provided with the Digital
Temperature Controller.

Waterproof Cover
Applicable Controller Model
E5EC Y92A-49N
E5AC Y92A-96N

Front Port Cover


Model
Y92S-P7
Note: This Front Port Cover is provided with the Digital Temperature
Controller.

Mounting Adapter
Model
Y92F-51
Note: This Mounting Adapter is provided with the Digital Temperature
Controller.

22
E5EC/E5AC
Specifications
Ratings
A in model number: 100 to 240 VAC, 50/60 Hz
Power supply voltage
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Models with option selection of 000:6.6 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or
E5EC 2.3 W max. at 24 VDC
All other models: 8.3 VA max. at 100 to 240 VAC, and 5.5 VA max. at 24 VAC or 3.2 W max. at 24 VDC
Power consumption
Models with option selection of 000:7.0 VA max. at 100 to 240 VAC, and 4.2 VA max. at 24 VAC or
E5AC 2.4 W max. at 24 VDC
All other models: 9.0 VA max. at 100 to 240 VAC, and 5.6 VA max. at 24 VAC or 3.4 W max. at 24 VDC
Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Sensor input Infrared temperature sensor (ES1B): 10 to 70C, 60 to 120C, 115 to 165C, or 140 to 260C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 max., Voltage input: 1 M min.
Input impedance
(Use a 1:1 connection when connecting the ES2-HB/THB.)
Control method ON/OFF or 2-PID control (with autotuning)
SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations,
Relay output
minimum applicable load: 5 V, 10 mA (reference value)
Control
Voltage output Output voltage: 12 VDC 20% (PNP), max. load current: 40 mA, with short-circuit protection circuit
output
(for driving SSR) (The maximum load current is 21 mA for models with two control outputs.)
Linear current output 4 to 20 mA DC/0 to 20 mA DC, load: 500 max., resolution: approx. 10,000
Number of outputs 4
Auxiliary
output SPST-NO. relay outputs, 250 VAC, Models with 4 outputs: 2 A (resistive load),
Output specifications
Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value)
Number of inputs 2, 4 or 6 (depends on model)
Contact input: ON: 1 k max., OFF: 100 k min.
Event input External contact input
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
specifications
Current flow: Approx. 7 mA per contact
Number of outputs 1 (only on models with a transfer output)
Transfer
output Current output: 4 to 20 mA DC, Load: 500 max., Resolution: Approx. 10,000
Output specifications
Linear voltage output: 1 to 5 VDC, load: 1 k min., Resolution: Approx. 10,000
Current input: 4 to 20 mA DC or 0 to 20 mA DC (input impedance: 150 max.)
Remote SP input
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V (input impedance: 1 M min.)
Potentiometer input 100 to 10 k
Setting method Digital setting using front panel keys
11-segment digital display and individual indicators
Character height: E5EC: PV: 18.0 mm, SV: 11.0 mm, MV: 7.8 mm
Indication method E5AC: PV: 25.0 mm, SV: 15.0 mm, MV: 9.5 mm
Three displays Contents: PV/SV/MV, PV/SV/Multi-SP, or PV/SV/Remaining soak time
Numbers of digits: 4 digits each for PM, SV, and MV displays
Up to eight set points (SP0 to SP7) can be saved and selected using event inputs, key operations, or
Multi SP
serial communications.
Bank switching None
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater
burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital
Other functions filter, self tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root,
MV change rate limit, logic operations, temperature status display, simple programming, moving av-
erage of input value, and display brightness setting
-10 to 55C (with no condensation or icing),
Ambient operating temperature
for 3-year warranty: -10 to 50C (with no condensation or icing)
Ambient operating humidity 25% to 85%
Storage temperature -25 to 65C (with no condensation or icing)
Altitude 2,000 m max.
Recommended fuse T2A, 250 VAC, time-lag, low-breaking capacity
Installation environment Installation Category II, Pollution Degree 2 (IEC 61010-1 compliant)

23
E5EC/E5AC

Input Ranges
Thermocouple/Platinum Resistance Thermometer (Universal inputs)
Sensor Platinum resistance Infrared temperature
Thermocouple
type thermometer sensor
Sensor
10 to 60 to 115 to 140 to
specifica- Pt100 JPt100 K J T E L U N R S B W PLII 70C 120C 165C 260C
tion
2300
2300
1800
1800
1700 1700
1700
1600
1500
Temperature range (C)

1400
1300 1300 1300
1300
1200
1100
1000
850 850 850
900
800
700
600
600
500.0 500.0 500.0
500
400.0 400 400.0 400 400.0
400
260
300
120 165
200
100.0 100.0 90
100
100
0.0 0.0 0 0 0 0 0 0 0 0
-100
-20.0 -100 -20.0 -100
-200
-200 -199.9 -199.9 -200 -200 -199.9 -200 -200 -199.9 -200
Set value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Shaded settings are the default settings.

The applicable standards for the input types are as follows:


K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 60584-1 JPt100: JIS C 1604-1989, JIS C 1606-1989
L: Fe-CuNi, DIN 43710-1985 Pt100: JIS C 1604-1997, IEC 60751
U: Cu-CuNi, DIN 43710-1985 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)
W: W5Re/W26Re, ASTM E988-1990

Analog input
Input type Current Voltage
Input
4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V
specification
Usable in the following ranges by scaling:
Setting range -1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
Set value 25 26 27 28 29

24
E5EC/E5AC

Alarm Types
Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.)
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
To use alarm 1, set the output assignment to alarm 1.

Alarm output operation


Set
value Alarm type When alarm value X When alarm value X Description of function
is positive is negative
0 Alarm function OFF Output OFF No alarm
Set the upward deviation in the set point for the alarm upper
L H
ON limit (H) and the lower deviation in the set point for the alarm
1 Upper- and lower-limit *1 OFF PV
*2
SP lower limit (L). The alarm is ON when the PV is outside this
deviation range.
X X Set the upward deviation in the set point by setting the alarm
2 ON ON
Upper-limit OFF PV OFF PV value (X). The alarm is ON when the PV is higher than the
(default) SP SP
SP by the deviation or more.
X X Set the downward deviation in the set point by setting the
ON ON
3 Lower-limit OFF PV OFF PV alarm value (X). The alarm is ON when the PV is lower than
SP SP
the SP by the deviation or more.
Set the upward deviation in the set point for the alarm upper
L H
Upper- and lower-limit ON limit (H) and the lower deviation in the set point for the alarm
4 OFF PV *3
range *1 SP lower limit (L). The alarm is ON when the PV is inside this de-
viation range.
L H
Upper- and lower-limit ON A standby sequence is added to the upper- and lower-limit
5 OFF PV *4
with standby sequence *1 *5 SP alarm (1). *6
X X
Upper-limit with standby ON ON
6 OFF PV OFF PV A standby sequence is added to the upper-limit alarm (2). *6
sequence SP SP

X X
Lower-limit with standby ON ON
7 OFF PV OFF PV A standby sequence is added to the lower-limit alarm (3). *6
sequence SP SP

X X
Absolute-value upper-lim- ON ON The alarm will turn ON if the process value is larger than the
8 OFF PV OFF PV
it 0 0 alarm value (X) regardless of the set point.
X X
ON ON The alarm will turn ON if the process value is smaller than the
9 Absolute-value lower-limit OFF PV OFF PV
0 0 alarm value (X) regardless of the set point.
X X
Absolute-value upper-lim- ON ON A standby sequence is added to the absolute-value upper-
10 OFF PV OFF PV
it with standby sequence 0 0 limit alarm (8). *6
X X
Absolute-value lower-limit ON ON A standby sequence is added to the absolute-value lower-
11 OFF PV OFF PV
with standby sequence 0 0 limit alarm (9). *6
12 LBA (alarm 1 type only) - *7
13 PV change rate alarm - *8
X X
SP absolute-value ON ON This alarm type turns ON the alarm when the set point (SP)
14 OFF SP OFF SP
upper-limit alarm 0 0 is higher than the alarm value (X).
X X
SP absolute-value ON ON This alarm type turns ON the alarm when the set point (SP)
15 OFF SP OFF SP
lower-limit alarm 0 0 is lower than the alarm value (X).
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
16 Heating/Cooling
upper-limit alarm *9 Heating/Cooling variable (MV) is higher than the alarm value (X).
Control (Heating MV) Control (Heating MV)
X
ON
OFF
0
MV Always ON
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
17 Heating/Cooling Heating/Cooling
lower-limit alarm *9 variable (MV) is lower than the alarm value (X).
Control (Cooling MV) Control (Cooling MV)
X
ON
OFF
0
MV Always ON
X X
RSP absolute-value ON ON This alarm type turns ON the alarm when the remote SP
18 OFF RSP OFF RSP
upper-limit alarm *10 0 0 (RSP) is higher than the alarm value (X).
X X
RSP absolute-value ON ON This alarm type turns ON the alarm when the remote SP
19 OFF RSP OFF RSP
lower-limit alarm *10 0 0 (RSP) is lower than the alarm value (X).

25
E5EC/E5AC

*1 With set values 1, 4 and 5, the upper and lower limit values can be set *4. Set value: 5, Upper- and lower-limit with standby sequence
independently for each alarm type, and are expressed as L and H. For Upper- and Lower-Limit Alarm Described Above *2
*2. Set value: 1, Upper- and lower-limit alarm
Case 2
Case 1 and 2
Case 1 Case 3 (Always ON)
H<0, L<0
Always OFF when the upper-limit and lower-limit hysteresis overlaps.
L H SP SP L H H SP L Case 3: Always OFF
H<0, L>0 *5. Set value: 5, Upper- and lower-limit with standby sequence
H<0, L>0 H>0, L<0
H L SP |H| |L| Always OFF when the upper-limit and lower-limit hysteresis overlaps.
|H| < |L| |H| > |L|
H>0, L<0
*6. Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No.
SP H L |H| |L|
H174) for information on the operation of the standby sequence.
*7. Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No.
*3. Set value: 4, Upper- and lower-limit range
H174) for information on the loop burnout alarm (LBA). This setting cannot
Case 1 Case 2 Case 3 (Always OFF)
be used with a position-proportional model.
H<0, L<0 *8. Refer to the E5@C Digital Temperature Controllers User's Manual (Cat. No.
L H SP SP L H H SP L
H174) for information on the PV change rate alarm.
H<0, L>0 H>0, L<0 H<0, L>0 *9. When heating/cooling control is performed, the MV absolute upper limit
|H| < |L| |H| > |L| H L SP |H| |L| alarm functions only for the heating operation and the MV absolute lower
H>0, L<0 limit alarm functions only for the cooling operation.
|H| |L| *10. This value is displayed only when a remote SP input is used. It functions in
SP H L
both Local SP Mode and Remote SP Mode.

26
E5EC/E5AC

Characteristics
Thermocouple: (0.3% of indication value or 1C, whichever is greater) 1 digit max. *1
Indication accuracy Platinum resistance thermometer: (0.2% of indication value or 0.8C, whichever is greater) 1 digit
(at the ambient temperature of Analog input: 0.2% FS 1 digit max.
23C) CT input: 5% FS 1 digit max.
Potentiometer input: 5% FS 1 digit max.
Transfer output accuracy 0.3% FS max.
Remote SP Input Type 0.2% FS 1 digit max.
Thermocouple input (R, S, B, W, PL II): (1% of indication value or 10C, whichever is greater) 1 digit
Influence of temperature *2
max.
Other thermocouple input: (1% of indication value or 4C, whichever is greater) 1 digit max. *3
Platinum resistance thermometer: (1% of indication value or 2C, whichever is greater) 1 digit max.
Influence of voltage *2 Analog input: 1%FS 1 digit max.
CT input: 5% FS 1 digit max.
Remote SP input: 1% FS 1 digit max.
Input sampling period 50ms
Temperature input: 0.1 to 999.9C or F (in units of 0.1C orF)
Hysteresis
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9C or F (in units of 0.1C or F)
Proportional band (P)
Analog input: 0.1 to 999.9% FS (in units of 0.1% FS)
Standard, heating/cooling, or Position-proportional (Close): 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in
Integral time (I) units of 0.1 s)
Position-proportional (Floating): 1 to 9999 s (in units of 1 s), 0.1 to 999.9 s (in units of 0.1 s)*4
Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Temperature input: 0.1 to 999.9C or F (in units of 0.1C or F)
Proportional band (P) for cooling
Analog input: 0.1 to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value 0.0 to 100.0% (in units of 0.1%)
Alarm setting range -1999 to 9999 (decimal point position depends on input type)
Influence of signal source resis- Thermocouple: 0.1C/ max. (100 max.)
tance Platinum resistance thermometer: 0.1C/ max. (10 max.)
Insulation resistance 20 M min. (at 500 VDC)
Dielectric strength 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Vibration
Resistance 10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions
Malfunction 100 m/s2, 3 times each in X, Y, and Z directions
Shock
Resistance 300 m/s2, 3 times each in X, Y, and Z directions
E5EC Controller: Approx. 210 g, Adapter: Approx. 4 g 2
Weight
E5AC Controller: Approx. 250 g, Adapter: Approx. 4 g 2
Degree of protection Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool CX-Thermo version 4.5 or higher
E5EC/E5AC top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect to a USB port
on the computer.*5
Setup Tool port
E5EC/E5AC front panel: An E58-CIFQ2 USB-Serial Conversion Cable and E58-CIFQ2-E Conversion
Cable are used together to connect to a USB port on the computer.*5
Approved standards UL 61010-1, Korean Radio Waves Act (Act 10564)
Standards
Conformed standards EN 61010-1 (IEC 61010-1): Pollution Degree 2, overvoltage category II, Lloyd's standards *6
EMI EN61326
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage: EN 55011 Group 1, class A
EMS: EN 61326
ESD Immunity: EN 61000-4-2
EMC
Electromagnetic Field Immunity: EN 61000-4-3
Burst Noise Immunity: EN 61000-4-4
Conducted Disturbance Immunity: EN 61000-4-6
Surge Immunity: EN 61000-4-5
Voltage Dip/Interrupting Immunity: EN 61000-4-11
*1 The indication accuracy of K thermocouples in the -200 to 1300C range, T and N thermocouples at a temperature of -100C max., and U and L thermocouples at
any temperatures is 2C 1 digit max. The indication accuracy of the B thermocouple at a temperature of 400C max.
is not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800C is 3C max. The indication accuracy of the R and S thermocouples
at a temperature of 200C max. is 3C 1 digit max. The indication accuracy of W thermocouples is (0.3% of PV or 3C, whichever is greater) 1 digit max. The
indication accuracy of PL II thermocouples is (0.3% of PV or 2C, whichever is greater) 1 digit max.
*2 Ambient temperature: -10C to 23C to 55C, Voltage range: -15% to 10% of rated voltage
*3 K thermocouple at -100C max.: 10C max.
*4 The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*5 External communications (RS-485) and USB-serial conversion cable communications can be used at the same time.
*6 Refer to information on maritime standards in Shipping Standards on page 92 for compliance with Lloyd's Standards.

27
E5EC/E5AC

USB-Serial Conversion Cable When Digital Temperature Controllers are con-


nected, set points and RUN/STOP commands
Applicable OS Windows XP, Vista, or 7 can be sent from the Digital Temperature Control-
Component ler that is set as the master to the Digital Temper-
Applicable software CX-Thermo version 4.5 or higher Communications*1 ature Controllers that are set as slaves.
Applicable models E5@C-T Series, E5@C Series, and E5CB Series Slope and offsets can be set for the set point.
Number of connected Digital Temperature Con-
USB interface standard Conforms to USB Specification 2.0. trollers: 32 max. (including master)
DTE speed 38,400 bps When Digital Temperature Controllers are con-
Computer: USB (type A plug) nected, the parameters can be copied from the
Connector Copying*2 Digital Temperature Controller that is set as the
Digital Temperature Controller:
specifications master to the Digital Temperature Controllers that
Special serial connector
are set as slaves.
Power supply Bus power (Supplied from USB host controller.)*
Power supply voltage 5 VDC
MELSEC is a registered trademark of Mitsubishi Electric Corporation.
KEYENCE is a registered trademark of Keyence Corporation.
Current consumption 450 mA max.
*1 A Temperature Controller with version 1.1 or higher is required.
4.70.2 VDC
Output voltage (Supplied from USB-Serial Conversion Cable to A Temperature Controller with version 2.1 or higher is required for
the Digital Temperature Controller.) the FX Series or the KV Series.
250 mA max. *2 Both the programless communications and the component
Output current (Supplied from USB-Serial Conversion Cable to communications support the copying.
the Digital Temperature Controller.)
Ambient operating
temperature
0 to 55C (with no condensation or icing) Current Transformer (Order Separately)
Ambient operating
10% to 80%
Ratings
humidity
Dielectric strength 1,000 VAC for 1 min
Storage temperature -20 to 60C (with no condensation or icing)
Vibration resistance 50 Hz, 98 m/s2
Storage humidity 10% to 80%
E54-CT1: Approx. 11.5 g,
Altitude 2,000 m max. Weight
E54-CT3: Approx. 50 g
Weight Approx. 120 g
Accessories Armatures (2)
Windows is a registered trademark of Microsoft Corporation in the (E54-CT3 only) Plugs (2)
United States and or other countries.
* Use a high-power port for the USB port.
Note: A driver must be installed on the computer. Refer to the Heater Burnout Alarms and SSR Failure
Instruction Manual included with the Cable for the installation Alarms
procedure.
Models with detection for singlephase
Communications Specifications CT input (for heater heaters: One input
current detection) Models with detection for singlephase or
Transmission line
RS-485: Multidrop three-phase heaters: Two inputs
connection method
Maximum heater
Communications RS-485 (two-wire, half duplex) 50 A AC
current
Synchronization
Start-stop synchronization Input current indica-
method 5% FS 1 digit max.
Protocol CompoWay/F, or Modbus
tion accuracy
Baud rate* 9600, 19200, 38400, or 57600 bps Heater burnout
0.1 to 49.9 A (in units of 0.1 A)
alarm setting range
Transmission
ASCII Minimum detection ON time: 100 ms *3
code *1
Data bit length* 7 or 8 bits SSR failure alarm 0.1 to 49.9 A (in units of 0.1 A)
Stop bit length* 1 or 2 bits setting range *2 Minimum detection OFF time: 100 ms *4
Vertical parity (none, even, odd) *1. For heater burnout alarms, the heater current will be measured when the
Error detection Block check character (BCC) with control output is ON, and the output will turn ON if the heater current is
CompoWay/F or CRC-16 Modbus lower than the set value (i.e., heater burnout detection current value).
Flow control None *2. For SSR failure alarms, the heater current will be measured when the
control output is OFF, and the output will turn ON if the heater current is
Interface RS-485
higher than the set value (i.e., SSR failure detection current value).
Retry function None *3. The value is 30 ms for a control period of 0.1 s or 0.2 s.
Communications buffer 217 bytes *4. The value is 35 ms for a control period of 0.1 s or 0.2 s.
Communications 0 to 99 ms
response wait time Default: 20 ms
* The baud rate, data bit length, stop bit length, and vertical parity can be in-
Electrical Life Expectancy Curve for
dividually set using the Communications Setting Level. Relays (Reference Values)
Life ( 104 operations)

500
Communications Functions 300
You can use the memory in the PLC to read and
write E5@C parameters, start and stop operation, E5EC/E5AC
etc. The E5@C automatically performs communi- 100 250 VAC, 30 VDC
cations with PLCs. No communications program- (resistive load)
50 cos = 1
ming is required.
Number of connected Temperature Controllers: 30
32 max. (Up to 16 for the FX Series)
Programless Applicable PLCs
communications*1 OMRON PLCs 10
CS Series, CJ Series, or CP Series
Mitsubishi Electric PLCs 5
MELSEC Q Series, L Series, or FX Series 3
(compatible with the FX2 or FX3 (excluding
the FX1S))
KEYENCE PLCs 1
KEYENCE KV Series 0 1 2 3 4 5 6
Switching current (A)

28
E5EC/E5AC
External Connections
E5EC/E5AC
E5EC-@@ 4 @ 5 M - @ @ @ E5AC-@@ 4 @ 5 M - @ @ @
(1) (2) (3) (4) (5) (6) (1) (2) (3) (4) (5) (6) The E5EC is set for a K-type thermocouple (input
type = 5) by default. An input error (s.err) will occur
if the input type setting does not agree with the
Terminal type Terminal type temperature sensor. Check the input type.
Control output 1 Control output 2 Auxiliary outputs 1 to 4 (6) Options
Relay output Relay output Relay output 004 005 009 010
250 VAC, 5 A 250 VAC, 5 A Models with 4 auxiliary Communications 4 event inputs Communications, 2 event 4 event inputs
(resistive load) (resistive load) outputs: 250 VAC, 2 A and 2 event inputs inputs, and 2 CT inputs and 1 CT input
Voltage output Voltage output (resistive load) B(+) B(+)
(for driving SSR) 13 13 13 13
(for driving SSR) RS-485 RS-485
12 VDC, 40 mA 12 VDC, 21 mA 14 14 14 14
A(-) EV3 A(-) EV3
When There Is a Linear current output 15 15 15 15
EV4 EV4
Control Output 2: 0 to 20 mA DC 16 16 16 16
21 mA 4 to 20 mA DC 17 17 17 17
Linear current output Load: 500 max. EV1 EV1 EV1 EV1
0 to 20 mA DC 18 18 18 18
EV2 EV2 EV2 EV2
4 to 20 mA DC 19 19 19 19
CT1 CT1
Load: 500 max. 20 20 COM 20 20
CT2
21 21 21 21
(1) Control output
RX QX CX
011
Models with Models with 1 Models with 1
1 Relay Output
6 event Inputs, 1 CT input,
Voltage Output Linear Current Output
(for Driving SSR) transfer output, and remote SP input

3 OUT1 3 OUT1 OUT1 13


+Q 3 + C (3) Input Power Supply
R - - 14
4 4 4 EV3
100 to 240 VAC 24 VAC/DC
5 5 15
5 1 EV4
1 28 16
6 6 6
2 2 29 17
EV5 EV1
QQ QR (no polarity) 30 18
EV6 EV2
Models with 2 Voltage Models with Voltage Output (for + 31 19
Outputs (for Driving SSR) Driving SSR) and Relay Output Transfer V + CT1
I32 20
output
3 OUT1 OUT1 - 33 21
+Q 3 +Q 1 25 13
4 - 4 - 2 26 14 + 34
Remote V + 35
5 +Q 5 3 27 15 SP mA
- R - 36
6 6 4 28 16
OUT2 OUT2
5 29 17
RR PR CC 013 014
Models with 2 Models with 2 Models with 2 6 30 18 6 event Inputs, transfer Communications, 4 event Inputs,
Relay Outputs Position-proportional Linear Current 7 31 19 output, and remote SP input transfer output, and remote SP input
Relay Output Outputs B(+)
Open 8 32 20
OUT1 OUT1 13 13
3 3 3 + C RS-485
R R 9 33 21 14 14
4 4 4 - EV3 A(-)
10 34 22 15 15
5 5 5 EV4
+ C 11 35 23 28 16 28 16
R R -
6 OUT2 6 Close
6 OUT2 12 36 24 29 17 29 17
EV5 EV1 EV5 EV1
CQ 30 18 30 18
EV6 EV2 EV6 EV2
Models with 2 Outputs: Linear Current Output + 31 19 + 31 19
and Voltage (for Driving SSR) Transfer V + Transfer V +
output I 32 20 I 32 20
output
3 OUT1 (2) Auxiliary Outputs Potentiometer Input - 33 21 - 33 21
+ C
- 19 + 34 + 34
4 Auxiliary outputs 1, 2, 3, 4
O V + V +
Remote Remote
5 7 20 mA 35
SP mA 35
+ Q Auxiliary output 4 W SP
- 36 - 36
- 8 21
6 OUT2 Auxiliary output 3 C
9 Note: 1. The application of the terminals depends on
10 the model.
Auxiliary output 2 (5) Sensor (Temperature/Analog) Input 2. Do not wire the terminals that are shown with
11
Auxiliary output 1 TC Pt I V a gray background.
12 A
22 22 + 22 22 3. When complying with EMC standards, the
- 23 B mA - cable that connects the sensor must be 30 m
23 23 23
B - V or less. If the cable length exceeds 30 m,
+ 24 24 24
+
24 compliance with EMC standards will not be
possible.
4. Connect M3 crimped terminals.

