Product Data Sheet: Tesys F Contactor - 3P (3 No) - Ac-3 - 440 V 185 A - Without Coil
Product Data Sheet: Tesys F Contactor - 3P (3 No) - Ac-3 - 440 V 185 A - Without Coil
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range TeSys
Product or component type Contactor
Product name TeSys F
Device short name LC1F
Contactor application Resistive load
Motor control
Complementary
Utilisation category AC-4
AC-3
AC-1
Poles description 3P
Pole contact composition 3 NO
System Voltage <= 1000 V AC 50/60 Hz
<= 460 V DC
[Ie] rated operational current 275 A (<= 104 F (40 C)) at <= 440 V AC AC-1
185 A (<= 131 F (55 C)) at <= 440 V AC AC-3
Motor power kW 90 kW at 380...400 V AC 50/60 Hz AC-3
100 kW at 415 V AC 50/60 Hz AC-3
100 kW at 440 V AC 50/60 Hz AC-3
110 kW at 500 V AC 50/60 Hz AC-3
110 kW at 660690 V AC 50/60 Hz AC-3
100 kW at 1000 V AC 50/60 Hz AC-3
33 kW at 400 V AC 50/60 Hz AC-4
55 kW at 220...240 V AC 50/60 Hz AC-3
[Uimp] rated impulse withstand voltage 8 kV
Overvoltage category III
[Ith] conventional free air thermal 275 A at <= 104 F (40 C)
current
Irms rated making capacity 1850 A AC conforming to IEC 60947-4-1
Aug 30, 2017
1
Rated breaking capacity 1480 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current 1500 A <= 104 F (40 C) 10 s
920 A <= 104 F (40 C) 30 s
740 A <= 104 F (40 C) 1 min
500 A <= 104 F (40 C) 3 min
400 A <= 104 F (40 C) 10 min
Associated fuse rating 200 A aM at <= 440 V
315 A gG at <= 440 V
Average impedance 0.33 mOhm at 50 Hz - Ith 275 A
[Ui] rated insulation voltage 1000 V conforming to IEC 60947-4-1
1500 V conforming to VDE 0110 group C
Power dissipation per pole 12 W AC-3
25 W AC-1
Connections - terminals Power circuit: connector 1 cable(s) 0.23 in (150 mm)
Power circuit: lugs-ring terminals 1 cable(s) 0.23 in (150 mm)
Power circuit: bar 2 x ( 25 x 3 mm)
Power circuit : bolted connection
Tightening torque Power circuit: 159.29 lbf.in (18 N.m)
Mounting support Plate
Mechanical robustness Vibrations contactor closed 5 Gn, 5...300 Hz
Shocks contactor open 7 Gn for 11 ms
Vibrations contactor open 2 Gn, 5...300 Hz
Shocks contactor closed 15 Gn for 11 ms
Height 6.85 in (174 mm)
Width 6.63 in (168.5 mm)
Depth 7.13 in (181 mm)
Product weight 12.02 lb(US) (5.45 kg)
Environment
Standards JIS C8201-4-1
IEC 60947-1
EN 60947-4-1
EN 60947-1
IEC 60947-4-1
Product certifications CB
RINA
DNV
CSA
RMRoS
UL
ABS
LROS (Lloyds register of shipping)
BV
IP degree of protection IP2x front face with shrouds (ordered separately) conforming to IEC 60529
IP2x front face with shrouds (ordered separately) conforming to VDE 0106
Protective treatment TH
Ambient air temperature for operation 23...131 F (-5...55 C)
Ambient air temperature for storage -76...176 F (-60...80 C)
Permissible ambient air temperature -40...158 F (-40...70 C)
around the device
Operating altitude 9842.52 ft (3000 m) without derating in temperature
2
Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant - since 0843 - Schneider Electric declaration of conformity
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product end of life instructions Available
Contractual warranty
Warranty period 18 months