0% found this document useful (0 votes)
167 views1 page

LPG Gas Press Above 5psi Pipe Sizing

This document provides a table for sizing pipes for propane gas systems with pressures above 5 psi. The table lists the capacity in thousands of BTUs per hour (MBH) that can flow through various pipe sizes from 1/2 inch to 5 inches in diameter for different upstream and downstream pressure combinations. It notes that an inlet upstream pressure above 5 psi is required and provides factors for converting pipe capacity to cubic feet per minute of gas flow and for accounting for additional length from fittings when sizing pipes.

Uploaded by

Sopi Labu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
167 views1 page

LPG Gas Press Above 5psi Pipe Sizing

This document provides a table for sizing pipes for propane gas systems with pressures above 5 psi. The table lists the capacity in thousands of BTUs per hour (MBH) that can flow through various pipe sizes from 1/2 inch to 5 inches in diameter for different upstream and downstream pressure combinations. It notes that an inlet upstream pressure above 5 psi is required and provides factors for converting pipe capacity to cubic feet per minute of gas flow and for accounting for additional length from fittings when sizing pipes.

Uploaded by

Sopi Labu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 1

Propane Gas - Pipe Sizing

Sizing pipes with propane gas - for pressure above 35 kPa (5 psi)

Capacity of 100 ft Steel Pipe Schedule 40 (MBH)


Pressure Pipe Dimension (in)
Upstream Downstream
(psig) (psig) 1/2 3/4 1 1 1/4 1 1/2 2 2 1/2 3 4 5
9.5 606 1265 2385 4896 7335 14126 22514 39800 81180 146870
10 9 875 1830 3550 7083 10612 20439 32576 57590 117460 212500
8.5 590 1239 2330 4785 7170 13810 22011 38910 79367 143590
9 8.1 810 1690 3190 6550 9810 18892 30112 53231 108575 196430
7.6 510 1070 2020 4150 6215 11969 19076 33723 68785 124440
8 7.2 741 1550 2625 6006 8999 17330 27622 48830 99598 180190
6.6 500 1046 1971 4050 6064 11678 18615 32904 67113 121420
7 6.3 975 1410 2658 5460 8178 15748 25100 44370 90500 163730
5.7 419 875 1647 3380 5064 9750 15550 27481 56053 101400
6 5.4 605 1268 2387 4998 7339 14140 22530 39826 81233 146960
4.7 407 850 1603 3290 4930 9490 15130 26748 54560 98710
5 4.5 536 1120 2110 4325 6481 12480 19890 35166 71730 129770
inlet upstream pressure is more than 35 kPa (5 psig)
one MBH is equivalent to 1000 BTU's per hour
fittings factor 1.2 - equivalent pipe length = pipe length + 20%
1 CFM 2.54 MBH