Isolation/Insulation Block Diagrams


Models with 4 Auxiliary Outputs

Sensor input, CT inputs, potentiometer input, and remote SP input

Communications and event inputs


Voltage output (for driving SSR),
Power linear current output, and transfer output
Supply
Relay output

Auxiliary outputs 1, 2

Auxiliary outputs 3, 4

: Reinforced insulation

: Functional isolation

Note: Auxiliary outputs 1 to 2 and 3 to 4 are not insulated.

29
E5EC/E5AC
Nomenclature
E5EC
Front panel

No. 1 display
PV or specified parameter Top View of E5EC
Temperature unit
No. 2 display
Operation indicators
SP or specified parameter value

No. 3 display Top-panel


Front-panel Setup Tool port Manipulated value or other value Setup
Tool port
Manipulated
Use the Uvalue or other
D Keys value
to set
the parameter.

Use S Key to change the digit (default setting).

Use the M Key to change to another parameter.

Press O Key once to go to Adjustment Level.

Press O Key for at least 3 seconds to go to Initial Setting Level.

E5AC

Front Panel

Top View of E5AC


Temperature unit
No. 1 display
Operation indicators
PV or specified parameter

No. 2 display

SP or specified parameter value

Front-panel Setup Tool port No. 3 display


Manipulated value or other value

Top-panel
Press the U or D Key to set the parameter.
Setup
Tool port

Press the S Key to change the digit (default setting).

Press the O Key once to go to the Adjustment Level.


Press the M Key to change to another parameter.
Press the O Key for at least 3 seconds to go to the Initial Setting Level.

30
E5EC/E5AC
Dimensions (Unit: mm)

Controllers
E5EC
(64)
4
48 60 44
1

The Setup Tool ports are on the front and top


of the Digital Temperature Controller.
It is used to connect the Temperature Con-
troller to the computer to use the Setup Tool.
The E58-CIFQ2 USB-Serial Conversion
Cable is required to make the connection.
96 110 91 Refer to the instructions that are provided
with the USB-Serial Conversion Cable for the
connection procedure.
Note: Do not leave the USB-Serial
Conversion Cable connected when
you use the Temperature Controller.
Waterproof
Packing (Accessory) Mounting Adapter
(Accessory)

Mounted Separately Group Mounted *


(48 number of units 2.5)+1.0
0
45+0.6
* Selections for Control Outputs 1 and 2: QQ, QR, RR, CC, PR, or CQ
0
If you also specify 011, 013, or 014 for the option selection and use
group mounting, the ambient temperature must be 45C or less.
If the ambient temperature is 55C, maintain the following mounting
spaces between Controllers.
92+0.8
0

60 min.
45-0.6
0

Group mounting does not


120 min.
allow waterproofing.

92+0.8
0

92-0.8
0

120 min.

Recommended panel thickness is 1 to 8 mm.


Group mounting is not possible in the vertical direction. (Maintain the
specified mounting space between Controllers.)
To mount the Controller so that it is waterproof, insert the waterproof
packing onto the Controller.
When two or more Controllers are mounted, make sure that the
surrounding temperature does not exceed the allowable operating
temperature specified in the specifications.

31
E5EC/E5AC

E5AC (64)
4
60
96 x 96 1 91 x 91

110 91

Waterproof
Packing (Accessory) Mounting Adapter
(Accessory)
The Setup Tool ports are on the front and top of the Digital Temperature Controller.
It is used to connect the Temperature Controller to the computer to use the Setup Tool.
The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection.
Refer to the instructions that are provided with the USB-Serial Conversion Cable for the connection procedure.
Note: Do not leave the USB-Serial Conversion Cable connected when you use the Temperature Controller.

Mounted Separately Group Mounted *


(96 number of units 3.5)+1.0
0
92+0.8
Recommended panel thickness is 1 to 8 mm.
0
Group mounting is not possible in the vertical direction. (Maintain the
specified mounting space between Controllers.)
To mount the Controller so that it is waterproof, insert the waterproof
packing onto the Controller.
92+0.8
0 When two or more Controllers are mounted, make sure that the
surrounding temperature does not exceed the allowable operating
temperature specified in the specifications.

120 min. Group mounting does not


allow waterproofing.

92+0.8
0

32
E5EC/E5AC

Accessories (Order Separately)


USB-Serial Conversion Cable
E58-CIFQ2 (2110)
250 263 1510

LED (RD)

USB connector
(type A plug)
LED (PWR) Serial connector

LED (SD)

Conversion Cable
E58-CIFQ2-E
Conversion Cable Connecting to the E58-CIFQ2 USB-Serial Conversion Cable
(2110)
(1510) 250 263 1510

E58-CIFQ2 (Order Separately) Conversion Cable


Note: Always use this product together with the E58-CIFQ2.

Terminal Covers Waterproof Packing


E53-COV24 (Three Covers provided.) Y92S-P9 (for DIN 48 96)
2 3.8
The Waterproof Packing is provided with the Temperature
Controller.
10 The degree of protection when the Waterproof Packing is used
is IP66.
Also, keep the Port Cover on the front-panel Setup Tool port
of the E5EC/E5AC securely closed.
To maintain an IP66 degree of protection, the Waterproof
Packing and the Port Cover for the front-panel Setup Tool port
91
must be periodically replaced because they may deteriorate,
shrink, or harden depending on the operating environment.
The replacement period will vary with the operating
environment.
Y92S-P10 (for DIN 96 96) Check the required period in the actual application.
Use 3 years or sooner as a guideline.
If a waterproof structure is not required, then the Waterproof
Packing does not need to be installed.

Setup Tool Port Cover for top panel Mounting Adapter


Y92S-P7 Y92F-51 (for DIN 48 96)

One pair is provided with the


Order this Port Cover
Controller.
separately if the Port Cover on
Order this Adapter
the front-panel Setup Tool port
separately if it becomes lost
is lost or damaged. The
or damaged.
Waterproof Packing must be
periodically replaced because
it may deteriorate, shrink, or
harden depending on the
operating environment.

33
E5EC/E5AC

Watertight Cover Watertight Cover


Y92A-49N (48 96) Y92A-96N (96 96)

21.9 21.9
(2) (2)

131.7 131.7

67.6 29.4 115.6 29.4

Current Transformers
E54-CT1 Thru-current (Io) vs. Output Voltage (Eo)
21
2.8
15
(Reference Values)
5.8 dia.
E54-CT1
7.5
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 4002
25 3
Winding resistance: 182
10.5 100V

Output voltage (Eo) V (r.m.s.)


Frequency: 50 Hz

40 10 Distortion
1k factor
Two, 3.5 dia.
10%
1
10 3%
1%
100mV
30

10 100
E54-CT3
2.36 dia. 1 RL=10
30
12 dia.
9 100V

10
1 10 100mA 1 10 100 1,000A
40 40
Thru-current (Io) A (r.m.s.)
Thru-current (Io) vs. Output Voltage (Eo)
(Reference Values)
Two, M3 (depth: 4) E54-CT3
Maximum continuous heater current: 120 A (50/60 Hz)
15
(Maximum continuous heater current for an OMRON Digital
Temperature Controller is 50 A.)
30
Number of windings: 4002
Winding resistance: 80.8
E54-CT3 Accessories 100V
Output voltage (Eo) V (r.m.s.)

Frequency: 50 Hz
Armature Connection Example Distortion

10 factor
Armature 1k
10%
Approx. 3 dia. Plug 500 3%
1 1%
Lead

100mV
100
18 50
10
RL=10
Plug
1

Approx. 6 dia. 100V

(22) 10
1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)

34
MEMO

35
Digital Temperature Controller

E5DC (22.5 mm Wide, and DIN Track-mounting Type)

The E5DC Mounts to DIN Track and Is Ideal


for Connections to HMIs and PLCs.
It provides the Same Easy Operation and
Advanced Performance as the Rest of the
E5@C Series.
A slim body at 85 22.5 mm (D W) that fits into narrow control
panels and mounts to DIN Track.
Removable terminal block for easy replacement to simplify maintenance.
High-speed sampling at 50 ms for applications with high-speed
temperature increases.
Easy connections to a PLC with programless communications.
Set up the Controller without wiring the power supply by connecting
to the computer with a Communications Conversion Cable (sold separately). 22.5 mm Wide, and
DIN Track-mounting Type
Setup is easy with the CX-Thermo (sold separately). E5DC
Models are available with up to 2 auxiliary outputs and 1 event input to
complete basic functions. Refer to your OMRON website for the most recent
information on applicable safety standards.
A white PV display (height: 8.5 mm) is easy to read when setting up,
checking alarms, and making settings in a control panel.
Refer to Safety Precautions on page 90.

Main I/O Functions

Sensor Input E5DC


Universal input
Thermocouple
Pt Dual displays: PV/SV 4-digit displays
Analog current/voltage

Indication Accuracy Control Output 1


Thermocouple input: Relay output
0.3% of PV Voltage output (for driving SSR)
Pt input: 0.2% of PV Linear current output
Analog input:
0.2% of FS
Auxiliary Outputs
Sampling Period None
50 ms 2

Event Inputs
None
PF (shift) Key
1
Temperature status display
Simple programming
Serial Communications
Independent heating and
None cooling PID control
RS-485 Changed parameter display
Display brightness setting

This datasheet is provided as a guideline for selecting products.


Be sure to refer to the following manuals for application precautions and other information required for operation before attempting
to use the product.
E5@C Digital Temperature Controllers Users Manual (Cat. No. H174)
E5@C Digital Temperature Controllers Communications Manual (Cat. No. H175)

36
E5DC
Model Number Legend and Standard Models
Model Number Legend
Models with Screw Terminals
E5DC-@@ @ @ S M @@@ (Example: E5DC-RX0ASM-015)

A B C D E F

A B C D E F
Model No. of Power Meaning
Control Terminal Input
auxiliary supply Options
output 1 type type
outputs voltage
E5DC 22.5 mm wide and mounts to DIN Track
Control output 1
RX Relay output
Voltage output
QX
(for driving SSR)
CX Linear current output *5
0 None
2 2 (one common)
A 100 to 240 VAC
D 24 VAC/DC
S Screw terminals
M Universal input
HB alarm and HS alarm Communications Event input
*1 000 --- --- ---
*2 002 1 RS-485 ---
*3 015 --- RS-485 ---
*4 016 --- --- 1
*2 017 1 --- 1
*1 Option 000 can be selected only if two auxiliary outputs are selected.
*2 Options 002 and 017 can be selected only if the control output is a relay output or voltage output and two auxiliary outputs are selected.
*3 Option 015 cannot be selected if the control output is a relay output or voltage output and two auxiliary outputs are selected.
*4 Options 016 can be selected only if the control output is a linear current output and two auxiliary outputs are selected.
*5 The control output cannot be used as a transfer output.

List of Models
Options Model Model
No. of auxiliary Power supply voltage Power supply voltage
Control output HB alarm and HS
outputs No. of event inputs Communications
alarm
100 to 240 VAC 24 VAC/DC
--- RS-485 E5DC-RX0ASM-015 E5DC-RX0DSM-015
---
--- --- E5DC-RX2ASM-000 E5DC-RX2DSM-000
Relay output
2 Detection for single- RS-485 E5DC-RX2ASM-002 E5DC-RX2DSM-002
phase heater 1 --- E5DC-RX2ASM-017 E5DC-RX2DSM-017
--- RS-485 E5DC-QX0ASM-015 E5DC-QX0DSM-015
---
Voltage output --- --- E5DC-QX2ASM-000 E5DC-QX2DSM-000
(for driving SSR) 2 RS-485 E5DC-QX2ASM-002 E5DC-QX2DSM-002
Detection for single-
phase heater 1 --- E5DC-QX2ASM-017 E5DC-QX2DSM-017
--- RS-485 E5DC-CX0ASM-015 E5DC-CX0DSM-015
Linear current --- --- E5DC-CX2ASM-000 E5DC-CX2DSM-000
---
output 2 RS-485 E5DC-CX2ASM-015 E5DC-CX2DSM-015
1 --- E5DC-CX2ASM-016 E5DC-CX2DSM-016

Note: These products are sold as a set with a terminal block (i.e., Terminal Unit).

Heating and Cooling Control


Using Heating and Cooling Control
A Control Output Assignment
An auxiliary output is used as the cooling control output.
B Control
If PID control is used, you can set PID control separately for heating and cooling.
This allows you to handle control systems with different heating and cooling response characteristics.

37
E5DC

Optional Products (Order Separately)


USB-Serial Conversion Cable End Plate
Model Model
E58-CIFQ2 PFP-M

Conversion Cable Spacer


Model Model
E58-CIFQ2-E PFP-S
Note: Always use this product together with the E58-CIFQ2.
This Cable is used to connect to the front-panel Setup Tool DIN Tracks
port.
Model
Current Transformers (CTs) PFP-100N
Hole diameter Model PFP-50N
5.8 mm E54-CT1
12.0 mm E54-CT3 Unit Labels
Model
Mounting Adapters Y92S-L2
Model
Y92F-53 End Cover
Model
Short Bars Y92F-54
Model
Y92S-P11

CX-Thermo Support Software


Model
EST2-2C-MV4
Note: CX-Thermo version 4.6 or higher is required for the E5DC.
For the system requirements for the CX-Thermo, refer to
information on the EST2-2C-MV4 on the OMRON website
(www.ia.omron.com).

38
E5DC
Specifications
Ratings
A in model number: 100 to 240 VAC, 50/60 Hz
Power supply voltage
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Power consumption 4.9 VA max. at 100 to 240 VAC, and 2.8 VA max. at 24 VDC or 1.5 W max. at 24 VDC
Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Sensor input Infrared temperature sensor (ES1B): 10 to 70C, 60 to 120C, 115 to 165C, or 140 to 260C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 max., Voltage input: 1 M min. (Use a 1:1 connection when connecting the ES2-HB/
Input impedance
THB.)
Control method ON/OFF control or 2-PID control (with auto-tuning)
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load: 5
Relay output
V, 10 mA (reference value)
Control
Voltage output
output Output voltage 12 VDC 20% (PNP), max. Load current: 21 mA, with short-circuit protection circuit
(for driving SSR)
Linear current output 4 to 20 mA DC/0 to 20 mA DC, load: 500 max., resolution: Approx. 10,000
Number of outputs 2 (depends on model)
Auxiliary
outputs SPST-NO relay outputs: 250 VAC, 2 A (resistive load),
Output specifications
Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value)
Number of inputs 1 (depends on model)
Event Contact input ON: 1 k max., OFF: 100 k min.
inputs External contact input
Non-contact input ON: Residual voltage 1.5 V max.; OFF: Leakage current 0.1 mA max.
specifications
Current flow: approx. 7 mA per contact
Setting method Digital setting using front panel keys
11-segment digital displays and individual indicators
Indication method
Character height: PV: 8.5 mm, SV: 8.0 mm
Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations, or
Multi SP
serial communications.*
Bank switching None
Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater burn-
out (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, self
Other functions tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root, MV change
rate limit, logic operations, temperature status display, simple programming, moving average of input val-
ue, and display brightness setting
10 to 55C (with no condensation or icing), for 3-year warranty: 10 to 50C (with no condensation or
Ambient operating temperature
icing)
Ambient operating humidity 25% to 85%
Storage temperature 25 to 65C (with no condensation or icing)
Altitude 2,000 m max.
Recommended fuse T2A, 250 VAC, time-lag, low-breaking capacity
Installation environment Installation Category II, Pollution Degree 2 (IEC 61010-1 compliant)
* Only two set points are selectable for event inputs.

39
E5DC

Input Ranges
Thermocouple/Platinum Resistance Thermometer (Universal inputs)
Sensor Platinum resistance Infrared temperature
Thermocouple
type thermometer sensor
Sensor
10 to 60 to 115 to 140 to
specifica- Pt100 JPt100 K J T E L U N R S B W PLII 70C 120C 165C 260C
tion
2300
2300
1800
1800
1700 1700
1700
1600
1500
Temperature range (C)

1400
1300 1300 1300
1300
1200
1100
1000
850 850 850
900
800
700
600
600
500.0 500.0 500.0
500
400.0 400 400.0 400 400.0
400
260
300
120 165
200
100.0 100.0 90
100
100
0.0 0.0 0 0 0 0 0 0 0 0
-100
-20.0 -100 -20.0 -100
-200
-200 -199.9 -199.9 -200 -200 -199.9 -200 -200 -199.9 -200
Set value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Shaded settings are the default settings.

The applicable standards for the input types are as follows:


K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 60584-1 JPt100: JIS C 1604-1989, JIS C 1606-1989
L: Fe-CuNi, DIN 43710-1985 Pt100: JIS C 1604-1997, IEC 60751
U: Cu-CuNi, DIN 43710-1985 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)
W: W5Re/W26Re, ASTM E988-1990

Analog input
Input type Current Voltage
Input specification 4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V
Usable in the following ranges by scaling:
Setting range -1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
Set value 25 26 27 28 29

40
E5DC

Alarm Types
Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (See note.)
Auxiliary outputs are allocated to alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not
displayed.
To use alarm 1, set the output assignment to alarm 1.

Alarm output operation


Set
value Alarm type When alarm value X When alarm value X Description of function
is positive is negative
0 Alarm function OFF Output OFF No alarm
Set the upward deviation in the set point for the alarm upper
L H
ON limit (H) and the lower deviation in the set point for the alarm
1 Upper- and lower-limit *1 OFF PV
*2
SP lower limit (L). The alarm is ON when the PV is outside this
deviation range.
X X Set the upward deviation in the set point by setting the alarm
2 ON ON
Upper-limit OFF PV OFF PV value (X). The alarm is ON when the PV is higher than the
(default) SP SP
SP by the deviation or more.
X X Set the downward deviation in the set point by setting the
ON ON
3 Lower-limit OFF PV OFF PV alarm value (X). The alarm is ON when the PV is lower than
SP SP
the SP by the deviation or more.
Set the upward deviation in the set point for the alarm upper
L H
Upper- and lower-limit ON limit (H) and the lower deviation in the set point for the alarm
4 OFF PV *3
range *1 SP lower limit (L). The alarm is ON when the PV is inside this de-
viation range.
L H
Upper- and lower-limit ON A standby sequence is added to the upper- and lower-limit
5 OFF PV *4
with standby sequence *1 *5 SP alarm (1). *6
X X
Upper-limit with standby ON ON
6 OFF PV OFF PV A standby sequence is added to the upper-limit alarm (2). *6
sequence SP SP

X X
Lower-limit with standby ON ON
7 OFF PV OFF PV A standby sequence is added to the lower-limit alarm (3). *6
sequence SP SP

X X
Absolute-value upper-lim- ON ON The alarm will turn ON if the process value is larger than the
8 OFF PV OFF PV
it 0 0 alarm value (X) regardless of the set point.
X X
ON ON The alarm will turn ON if the process value is smaller than the
9 Absolute-value lower-limit OFF PV OFF PV
0 0 alarm value (X) regardless of the set point.
X X
Absolute-value upper-lim- ON ON A standby sequence is added to the absolute-value upper-
10 OFF PV OFF PV
it with standby sequence 0 0 limit alarm (8). *6
X X
Absolute-value lower-limit ON ON A standby sequence is added to the absolute-value lower-
11 OFF PV OFF PV
with standby sequence 0 0 limit alarm (9). *6
12 LBA (alarm 1 type only) - *7
13 PV change rate alarm - *8
X X
SP absolute-value ON ON This alarm type turns ON the alarm when the set point (SP)
14 OFF SP OFF SP
upper-limit alarm 0 0 is higher than the alarm value (X).
X X
SP absolute-value ON ON This alarm type turns ON the alarm when the set point (SP)
15 OFF SP OFF SP
lower-limit alarm 0 0 is lower than the alarm value (X).
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
16 Heating/Cooling
upper-limit alarm *9 Heating/Cooling variable (MV) is higher than the alarm value (X).
Control (Heating MV) Control (Heating MV)
X
ON
OFF
0
MV Always ON
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
17 Heating/Cooling Heating/Cooling
lower-limit alarm *9 variable (MV) is lower than the alarm value (X).
Control (Cooling MV) Control (Cooling MV)
X
ON
OFF
0
MV Always ON

41
E5DC

*1 With set values 1, 4, and 5, the upper- and lower-limit values can *4 Set value: 5, Upper- and lower-limit with standby sequence
be set independently for each alarm type, and are expressed as For Upper- and Lower-Limit Alarm Described Above at *2
L and H. In cases 1 and 2 above, the alarm is always OFF if the upper-
*2 Set value: 1, Upper- and lower-limit alarm and lower-limit hysteresis overlaps.
Case 1 Case 2 Case 3 (Always OFF) In case 3, the alarm is always OFF.
H<0, L<0 *5 Set value: 5, Upper- and lower-limit alarm with standby sequence
L H SP SP L H H SP L The alarm is always OFF if upper- and lower-limit hysteresis
H<0, L>0 overlaps.
H<0, L>0 H>0, L<0
H L SP |H| |L| *6 Refer to the E5@C Digital Temperature Controllers Users Manual
|H| < |L| |H| > |L|
H>0, L<0 (Cat. No. H174) for information on the operation of the standby
SP H L |H| |L| sequence.
*3 Set value: 4, Upper- and lower-limit range *7 Refer to the E5@C Digital Temperature Controllers Users Manual
Case 1 Case 2 Case 3 (Always ON) (Cat. No. H174) for information on the LBA.
H<0, L<0 *8 Refer to the E5@C Digital Temperature Controllers Users Manual
L H SP SP L H H SP L (Cat. No. H174) for information on the PV change rate alarm.
H<0, L>0 H>0, L<0
H<0, L>0 *9 When heating/cooling control is performed, the MV absolute-
H L SP |H| |L| value upper-limit alarm functions only for the heating operation
|H| < |L| |H| > |L|
H>0, L<0 and the MV absolute-value lower-limit alarm functions only for the
SP H L |H| |L| cooling operation.

42
E5DC

Characteristics
Thermocouple:*1 (0.3 % of indication value or 1C, whichever is greater) 1 digit max.
Indication accuracy
Platinum resistance thermometer: (0.2 % of indication value or 0.8C, whichever is greater) 1 digit max.
(when mounted individually, ambi-
Analog input: 0.2% FS 1 digit max.
ent temperature of 23C)
CT input: 5% FS 1 digit max.
Influence of temperature *2 Thermocouple input (R, S, B, W, PL II): (1% of indication value or 10C, whichever is greater) 1 digit
max.
Other thermocouple input: (1% of indication value or 4C, whichever is greater) 1 digit max. *3
Influence of voltage *2 Platinum resistance thermometer: (1% of indication value or 2C, whichever is greater) 1 digit max.
Analog input: 1% FS 1 digit max.
CT input: 5% FS 1 digit max.
R, S, B, W, or PLII thermocouple: (1% of PV or 10C, whichever is greater) 1 digit max.
Installation influence (E5DC only)
Other thermocouple: (1% of PV or 4C, whichever is greater) 1 digit max. *3
Input sampling period 50 ms
Temperature input: 0.1 to 999.9C or F (in units of 0.1C or F)
Hysteresis
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9C or F (in units of 0.1C or F)
Proportional band (P)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Temperature input: 0.1 to 999.9C or F (in units of 0.1C or F)
Proportional band (P) for cooling
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value 0.0% to 100.0% (in units of 0.1%)
Alarm setting range 1,999 to 9,999 (decimal point position depends on input type)
Influence of signal source resis-
Thermocouple: 0.1C/ max. (100 max.), Platinum resistance thermometer: 0.1C/ max. (10 max.)
tance
Insulation resistance 20 M min. (at 500 VDC)
Dielectric strength 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y and Z directions
Vibration
Resistance 10 to 55 Hz, 20 m/s2 for 2 hr each in X, Y, and Z directions
Malfunction 100 m/s2, 3 times each in X, Y, and Z directions
Shock
Resistance 300 m/s2, 3 times each in X, Y, and Z directions
Weight Controller: Approx. 120 g
Degree of protection Main unit: IP20, Terminal unit: IP00
Memory protection Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool CX-Thermo version 4.6 or higher
E5DC bottom panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect a USB port on the
computer. *5
Setup Tool port
E5DC front panel: An E58-CIFQ2 USB-Serial Conversion Cable and E58-CIFQ2-E Conversion Cable are
used together to connect a USB port on the computer.*5
Approved standards UL 61010-1, Korean Radio Waves Act (Act 10564)
Standards
Conformed standards EN 61010-1 (IEC 61010-1): Pollution Degree 2 , overvoltage category II
EMI: EN61326
Radiated Interference Electromagnetic Field Strength: EN55011 Group 1, class A
Noise Terminal Voltage: EN55011 Group 1, class A
EMS: EN61326
ESD Immunity: EN61000-4-2
EMC
Electromagnetic Field Immunity: EN61000-4-3
Burst Noise Immunity: EN61000-4-4
Conduction Disturbance Immunity: EN61000-4-6
Surge Immunity: EN61000-4-5
Voltage Dip/Interrupting Immunity: EN61000-4-11
*1 The indication accuracy of K thermocouples in the 200 to 1,300C range, T and N thermocouples at a temperature of 100C or less, and U
and L thermocouples at any temperature is 2C 1 digit max. The indication accuracy of B thermocouples at a temperature of 400C max. is
not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800C is 3C max.
The indication accuracy of R and S thermocouples at a temperature of 200C max. is 3C 1 digit max. The indication accuracy of W
thermocouples is (0.3% of PV or 3C, whichever is greater) 1 digit max.
The indication accuracy of PLII thermocouples is (0.3% of PV or 2C, whichever is greater) 1 digit max.
*2 Ambient temperature: 10 to 23 to 55C, Voltage range: 15% to 10% of rated voltage
*3 K thermocouple at 100C max: 10C max.
*4 The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*5 External serial communications (RS-485) and USB-Serial Conversion Cable communications can be used at the same time.

43
E5DC

USB-Serial Conversion Cable When Digital Temperature Controllers are connected, set
points and RUN/STOP commands can be sent from the Digital
Specifications Component Temperature Controller that is set as the master to the Digital
Communi- Temperature Controllers that are set as slaves.
Applicable OS Windows XP, Vista, or 7 cations*1 Slope and offsets can be set for the set point.
Applicable software CX-Thermo version 4.6 or higher Number of connected Digital Temperature Controllers: 32
max. (including master)
Applicable models E5@C-T Series, E5@C Series, and E5CB Series
When Digital Temperature Controllers are connected, the pa-
USB interface stan- rameters can be copied from the Digital Temperature Control-
Conforms to USB Specification 2.0 Copying*2
dard ler that is set as the master to the Digital Temperature
DTE speed 38,400 bps Controllers that are set as slaves.
Computer: USB (Type A plug) MELSEC is a registered trademark of Mitsubishi Electric Corporation.
Connector
Digital Temperature Controller: Special serial con- KEYENCE is a registered trademark of Keyence Corporation.
specifications
nector
*1 A Temperature Controller with version 2.1 or higher is required for
Power supply Bus power (supplied from the USB host controller) * the FX Series or the KV Series.
Power supply voltage 5 VDC *2 Both the programless communications and the component
Current consumption 450 mA max. communications support the copying.
4.70.2 VDC (Supplied from USB-Serial Conver-
Output voltage
sion Cable to the Digital Temperature Controller.) Current Transformer (Order Separately)
250 mA max. (Supplied from USB-Serial Conver-
Output current
sion Cable to the Digital Temperature Controller.) Ratings
Ambient operating Dielectric strength 1,000 VAC for 1 min
0 to 55C (with no condensation or icing)
temperature
Vibration resistance 50 Hz, 98 m/s2
Ambient operating
10% to 80% E54-CT1: Approx. 11.5 g,
humidity Weight
E54-CT3: Approx. 50 g
Storage temperature 20 to 60C (with no condensation or icing)
Armatures (2)
Storage humidity 10% to 80% Accessories (E54-CT3 only)
Plugs (2)
Altitude 2,000 m max.
Weight Approx. 120 g
Heater Burnout Alarms and SSR Failure
Windows is a registered trademark of Microsoft Corporation in the United
States and other countries.
Alarms
* Use a high-power port for the USB port. CT input (for heater current Models with detection for single-phase heat-
detection) ers: 1 input
Note: A driver must be installed on the computer. Refer to the
Instruction Manual included with the Cable for the installation Maximum heater current 50 A AC
procedure. Input current
5% FS 1 digit max.
indication accuracy

Communications Specifications Heater burnout alarm


setting range *1
0.1 to 49.9 A (in units of 0.1 A)
Minimum detection ON time: 100 ms *3
Transmission line connection SSR failure alarm setting 0.1 to 49.9 A (in units of 0.1 A)
RS-485: Multidrop
method range *2 Minimum detection OFF time: 100 ms *4
Communications RS-485 (two-wire, half-duplex) *1 For heater burnout alarms, the heater current will be measured when the
Synchronization method Start-stop synchronization control output is ON, and the output will turn ON if the heater current is
lower than the set value (i.e., heater burnout detection current value).
Protocol CompoWay/F or Modbus *2 For SSR failure alarms, the heater current will be measured when the
Baud rate* 9,600, 19,200, 38,400, or 57,600 bps control output is OFF, and the output will turn ON if the heater current is
higher than the set value (i.e., SSR failure detection current value).
Transmission code ASCII *3 The value is 30 ms for a control period of 0.1 s or 0.2 s.
Data bit length * 7 or 8 bits *4 The value is 35 ms for a control period of 0.1 s or 0.2 s.
Stop bit length * 1 or 2 bits
Vertical parity (none, even, or odd) Electrical Life Expectancy Curve for
Block check character (BCC)
Error detection
with CompoWay/F or Control Output Relay (Reference Values)
CRC-16 with Modbus
Life ( 104 operations)

500
Flow control None
300
Interface RS-485
Retry function None
100
Communications buffer 217 bytes
Communications response 0 to 99 ms 50
wait time Default: 20 ms
30
* The baud rate, data bit length, stop bit length, and vertical parity can
be individually set using the Communications Setting Level.
Communications Functions 10

You can use the memory in the PLC to read and write E5@C 5
E5DC
parameters, start and stop operation, etc. 3 250 VAC, 30 VDC
The E5@C automatically performs communications with the (resistive load)
PLC. No communications programming is required. cos = 1

Program- Number of connected Digital Temperature Controllers: 32 1


max. (Up to 16 for the FX Series) 0 1 2 3 4 5 6
less
communi- Applicable PLCs: OMRON PLCs
CS Series, CJ Series, or CP Series Switching current (A)
cations *1
Mitsubishi Electric PLCs
MELSEC Q Series, L Series, or FX Series (compatible
with the FX2 or FX3 (excluding the FX1S))
KEYENCE PLCs
KEYENCE KV Series

44
E5DC
External Connections
E5DC
Control output Auxiliary outputs 1 and 2
The E5DC is set for a K-type thermocouple (input type = 5) by default.
Relay output Relay outputs An input error (s.err) will occur if the input type setting does not agree
250 VAC, 3 A (resistive load) 250 VAC: 2 A (resistive load) with the temperature sensor. Check the input type.
Voltage output (for driving SSR)
12 VDC, 21 mA
Linear current output E5DC SM
0 to 20 mA DC Control output Options
4 to 20 mA DC
Load: 500 max. Input Power Supply Control Output
100 to 240 VAC 24 VAC/DC RX QX CX
1 relay 1 voltage output 1 linear
1 1 output (for driving SSR) current output
2 2 5 5 +Q 5 + C
R
6 6 - 6 -
(no polarity)

1 5 9
2 6 10 Auxiliary Outputs
Options
9
002 11 Auxiliary output 2
10
Communications and 1 CT Auxiliary output 1
B(+) 11
3 7
RS-485 CT1
4 8
A(-)

015 Sensor (Temperature/Analog) Input


Communications
TC Pt I V
B(+) A + 12
3 7 12 12 12 12
- B mA - 13
RS-485 13 13 13
4 8 B - V
3 7 13
A(-) + 14 14 14
+
14

016 4 8 14 Do not connect anything to the terminals


One event input that are shaded gray.

- 3 7
+ 4 8
EV1

017
One event input and one CT
- 3 7
CT1
+ 4 8
EV1

Note: 1. The application of the terminals depends on the model.


2. Do not wire the terminals that are shown with a gray background.
3. When complying with EMC standards, the cable that connects the sensor must be 30 m or less. If the cable length exceeds 30m,
compliance with EMC standards will not be possible.
4. Connect M3 crimped terminals.

Isolation/Insulation Block Diagrams

Sensor input and CT input

Communications and event input


Power
Voltage output (for driving SSR) and linear current output
supply

Relay output

Auxiliary outputs 1 and 2

: Reinforced insulation

: Functional isolation

Note: Auxiliary outputs 1 to 2 are not insulated.

45
E5DC
Nomenclature
E5DC Front panel

No. 1 display Bottom View of E5DC


Operation indicators PV or specified parameter
No.2 display
SP or specified parameter value
Press O Key once to go to Use the M Key to change to another
Adjustment Level. parameter.

Press O Key for at least 3 Use the U D Keys to Bottom-


seconds to go to Initial set the parameter. panel Setup
Setting Level. Tool port

Use S Key to change the digit (default setting). Front-panel Setup Tool port

Dimensions (Unit: mm)

Controllers
E5DC (85)
4 81
22.5 22.5

96 35 110 91

Mounting Adapter
(Accessory: Sold separately)
The Setup Tool ports are on the front and bottom of the Digital Temperature Controller.
It is used to connect the Temperature Controller to the computer to use the Setup Tool.
The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection.
Refer to the instructions that are provided with the USB-Serial Conversion Cable for the connection procedure.

Note: Do not leave the USB-Serial Conversion Cable connected when you use the Digital
Temperature Controller.

Mounted Separately Two-Unit Mounting Group Mounted


(22.5 number of units) +1.0
0
22.7 +0.3
0 45 +0.6
0

92 +0.8
0 92 +0.8 92 +0.8
0 0

120 min

Recommended panel thickness is 1 to 8 mm.


Group mounting is not possible in the vertical direction. (Maintain the specified mounting space between Controllers.)
When two or more Digital Temperature Controllers are mounted, make sure that the surrounding temperature does
not exceed the allowable operating temperature specified in the specifications.

46
E5DC
Accessories (Order Separately)
USB-Serial Conversion Cable (2110)
E58-CIFQ2 250 263 1510

LED (RD)

USB connector
(type A plug)
LED (PWR) Serial connector

LED (SD)

Conversion Cable
E58-CIFQ2-E
Conversion Cable Connecting to the E58-CIFQ2 USB-Serial Conversion Cable
(2110)
(1510) 250 263 1510

E58-CIFQ2 (sold separately) Conversion Cable


Note: Always use this product together with the E58-CIFQ2.

Current Transformers
E54-CT1 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values)
21
2.8
15 E54-CT1
5.8 dia.
Maximum continuous heater current: 50 A (50/60 Hz)
7.5
Number of windings: 4002
Winding resistance: 182
25 3
100V
Output voltage (Eo) V (r.m.s.)

Frequency: 50 Hz
10.5
10
Distortion
40 1k factor
10%
Two, 3.5 dia. 1
3%
1%
10
100mV

30
10 100
E54-CT3 2.36 dia.
30
1 RL=10
12 dia.
9
100V

10
40 40 1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)

Thru-current (Io) vs. Output Voltage (Eo) (Reference Values)


Two , M3 holes (depth: 4)
E54-CT3
15
Maximum continuous heater current: 120 A (50/60 Hz) (Maximum
continuous heater current for an OMRON Digital Temperature Con-
troller is 50 A.)
30
Number of windings: 4002
Winding resistance: 80.8
E54-CT3 Accessories 100V
Output voltage (Eo) V (r.m.s.)

Frequency: 50 Hz
Armature Connection Example Distortion

10 factor
Armature 1k
10%
Approx. 3 dia. Plug 500 3%
1 1%
Lead

100mV
100
18 50
10
RL=10
Plug
1

Approx. 6 dia. 100V

10
(22) 1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)

47
E5DC

Mounting Adapters Short Bars


Y92F-53 (Two included.) Y92S-P11 (Four included.)
This accessory is not included with the Use this product to connect between terminals (for power supplies,
product. Order it separately to mount communications, etc.) when you use multiple E5DC Controllers.
the product to a panel.
27.5
34.7 2.4
22.5

12

24.8

11.8 9.4 0.8 3


5

End Plate DIN Tracks


PFP-M PFP-100N
PFP-50N
10
6.2
1.8
M48
pan head
screw 1
50 35.5 35.3
1.8

11.5
7.30.15
10 1.3
M4 spring washer 4.8 4.5
350.3 270.15

15 25 25 25 25 15 (5)* 1
10 10
1000 (500)*
* Dimensions in parentheses are for the PFP-50N.

Spacer Unit Labels


PFP-S Y92S-L2
16
5 12
The Unit Labels for the Digital Panel
Meter are used. Use either the C or F
label from the sheet.
34.8
44.3

16.5

End Cover
Y92F-54 (Two included.)
3.9 5.3

Use the End Cover when you mount the E5DC to a


panel to hide the gap between the Controller and the
96 panel.
68

48
MEMO

49
Programmable Temperature Controller (Digital Controller)

E5CC-T (48 48 mm)

Programmable Controllers Join the E5C Series!


Program up to 256 segments can handle a wide
variety of applications.
Set up to 8 Programs (Patterns) with 32 Segments (Steps) Each
The white PV display with a height of 15.2 mm improves visibility.
High-speed sampling at 50 ms.
Models are available with up to 3 auxiliary outputs, up to 4 event
inputs, and a transfer output to cover a wide range of applications.
Short body with depth of only 60 mm.
Set up the Controller without wiring the power supply by connecting to 48 48 mm
the computer with a Communications Conversion Cable (sold E5CC-T

separately). Setup is easy with the CX-Thermo (sold separately). Refer to your OMRON website for the most recent
Easy connections to a PLC with programless communications. Use information on applicable safety standards.

component communications to link Temperature Controllers to each


Refer to Safety Precautions on page 90.
other.

E5CC-T is scheduled to be released in January, 2014.

Main I/O Functions

Sensor Input E5CC-T


Universal input
Thermocouple Dual displays: PV/SV 4-digit displays
Pt
Analog current/voltage
Control Output 1
Indication Accuracy Relay output
Thermocouple input: 0.3% Voltage output (for driving
of PV
Pt input: 0.2% of PV
SSR)
Analog input: 0.2% of FS Linear current output

Sampling Period Control Output 2


50 ms None
Voltage output (for driving
Event Inputs SSR)

None Auxiliary Outputs


2
3
4
PF (shift) Key
Temperature status display Transfer Output
Serial Communications Operating and editing the program
Independent heating and cooling None
None 1
RS-485 PID control
Parameter mask setting
Display brightness setting

This datasheet is provided as a guideline for selecting products.


Be sure to refer to the following manuals for application precautions and other information required for operation before attempting
to use the product.
E5@C-T Digital Temperature Controllers Programmable Type Users Manual (Cat. No. H185)
E5@C-T Digital Temperature Controllers Programmable Type Communications Manual (Cat. No. H186)

50
E5CC-T
Model Number Legend and Standard Models
Model Number Legend
Models with Screw Terminals
E5CC-T @@3 @5 M @@@ (Example: E5CC-TRX3A5M-000)

A BC D E F

A B C D E F
Model No. of Power Meaning
Control outputs Terminal Input
auxiliary supply Options
1 and 2 type type
outputs voltage
E5CC-T 48 48 mm Programmable Type
Control output 1 Control output 2
RX Relay output None
Voltage output
QX None
(for driving SSR)
*1 CX Linear current output *2 None
Voltage output Voltage output
QQ
(for driving SSR) (for driving SSR)
Voltage output
CQ Linear current output *2
(for driving SSR)
3 3 (one common)
A 100 to 240 VAC
D 24 VAC/DC
5 Screw terminals (with cover)
M Universal input
HB alarm
Communica- Event Transfer
and HS
tions inputs output
alarm
000 --- --- --- ---
*1 001 1 --- 2 ---
2 (for 3-phase
*1 003 RS-485 --- ---
heaters)
004 --- RS-485 2 ---
005 --- --- 4 ---
006 --- --- 2 Provided.
*1. Options with HB and HS alarms (001 and 003) cannot be selected if a linear current output is selected for the control output.
*2. The linear current output cannot be used as a transfer output.

Heating and Cooling Control


Using Heating and Cooling Control
A Control Output Assignment
If there is no control output 2, an auxiliary output is used as the cooling control output.
If there is a control output 2, the two control outputs are used for heating and cooling.
(It does not matter which output is used for heating and which output is used for cooling.)
B Control
If PID control is used, you can set PID control separately for heating and cooling.
This allows you to handle control systems with different heating and cooling response characteristics.

51
E5CC-T

Optional Products (Order Separately)


USB-Serial Conversion Cable Front Covers
Model Type Model
E58-CIFQ2 Hard Front Cover Y92A-48H
Soft Front Cover Y92A-48D
Terminal Covers
Model CX-Thermo Support Software
E53-COV17 Model
E53-COV23 EST2-2C-MV4
Note: The Terminal Covers E53-COV23 are provided with the Digital Note: CX-Thermo version 4.61 or higher is required for the E5CC-T.
Temperature Controller. The E53-COV10 cannot be used. For the system requirements for the CX-Thermo, refer to
Refer to page 61 for the mounted dimensions. information on the EST2-2C-MV4 on the OMRON website
(www.ia.omron.com).
Waterproof Packing
Model
Y92S-P8
Note: The Waterproof Packing is provided with the Digital
Temperature Controller.

Current Transformers (CTs)


Hole diameter Model
5.8 mm E54-CT1
12.0 mm E54-CT3

Adapter
Model
Y92F-45
Note: Use this Adapter when the panel has already been prepared for
an E5B@ Controller.

Waterproof Cover
Model
Y92A-48N

Mounting Adapter
Model
Y92F-49
Note: This Mounting Adapter is provided with the Digital Temperature
Controller.

DIN Track Mounting Adapter


Model
Y92F-52

52
E5CC-T
Specifications
Ratings
A in model number: 100 to 240 VAC, 50/60 Hz
Power supply voltage
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85% to 110% of rated supply voltage
Power consumption 7.5 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC
Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Sensor input Infrared temperature sensor (ES1B): 10 to 70C, 60 to 120C, 115 to 165C, or 140 to 260C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 max., Voltage input: 1 M min.
Input impedance
(Use a 1:1 connection when connecting the ES2-HB/THB.)
Control method 2-PID control (with auto-tuning) or ON/OFF control
SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum applicable load:
Relay output
5 V, 10 mA (reference value) *
Control
Voltage output
output Output voltage: 12 VDC 20% (PNP), max. load current: 21 mA, with short-circuit protection circuit
(for driving SSR)
Linear current output 4 to 20 mA DC/0 to 20 mA DC, load: 500 max., resolution: approx. 10,000*
Number of outputs 3
Auxiliary
output SPST-NO relay outputs, 250 VAC, Models with 3 outputs: 2 A (resistive load), Electrical life: 100,000
Output specifications
operations, Minimum applicable load: 10 mA at 5 V (reference value)
Number of inputs 2 or 4 (depends on model)
Contact input: ON: 1 k max., OFF: 100 k min.
Event input External contact input
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
specifications
Current flow: Approx. 7 mA per contact
Number of outputs 1 (only on models with a transfer output)
Transfer
output Current output: 4 to 20 mA DC, load: 500 max., resolution: approx. 10,000
Output specifications
Linear voltage output: 1 to 5 VDC, load: 1 k min., resolution: Approx. 10,000
Setting method Digital setting using front panel keys
11-segment digital display and individual indicators
Indication method
Character height: PV: 15.2 mm, SV: 7.1 mm
Bank switching None
Manual output, heating/cooling control, loop burnout alarm, other alarm functions, heater burnout (HB)
alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, robust
Other functions
tuning, PV input shift, protection functions, extraction of square root, MV change rate limit, logic
operations, temperature status display, moving average of input value, and display brightness setting
-10 to 55C (with no condensation or icing),
Ambient operating temperature
for 3-year warranty: -10 to 50C (with no condensation or icing)
Ambient operating humidity 25% to 85%
Storage temperature -25 to 65C (with no condensation or icing)
Altitude 2,000 m max.
Recommended fuse T2A, 250 VAC, time-lag, low-breaking capacity
Installation environment Installation Category II, Pollution Degree 2 (IEC 61010-1 compliant)
* You cannot select a relay output or linear current output for control output 2.

53
E5CC-T

Input Ranges
Thermocouple/Platinum Resistance Thermometer (Universal inputs)
Sensor Platinum resistance Infrared temperature
Thermocouple
type thermometer sensor
Sensor
10 to 60 to 115 to 140 to
specifica- Pt100 JPt100 K J T E L U N R S B W PLII 70C 120C 165C 260C
tion
2300
2300
1800
1800
1700 1700
1700
1600
1500
Temperature range (C)

1400
1300 1300 1300
1300
1200
1100
1000
850 850 850
900
800
700
600
600
500.0 500.0 500.0
500
400.0 400 400.0 400 400.0
400
260
300
120 165
200
100.0 100.0 90
100
100
0
0.0 0.0 0 0 0 0 0 0 0 0
-100
-20.0 -100 -20.0 -100
-200
-200 -199.9 199.9 -200 -200 -199.9 -200 -200 -199.9 -200
Set value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Shaded settings are the default settings.

The applicable standards for the input types are as follows:


K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 60584-1 JPt100: JIS C 1604-1989, JIS C 1606-1989
L: Fe-CuNi, DIN 43710-1985 Pt100: JIS C 1604-1997, IEC 60751
U: Cu-CuNi, DIN 43710-1985 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)
W: W5Re/W26Re, ASTM E988-1990

Analog input
Input type Current Voltage
Input
4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V
specification
Usable in the following ranges by scaling:
Setting range -1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
Set value 25 26 27 28 29

54
E5CC-T

Alarm Types
Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (see note.)
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
To use alarm 1, set the output assignment to alarm 1.

Alarm output operation


Set Alarm type Description of function
value When alarm value X When alarm value X
is positive is negative
0 Alarm function OFF Output OFF No alarm
Set the upward deviation in the set point for the alarm upper
L H
ON limit (H) and the lower deviation in the set point for the alarm
1 Upper- and lower-limit *1 OFF PV
*2
SP lower limit (L). The alarm is ON when the PV is outside this
deviation range.
X X Set the upward deviation in the set point by setting the alarm
2 ON ON
Upper-limit OFF PV OFF PV value (X). The alarm is ON when the PV is higher than the
(default) SP SP
SP by the deviation or more.
X X Set the downward deviation in the set point by setting the
ON ON
3 Lower-limit OFF PV OFF PV alarm value (X). The alarm is ON when the PV is lower than
SP SP
the SP by the deviation or more.
Set the upward deviation in the set point for the alarm upper
L H
Upper- and lower-limit ON limit (H) and the lower deviation in the set point for the alarm
4 OFF PV *3
range *1 SP lower limit (L). The alarm is ON when the PV is inside this de-
viation range.
L H
Upper- and lower-limit ON A standby sequence is added to the upper- and lower-limit
5 OFF PV *4
with standby sequence *1 *5 SP alarm (1). *6
X X
Upper-limit with standby ON ON
6 OFF PV OFF PV A standby sequence is added to the upper-limit alarm (2). *6
sequence SP SP

X X
Lower-limit with standby ON ON
7 OFF PV OFF PV A standby sequence is added to the lower-limit alarm (3). *6
sequence SP SP

X X
Absolute-value upper-lim- ON ON The alarm will turn ON if the process value is larger than the
8 OFF PV OFF PV
it 0 0 alarm value (X) regardless of the set point.
X X
ON ON The alarm will turn ON if the process value is smaller than the
9 Absolute-value lower-limit OFF PV OFF PV
0 0 alarm value (X) regardless of the set point.
X X
Absolute-value upper-lim- ON ON A standby sequence is added to the absolute-value upper-
10 OFF PV OFF PV
it with standby sequence 0 0 limit alarm (8). *6
X X
Absolute-value lower-limit ON ON A standby sequence is added to the absolute-value lower-
11 OFF PV OFF PV
with standby sequence 0 0 limit alarm (9). *6
12 LBA (alarm 1 type only) - *7
13 PV change rate alarm - *8
X X
SP absolute-value ON ON This alarm type turns ON the alarm when the set point (SP)
14 OFF SP OFF SP
upper-limit alarm 0 0 is higher than the alarm value (X).
X X
SP absolute-value ON ON This alarm type turns ON the alarm when the set point (SP)
15 OFF SP OFF SP
lower-limit alarm 0 0 is lower than the alarm value (X).
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
16 Heating/Cooling
upper-limit alarm *9 Heating/Cooling variable (MV) is higher than the alarm value (X).
Control (Heating MV) Control (Heating MV)
X
ON
OFF
0
MV Always ON
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
17 Heating/Cooling Heating/Cooling
lower-limit alarm *9 variable (MV) is lower than the alarm value (X).
Control (Cooling MV) Control (Cooling MV)
X
ON
OFF
0
MV Always ON

55
E5CC-T

*1 With set values 1, 4 and 5, the upper and lower limit values can be set *4 Set value: 5, Upper- and lower-limit with standby sequence
independently for each alarm type, and are expressed as L and H. For Upper- and Lower-Limit Alarm Described Above *2
*2 Set value: 1, Upper- and lower-limit alarm
Case 1 and 2
Case 1 Case 2 Case 3 (Always ON)
Always OFF when the upper-limit and lower-limit hysteresis overlaps.
H<0, L<0
L H SP SP L H H SP L Case 3: Always OFF
H<0, L>0 *5. Set value: 5, Upper- and lower-limit with standby sequence
H<0, L>0 H>0, L<0
H L SP |H| |L| Always OFF when the upper-limit and lower-limit hysteresis overlaps.
|H| < |L| |H| > |L|
*6 Refer to the E5@C-T Digital Temperature Controllers Programmable Type
H>0, L<0
User's Manual (Cat. No. H185) for information on the operation of the
SP H L |H| |L|
standby sequence.
*3 Set value: 4, Upper- and lower-limit range *7 Refer to the E5@C-T Digital Temperature Controllers Programmable Type
Case 1 Case 2 Case 3 (Always OFF) User's Manual (Cat. No. H185) for information on the loop burnout alarm
H<0, L<0 (LBA).
L H SP SP L H H SP L *8 Refer to the E5@C-T Digital Temperature Controllers Programmable Type
H<0, L>0 H>0, L<0 H<0, L>0 User's Manual (Cat. No. H185) for information on the PV change rate
|H| < |L| |H| > |L| H L SP |H| |L| alarm.
*9 When heating/cooling control is performed, the MV absolute upper limit
H>0, L<0
alarm functions only for the heating operation and the MV absolute lower
SP H L |H| |L|
limit alarm functions only for the cooling operation.

56
E5CC-T

Characteristics
Thermocouple: (0.3% of indication value or 1C, whichever is greater) 1 digit max. *1
Indication accuracy Platinum resistance thermometer: (0.2% of indication value or 0.8C, whichever is greater) 1 digit
(at the ambient temperature of 23C) Analog input: 0.2% FS 1 digit max.
CT input: 5% FS 1 digit max.
Transfer output accuracy 0.3% FS max.
Influence of temperature *2 Thermocouple input (R, S, B, W, PL II): (1% of indication value or 10C, whichever is greater) 1 digit
max.
Other thermocouple input: (1% of indication value or 4C, whichever is greater) 1 digit max. *3
Influence of voltage *2 Platinum resistance thermometer: (1% of indication value or 2C, whichever is greater) 1 digit max.
Analog input: 1%FS 1 digit max.
CT input: 5% FS 1 digit max.
Input sampling period 50 ms
Temperature input: 0.1 to 999.9C or F (in units of 0.1C or F)
Hysteresis
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9C or F (in units of 0.1C or F)
Proportional band (P)
Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Temperature input: 0.1 to 999.9C or F (in units of 0.1C or F)
Proportional band (P) for cooling Analog input: 0.1% to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value 0.0 to 100.0% (in units of 0.1%)
Alarm setting range -1999 to 9999 (decimal point position depends on input type)
Thermocouple: 0.1C/ max. (100 max.)
Influence of signal source resistance
Platinum resistance thermometer: 0.1C/ max. (10 max.)
Insulation resistance 20 M min. (at 500 VDC)
Dielectric strength 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Vibration
Resistance 10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions
Malfunction 100 m/s2, 3 times each in X, Y, and Z directions
Shock
Resistance 300 m/s2, 3 times each in X, Y, and Z directions
Weight Controller: Approx. 120 g, Adapter: Approx. 10 g
Degree of protection Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool CX-Thermo version 4.61 or higher
E5CC-T top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect to a USB port on
Setup Tool port
the computer. *5
Approved standards UL 61010-1, Korean Radio Waves Act (Act 10564)
Standards
Conformed standards EN 61010-1 (IEC 61010-1): Pollution Degree 2, overvoltage category II
EMI: EN61326
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage: EN 55011 Group 1, class A
EMS: EN 61326
ESD Immunity: EN 61000-4-2
EMC
Electromagnetic Field Immunity: EN 61000-4-3
Burst Noise Immunity: EN 61000-4-4
Conducted Disturbance Immunity: EN 61000-4-6
Surge Immunity: EN 61000-4-5
Voltage Dip/Interrupting Immunity: EN 61000-4-11
*1 The indication accuracy of K thermocouples in the -200 to 1300C range, T and N thermocouples at a temperature of -100C max., and U and
L thermocouples at any temperatures is 2C 1 digit max. The indication accuracy of the B thermocouple at a temperature of 400C max. is
not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800C is 3C max. The indication accuracy of the R and
S thermocouples at a temperature of 200C max. is 3C 1 digit max. The indication accuracy of W thermocouples is (0.3% of PV or 3C,
whichever is greater) 1 digit max. The indication accuracy of PL II thermocouples is 0.3% of PV or 2C, whichever is greater, 1 digit max.
*2 Ambient temperature: -10C to 23C to 55C, Voltage range: -15% to 10% of rated voltage
*3 K thermocouple at -100C max.: 10C max.
*4 The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*5 External communications (RS-485) and USB-serial conversion cable communications can be used at the same time.

57
E5CC-T

Program Control
Number of programs (patterns) 8
Number of segments (steps) 32
Time setting (Segment set with set point and time.)
Segment setting method
Slope setting (Segment set with segment type, set point, slope, and time.)
0 h 0 min to 99 h 59 min
Segment times
0 min 0 s to 99 min 59 s
Alarm setting Set separately for each program.
Reset operation Select either stopping control or fixed SP operation.
Startup operation Select continuing, resetting, manual operation, or run mode.
Number of sets 8
PID sets
Setting method Set separately for each program (automatic PID group selection also supported).
Alarm SP function Select from ramp SP and target SP.
Segment operation Advance, segment jump, hold, and wait
Program status control
Program operation Program repetitions and program links
Wait method Waiting at segment ends
Wait operation
Wait width setting Same wait width setting for all programs
Number of outputs 2
Number of ON/OFF
Time signals 1 each per output
Operations
Setting method Set separately for each program.
Program status output Program end output (pulse width can be set), run output, stage output
PV start Select from segment 1 set point, slope-priority PV start
Program startup operation 0 h 0 min to 99 h 59 min
Standby
0 day 0 h to 99 day 23h
Operation end operation Select from resetting, continuing control at final set point, and fixed SP control.
Program SP shift Same program SP shift for all programs

58
E5CC-T

USB-Serial Conversion Cable When Digital Temperature Controllers are con-


nected, set points and RUN/STOP commands
Applicable OS Windows XP, Vista, or 7 can be sent from the Digital Temperature Control-
Component ler that is set as the master to the Digital Temper-
Applicable software CX-Thermo version 4.61 or higher Communications ature Controllers that are set as slaves.
Applicable models E5@C-T Series, E5@C Series, and E5CB Series Slope and offsets can be set for the set point.
Number of connected Digital Temperature Con-
USB interface standard Conforms to USB Specification 2.0. trollers: 32 max. (including master)
DTE speed 38400 bps When Digital Temperature Controllers are con-
Computer: USB (type A plug) nected, the parameters can be copied from the
Connector Copying*1 Digital Temperature Controller that is set as the
Digital Temperature Controller:
specifications master to the Digital Temperature Controllers that
Special serial connector
are set as slaves.
Power supply Bus power (Supplied from USB host controller.)*
Power supply voltage 5 VDC
MELSEC is a registered trademark of Mitsubishi Electric Corporation.
*1 Both the programless communications and the component
Current consumption 450 mA max.
communications support the copying.
4.70.2 VDC
Output voltage (Supplied from USB-Serial Conversion Cable to
the Digital Temperature Controller.) Current Transformer (Order Separately)
250 mA max. Ratings
Output current (Supplied from USB-Serial Conversion Cable to
the Digital Temperature Controller.) Dielectric strength 1,000 VAC for 1 min
Ambient operating Vibration resistance 50 Hz, 98 m/s2
0 to 55C (with no condensation or icing)
temperature
E54-CT1: Approx. 11.5 g,
Ambient operating
10% to 80% Weight
humidity E54-CT3: Approx. 50 g
Storage temperature -20 to 60C (with no condensation or icing) Accessories Armatures (2)
Storage humidity 10% to 80% (E54-CT3 only) Plugs (2)
Altitude 2,000 m max.
Weight Approx. 120 g Heater Burnout Alarms and SSR Failure
Windows is a registered trademark of Microsoft Corporation in the Alarms
United States and or other countries.
Models with detection for singlephase
* Use a high-power port for the USB port. CT input (for heater heaters: One input
Note: A driver must be installed on the computer. Refer to the current detection) Models with detection for singlephase or
Instruction Manual included with the Cable for the installation three-phase heaters: Two inputs
procedure.
Maximum heater
50 A AC
current
Communications Specifications Input current
Transmission line 5% FS 1 digit max.
RS-485: Multidrop indication accuracy
connection method
Heater burnout
Communications RS-485 (two-wire, half duplex) 0.1 to 49.9 A (in units of 0.1 A)
alarm setting range
Synchronization Minimum detection ON time: 100 ms *3
method
Start-stop synchronization *1
Protocol CompoWay/F, or Modbus SSR failure alarm 0.1 to 49.9 A (in units of 0.1 A)
setting range *2 Minimum detection OFF time: 100 ms *4
Baud rate* 9600, 19200, 38400, or 57600 bps
Transmission code ASCII *1 For heater burnout alarms, the heater current will be measured
Data bit length* 7 or 8 bits when the control output is ON, and the output will turn ON if the
heater current is lower than the set value (i.e., heater burnout
Stop bit length* 1 or 2 bits
detection current value).
Vertical parity (none, even, odd) *2 For SSR failure alarms, the heater current will be measured when
Error detection Block check character (BCC) with
CompoWay/F or CRC-16 Modbus the control output is OFF, and the output will turn ON if the heater
current is higher than the set value (i.e., SSR failure detection
Flow control None current value).
Interface RS-485 *3 The value is 30 ms for a control period of 0.1 s or 0.2 s.
Retry function None *4 The value is 35 ms for a control period of 0.1 s or 0.2 s.
Communications buffer 217 bytes
Communications 0 to 99 ms
Electrical Life Expectancy Curve for
response wait time Default: 20 ms
Relays (Reference Values)
* The baud rate, data bit length, stop bit length, and vertical parity can
Life ( 104 operations)

500
be individually set using the Communications Setting Level.
300

Communications Functions
100
You can use the memory in the PLC to read and
write E5@C-T parameters, start and reset opera- 50
tion, etc. The E5@C-T automatically performs
communications with PLCs. No communications 30
programming is required.
Number of connected Temperature Controllers:
Programless 10
communications*1 32 max.
Applicable PLCs
5
OMRON PLCs E5CC-T
CS Series, CJ Series, or 3 250 VAC, 30 VDC
(resistive load)
CP Series cos = 1
Mitsubishi Electric PLCs
MELSEC Q Series, L Series 1
0 1 2 3 4 5 6
Switching current (A)

59
E5CC-T
External Connections
E5CC-T
Control output 1
Relay output
250 VAC, 3 A
E5CC T 3 5M
(1) (2) (3) (4) (5) (6)
(resistive load)
Voltage output Terminal type
(for driving SSR)
12 VDC, 21 mA Auxiliary outputs
Control output 2 The E5CC-T is set for a K-type thermocouple (input
Linear current output Relay output
Voltage output type = 5) by default. An input error (s.err) will occur
0 to 20 mA DC Models with 3 auxiliary outputs:
4 to 20 mA DC (for driving SSR) if the input type setting does not agree with the
250 VAC: 2 A
Load: 500 max. 12 VDC, 21 mA (resistive load) temperature sensor. Check the input type.

(1) Control outputs 1, 2


RX QX CX QQ CQ
Models with Models with 1 Models with 1 Models with 2 Models with 2 Outputs:
1 Relay Voltage Output Linear Current Voltage Outputs Linear Current Output
Output (for Driving SSR) Output (for Driving SSR) and Voltage (for Driving SSR)
(2) Auxiliary Outputs
OUT1 OUT1 OUT1 OUT1 OUT1
1 1 +Q 1 + C 1 +Q 1 + C Auxiliary outputs 1, 2, and 3
R
2 2 2 2 OUT2 2 - OUT2
+Q 7
3 3 3 3 3 + Q Auxiliary output 3
8
Auxiliary output 2
9
Auxiliary output 1
1 13 7 10
2 14 8
(5) Sensor (Temperature/Analog) Input 3 15 9
(3) Input Power Supply
4 16 10
TC Pt I V 100 to 240 VAC 24 VAC/DC
A 5 17 11
4 4 + 4 4
6 18 12
11 11
5 B
5
mA
5 5
B V 12 12
+ 6 6 6
+
6
(no polarity)

(6) Options
001 003 004 005 006
Event inputs 1 and 2, Communications Communications (RS-485) Event inputs 1 to 4 Event inputs 1 and 2, and
and CT1 (RS-485), CT1, and CT2 and event inputs 3 and 4 transfer output
B(+) B(+) 13
- 13 13 13 13
+ RS-485 RS-485
14 14 14 + 14 + 14
EV1+ A() A() EV1+ EV1+
EV2 15 15 15 EV2
15 EV2
15
16 16 16 16 16 +
CT1
17
CT1
COM 17 + 17 + 17 17 +V Transfer output
CT2 EV3 + EV3+ I
18 18 EV4 18 18 18
EV4

Note: 1. The application of the terminals depends on the model.


2. Do not wire the terminals that are shown with a gray background.
3. When complying with EMC standards, the cable that connects the sensor must be 30 m or less.
If the cable length exceeds 30 m, compliance with EMC standards will not be possible.
4. Connect M3 crimped terminals.

Isolation/Insulation Block Diagrams


Models with 3 Auxiliary Outputs

Sensor input and CT inputs

Communications and event inputs

Power Voltage output (for driving SSR),


supply linear current output, and transfer output

Relay output

Auxiliary outputs 1, 2, 3

: Reinforced insulation

: Functional isolation

Note: Auxiliary outputs 1 to 3 are not insulated.

60
E5CC-T
Nomenclature
E5CC-T Front panel
Temperature unit

Operation indicators No. 1 display


PV or specified monitor/setting parameter
Top View of E5CC-T
No. 2 display
Press O Key once to go to SP or specified monitor/parameter value
Program Setting Level.
Top-panel Setup Tool port
Press O Key for at least 3
seconds to go to Initial Setting
Level. Use the UD Keys to set the
parameter.

Use the M Key to change to another parameter. Press U Key for at least 1 second
when Process value/Set point
Press M and D Keys simultaneously for at parameter are displayed in Program
least 1 second to switch between run and reset SP Mode to go to Display Segment
status. Selection parameter in Program
Setting Level.

Use S Key to change the digit (default setting).

Dimensions (Unit: mm)

Controllers
E5CC-T
Panel Cutout
Mounted Separately Group Mounted
(64) (48 number of units - 2.5)+1.0
0
4 60
48 48 1 48 48

45+0.6
0
58

60 min. Group mounting does not


allow waterproofing.

45+0.6
0

Waterproof Packing Mounting Adapter


45+0.6
0
(Accessory) (Accessory)

Recommended panel thickness is 1 to 5 mm.


The Setup Tool port is on the top of the Temperature Controller.
It is used to connect the Temperature Controller to the computer Group mounting is not possible in the vertical direction. (Maintain
to use the Setup Tool. the specified mounting space between Controllers.)
The E58-CIFQ2 USB-Serial Conversion Cable is required to To mount the Controller so that it is waterproof, insert the
make the connection. waterproof packing onto the Controller.
Refer to the instructions that are provided with the USB-Serial
Conversion Cable for the connection procedure. When two or more Controllers are mounted, make sure that the
surrounding temperature does not exceed the allowable operating
Note: Do not leave the USB-Serial Conversion Cable temperature specified in the specifications.
connected when you use the Temperature Controller. To attach the USB-Serial Conversion Cable to the control panel,
use a panel thickness of 1 to 2.5 mm.

61
E5CC-T
Accessories (Order Separately)
USB-Serial Conversion Cable
E58-CIFQ2 (2110)
250 263 1510

LED (RD)

USB connector
(type A plug)
LED (PWR) Serial connector

LED (SD)

Terminal Covers 48 Terminal Covers


E53-COV17 E53-COV23 (Three Covers provided.)
2 3.8
48.8

10

Terminal Cover
(E53-COV23)
22 44.8

9.1

Waterproof Packing The Waterproof Packing is provided with the Temperature Controller.
Y92S-P8 (for DIN 48 48) Order the Waterproof Packing separately if it becomes lost or damaged.
The Waterproof Packing can be used to achieve an IP66 degree of protection.
(Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the
operating environment. Therefore, periodic replacement is recommended to ensure the level of
waterproofing specified in IP66. The time for periodic replacement depends on the operating
environment. Be sure to confirm this point at your site.
Consider three years as a rough standard.)
The Waterproof Packing does not need to be attached if a waterproof structure is not required.

62
E5CC-T

Current Transformers
E54-CT1 Thru-current (Io) vs. Output Voltage (Eo)
21
2.8
15 (Reference Values)
5.8 dia.
E54-CT1
7.5
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 4002
25 3
Winding resistance: 182
10.5
100V

Output voltage (Eo) V (r.m.s.)


Frequency: 50 Hz
40
10 Distortion
Two, 3.5 dia. factor
1k
10%
10 1
3%
1%
30 100mV

10 100
E54-CT3
2.36 dia.
30 RL=10
1
12 dia.
9
100V

10
40 40 1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)

Thru-current (Io) vs. Output Voltage (Eo)


Two, M3 (depth: 4) (Reference Values)
15
E54-CT3
Maximum continuous heater current: 120 A (50/60 Hz)
30 (Maximum continuous heater current for an OMRON
Digital Temperature Controller is 50 A.)
Number of windings: 4002
E54-CT3 Accessories
Winding resistance: 80.8
Armature Connection Example
100V
Output voltage (Eo) V (r.m.s.)

Frequency: 50 Hz
Armature Distortion
Approx. 3 dia. Plug
10 factor
1k
10%
Lead 500 3%
1 1%

100mV
18
100
50
Plug 10
RL=10

1
Approx. 6 dia.

100V
(22)
10
1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)

63
E5CC-T

Adapter
Y92F-45 Note: 1. Use this Adapter when the Front Panel has already been prepared for the E5B@.
2. Only black is available.
3. You cannot use the E58-CIFQ2 USB-Serial Conversion Cable if you use the Y92F-45 Adapter. To use the USB-Serial
Conversion Cable to make the settings, do so before you mount the Temperature Controller in the panel.
Fixture (Accessory)
4.7 76
69.6 to 77.6
72 72

67 67 87

Mounted to E5CC-T Panel (1 to 8 mm) Mounting Adapter


Y92F-30
72 72 (Accessory)

48 48

2.2 4.7
62.8
To back of the E5CC-T

DIN Track Mounting Adapter


Y92F-52 Note: This Adapter cannot be used together with the Terminal Cover.
Remove the Terminal Cover to use the Adapter.

This Adapter is used to mount the


E5CC-T to a DIN Track.
61
If you use the Adapter, there is no
need for a plate to mount in the
panel or to drill mounting holes in
3.5 the panel.
50 38

Mounted to E5CC-T

48

80.5

64
E5CC-T

Watertight Cover Mounting Adapter


Y92A-48N Y92F-49
21.9 14
The Mounting Adapter is provided with the
(2)
Temperature Controller.
Order this Adapter separately if it becomes
lost or damaged.

87.7 69
79.2

12

67.6

Protective Cover Protective Cover


Y92A-48D Note: This Protective Cover cannot be used Y92A-48H
if the Waterproof Packing is installed. This Protective Cover is hard type.
Please use it for the mis-operation
This Protective Cover is soft type.
prevention etc.
It is able to operate the controller with using
this cover.

65
Programmable Temperature Controller (Digital Controller)

E5EC-T/E5AC-T (48 96 mm/96 96 mm)

Programmable Controllers Join the E5C Series!


Program up to 256 segments can handle a
wide variety of applications.
Set up to 8 Programs (Patterns) with 32 Segments (Steps) Each
A white LCD PV display with a height of approx. 18 mm for the E5EC-
T and 25 mm for the E5AC-T improves visibility.
Tool ports are provided both on the top panel and the front panel. Set
up the Controller without wiring the power supply by connecting to the
computer with a Communications Conversion Cable (sold
separately). Setup is easy with the CX-Thermo (sold separately).
High-speed sampling at 50 ms. 48 96 mm 96 96 mm
Models are available with up to 4 auxiliary outputs, up to 6 event E5EC-T E5AC-T
inputs, and a transfer output to cover a wide range of applications.
Short body with depth of only 60 mm. Refer to your OMRON website for the most recent
information on applicable safety standards.
Easy connections to a PLC with programless communications. Use
component communications to link Temperature Controllers to each
other. Refer to Safety Precautions on page 90.
The new position-proportional control models allow you to control
valves as well. (The position-proportional control models are E5@C-T is scheduled to be released in January, 2014.
scheduled to be released in May, 2014.)

Main I/O Functions


Sensor Input
E5EC-T E5AC-T
Universal input
Thermocouple
Three-level Display
Pt
Simultaneous display of the PV, SP, 4-digit
Analog current/voltage
Program No., Segment No., etc. displays
Indication Accuracy
Thermocouple input: 0.3% of PV Control Output 1
Pt input: 0.2% of PV Relay output
Analog input: 0.2% of FS Voltage output (for driving SSR)
Sampling Period Linear current output
50 ms

Control Output 2
Event Inputs
Voltage output (for driving SSR)
None Relay output
2 Linear current output
PF (shift) Key
4
Setup Tool port on front panel
6
Temperature status display Auxiliary Outputs
Operating and editting the program 4
Serial Communications Independent heating and
None cooling PID control
Transfer Output
RS-485 Parameter mask setting
Display brightness setting None
1

This datasheet is provided as a guideline for selecting products.


Be sure to refer to the following manuals for application precautions and other information required for operation before attempting
to use the product.
E5@C-T Digital Temperature Controllers Programmable Type Users Manual (Cat. No. H185)
E5@C-T Digital Temperature Controllers Programmable Type Communications Manual (Cat. No. H186)

66
E5EC-T/E5AC-T
Model Number Legend and Standard Models
Model Number Legend
Models with Screw Terminals
E5EC-T@@ 4 @ 5 M -@@@ (Example: E5EC-TRX4A5M-000)

A BC D E F
E5AC-T@@ 4 @ 5 M -@@@ (Example: E5AC-TRX4A5M-000)

A BC D E F

A B C D E F
Model No. of auxil- Power Meaning
Control outputs Terminal Input
iary out- supply Options
1 and 2 type type
puts voltage
E5EC-T 48 96 mm Programmable Type
E5AC-T 96 96 mm Programmable Type
Control output 1 Control output 2
RX Relay output None
Voltage output
QX None
(for driving SSR)
*2 CX Linear current output None
Voltage output Voltage output
QQ
(for driving SSR) (for driving SSR)
Voltage output
QR Relay output
(for driving SSR)
RR Relay output Relay output
*2 CC Linear current output Linear current output
Voltage output
*2 CQ Linear current output
(for driving SSR)
Position-proportional relay out- Position-proportional re-
*3 PR
put lay output
4 (auxiliary outputs 1 and 2 with same common and
4
auxiliary outputs 3 and 4 with same common)
A 100 to 240 VAC
D 24 VAC/DC
5 Screw terminals (with cover)
Control outputs 1 and 2 M Universal input
For RX,
QX, QQ, For CX or
For PR HB alarm and Event
QR, RR, or CC Communications Transfer output
HS alarm inputs
CQ
Selectable Selectable Selectable 000 --- --- --- ---
Option
selection Selectable Selectable 004 --- RS-485 2 ---
conditions Selectable 005 --- --- 4 ---
*1 Selectable 008 1 RS-485 2 ---
Selectable 010 1 --- 4 ---
Selectable 019 1 --- 6 Provided.
Selectable 021 --- --- 6 Provided.
Selectable Selectable 022 --- RS-485 4 Provided.
*1. The options that can be selected depend on the type of control output.
*2. The linear current output cannot be used as a transfer output.
*3. Models with Position-proportional Control are scheduled for release in May 2014.

Heating and Cooling Control


Using Heating and Cooling Control
A Control Output Assignment
If there is no control output 2, an auxiliary output is used as the cooling control output.
If there is a control output 2, the two control outputs are used for heating and cooling.
(It does not matter which output is used for heating and which output is used for cooling.)
B Control
If PID control is used, you can set PID control separately for heating and cooling.
This allows you to handle control systems with different heating and cooling response characteristics.

67
E5EC-T/E5AC-T

Optional Products (Order Separately)


USB-Serial Conversion Cable Current Transformers (CTs)
Model Hole diameter Model
E58-CIFQ2 5.8 mm E54-CT1
12.0 mm E54-CT3
Communications Conversion Cable
Model CX-Thermo Support Software
E58-CIFQ2-E Model
Note: Always use this product together with the E58-CIFQ2. EST2-2C-MV4
This Cable is used to connect to the front-panel Setup Tool Note: CX-Thermo version 4.61 or higher is required for the E5EC-T/
port. E5AC-T.
For the system requirements for the CX-Thermo, refer to
Terminal Covers information on the EST2-2C-MV4 on the OMRON website
(www.ia.omron.com).
Model
E53-COV24
Note: The Terminal Covers E53-COV24 are provided with the Digital
Temperature Controller.

Waterproof Packing
Applicable Controller Model
E5EC-T Y92S-P9
E5AC-T Y92S-P10
Note: This Waterproof Packing is provided with the Digital
Temperature Controller.

Waterproof Cover
Applicable Controller Model
E5EC-T Y92A-49N
E5AC-T Y92A-96N

Front Port Cover


Model
Y92S-P7
Note: This Front Port Cover is provided with the Digital Temperature
Controller.

Mounting Adapter
Model
Y92F-51
Note: This Mounting Adapter is provided with the Digital Temperature
Controller.

68
E5EC-T/E5AC-T
Specifications
Ratings
A in model number: 100 to 240 VAC, 50/60 Hz
Power supply voltage
D in model number: 24 VAC, 50/60 Hz; 24 VDC
Operating voltage range 85% to 110% of rated supply voltage
E5EC-T 8.7 VA max. at 100 to 240 VAC, and 5.5 VA max. at 24 VAC or 3.2 W max. at 24 VDC
Power consumption
E5AC-T 9.0 VA max. at 100 to 240 VAC, and 5.6 VA max. at 24 VAC or 3.4 W max. at 24 VDC
Temperature input
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, or PL II
Platinum resistance thermometer: Pt100 or JPt100
Sensor input Infrared temperature sensor (ES1B): 10 to 70C, 60 to 120C, 115 to 165C, or 140 to 260C
Analog input
Current input: 4 to 20 mA or 0 to 20 mA
Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V
Current input: 150 max., Voltage input: 1 M min.
Input impedance
(Use a 1:1 connection when connecting the ES2-HB/THB.)
Control method 2-PID control (with auto-tuning) or ON/OFF control
SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations,
Relay output
minimum applicable load: 5 V, 10 mA (reference value)
Control
Voltage output Output voltage: 12 VDC 20% (PNP), max. load current: 40 mA, with short-circuit protection circuit
output
(for driving SSR) (The maximum load current is 21 mA for models with two control outputs.)
Linear current output 4 to 20 mA DC/0 to 20 mA DC, load: 500 max., resolution: approx. 10,000
Number of outputs 4
Auxiliary
output SPST-NO. relay outputs, 250 VAC, Models with 4 outputs: 2 A (resistive load),
Output specifications
Electrical life: 100,000 operations, Minimum applicable load: 10 mA at 5 V (reference value)
Number of inputs 2, 4 or 6 (depends on model)
Contact input: ON: 1 k max., OFF: 100 k min.
Event input External contact input
Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.
specifications
Current flow: Approx. 7 mA per contact
Number of outputs 1 (only on models with a transfer output)
Transfer
output Current output: 4 to 20 mA DC, Load: 500 max., Resolution: Approx. 10,000
Output specifications
Linear voltage output: 1 to 5 VDC, load: 1 k min., Resolution: Approx. 10,000
Potentiometer input 100 to 10 k
Setting method Digital setting using front panel keys
11-segment digital display and individual indicators
Character height: E5EC-T: PV: 18.0 mm, SV: 11.0 mm, MV: 7.8 mm
E5AC-T: PV: 25.0 mm, SV: 15.0 mm, MV: 9.5 mm
Indication method
Three displays. Contents: PV, SP, program No. and segment No., remaining segment time, or MV
(valve opening)
Numbers of digits: 4 digits
Bank switching None
Manual output, heating/cooling control, loop burnout alarm, other alarm functions, heater burnout (HB)
alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital filter, robust tun-
Other functions
ing, PV input shift, protection functions, extraction of square root, MV change rate limit, logic opera-
tions, temperature status display, moving average of input value, and display brightness setting
-10 to 55C (with no condensation or icing),
Ambient operating temperature
for 3-year warranty: -10 to 50C (with no condensation or icing)
Ambient operating humidity 25% to 85%
Storage temperature -25 to 65C (with no condensation or icing)
Altitude 2,000 m max.
Recommended fuse T2A, 250 VAC, time-lag, low-breaking capacity
Installation environment Installation Category II, Pollution Degree 2 (IEC 61010-1 compliant)

69
E5EC-T/E5AC-T

Input Ranges
Thermocouple/Platinum Resistance Thermometer (Universal inputs)
Sensor Platinum resistance Infrared temperature
Thermocouple
type thermometer sensor
Sensor
10 to 60 to 115 to 140 to
specifica- Pt100 JPt100 K J T E L U N R S B W PLII 70C 120C 165C 260C
tion
2300
2300
1800
1800
1700 1700
1700
1600
1500
Temperature range (C)

1400
1300 1300 1300
1300
1200
1100
1000
850 850 850
900
800
700
600
600
500.0 500.0 500.0
500
400.0 400 400.0 400 400.0
400
260
300
120 165
200
100.0 100.0 90
100
100
0
0.0 0.0 0 0 0 0 0 0 0 0
-100
-20.0 -100 -20.0 -100
-200
-200 -199.9 199.9 -200 -200 -199.9 -200 -200 -199.9 -200
Set value 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Shaded settings are the default settings.

The applicable standards for the input types are as follows:


K, J, T, E, N, R, S, B: JIS C 1602-1995, IEC 60584-1 JPt100: JIS C 1604-1989, JIS C 1606-1989
L: Fe-CuNi, DIN 43710-1985 Pt100: JIS C 1604-1997, IEC 60751
U: Cu-CuNi, DIN 43710-1985 PL II: According to Platinel II electromotive force charts from BASF (previously Engelhard)
W: W5Re/W26Re, ASTM E988-1990

Analog input
Input type Current Voltage
Input
4 to 20 mA 0 to 20 mA 1 to 5 V 0 to 5 V 0 to 10 V
specification
Usable in the following ranges by scaling:
Setting range -1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99 or -1.999 to 9.999
Set value 25 26 27 28 29

70
E5EC-T/E5AC-T

Alarm Types
Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (see note.)
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
To use alarm 1, set the output assignment to alarm 1.

Alarm output operation


Set Alarm type Description of function
value When alarm value X When alarm value X
is positive is negative
0 Alarm function OFF Output OFF No alarm
Set the upward deviation in the set point for the alarm upper
L H limit (H) and the lower deviation in the set point for the alarm
ON
1 Upper- and lower-limit *1 OFF PV
*2
SP lower limit (L). The alarm is ON when the PV is outside this
deviation range.
X X Set the upward deviation in the set point by setting the alarm
2 ON ON
Upper-limit OFF PV OFF PV
value (X). The alarm is ON when the PV is higher than the
(default) SP SP
SP by the deviation or more.
X X Set the downward deviation in the set point by setting the
ON ON
3 Lower-limit OFF PV OFF PV
alarm value (X). The alarm is ON when the PV is lower than
SP SP
the SP by the deviation or more.
Set the upward deviation in the set point for the alarm upper
Upper- and lower-limit L H limit (H) and the lower deviation in the set point for the alarm
ON
4 OFF PV
*3
range *1 SP lower limit (L). The alarm is ON when the PV is inside this de-
viation range.
Upper- and lower-limit L H A standby sequence is added to the upper- and lower-limit
ON
5 *4
with standby sequence *1 *5OFF SP
PV alarm (1). *6
X X
Upper-limit with standby ON ON
6 OFF PV OFF PV A standby sequence is added to the upper-limit alarm (2). *6
sequence SP SP

X X
Lower-limit with standby ON ON
7 OFF PV OFF PV A standby sequence is added to the lower-limit alarm (3). *6
sequence SP SP

X X
Absolute-value upper-lim- ON ON The alarm will turn ON if the process value is larger than the
8 OFF PV OFF PV
it 0 0 alarm value (X) regardless of the set point.
X X
ON ON The alarm will turn ON if the process value is smaller than the
9 Absolute-value lower-limit OFF PV OFF PV
0 0 alarm value (X) regardless of the set point.
X X
Absolute-value upper-lim- ON ON A standby sequence is added to the absolute-value upper-
10 OFF PV OFF PV
it with standby sequence 0 0 limit alarm (8). *6
X X
Absolute-value lower-limit ON ON A standby sequence is added to the absolute-value lower-
11 OFF PV OFF PV
with standby sequence 0 0 limit alarm (9). *6
12 LBA (alarm 1 type only) - *7
13 PV change rate alarm - *8
X X
SP absolute-value ON ON This alarm type turns ON the alarm when the set point (SP)
14 OFF SP OFF SP
upper-limit alarm 0 0 is higher than the alarm value (X).
X X
SP absolute-value ON ON This alarm type turns ON the alarm when the set point (SP)
15 OFF SP OFF SP
lower-limit alarm 0 0 is lower than the alarm value (X).
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
16 Heating/Cooling
upper-limit alarm *9 Heating/Cooling variable (MV) is higher than the alarm value (X).
Control (Heating MV) Control (Heating MV)
X
ON
OFF
0
MV Always ON
Standard Control Standard Control
X X
ON ON
OFF MV OFF MV
0 0
MV absolute-value This alarm type turns ON the alarm when the manipulated
17 Heating/Cooling Heating/Cooling
lower-limit alarm *9 variable (MV) is lower than the alarm value (X).
Control (Cooling MV) Control (Cooling MV)
X
ON
OFF
0
MV Always ON

71
E5EC-T/E5AC-T

*1 With set values 1, 4 and 5, the upper and lower limit values can be set *4 Set value: 5, Upper- and lower-limit with standby sequence
independently for each alarm type, and are expressed as L and H. For Upper- and Lower-Limit Alarm Described Above *2
*2 Set value: 1, Upper- and lower-limit alarm
Case 1 and 2
Case 1 Case 2 Case 3 (Always ON)
Always OFF when the upper-limit and lower-limit hysteresis overlaps.
H<0, L<0
L H SP SP L H H SP L Case 3: Always OFF
H<0, L>0 *5. Set value: 5, Upper- and lower-limit with standby sequence
H<0, L>0 H>0, L<0
H L SP |H| |L| Always OFF when the upper-limit and lower-limit hysteresis overlaps.
|H| < |L| |H| > |L|
*6 Refer to the E5@C-T Digital Temperature Controllers Programmable Type
H>0, L<0
User's Manual (Cat. No. H185) for information on the operation of the
SP H L |H| |L|
standby sequence.
*3 Set value: 4, Upper- and lower-limit range *7 Refer to the E5@C-T Digital Temperature Controllers Programmable Type
Case 1 Case 2 Case 3 (Always OFF) User's Manual (Cat. No. H185) for information on the loop burnout alarm
H<0, L<0 (LBA). This setting cannot be used with a position-proportional model.
L H SP SP L H H SP L *8 Refer to the E5@C-T Digital Temperature Controllers Programmable Type
H<0, L>0 H>0, L<0 H<0, L>0 User's Manual (Cat. No. H185) for information on the PV change rate
|H| < |L| |H| > |L| H L SP |H| |L| alarm.
*9 When heating/cooling control is performed, the MV absolute upper limit
H>0, L<0
alarm functions only for the heating operation and the MV absolute lower
SP H L |H| |L|
limit alarm functions only for the cooling operation.

72
E5EC-T/E5AC-T

Characteristics
Thermocouple: (0.3% of indication value or 1C, whichever is greater) 1 digit max. *1
Indication accuracy Platinum resistance thermometer: (0.2% of indication value or 0.8C, whichever is greater) 1 digit
(at the ambient temperature of Analog input: 0.2% FS 1 digit max.
23C) CT input: 5% FS 1 digit max.
Potentiometer input: 5% FS 1 digit max.
Transfer output accuracy 0.3% FS max.
Thermocouple input (R, S, B, W, PL II): (1% of indication value or 10C, whichever is greater) 1 digit
Influence of temperature *2
max.
Other thermocouple input: (1% of indication value or 4C, whichever is greater) 1 digit max. *3
Platinum resistance thermometer: (1% of indication value or 2C, whichever is greater) 1 digit max.
Influence of voltage *2 Analog input: 1%FS 1 digit max.
CT input: 5% FS 1 digit max.
Input sampling period 50ms
Temperature input: 0.1 to 999.9C or F (in units of 0.1C orF)
Hysteresis
Analog input: 0.01% to 99.99% FS (in units of 0.01% FS)
Temperature input: 0.1 to 999.9C or F (in units of 0.1C or F)
Proportional band (P)
Analog input: 0.1 to 999.9% FS (in units of 0.1% FS)
Standard, heating/cooling, or Position-proportional (Close): 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in
Integral time (I) units of 0.1 s)
Position-proportional (Floating): 1 to 9999 s (in units of 1 s), 0.1 to 999.9 s (in units of 0.1 s)*4
Derivative time (D) 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Temperature input: 0.1 to 999.9C or F (in units of 0.1C or F)
Proportional band (P) for cooling
Analog input: 0.1 to 999.9% FS (in units of 0.1% FS)
Integral time (I) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Derivative time (D) for cooling 0 to 9999 s (in units of 1 s), 0.0 to 999.9 s (in units of 0.1 s) *4
Control period 0.1, 0.2, 0.5, 1 to 99 s (in units of 1 s)
Manual reset value 0.0 to 100.0% (in units of 0.1%)
Alarm setting range -1999 to 9999 (decimal point position depends on input type)
Influence of signal source resis- Thermocouple: 0.1C/ max. (100 max.)
tance Platinum resistance thermometer: 0.1C/ max. (10 max.)
Insulation resistance 20 M min. (at 500 VDC)
Dielectric strength 3,000 VAC, 50/60 Hz for 1 min between terminals of different charge
Malfunction 10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions
Vibration
Resistance 10 to 55 Hz, 20 m/s2 for 2 hrs each in X, Y, and Z directions
Malfunction 100 m/s2, 3 times each in X, Y, and Z directions
Shock
Resistance 300 m/s2, 3 times each in X, Y, and Z directions
E5EC-T Controller: Approx. 210 g, Adapter: Approx. 4 g 2
Weight
E5AC-T Controller: Approx. 250 g, Adapter: Approx. 4 g 2
Degree of protection Front panel: IP66, Rear case: IP20, Terminals: IP00
Memory protection Non-volatile memory (number of writes: 1,000,000 times)
Setup Tool CX-Thermo version 4.61 or higher
E5EC-T/E5AC-T top panel: An E58-CIFQ2 USB-Serial Conversion Cable is used to connect to a USB
port on the computer.*5
Setup Tool port
E5EC-T/E5AC-T front panel: An E58-CIFQ2 USB-Serial Conversion Cable and E58-CIFQ2-E Conver-
sion Cable are used together to connect to a USB port on the computer.*5
Approved standards UL 61010-1, Korean Radio Waves Act (Act 10564)
Standards
Conformed standards EN 61010-1 (IEC 61010-1): Pollution Degree 2, overvoltage category II
EMI EN61326
Radiated Interference Electromagnetic Field Strength: EN 55011 Group 1, class A
Noise Terminal Voltage: EN 55011 Group 1, class A
EMS: EN 61326
ESD Immunity: EN 61000-4-2
EMC
Electromagnetic Field Immunity: EN 61000-4-3
Burst Noise Immunity: EN 61000-4-4
Conducted Disturbance Immunity: EN 61000-4-6
Surge Immunity: EN 61000-4-5
Voltage Dip/Interrupting Immunity: EN 61000-4-11
*1 The indication accuracy of K thermocouples in the -200 to 1300C range, T and N thermocouples at a temperature of -100C max., and U and L thermocouples at
any temperatures is 2C 1 digit max. The indication accuracy of the B thermocouple at a temperature of 400C max.
is not specified. The indication accuracy of B thermocouples at a temperature of 400 to 800C is 3C max. The indication accuracy of the R and S thermocouples
at a temperature of 200C max. is 3C 1 digit max. The indication accuracy of W thermocouples is (0.3% of PV or 3C, whichever is greater) 1 digit max. The
indication accuracy of PL II thermocouples is (0.3% of PV or 2C, whichever is greater) 1 digit max.
*2 Ambient temperature: -10C to 23C to 55C, Voltage range: -15% to 10% of rated voltage
*3 K thermocouple at -100C max.: 10C max.
*4 The unit is determined by the setting of the Integral/Derivative Time Unit parameter.
*5 External communications (RS-485) and USB-serial conversion cable communications can be used at the same time.

73
E5EC-T/E5AC-T

Program Control
Number of programs (patterns) 8
Number of segments (steps) 32
Time setting (Segment set with set point and time.)
Segment setting method
Slope setting (Segment set with segment type, set point, slope, and time.)
0 h 0 min to 99 h 59 min
Segment times
0 min 0 s to 99 min 59 s
Alarm setting Set separately for each program.
Reset operation Select either stopping control or fixed SP operation.
Startup operation Select continuing, resetting, manual operation, or run mode.
Number of sets 8
PID sets
Setting method Set separately for each program (automatic PID group selection also supported).
Alarm SP function Select from ramp SP and target SP.
Segment operation Advance, segment jump, hold, and wait
Program status control
Program operation Program repetitions and program links
Wait method Waiting at segment ends
Wait operation
Wait width setting Same wait width setting for all programs
Number of outputs 2
Number of ON/OFF
Time signals 1 each per output
Operations
Setting method Set separately for each program.
Program status output Program end output (pulse width can be set), run output, stage output
PV start Select from segment 1 set point, slope-priority PV start
Program startup operation 0 h 0 min to 99 h 59 min
Standby
0 day 0 h to 99 day 23h
Operation end operation Select from resetting, continuing control at final set point, and fixed SP control.
Program SP shift Same program SP shift for all programs

74
E5EC-T/E5AC-T

USB-Serial Conversion Cable When Digital Temperature Controllers are con-


nected, set points and RUN/STOP commands
Applicable OS Windows XP, Vista, or 7 can be sent from the Digital Temperature Control-
Component ler that is set as the master to the Digital Temper-
Applicable software CX-Thermo version 4.61 or higher Communications ature Controllers that are set as slaves.
Applicable models E5@C-T Series, E5@C Series, and E5CB Series Slope and offsets can be set for the set point.
Number of connected Digital Temperature Con-
USB interface standard Conforms to USB Specification 2.0. trollers: 32 max. (including master)
DTE speed 38400 bps When Digital Temperature Controllers are con-
Computer: USB (type A plug) nected, the parameters can be copied from the
Connector Copying*1 Digital Temperature Controller that is set as the
Digital Temperature Controller:
specifications master to the Digital Temperature Controllers that
Special serial connector
are set as slaves.
Power supply Bus power (Supplied from USB host controller.)*
Power supply voltage 5 VDC
MELSEC is a registered trademark of Mitsubishi Electric Corporation.
*1 Both the programless communications and the component
Current consumption 450 mA max.
communications support the copying.
4.70.2 VDC
Output voltage (Supplied from USB-Serial Conversion Cable to
the Digital Temperature Controller.) Current Transformer (Order Separately)
250 mA max. Ratings
Output current (Supplied from USB-Serial Conversion Cable to
the Digital Temperature Controller.) Dielectric strength 1,000 VAC for 1 min
Ambient operating Vibration resistance 50 Hz, 98 m/s2
0 to 55C (with no condensation or icing)
temperature
E54-CT1: Approx. 11.5 g,
Ambient operating
10% to 80% Weight
humidity E54-CT3: Approx. 50 g
Storage temperature -20 to 60C (with no condensation or icing) Accessories Armatures (2)
Storage humidity 10% to 80% (E54-CT3 only) Plugs (2)
Altitude 2,000 m max.
Weight Approx. 120 g Heater Burnout Alarms and SSR Failure
Windows is a registered trademark of Microsoft Corporation in the Alarms
United States and or other countries.
CT input (for heater Models with detection for singlephase
* Use a high-power port for the USB port. current detection) heaters: One input
Note: A driver must be installed on the computer. Refer to the
Instruction Manual included with the Cable for the installation Maximum heater
50 A AC
procedure. current
Input current
5% FS 1 digit max.
Communications Specifications indication accuracy
Heater burnout
Transmission line 0.1 to 49.9 A (in units of 0.1 A)
connection method
RS-485: Multidrop alarm setting range
Minimum detection ON time: 100 ms *3
*1
Communications RS-485 (two-wire, half duplex)
Synchronization SSR failure alarm 0.1 to 49.9 A (in units of 0.1 A)
Start-stop synchronization setting range *2 Minimum detection OFF time: 100 ms *4
method
Protocol CompoWay/F, or Modbus *1 For heater burnout alarms, the heater current will be measured
Baud rate* 9600, 19200, 38400, or 57600 bps when the control output is ON, and the output will turn ON if the
Transmission code ASCII heater current is lower than the set value (i.e., heater burnout
Data bit length* 7 or 8 bits detection current value).
*2 For SSR failure alarms, the heater current will be measured when
Stop bit length* 1 or 2 bits the control output is OFF, and the output will turn ON if the heater
Vertical parity (none, even, odd) current is higher than the set value (i.e., SSR failure detection
Error detection Block check character (BCC) with current value).
CompoWay/F or CRC-16 Modbus *3 The value is 30 ms for a control period of 0.1 s or 0.2 s.
Flow control None *4 The value is 35 ms for a control period of 0.1 s or 0.2 s.
Interface RS-485
Retry function None Electrical Life Expectancy Curve for
Communications buffer 217 bytes
Communications 0 to 99 ms Relays (Reference Values)
response wait time Default: 20 ms
Life ( 104 operations)

500
* The baud rate, data bit length, stop bit length, and vertical parity can 300
be individually set using the Communications Setting Level.
E5EC-T/E5AC-T
Communications Functions 100 250 VAC, 30 VDC
(resistive load)
50 cos = 1
You can use the memory in the PLC to read and
write E5@C-T parameters, start and reset opera- 30
tion, etc. The E5@C-T automatically performs
communications with PLCs. No communications
programming is required. 10
Number of connected Temperature Controllers:
Programless 5
communications*1 32 max.
Applicable PLCs 3
OMRON PLCs
CS Series, CJ Series, or
CP Series 1
Mitsubishi Electric PLCs 0 1 2 3 4 5 6
MELSEC Q Series, L Series Switching current (A)

75
E5EC-T/E5AC-T
External Connections
E5EC-T/E5AC-T
E5EC T 4 5M E5AC T 4 5M
(1) (2) (3) (4) (5) (6) (1) (2) (3) (4) (5) (6)

Terminal type Terminal type

Control output 1 Control output 2 Auxiliary outputs


Relay output Relay output Relay output
250 VAC, 5A (resistive load) 250 VAC, 5 A Models with 4 auxiliary
Voltage output (for driving SSR) (resistive load) outputs:
12 VDC, 40 mA Voltage output 250 VAC, 2 A
(for driving SSR) (resistive load)
21 mA if there are two control outputs
Linear current output 12 VDC, 21 mA (6) Options
0 to 20 mA DC Linear current output 004 005 008 010
4 to 20 mA DC 0 to 20 mA DC Communications Four event inputs Communications, two Four event inputs
4 to 20 mA DC and two event inputs event inputs, and one CT and one CT
Load: 500 max. Load: 500 max.
B(+) - B(+) -
13 13 13 13
RS-485 + RS-485 +
(1)Control Outputs 14 14 14 14
A(-) EV3 + A(-) EV3 +
15 15 15 15
- EV4 - - EV4 -
RX QX 16 16 16 16
Models with Models with 1 + + + +
17 17 17 17
1 Relay Output Voltage Output EV1+ EV1 + EV1+ EV1 +
18 18 18 18
(for Driving SSR) EV2 EV2 EV2 EV2
19 19 19 19
3 OUT1 3 OUT1 CT1 CT1
R +Q 20 20 20 20
4 4
(3) Input Power Supply 21 21 21 21
5 5 100 to 240 VAC 24 VAC/DC
6 6 019
1 1
Six event inputs, one CT, and
CX QQ QR 2 2 transfer output
-
Models with 1 Models with 2 Voltage Models with Voltage Output (for (no polarity) 13
Linear Current Outputs (for Driving SSR) Driving SSR) and Relay Output +
14
Output EV3+
15
OUT1 - EV4 -
3 OUT1 3 3 OUT1 16
+ C +Q +Q 1 25 13 28
+
4 4 4 2 26 14
+
29 17
EV5+ EV1+
5 5 OUT2 5 OUT2 3 27 15 30 18
+Q EV6 EV2
R 4 28 16 + 31 19
6 6 6 + CT1
Transfer V 32 20
5 29 17 output I
RR/PR CC CQ 21
6 30 18 - 33
Models with 2 Models with 2 Models with 2 Output:
Relay Outputs Linear Current Outputs Linear Current Output 7 31 19
and Voltage (for Driving SSR) 8 32 20
OUT1 OUT1 9 33 21
3 3 + C 3 + OUT1 022
R 10 34 22 021
4 - C Communications, four event inputs,
4 4 Six event inputs and
11 35 23 and transfer output
5 transfer output
5 OUT2 5 OUT2
+ C + OUT2 12 36 24 - B(+)
R 6 - Q 13 13
6 6 + RS-485
14 14
EV3+ A(-)
15 15
(2) Auxiliary Outputs - EV4 - - -
28 16 28 16
(5) Sensor (Temperature/Analog) Input Potentiometer + + + +
Auxiliary outputs 1 to 4 29 17 29 17
TC Pt I V input EV5 + EV1+ EV5 + EV1 +
7 A 30 18 30 18
Auxiliary output 4 22 22 + 22 22 O
19 EV6 EV2 EV6 EV2
8 B + 31 19 + 31 19
Auxiliary output 3 mA 20
23 23 23 23 +
9 B V
W Transfer V + 32 20
Transfer V
32 20
21 output I output I
10 + 24 24 24
+
24 C
- 33 21 - 33 21
Auxiliary output 2
11
Auxiliary output 1
12 The E5@C-T is set for a K-type thermocouple (input type = 5) by
default. An input error (s.err) will not occur if the input type setting * The position-proportional control models (E5EC-TPR@@@M-@@@)
does not agree with the temperature sensor. Check the input type. will be released in May 2014.

Note: 1. The application of the terminals depends on the model.


2. Do not wire the terminals that are shown with a gray background.
3. When complying with EMC standards, the cable that connects the sensor must be 30 m or less. If the cable length exceeds 30 m, compliance with
EMC standards will not be possible.
4. Connect M3 crimped terminals.

Isolation/Insulation Block Diagrams


Models with 4 Auxiliary Outputs

Sensor input, CT input, potentiometer input, and remote SP input

Communications and event inputs


Voltage output (for driving SSR),
Power linear current output, and transfer output
Supply
Relay output

Auxiliary outputs 1, 2

Auxiliary outputs 3, 4

: Reinforced insulation

: Functional isolation

Note: Auxiliary outputs 1 to 2 and 3 to 4 are not insulated.

76
E5EC-T/E5AC-T
Nomenclature
E5EC-T Front panel

Top View of E5EC-T


Temperature unit No. 1 display

PV or specified monitor/parameter
Operation indicators

No. 2 display
Top-panel
SP or specified monitor/parameter value Setup
Tool port
No. 3 display
Use S Key to change the Program No., segment No.,
digit (default setting). remaining segment time, or MV
(valve opening).
Use the U D Keys to set
Front-panel Setup Tool port the parameter.

Press U Key for at least 1 second when


Process value/Set point parameter are
displayed in Program SP Mode to go to
Display Segment Selection parameter in
Program Setting Level.

Press O Key once to go to Program Setting Level.


Use the M Key to change to another parameter.
Press O Key for at least 3 seconds to go to Initial Setting Level.
Press M and D Keys simultaneously for at
least 1 second to switch between run and
reset status.

E5AC-T

Front Panel

Top View of E5AC-T


Temperature unit
No. 1 display
Operation indicators
PV or specified monitor/parameter

No. 2 display
SP or specified monitor/parameter value

Front-panel Setup Tool port No. 3 display


Program No. and segment No.,
remaining segment time, or MV
(valve opening).
Top-panel
Press the U or D Key Setup
Press the O Key once to go to the to set the parameter. Tool port
Program Setting Level.
Press U Key for at least 1 second when
Process value/Set point parameter are
Press the O Key for at least 3 displayed in Program SP Mode to go to
seconds to go to the Initial Setting Display Segment Selection parameter in
Level. Program Setting Level.

Press the M Key to switch to another parameter.


Press the S Key to change the digit (default setting).

Press M and D Keys simultaneously for at least 1


second to change between run and reset status.

77
E5EC-T/E5AC-T
Dimensions (Unit: mm)

Controllers
E5EC-T (64)
4 60
48 1 44

The Setup Tool ports are on the front and top


of the Digital Temperature Controller.
It is used to connect the Temperature Con-
troller to the computer to use the Setup Tool.
The E58-CIFQ2 USB-Serial Conversion
Cable is required to make the connection.
96 91 Refer to the instructions that are provided
110
with the USB-Serial Conversion Cable for the
connection procedure.
Note: Do not leave the USB-Serial
Conversion Cable connected when
you use the Temperature Controller.

Waterproof
Packing (Accessory) Mounting Adapter
(Accessory)
Mounted Separately Group Mounted *
(48 number of units 2.5)+1.0
0
45+0.6
* Selections for Control Outputs 1 and 2: QQ, QR, RR, CC, PR, or CQ
0
If you also specify 019, 021, 022 for the option selection and use
group mounting, the ambient temperature must be 45C or less.
If the ambient temperature is 55C, maintain the following mounting
spaces between Controllers.
92+0.8
0

60 min.
45-0.6
0

Group mounting does not


120 min.
allow waterproofing.

92+0.8
0

92-0.8
0

120 min.

Recommended panel thickness is 1 to 8 mm.


Group mounting is not possible in the vertical direction. (Maintain the
specified mounting space between Controllers.)
To mount the Controller so that it is waterproof, insert the waterproof
packing onto the Controller.
When two or more Controllers are mounted, make sure that the
surrounding temperature does not exceed the allowable operating
temperature specified in the specifications.

78
E5EC-T/E5AC-T

E5AC-T (64)
60
96 x 96 4
1 91 x 91

110

Waterproof
Packing (Accessory) Mounting Adapter
(Accessory)

The Setup Tool ports are on the front and top of the Digital Temperature Controller.
It is used to connect the Temperature Controller to the computer to use the Setup Tool.
The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection.
Refer to the instructions that are provided with the USB-Serial Conversion Cable for the connection procedure.
Note: Do not leave the USB-Serial Conversion Cable connected when you use the Temperature Controller.

Mounted Separately Group Mounted *


(96 number of units 3.5)+1.0
0
92+0.8
Recommended panel thickness is 1 to 8 mm.
0
Group mounting is not possible in the vertical direction. (Maintain the
specified mounting space between Controllers.)
To mount the Controller so that it is waterproof, insert the waterproof
packing onto the Controller.
92+0.8
0 When two or more Controllers are mounted, make sure that the
surrounding temperature does not exceed the allowable operating
temperature specified in the specifications.

120 min. Group mounting does not


allow waterproofing.

92+0.8
0

Accessories (Order Separately)


USB-Serial Conversion Cable
E58-CIFQ2 (2110)
250 263 1510

LED (RD)

USB connector
(type A plug)
LED (PWR) Serial connector

LED (SD)

Conversion Cable
E58-CIFQ2-E
Conversion Cable Connecting to the E58-CIFQ2 USB-Serial Conversion Cable
(2110)
(1510) 250 263 1510

E58-CIFQ2 (Order Separately) Conversion Cable


Note: Always use this product together with the E58-CIFQ2.

79
E5EC-T/E5AC-T

Terminal Covers Waterproof Packing


E53-COV24 (Three Covers provided.) Y92S-P9 (for DIN 48 96)
2 3.8
The Waterproof Packing is provided with the Temperature
Controller.
10 The degree of protection when the Waterproof Packing is used
is IP66.
Also, keep the Port Cover on the front-panel Setup Tool port
of the E5EC-T/E5AC-T securely closed.
To maintain an IP66 degree of protection, the Waterproof
Packing and the Port Cover for the front-panel Setup Tool port
91
must be periodically replaced because they may deteriorate,
shrink, or harden depending on the operating environment.
The replacement period will vary with the operating
environment.
Y92S-P10 (for DIN 96 96) Check the required period in the actual application.
Use 3 years or sooner as a guideline.
If a waterproof structure is not required, then the Waterproof
Packing does not need to be installed.

Setup Tool Port Cover for top panel Mounting Adapter


Y92S-P7 Y92F-51 (for DIN 48 96)

One pair is provided with the


Order this Port Cover
Controller.
separately if the Port Cover on
Order this Adapter
the front-panel Setup Tool port
separately if it becomes lost
is lost or damaged. The
or damaged.
Waterproof Packing must be
periodically replaced because
it may deteriorate, shrink, or
harden depending on the
operating environment.

80
E5EC-T/E5AC-T

Watertight Cover Watertight Cover


Y92A-49N (48 96) Y92A-96N (96 96)

21.9 21.9
(2) (2)

131.7 131.7

67.6 29.4 115.6 29.4

Current Transformers
E54-CT1 Thru-current (Io) vs. Output Voltage (Eo)
21
2.8
15
(Reference Values)
5.8 dia.
E54-CT1
7.5
Maximum continuous heater current: 50 A (50/60 Hz)
Number of windings: 4002
25 3
Winding resistance: 182
10.5 100V

Output voltage (Eo) V (r.m.s.)


Frequency: 50 Hz

40 10 Distortion
1k factor
Two, 3.5 dia.
10%
1
10 3%
1%
100mV
30

10 100
E54-CT3
2.36 dia. 1 RL=10
30
12 dia.
9 100V

10
1 10 100mA 1 10 100 1,000A
40 40
Thru-current (Io) A (r.m.s.)
Thru-current (Io) vs. Output Voltage (Eo)
(Reference Values)
Two, M3 (depth: 4) E54-CT3
Maximum continuous heater current: 120 A (50/60 Hz)
15
(Maximum continuous heater current for an OMRON Digital
Temperature Controller is 50 A.)
30
Number of windings: 4002
Winding resistance: 80.8
E54-CT3 Accessories 100V
Output voltage (Eo) V (r.m.s.)

Frequency: 50 Hz
Armature Connection Example Distortion

10 factor
Armature 1k
10%
Approx. 3 dia. Plug 500 3%
1 1%
Lead

100mV
100
18 50
10
RL=10
Plug
1

Approx. 6 dia. 100V

(22) 10
1 10 100mA 1 10 100 1,000A
Thru-current (Io) A (r.m.s.)

81
E5@C/E5@C-T
Operation
Setting Levels Diagram
E5C
This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some
parameters are not displayed depending on the protect level setting and the conditions of use.
Control stops when you move from the operation level to the initial setting level.

Press the O + M Keys for Protect Level


at least 1 s
Only when Manual Mode was used Used to set protection
just before power OFF
for operations.
Power ON
Operation in progress

Press the O Key


for at least 1 s or Level changes Press the O + M
the S Key for at automatically. Keys for at least 3 s.*2
least 1 s

Manual Control Press the O Key once.


Adjustment Level
Level Operation Level
Used to change adjustment
Used to set the MV parameters (PID constants,
Used for SP, alarm Press the O Key once.
manually. O Key for at adjustment sensitivity, etc.).
values, and other basic
least 3 s while settings and monitoring.
a-m is
displayed.*2

Press the S Key. Press the S Key.*3


S Key for at least 1 s*1

Press the O Key for Press the O Key


at least 3 s*2 for at least 1 s. Monitor/Setting
Item Level
Used to display
specified monitor
and setting items.

Press O Key once


Initial Setting Level (models with communications only). Communications
Setting Level
Used to set the input type Used to set up
and other basic settings. Press the O Key once. communications.

Release protection and


then enter the password
(169) for the amoV (Move Press the O Key for at least 1 s.
Stopped

to Advanced Setting
Level) parameter.

Advanced Function
Setting Level
Used to set application functions.

Enter the password


(1201) for the Move to
Calibration Level
parameter.

Calibration Level

*1 To use a key procedure to move to Manual Control Level, set the Auto/Manual Select Addition parameter to ON and set the PF Setting
parameter to a-m (Auto/Manual).
*2 The No. 1 display will flash when the keys are pressed for 1 s or longer.
*3 Set the PF Setting parameter to pfdp (monitor/setting items).

82
E5@C/E5@C-T

E5C-T
This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some
parameters are not displayed depending on the protect level setting and the conditions of use.

Press O and M Keys Protect Level


for at least 1 s.
Used to set protection
Starting in manual mode for operations.
Power ON
Press O and M Keys
Level changes
for at least 3 s.*2
automatically.

Press O or Press S Key.*3


S Key for at least 1 s.*1
Manual Control
Level
Operation in progress

Used to set the MV Operation Level Program Setting


Press O Key
manually. for less than 1 s.
Level
Press O Key for at Parameter and
least 3 s while a-m is Used for SPs and other segment settings for
displayed.*2 basic settings and all programs
monitoring.
Press S Key Press O Key
for at least 1 s.*1 for less than 1 s.

Press O
Key for at
least 1 s. Press O Key
for less than 1 s.
Press O Key
PID Setting for less than 1 s. Adjustment Level
Level
Parameters for all PID Adjustment parameters
sets (e.g., PID (e.g., PID constants for
constants) current PID set)

Press S Key.*3

Press O Key for


at least 3 s.*2 Monitor/Setting
Item Level
Used to display
specified monitor and
setting items.

Control stops.

Press O Key for less


than 1 s (only models
Initial Setting Level with communications). Communications
Setting Level
Used to set the input type
Communications settings
and other basic settings.
Stopped

Release protection and then


Press O Key for at
enter the password (169) for
least 1 s.
the amoV (Move to Advanced
Function Setting Level)
parameter.
Advanced Function
Setting Level
Advanced settings

Enter the password


(1201) for the Move to
Calibration Level
parameter.

Calibration Level

*1 Set the PF Setting parameter to a-m (Auto/Manual).


*2 The No. 1 display will flash when the keys are pressed for 1 s or longer.
*3 Set the PF Setting parameter to pfdp (monitor/setting items).

83
E5@C/E5@C-T
Operation
Parameters
E5@C
The following pages describe the parameters set in each level. Pressing the M (Mode) Key at the last parameter in each level returns to the top
parameter in that level. Some parameters may not be displayed depending on the model and other settings.
Press the S Key*2
Power ON
Starting in Manual Mode.
Press the O Key for at least 3 s. Press the S Key*2
Starting in Other than the Auto/Manual Switch display
Manual Control Level Automatic
Press the O
Mode. Initial Setting Level
Press the S Key PID
for at least 1 s. C
25 Key or the S Press the Press the O Key for less than 1 s.
Control
0 only Key for at least O Key for
*1
PV/MV 1 s. *1 at least 1 s.
in-t Input Type
5
Adjustment Press the O Key less than 1 s.
M
Level Operation Level
Press the O Key less than 1 s. in-h Scaling Upper Limit
100
Adjustment Level
Display
Process Value/ M
Displayed only 25 al1h Alarm Value
l.adj once when
entering
0 Set Point 1 Upper Limit
0 1 in-l Scaling Lower Limit

adjustment level.
ins Process Value Input orl MV Change Rate
Limit M M
0
0.0 Shift 0
M
M M M 25 Process Value/
al1l Alarm Value
Decimal Point
0 Set Point 2 0 1
Lower Limit
dp
at AT Execute/Cancel inrt Process Value Slope
db Position 0 For input type of analog
off 1.000 Coefficient Proportional M M
M

Set either of these parameters.


2.0 Auto/Manual Switch
Dead Band
M M a-m PID control only. al-2 Alarm
Temperature Unit
M Added when 0
Value 2 d-u C, F
Communications
cmwt Writing rss Remote SP Input Shift
oc-h Open/Close Press the
auto/manual select
M addition is ON.
c
For input type of
off 0.0 Hysteresis O Key M temperature
0.8 Multi-SP Set M
M M for at m-sp Point Selection al2h Alarm Value
M least 3 s. 0 0 2
Upper Limit sl-h SP Upper Limit
Remote SP Input
spmd SP Mode rsrt Extraction of
sqrp Square M
1300
lsp 1.000
Slope Coefficient Root M
Low-cut Point
0 Alarm Value M Limit the set point
M rsp Remote SP Monitor al2l Lower Limit
M M 0.0 0 2 sl-l SP Lower Limit

ct1 Heater Current 1 p Proportional Band


w1on Work Bit 1
-200
Value Monitor M M

Set either of these parameters.


8.0
0.0 ON Delay
Set Point During M
M sp-m SP Ramp al-3 Alarm
M
Integral Time
M 0 0
Value 3 cntl PID ON/OFF
hb1
Heater Burnout i onof
Detection 1 233 w1of Work Bit 1 M M
0.0 OFF Delay Heater Current 1 Value Alarm Value
M
M M PID settings ct-1 Monitor al3h Upper Limit s-hc Standard or
M 0.0 0 3 Heating/Cooling
ct2 Heater Current 2 d Derivative Time
M
stnd
Value Monitor 40 w2on Work Bit 2 M
0.0 ON Delay Heater Current 2 Value Alarm Value M
M ct-2 Monitor al3l Lower Limit
M M 0.0 0 3 st ST (Self-tuning)
Heater Burnout on For input type of
hb2 Detection 2 c-p Proportional Band
w2of Work Bit 2 M M temperature, standard
0.0 8.0 (Cooling) OFF Delay Alarm Set either of these parameters. M control, or PID
Leakage Current 1
M M lcr1 Monitor al-4 Value 4
ptrn Program Pattern
M 0.0 0
off When assigning PID or
lcr1 Leakage Current 1
c-i Integral Time
M M
0.0
Monitor
233 (Cooling) w3on Work Bit 3
ON Delay M
control output to ON/OFF
output
Leakage Current 2 Alarm Value
M M lcr2 Monitor al4h Upper Limit
M 0.0 0 4
cp Control Period (Heating)
hs1 HS Alarm 1 c-d Derivative Time
M M 20
50.0 40 (Cooling) w3of Work Bit 3
OFF Delay
Set the ON/OFF
output cycle.
M prst Program Start al4l Alarm Value M
M rset
Lower Limit
0 4 Control Period (Cooling)
Leakage Current 2 M c-cp
lcr2 Monitor c-db Dead Band M M 20
0.0 0.0
w4on Work Bit 4
Soak Time Remain
ON Delay
sktr o MV Monitor M
M M 0 0.0
(Heating)
orev Direct/Reverse Operation
HS Alarm 2 Manual Reset Value M
hs2 of-r Clear the offset during M M or-r
50.0 50.0 stabilization of P or PD w4of Work Bit 4
RUN/STOP
control.
OFF Delay r-s c-o MV Monitor
(Cooling)
M
M M run 0.0
M alt1 Alarm 1 Type
sp-0 SP 0
hys Hysteresis (Heating) M M 2
0 1.0 w5on Work Bit 5
ON Delay al-1 Alarm
Value 1 Set either of v-m Valve Opening
Monitor
M
M M Hysteresis settings 0 these Alarm 1
Hysteresis (Cooling) M parameters.
0.0
alh1
sp-1 SP 1 chys M M 0.2 Hysteresis
0 1.0 w5of Work Bit 5
OFF Delay M
M M Press the O and M Keys for Press the O and M Keys Press the O Key
M for at least 1 s.
sp-2 SP 2
soak Soak Time at least 3 s. less than 1 s.
0 1 w6on Work Bit 6
ON Delay Communications
M M Protect Level Setting Level
Wait Band M The time taken to move to the protect level Displayed only for models with
sp-3 SP 3
wt-b can be adjusted by changing the "Move to communications. Changes are * Used with programless communications
0 off w6of Work Bit 6
OFF Delay
protect level time" setting. effective after cycling power or
after a software reset.
M pmov Move to Protect Level:
up 1 Upload
MV at Stop M 0
Displayed only when a Setting 1
sp-4 SP 4 mv-s password is set. Restricts Protocol Setting: Highest
0
0 0.0 w7on Work Bit 7 M moving to protect level. psel Switches between maxu Communications
ON Delay cwf CompoWay/F and 0 M
Unit No.
M M Operation/Adjustment Protect: Modbus.
up13 Upload
M oapt Restricts displaying and M M *3 Setting 13
sp-5 SP 5 mv-e MV at PV Error modifying menus in operation, Communications
0
0 0.0 w7of Work Bit 7
0 adjustment, and manual
u-no Unit No. area Area
M
M
OFF Delay M control levels. 1 0
Download
M Initial Setting/Communications Protect: dn 1
SP Ramp Set Value M icpt This protect level restricts movement to M M 0
Setting 1
sp-6 SP 6 sprt 1 the initial setting, communications setting, Communications First Address
0 off w8on Work Bit 8 and advanced function setting levels. bps Baud Rate adrh M
ON Delay M 9.6
CompoWay/F 0
Upper Word
Download
M M wtpt Setting Change Protect: only dn13
M Protects changes to setups by M M 1000
Setting 13
sp-7 SP 7 sprl SP Ramp Fall Value off operating the front panel keys.
First Address
0 same w8of Work Bit 8 M len Communications
Data Length adrl Lower Word
M
OFF Delay 7 0 Copy
M M pfpt PF Key Protect copy
M off
M M off *3
ol-h MV Upper Limit
Communications sbit Communications
rwat Receive Data
100.0 plcm Monitor
M 2
Stop Bits
1000
Wait Time
SP Slope
M
1234
chgp Changed Parameters Only *3 sps *3
M off M M 1.000
ol-l MV Lower Limit
M prty Communications Communications
M
0.0 unit Node Number
even Parity 0 SP Offset
M pmsk Parameter Mask Enable:
Displayed only when a spos *3
on parameter mask is set. M M 0.0

M sdwt
Send Data Wait M
prlp Password to Move to 20 Time
Protect Level: *1. When the PF Setting parameter is set to A-M.
0 Password setting
M *2. When the PF Setting parameter is set to PFDP.
M *3. Used with component communications.

84
E5@C/E5@C-T

Monitor/Setting Item Level


Monitor/Setting Monitor/Setting Monitor/Setting Monitor/Setting
25 Item Display 1 S Monitor/Setting S Item Display 3
S Item Display 4 S Item Display 5
Item Display 2
0

Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level).

Press the O Key


for at least 1 s.
Advanced Function Setting Level

alt2 Alarm 2 Type


2

M RT
Parameter Initialization Automatic Display SP Tracking
alh2 Alarm 2 init ret Return Time rt sptr
Hysteresis off off off off
0.2
M M M M
M PV Dead Band
alt3 Alarm 3 Type mspu Number
Points
of Multi-SP
brgt Display Brightness
hsu HS Alarm Use p-db
off 3 on 0
2

M M M M M
Alarm 1 Latch Manual MV
alh3 Alarm 3 spru SP Ramp Time Unit a1lt hsl HS Alarm Latch manl Limit Enable
m off off off
0.2 Hysteresis
M M M M
M Direct Setting of
alt4 Alarm 4 Type rest Standby
Reset
Sequence
a2lt Alarm 2 Latch
hsh HS Alarm Hysteresis
pmvd Position Proportional
a off 0.1 off MV
2

M M M M
M Alarm 3 Latch PV Rate of Change
alh4 Alarm 4 sb1n Auxiliary Output 1 a3lt lba LBA Detection Time
pvrp Calculation Period
n-o Open in Alarm off 0 20
Hysteresis
0.2

M M M M
M Alarm 4 Latch LBA Level
o1st Control Output 1 Signal sb2n Auxiliary Output 2 a4lt lbal hctm Heating/Cooling
Tuning Method
n-o Open in Alarm off 8.0 off
4-20

M M M M
M
sb3n Auxiliary Output 3
prlt Move to Protect Level
Time lbab LBA Band
ompw Minimum Output
o2st Control Output 2 Signal Open in Alarm
n-o 3 3.0 1.0 ON/OFF Band
4-20
M M M M
M Auxiliary Output 4
Cold Junction Control Output 1 PF Setting
trst Transfer Output Signal sb4n Open in Alarm cjc Compensation out1 Assignment pf
n-o on Method o shft
4-20 (E5EC/E5AC only)
M M M M
M Alarm 1 ON Delay Control Output 2
hbu HB ON/OFF a1on out2 Assignment pfd1 Monitor/Setting Item 1
tr-t Transfer Output Type on 0 none 1
off
Linear output
M M M M
M Auxiliary Output 1
tr-h Transfer Output hbl Heater Burnout Latch a2on Alarm 2 ON Delay
sub1 Assignment pfd2 Monitor/Setting Item 2
Upper Limit off 0 alm1 0
100.0

M M M M
M Auxiliary Output 2
hbh Heater Burnout a3on Alarm 3 ON Delay sub2 Assignment pfd3 Monitor/Setting Item 3
tr-l Transfer Output
Lower Limit Hysteresis
0.1 0 alm2 0
0.0
M M M M
M
st-b ST Stable Range a4on Alarm 4 ON Delay
sub3 Auxiliary
Assignment
Output 3
pfd4 Monitor/Setting Item 4
ev-1 Event Input
Assignment 1 15.0
0 alm3 0
msp0

M M M M M
alfa a1of
Alarm 1 OFF Delay
sub4 Auxiliary Output 4
pfd5 Monitor/Setting Item 5
ev-2 Event Input
Assignment 2 0.65 0
Assignment
alm4 (E5EC/E5AC only) 0
stop

M M M M
M
ev-3 Event Input tidu Integral/Derivative a2of Alarm 2 OFF Delay alma Integrated Alarm spd1 PV/SP No. 1 Display
Selection
Assignment 3 1 Time Unit 0 49 Assignment 4
none

M M M M M
Alarm 3 OFF Delay Soak Time Unit PV/SP No. 2 Display
Event Input at-g AT Calculated Gain a3of t-u spd2 Selection
ev-4 Assignment 4 0.8 0 m 0
none
M M M M
M Alarm 4 OFF Delay Alarm SP Selection MV Display Selection
ev-5 Event Input at-h AT Hysteresis a4of alsp odsl
Assignment 5 0.8 0 sp-m o
none
(E5EC/E5AC only)
M M M M
M PV Decimal Point
MV at Stop and Error Remote SP Input
ev-6
Event Input lcma Limit Cycle MV mvse Addition rs-t pvdp Display
Assignment 6 20.0 Amplitude off 4-20 on
none (E5EC/E5AC only)
M M M M
M PV Status Display
clfl Close/Floating inf Input Digital Filter amad Auto/Manual Select
Addition rspu Remote SP Enable pvst Function
flot 0.0 off off off

M M M M M
calb Motor Calibration mav Moving Average Count mant Manual Output Method rsph Remote SP
Upper Limit
svst SV Status Display
Function
off off hold 1300 off

M M M M M
MV Display Display Refresh
mot Travel Time o-dp mani Manual MV Initial Value rspl Remote SP
Lower Limit
d.ref Period
30 M
off M0.0 -200 0.25

M M M M M
sqr Extraction of Square lcmt LCT Cooling Output
Minimum ON Time
Root Enable 0.2
off

M Move to Advanced Function M


amov Setting Level: cmov Move
Level
to Calibration
Displayed when initial 0
0
setting/communications
M protect is set to 0. M
Move by setting password (169).

85
E5@C/E5@C-T

E5@C-T
Some parameters may not be displayed depending on the model and other settings.

Starting in manual mode


Monitor/Setting Item Level
PF Monitor/
S
Manual Control Level Power ON 25 Setting Item
0
display 1
PF Monitor/Setting
Item display 2 to 5

* The monitor/setting items to display are set in the Monitor/Setting Item 1 to 5 parameters
25 PV/Manual MV (Advanced Function Setting Level).
50.0
Press S Key.*2 Press S Key.*2
Press O Key for Press O or S
at least 3 s while Key for at least
a-m is displayed. 1 s.*1

Press S
Key for at Program Setting Level
least 1 s.*1
U
Display Program
Selection
Operation Level 6 7
d.prg 45
23
01
Process Value/Set
D 25 Point 1 or Process
Value/Set Point 2 in
25 Process prgt Elapsed
Program Time
Press O M 0 Operation Level
Value/Set Point 1
0 0.00 Key for
M M
Monitor
less than
s-no Number of
Segments Used
Press the U Key
8 Display Segment Selection for at least 1 s in
Program Execution 1 s. Program SP Mode.
25 Process rptm Repetitions Monitor
M END or 0 to Number of segments used 1
Value/Set Point 2
0 0
U
M M

ct1 67
a-m Auto/Manual Switch Heater Current 1 to
2 Value Monitor d.seg U
d.seg 3 45
0.0
end D 0 12 D
M M
pgsg Program No. Monitor/
Segment No. Monitor lcr1 Leakage Current 1
to 2 Value Monitor
For end M For 0 to 7 M
0.00 0.0 rpt Program
M
M
pid PID Set No.
0
Repetitions styp Segment n Format

1 M
ramp
prg Program Number
r-r Run/Reset M M
0 rst
(of the program)
link Program
M M al-1 Alarm Value
1 to 4 end
Link
Destination
sp Segment n SP

0 M 0
hold Hold
o MV Monitor M
(Heating) M
off 0.0 al1h Alarm
ts1s Time Signal 1 to 2
M M 0
Upper Limit
0
Set Segment pr Segment n Slope
1 to 4
0
seg Segment Number
c-o MV Monitor M M
M
0 0.0
(Cooling) al1l Alarm
Lower Limit
on1 Time Signal 1 to 2
ON Time
M 0 1 to 4 0.00 time Segment n Time
M
M 0.00
stbm Remaining
v-m Valve Opening M
0.00
Standby Time
Monitor of1 Time Signal 1 to 2
OFF Time
M
Monitor 0.0 0.00
M M
M

Press O Key for less than 1 s. Adjustment Level Press O Key for less than 1 s.
PID Setting Level
Adjustment Level
l.adj Display
d.pid U Display PID
1234 Displayed only once
p Proportional Band
1 2 Selection
M when entering lcr1 Leakage Current 1 to 2
3 4 Adjustment Level. 0.0 Value Monitor 8.0
5 6 Press O M M
7 8
D Key for less AT Execute/Cancel hs1
than 1 s.
at HS Alarm 1 to 2
i Integral Time
M off 50.0 233
1.p PID 1
Proportional 1.cdb PID 1 Dead M M M
8.0 Band
Band 0.0 cmwt Communications
Writing ins PV Input Shift d Derivative Time
M M off 0.0 40
1.i PID 1 Integral
Time 1.ofr PID 1 Manual M M M
233 Reset Value
s0.0 spmd SP Mode
inrt PV Input Slope c-p Proportional Band (Cooling)
M Coefficient
M psp 1.000 8.0
1.d PID 1
Derivative Time 1.olh PID 1 MV Upper M M M
40 Limit
100.0 fsp Fixed SP
wt-b Wait Band c-i Integral Time (Cooling)
M M 0 off 233
1.c-p PID 1
Proportional
1.oll PID 1 MV Lower M M M
Limit
8.0 0.0
Band (Cooling)
ct1 Heater Current 1 to 2 stb Standby Time c-d Derivative Time (Cooling)
M M Value Monitor
40
0.0 0.00
1.c-i PID 1 Integral 1.aut PID 1 Automatic M M M
Time (Cooling) Selection Range
233 1320 Upper Limit hb1 Heater Burnout
psps Program SP Shift Value c-db Dead Band
Detection 1 to 2
M M 0.0
0 0.0
1.c-d PID 1
Derivative Time
1.lba PID 1 LBA
Detection
M M M
40 (Cooling) 0 Time
M M

86
E5@C/E5@C-T

Press O Key
Protect Level for at least 1 s.

Press O + M Key
for at least 3 s. M Operation/Adjustment PF Key Protect
pmov oapt Protect pfpt
0 0 off
Move to Protect Level M M
Initial Setting/ Parameter Mask Enable
Press O + M Key for at least 3 s. (The key pressing icpt Communications Protect pmsk
time can be changed in the Move to Protect Level 1 on
Time parameter (Advanced Function Setting Level).) M M
Setting Change Protect Password to Move
wtpt prlp to Protect Level
Press O + M Key for at least 1 s. off 0
M M

Initial Setting Level


Press O Key
for at least 3 s. Control Period
in-t Input Type sl-l SP Lower Limit
eset Operation End
Operation
c-cp (Cooling) tr-t Transfer Output
Type
calb Motor Calibration

5 -200 rst 20 off off


M M M M M M
Press O Key Direct/Reverse
Scaling Upper Limit
for at least 1 s. in-h t-u Program Time Unit
pvst PV Start orev Operation tr-h Transfer Output
Upper Limit
mot Travel Time

100 h-m sp or-r 100.0 30


M M M M M M
Scaling Lower Limit
Press O Key in-l t-pr Step Time/Rate of
Rise Programming
tspu All PID AT Upper
Limit SP
alt1 Alarm 1 to 4
Type
tr-l Transfer Output
Lower Limit
vl-c Valve Completely
Closed Position
for at least 3 s. 0 time 0 2 0.0 0
M M M M M M
Decimal Point alh1 Alarm 1 to 4
ev-1 vl-o
dp pru Time Unit of Ramp
Rate
cntl PID ON/OFF
0.2
Hysteresis Event Input
Assignment 1
Valve Completely
Open Position
0 m pid rr-1 9999
M M M M M M

d-u Temperature rtsm Reset Operation s-hc Standard or


Heating/Cooling
o1st Control output
1 to 2 Signal ev-2 Event Input pms Potentiometer
Unit Assignment 2 Specification Setting
c stop stnd 4-20 adv 0
M M M M M
M
Control Period
sl-h SP Upper Limit p-on Startup Operation cp (Heating) trst Transfer Output
Signal
ev-3 Event Input
Assignment 3
sqr Extraction of
Square Root
1300 cont 20 4-20 none to 6 off Enable
M M M M M M

clfl Close/Floating amov Moves to Advanced


Function Setting
flot 0 Level

M M Enter password (169)


to move.

Press O Key for less than 1 s.

Communications Setting Level

Communications
psel Protocol Setting
sdwt Send Data
Wait Time
unit Node Number
cwf 20 0
M M M
of-r Manual Reset Value orl MV Change Rate
Limit u-no Communications
maxu
Highest
Communications up 1 Upload
Unit No.
50.0 0.0 1 0 Unit No. 0
Setting
1 to 23
M M M M M
hys Hysteresis (Heating)
db Position Proportional
bps Communications
area Area
1.0 2.0
Dead Band Baud Rate dn 1 Download
9.6 0 0 Setting
M M M M 1 to 43
M
chys Hysteresis (Cooling)
oc-h Open/Close
adrh
First Address

1.0 0.8
Hysteresis len Communications
Data Length
Upper Word
copy Copy
7 0
M M off
M
M M
M
mv-r MV at Reset
sqrp Extraction of Square
Root Low-cut Point sbit Communications adrl
First Address
Lower Word
0.0 0.0 2
Stop Bits
0
M M M
M
mv-e MV at PV Error
w1on Work Bit 1 to 8 ON
prty Communications
rwat
Receive Data
Wait Time
0.0 Delay Parity
0 even 1000
M M M M
Work Bit 1 to 8 OFF
ol-h MV Upper Limit w1of Delay
100.0 0
Models with communications only: Changes to settings are applied
M
M when the power is cycled or a software reset is performed.
ol-l MV Lower Limit

0.0 plcm Communications


Monitor
M
0 *1 When PF Setting = A-M.
M
*2 When PF Setting = PFDP.

87
E5@C/E5@C-T

Advanced Function Setting Level

Direct Setting of Position


init Parameter Initialization mant Manual Output Method pmvd Proportional MV
off hold off
M M M
PV Rate of Change
pend Program End ON Time mani Manual MV Initial Value pvrp Calculation Period
0.0 0.0 20
M M M
Heating/Cooling Tuning
s-u Standby Time Unit rt RT hctm Method
h-m off 0
M M M

rest Standby Sequence Reset hsu HS Alarm Use ompw Minimum Output ON/OFF
1.0 Band
a on
M M M

sb1n Auxiliary Output 1 to 4 hsl HS Alarm Latch lcmt LCT Cooling Output Min.
0.2 ON Time
n-o Open in Alarm off
M M M

hbu HB ON/OFF hsh HS Alarm Hysteresis pf PF Setting

on 0.1 shft
M M M

hbl Heater Burnout Latch lba LBA Detection Time pfd1 PF Monitor/Setting Item 1

off 0 1
M M M

hbh Heater Burnout Hysteresis lbal LBA Level pfd2 PF Monitor/


Setting Item 2 to 5
0.1 8.0 0
M M M
PV/SP No. 1
alfa lbab LBA Band spd1 Display Selection
0.65 3.0 6
M M M
PV/SP No. 2
tidu Integral/Derivative Time Unit out1 Control Output 1 spd2 Display Selection
1 o Assignment 7
M M M

at-g AT Calculated Gain out2 Control Output 2


Assignment
pvst PV Status Display Function
0.8 none off
M M M

at-h AT Hysteresis
sub1 Auxiliary Output 1 svst SV Status Display Function
0.8 alm1 Assignment
off
M M M

lcma Limit Cycle MV Amplitude


sub2 Auxiliary Output 2 d.ref Display Refresh Period
20.0 alm2 Assignment 0.25
M M M

inf Input Digital Filter sub3 Auxiliary Output 3 burn Burnout Method
Assignment
0.0 alm3 up
M M M
Auxiliary Output 4
mav Moving Average Count sub4 Assignment pmst Parameter Mask Setting
off alm4 off
M M M

ret Automatic Display


Return Time
alma Integrated Alarm cmov Move to Calibration Level
off 49 Assignment 0
M M M

brgt Display Brightness alsp Alarm SP Selection


3 sp-m
M M

a1lt Alarm 1 to 4 Latch sptr SP Tracking


off off
M M

prlt Move to Protect Level Time pidi PID Set Automatic

3 pv Selection Data

M
M

cjc Cold Junction pidh PID Set Automatic

on Compensation Method 0.50 Selection Hysteresis

M
M

a1on Alarm 1 to 4 ON Delay


p-db PV Dead Band

0 0
M
M
Manual MV Limit Enable
a1of Alarm 1 to 4 OFF Delay
manl
off
0
M
M

88
E5@C/E5@C-T
Error Displays (Troubleshooting)
When an error occurs, the No. 1 display or No. 2 display shows the error code.
Take necessary measure according to the error code, referring the following table.
Display Name Meaning Action Operation
After the error occurs and it is
The input value exceeded the control Check the wiring for input to be sure displayed, the alarm output will
range.* it is wired correctly, not broken, and operate as if the upper limit was
The input type is not set correctly. not shorted. Also check the input exceeded.
The sensor is disconnected or short- type. It will also operate as if transfer
circuited. If there are no problems in the wiring output exceeded the upper limit.
The sensor is not wired correctly. or input type settings, cycle the If an input error is assigned to a
The sensor is not wired. power supply. control output or auxiliary output, the
If the display remains the same, output will turn ON when the input
* Control Range replace the Digital Temperature error occurs.
s.err Input error Temperature resistance
thermometer or thermocouple input:
Controller. The error message will appear in the
If the display is restored to normal, display for the PV.
SP Lower Limit - 20C to SP Upper then the probable cause is external
Limit + 20C noise affecting the control system. Note: 1. The heating and cooling
(SP Lower Limit - 40F to SP Upper Check for external noise. control outputs will turn
Limit + 40F) OFF.
ESIB input: Note: For a temperature resistance 2. When the manual MV, MV
Same as specified input range. thermometer, the input is at stop, MV at reset, or MV
Analog input: considered disconnected if at error is set, the control
Scaling range -5% to 105% the A, B, or B line is broken. output is determined by the
set value.
This is not an error. It Control continues and operation is
is displayed when the normal.
[[[[ Below -1,999 control range is wider
than the display
The value will appear in the display
for the PV.
range and the PV Refer to the E5@C Digital
Display
range exceeds the display - Temperature Controllers Users
range. The PV is Manual (Cat. No. H174) or the
exceeded displayed for the E5@C-T Digital Temperature
range that is given on Controllers Programmable Type
]]]] Above 9,999 the left (the number Users Manual (Cat. No. H185) for
without the decimal information on the
point). controllable range.
First, cycle the power supply.
If the display remains the same, the The control outputs, auxiliary
A/D controller must be repaired. outputs, and transfer outputs turn
There is an error in the internal
e333 converter
error
circuits.
If the display is restored to normal,
then a probable cause can be
OFF. (A current output will be approx.
0 mA and a linear voltage output will
external noise affecting the control be approx. 0V.)
system. Check for external noise.
First, cycle the power supply.
If the display remains the same, the The control outputs, auxiliary
controller must be repaired. outputs, and transfer outputs turn
Memory There is an error in the internal
e111 error memory operation.
If the display is restored to normal,
then a probable cause can be
OFF. (A current output will be approx.
0 mA and a linear voltage output will
external noise affecting the control be approx. 0V.)
system. Check for external noise.
Control continues and operation is
normal.
The error message will appear for the
This error is displayed when the peak following displays.
ffff Overcurrent
current exceeds 55.0 A.
-
Heater Current Value 1 Monitor
Heater Current Value 2 Monitor
Leakage Current Value 1 Monitor
Leakage Current Value 2 Monitor
The No. 1 display for the following
parameter flashes in Operation Level
ct1 or Adjustment Level.
If there is a HB or HS alarm, the No. Heater Current Value 1 Monitor
ct2 HB or HS 1 display will flash in the relevant - Heater Current Value 2 Monitor
alarm
lcr1 setting level. Leakage Current Value 1 Monitor
Leakage Current Value 2 Monitor
lcr2 However, control continues and
operation is normal.
"----" will be displayed for the Valve
Opening Monitor parameter if any of
the following error occurs.
Motor calibration has not been
Potentiometer performed. Close control: The control output is
Input Error OFF or the value that is set for the
---- (Position- The wiring of the potentiometer is Check for the above errors. MV at PV Error parameter is output.
proportional incorrect or broken. Floating control: Operation will be
Models Only) The potentiometer input value is normal.
incorrect (e.g., the input is out of
range or the potentiometer has
failed).

89
E5@C/E5@C-T
Safety Precautions
Be sure to read the precautions for all E5@C/E5@C-T models in the website at:
http://www.ia.omron.com/.
Warning Indications
Minor electric shock or fire may occasionally occur.
Indicates a potentially hazardous
Do not use any cables that are damaged.
situation which, if not avoided, may
CAUTION result in minor or moderate injury or in
property damage. Never disassemble, modify, or repair the product or
Supplementary comments on what to touch any of the internal parts. Minor electric shock,
Precautions for
do or avoid doing, to use the product fire, or malfunction may occasionally occur.
Safe Use safely.
CAUTION - Risk of Fire and Electric Shock
Supplementary comments on what to
Precautions for a. This product is UL listed*1 as Open Type Process
do or avoid doing, to prevent failure to
Control Equipment. It must be mounted in an
Correct Use operate, malfunction or undesirable enclosure that does not allow fire to escape
effect on product performance. externally.
b. More than one disconnect switch may be required to de-
Meaning of Product Safety Symbols energize the equipment before servicing the product.
c. Signal inputs are SELV, limited energy. *2
d. Caution: To reduce the risk of fire or electric shock, do not
Used to warn of the risk of electric shock under interconnect the outputs of different Class 2 circuits. *3
specific conditions.
If the output relays are used past their life expectancy,
contact fusing or burning may occasionally occur.
Used for general prohibitions for which there is no Always consider the application conditions and use
specific symbol. the output relays within their rated load and electrical
life expectancy. The life expectancy of output relays varies
considerably with the output load and switching conditions.
Used to indicate prohibition when there is a risk of
minor injury from electrical shock or other source
Even if you replace only the Main Unit of the E5DC, check
if the product is disassembled.
the condition of the Terminal Unit.
Used for general CAUTION, WARNING, or If corroded terminals are used, contact failure in the
DANGER precautions for which there is no terminals may cause the temperature inside the
specified symbol. (This symbol is also used as the Digital Controller to increase, possibly resulting in fire.
alerting symbol, but shall not be used in this If the terminals are corroded, replace the Terminal Unit as well.
meaning on the product.)
Tighten the terminal screws to the rated torque of
between 0.43 and 0.58 Nm. *4
Used for general mandatory action precautions
Loose screws may occasionally result in fire.
for which there is no specified symbol.

Set the parameters of the product so that they are


CAUTION suitable for the system being controlled. If they are
not suitable, unexpected operation may occasionally
Do not touch the terminals while power is being result in property damage or accidents.
supplied.
Doing so may occasionally result in minor injury due A malfunction in the product may occasionally make
to electric shock. control operations impossible or prevent alarm
outputs, resulting in property damage.
Electric shock may occur. Do not touch any cables or To maintain safety in the event of malfunction of the
connectors with wet hands. product, take appropriate safety measures, such as installing a
monitoring device on a separate line.

Electric shock, fire, or malfunction may occasionally *1. E5CC, E5EC, E5AC, and E5DC Controllers that were shipped through
November 2013 are UL recognized.
occur. Do not allow metal objects, conductors,
*2. An SELV (separated extra-low voltage) system is one with a
cuttings from installation work, or moisture to enter power supply that has double or reinforced insulation between the
the Digital Temperature Controller or the Setup Tool primary and the secondary circuits and has an output voltage of
port or ports. Attach the cover to the front-panel Setup Tool port 30 V r.m.s. max. and 42.4 V peak max. or 60 VDC max.
whenever you are not using it to prevent foreign objects from *3. A class 2 circuit is one tested and certified by UL as having the current and
voltage of the secondary output restricted to specific levels.
entering the port. *4. The specified torque is 0.5 Nm for the E5CC-U.

Do not use the Digital Temperature Controller where


subject to flammable or explosive gas. Otherwise,
minor injury from explosion may occasionally occur.

Not doing so may occasionally result in fire. Do not


allow dirt or other foreign objects to enter the Setup
Tool port or ports, or between the pins on the
connectors on the Setup Tool cable.

90
E5@C/E5@C-T

Precautions for Safe Use


Be sure to observe the following precautions to prevent malfunction product. If power is turned ON to the product before turning ON
or adverse affects on the performance or functionality of the product. power to the load, self-tuning will not be performed properly and
Not doing so may occasionally result in faulty operation. Do not optimum control will not be achieved.
handle the Digital Controller in ways that exceed the ratings. 13.A switch or circuit breaker must be provided close to the product.
1. This product is specifically designed for indoor use only. The switch or circuit breaker must be within easy reach of the
Do not use this product in the following places: operator, and must be marked as a disconnecting means for this
Places directly subject to heat radiated from heating equipment. unit.
14.Use a soft and dry cloth to clean the product carefully. Do not use
Places subject to splashing liquid or oil atmosphere.
organic solvent, such as paint thinner, benzine or alcohol to clean
Places subject to direct sunlight. the product.
Places subject to dust or corrosive gas (in particular, sulfide gas 15.Design the system (e.g., control panel) considering the 2 seconds
and ammonia gas). of delay that the product's output to be set after power ON.
Places subject to intense temperature change. 16.The output may turn OFF when you move to the initial setting level.
Places subject to icing and condensation. Take this into consideration when performing control operations.
Places subject to vibration and large shocks. 17.The number of non-volatile memory write operations is limited.
2. Use and store the product within the rated ambient temperature Therefore, use RAM write mode when frequently overwriting data
and humidity. during communications or other operations.
Gang-mounting two or more Digital Temperature Controllers, or 18.Use suitable tools when taking the Digital Temperature
mounting Digital Temperature Controllers above each other may Temperature Controller apart for disposal. Sharp parts inside the
cause heat to build up inside the Digital Temperature Controllers, Digital Temperature Controller may cause injury.
which will shorten their service life. In such a case, use forced 19.For compliance with Lloyds standards, the E5CC, E5CC-U,
cooling by fans or other means of air ventilation to cool down the E5EC, and E5AC must be installed under the conditions that are
Digital Temperature Controllers. specified in Shipping Standards.
3. To allow heat to escape, do not block the area around the Digital 20.Do not connect cables to both the front Setup Tool port and the
Temperature Controller. top-panel or bottom-panel Setup Tool port at the same time. The
Do not block the ventilation holes on the Digital Temperature Digital Controller may be damaged or may malfunction.
Controller. 21.Do not place heavy object on the Conversion Cable, bend the
4. Be sure to wire properly with correct polarity of terminals. cable past its natural bending radius, or pull on the cable with
5. Use the specified size of crimped terminals (M3, width of 5.8 mm undue force.
or less) to wire the E5CC, E5EC, E5AC, E5DC, or E5@C-T. To 22.Do not disconnect the Communications Conversion Cable or the
connect bare wires to the terminal block of the E5CC, E5EC, USB-Serial Conversion Cable while communications are in
E5AC, E5DC, or E5@C-T, use copper braided or solid wires with progress. Damage or malfunction may occur.
a gage of AWG24 to AWG18 (equal to a cross-sectional area of 23.Do not touch the external power supply terminals or other metal
0.205 to 0.8231 mm2). (The stripping length is 6 to 8 mm.) Up to parts on the Digital Temperature Controller.
two wires of the same size and type, or two crimped terminals can 24.Refer to the E5@C Digital Temperature Controllers Users Manual
be inserted into a single terminal. (Cat. No. H174) for information on the communications distances
Use the specified size of crimped terminals (M3.5, width of 7.2 mm and cables for the E5@C.
or less) to wire the E5CC-U. To connect bare wires to the terminal For details on the E5@C-T, refer to the E5@C-T Digital
block of the E5CC-U, use copper braided or solid wires with a Temperature Controllers Programmable Type Users Manual (Cat.
gage of AWG24 to AWG14 (equal to a cross-sectional area of No. H185).
25.Do not bend the communications cables past their natural bending
0.205 to 2.081 mm2). (The stripping length is 5 to 6 mm.) Up to two
radius. Do not pull on the communications cables.
wires of the same size and type, or two crimped terminals can be
26.Do not turn the power supply to the Digital Temperature Controller
inserted into a single terminal.
ON or OFF while the USB-Serial Conversion Cable is connected.
6. Do not wire the terminals that are not used.
The Digital Temperature Controller may malfunction.
7. Use a commercial power supply for the power supply voltage input
27.Make sure that the indicators on the USB-Serial Conversion Cable
to a Digital Temperature Controller with AC input specifications.
are operating properly. Depending on the application conditions,
Do not use the output from an inverter as the power supply.
deterioration in the connectors and cable may be accelerated, and
Depending on the output characteristics of the inverter,
normal communications may become impossible. Perform
temperature increases in the Digital Temperature Controller may
periodic inspection and replacement.
cause smoke or fire damage even if the inverter has a specified
28.Connectors may be damaged if they are inserted with excessive
output frequency of 50/60 Hz.
force. When connecting a connector, always make sure that it is
8. To avoid inductive noise, keep the wiring for the products terminal
oriented correctly. Do not force the connector if it does not connect
block away from power cables carry high voltages or large
smoothly.
currents. Also, do not wire power lines together with or parallel to
29.Noise may enter on the USB-Serial Conversion Cable, possibly
product wiring. Using shielded cables and using separate conduits
causing equipment malfunctions. Do not leave the USB-Serial
or ducts is recommended.
Conversion Cable connected constantly to the equipment.
Attach a surge suppressor or noise filter to peripheral devices that
30.For the E5DC, when you attach the Main Unit to the Terminal Unit,
generate noise (in particular, motors, transformers, solenoids,
make sure that the hooks on the Main Unit are securely inserted
magnetic coils, or other equipment that have an inductance
into the Terminal Unit.
component).
31.For the E5CC-U, when you attach the Main Unit to the socket,
When a noise filter is used at the power supply, first check the
make sure that the hooks on the socket are securely inserted into
voltage or current, and attach the noise filter as close as possible
the Main Unit.
to the product.
32.Install the DIN Track vertically to the ground.
Allow as much space as possible between the product and
33.For the E5DC, always turn OFF the power supply before
devices that generate powerful high frequencies (high-frequency
connecting the Main Unit to or disconnecting the Main Unit from
welders, high-frequency sewing machines, etc.) or surge.
the Terminal Unit, and never touch nor apply shock to the
9. Use this product within the rated load and power supply.
terminals or electronic components. When connecting or
10.Make sure that the rated voltage is attained within two seconds of
disconnecting the Main Unit, do not allow the electronic
turning ON the power using a switch or relay contact. If the voltage
components to touch the case.
is applied gradually, the power may not be reset or output
malfunctions may occur.
11.Make sure that the Digital Temperature Controller has 30 minutes
or more to warm up after turning ON the power before starting
actual control operations to ensure the correct temperature
display.
12.When executing self-tuning with E5@C, turn ON power to the load
(e.g., heater) at the same time as or before supplying power to the

91
E5@C/E5@C-T

Shipping Standards
The E5CC, E5CC-U, E5EC, and E5AC comply with Lloyd's Operating Precautions
standards. When applying the standards, the following installation 1. When using self-tuning, turn ON power for the load (e.g., heater)
requirements must be met in the application. at the same time as or before supplying power to the Digital
Controller. If power is turned ON for the Digital Controller before
Application Conditions turning ON power for the load, self-tuning will not be performed
Installation Location properly and optimum control will not be achieved.
When starting operation after the Digital Temperature Controller
The E5CC, E5CC-U, E5EC, and E5AC comply with installation
has warmed up, turn OFF the power and then turn it ON again at
category ENV1 and ENV2 of Lloyd's standards. Therefore, they must the same time as turning ON power for the load. (Instead of turning
be installed in a location equipped with air conditioning. They cannot the Digital Temperature Controller OFF and ON again, switching
be used on the bridge or decks, or in a location subject to strong from STOP mode to RUN mode can also be used.)
vibration. 2. Avoid using the Controller in places near a radio, television set, or
wireless installing. These devices can cause radio disturbances
which adversely affect the performance of the Controller.
Precautions for Correct Use
Others
Service Life 1. Do not Connect or disconnect the Conversion Cable connector
1. Use the product within the following temperature and humidity ranges: repeatedly over a short period of time.
Temperature: -10 to 55C (with no icing or condensation) The computer may malfunction.
Humidity: 25% to 85% 2. After connecting the Conversion Cable to the computer, check the
If the product is installed inside a control board, the ambient COM port number before starting communications. The computer
temperature must be kept to under 55C, including the temperature requires time to recognize the cable connection. This delay does
not indicate failure.
around the product.
3. Do not connect the Conversion Cable through a USB hub. Doing
2. The service life of electronic devices like Digital Temperature so may damage the Conversion Cable.
Controllers is determined not only by the number of times the relay is 4. Do not use an extension cable to extend the Conversion Cable
switched but also by the service life of internal electronic components. length when connecting to the computer. Doing so may damage
Component service life is affected by the ambient temperature: the the Conversion Cable.
higher the temperature, the shorter the service life and, the lower
the temperature, the longer the service life. Therefore, the service Mounting
life can be extended by lowering the temperature of the Digital
Temperature Controller. Mounting to a Panel
3. When two or more Digital Temperature Controllers are mounted E5CC/E5CC-T
horizontally close to each other or vertically next to one another,
the internal temperature will increase due to heat radiated by the There are two models of Terminal Covers that you can use with the E5CC/
Digital Temperature Controllers and the service life will decrease. E5CC-T.
In such a case, use forced cooling by fans or other means of air Terminal Cover
Terminal Cover
ventilation to cool down the Digital Temperature Controllers. When (E53-COV17)
(E53-COV23)
(Sold separately) Adapter
providing forced cooling, however, be careful not to cool down the
terminals sections alone to avoid measurement errors.

Measurement Accuracy
1. When extending or connecting the thermocouple lead wire, be sure to
use compensating wires that match the thermocouple types.
2. When extending or connecting the lead wire of the platinum resistance
thermometer, be sure to use wires that have low resistance and keep Water Proof Packing
the resistance of the three lead wires the same. Panel
3. Mount the product so that it is horizontally level.
4. If the measurement accuracy is low, check to see if input shift has E5CC-U
been set correctly. For the Wiring Socket for the E5CC-U, purchase the P2CF-11 or
PG3A-11 separately.
Waterproofing (Not applicable to the E5CC-U/
E5DC.)
The degree of protection is as shown below. Sections without any
specification on their degree of protection or those with IP@0 are not
waterproof.
Front panel: IP66, Rear case: IP20, Terminal section: IP00
When waterproofing is required, insert the Waterproof Packing on the
backside of the front panel. Keep the Port Cover on the front-panel
Setup Tool port of the E5EC/E5AC/E5EC-T/E5AC-T securely closed.
The degree of protection when the Waterproof Packing is used is
1. For waterproof mounting, waterproof packing must be installed on the
IP66. To maintain an IP66 degree of protection, the Waterproof
Controller. Waterproofing is not possible when group mounting several
Packing and the Port Cover for the front-panel Setup Tool port must Controllers. Waterproof packing is not necessary when there is no
be periodically replaced because they may deteriorate, shrink, or need for the waterproofing function.
harden depending on the operating environment. The replacement The E5CC-U cannot be waterproofed even if the Waterproof Packing
period will vary with the operating environment. Check the required is inserted.
period in the actual application. Use 3 years or sooner as a guideline. 2. Insert the E5CC/E5CC-U/E5CC-T into the mounting hole in the
If the Waterproof Packing and Port Cover are not periodically panel.
replaced, waterproof performance may not be maintained. If a 3. Push the adapter from the terminals up to the panel, and
waterproof structure is not required, then the Waterproof Packing temporarily fasten the E5CC.
4. Tighten the two fastening screws on the adapter.
does not need to be installed.
Alternately tighten the two screws little by little to maintain a
balance. Tighten the screws to a torque of 0.29 to 0.39 Nm.

92
E5@C/E5@C-T

E5EC/E5AC/E5EC-T/E5AC-T from the Terminal Unit.


Adapter

Adapter
(1)
Panel

Terminal Cover
(E53-COV24)

(2)
Terminal Cover
(E53-COV24) (1)
Water Proof Packing

1. For waterproof mounting, waterproof packing must be installed on End Plate Installation
the Controller. Waterproofing is not possible when group mounting
Make sure to attach PFP-M End Plates to the ends of the Units.
several Controllers. Waterproof packing is not necessary when
there is no need for the waterproofing function.
2. Insert the E5EC/E5AC/E5EC-T/E5AC-T into the mounting hole in B
the panel.
3. Push the adapter from the terminals up to the panel, and
temporarily fasten the E5EC/E5AC/E5EC-T/E5AC-T.
4. Tighten the two fastening screws on the adapter. A
Alternately tighten the two screws little by little to maintain a
balance. Tighten the screws to a torque of 0.29 to 0.39 Nm.

Mounting to and Removing from DIN Track


E5DC
Mounting a Unit
Pull down the DIN Track hook on the Terminal Unit and catch the
top hook on the DIN Track.
Press the Unit onto the DIN Track until the DIN Track hooks are
locked in place.
Individual Group Mounting
2. Catch the top hook on Mounting
the DIN Track.

Mounting the DIN Track


Attach the DIN Track to the inside of the control panel with screws to
at least three locations.
DIN Track (sold separately)
PFP-50N (50 cm) and PFP-100N (100 cm)

3. Press the Unit onto


the DIN Track.
4. Make sure that the hooks
1. Pull down the hook.
are locked in place.
Removing a Unit
Pull down on the DIN Track Hook with a flat-blade screwdriver and Install the DIN Track vertically to the ground.
lift up the Unit.

Vertical: OK Horizontal: NG

Removing the Main Unit


Press in the two hooks on the Main Unit and remove the Main Unit

93
E5@C/E5@C-T

Mounting to a Panel Attaching the End Cover


E5DC E5DC
Adapter 1. Install the E5DC in a panel.
Panel

Terminal Unit

Main Unit

1. Insert the E5DC into the mounting hole in the panel. (Attach the
Terminal Unit after you insert the Main Unit.)
2. Push the Adapter from the Terminal Unit up to the panel, and
temporarily fasten the E5DC. 2. Peel off the release paper from the double-sided tape on the End
3. Tighten the two fastening screws on the Adapter. Alternately Cover.
tighten the two screws little by little to maintain a balance. Tighten
the screws to a torque of 0.29 to 0.39 Nm.

Mounting the Terminal Cover


E5CC/E5CC-T
Slightly bend the E53-COV23 Terminal Cover to attach it to the
terminal block as shown in the following diagram. The Terminal Cover
Double-sided tape
cannot be attached in the opposite direction. E53-COV17 Terminal
Cover can be also attached.
Make sure that the "UP" mark is facing up, and then attach the E53-
COV17 Terminal Cover to the holes on the top and bottom of the 3. Align the tabs on the End Cover with the depressions on the E5DC
Digital Temperature Controller. and attach the End Cover.

E53-COV17 E53-COV23

Adapter
Terminal Cover
(E53-COV17) Enlarged illustration of
(Sold separately) Terminal Section

E5EC/E5AC/E5EC-T/E5AC-T
Slightly bend the E53-COV24 Terminal Cover to attach it to the
terminal block as shown in the following diagram. The Terminal Cover
cannot be attached in the opposite direction.

Slightly bend the


E53-COV24 Terminal
Cover in the direction
shown by the arrows to
attach it to the terminal block.

Enlarged illustration of the terminal part

94
E5@C/E5@C-T

4. Secure the End Cover so that the double-sided tape is firmly


attached.
5.8 mm max.

5.8 mm max.

For the E5CC-U, use the following types of crimp terminals for
M3.5 screws.

7.2 mm max.

7.2 mm max.

Precautions when Wiring


Separate input leads and power lines in order to prevent external
noise.
Use a shielded, AWG24 to AWG18 (cross-sectional area of 0.205
to 0.8231 mm2) twisted-pair cable. Use a shielded, AWG24 to
AWG14 (cross-sectional area of 0.205 to 2.081 mm2) twisted-pair
cable for the E5CC-U. The stripping length is 6 to 8 mm for the
E5CC, E5EC, E5AC, E5DC, or E5CC-T and 5 to 6 mm for the
E5CC-U.
Use crimp terminals when wiring the terminals.
Use the suitable wiring material and crimp tools for crimp terminals.
Tighten the terminal screws to a torque of 0.43 to 0.58 Nm.
The specified torque is 0.5 Nm for the E5CC-U.
For the E5CC, E5EC, E5AC, E5DC, or E5@C-T, use the following
types of crimp terminals for M3 screws.

Three-year Guarantee
Period of Guarantee Note: Average Operating Temperature
The guarantee period of the Unit is three years starting from the date Refer to the process temperature of the Unit mounted to a
control panel and connected to peripheral devices on condition
the Unit is shipped from the factory.
that the Unit is in stable operation, sensor input type K is
selected for the Unit, the positive and negative thermocouple
Scope of Guarantee input terminals of the Unit are short-circuited, and the ambient
The Unit is guaranteed under the temperature is stable.
following operating conditions. Top
1. Average Operating Temperature Should the Unit malfunction during the guarantee period, OMRON
(see note): 10C to 50C shall repair the Unit or replace any parts of the Unit at the expense of
2. Mounting Method: Standard mounting OMRON.
Bottom

95
MEMO

96
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have
any questions or comments.

Warranties.
(a) Exclusive Warranty. Omrons exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing
by Omron). Omron disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE
PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL
SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products
or otherwise of any intellectual property right. (c) Buyer Remedy. Omrons sole obligation hereunder shall be, at Omrons election,
to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the
non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price
of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other
claims or expenses regarding the Products unless Omrons analysis confirms that the Products were properly handled, stored,
installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by
Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or
unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system
assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in
writing, are not to be construed as an amendment or addition to the above warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.

Limitation on Liability; Etc.


OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.

Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyers application or use of the Product. At Buyers request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyers application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.

Programmable Products.
Omron Companies shall not be responsible for the users programming of a programmable Product, or any consequence
thereof.

Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omrons test conditions, and the user must correlate it
to actual application requirements. Actual performance is subject to the Omrons Warranty and Limitations of Liability.

Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice
to change part numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be
assigned to fix or establish key specifications for your application. Please consult with your Omrons representative at any time to
confirm actual specifications of purchased Product.

Errors and Omissions.


Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
OMRON Corporation Industrial Automation Company Authorized Distributor:
Tokyo, JAPAN
Contact: www.ia.omron.com
Regional Headquarters
OMRON EUROPE B.V. OMRON ELECTRONICS LLC
Wegalaan 67-69-2132 JD Hoofddorp One Commerce Drive Schaumburg,
The Netherlands IL 60173-5302 U.S.A.
Tel: (31)2356-81-300/Fax: (31)2356-81-388 Tel: (1) 847-843-7900/Fax: (1) 847-843-7787

OMRON ASIA PACIFIC PTE. LTD. OMRON (CHINA) CO., LTD. OMRON Corporation 2011-2013 All Rights Reserved.
No. 438A Alexandra Road # 05-05/08 (Lobby 2), Room 2211, Bank of China Tower, In the interest of product improvement,
Alexandra Technopark, 200 Yin Cheng Zhong Road, specifications are subject to change without notice.
Singapore 119967 PuDong New Area, Shanghai, 200120, China CSM_9_2_1213