Distech Network Guide PDF
Distech Network Guide PDF
Network Guide
05DI-UGBACNG-12
Copyright Distech Controls Inc.
First printing June 2010. Printed in Canada.
While all efforts have been made to verify the accuracy of information in this manual, Distech
Controls is not responsible for damages or claims arising from the use of this manual.
Persons using this manual are assumed to be trained HVAC professionals and are
responsible for using the correct wiring procedures, correct override methods for equipment
control and maintaining safe working conditions in fail-safe environments. Distech Controls
reserves the right to change, delete or add to the information in this manual at any time
without notice.
Distech Controls and the Distech Controls logo are trademarks of Distech Controls Inc.
LONWORKS is a registered trademark of Echelon Corporation. BACnet is a registered
trademark of ASHRAE. Windows, Windows XP, Windows Vista, and Visual Basic.Net are
registered trademarks of Microsoft Corporation. NiagaraAX is a registered trademark of
Tridium, Inc.
TABLE OF CONTENTS
CHAPTER 1 ........................................................................................................................................... 5
Introduction ........................................................................................................................................ 5
Introduction .................................................................................................................................... 6
About BACnet .............................................................................................................................. 6
About LonWorks .......................................................................................................................... 6
About Subnetworks ..................................................................................................................... 6
About This User Guide .................................................................................................................. 7
Purpose of the User Guide .......................................................................................................... 7
Intended Audience....................................................................................................................... 7
Conventions Used in this Document ........................................................................................... 8
Notes ........................................................................................................................................... 8
Cautions and Warnings ............................................................................................................... 8
Related Documentation ............................................................................................................... 8
Acronyms and Abbreviations Used in this Document ................................................................... 9
CHAPTER 2 ......................................................................................................................................... 10
BACnet MS/TP Communication Bus Fundamentals .................................................................... 10
BACnet MS/TP Data Transmission Essentials............................................................................ 11
Data Bus Devices and Baud Rate ............................................................................................... 13
Data Bus Physical Specifications and Cable Requirements ....................................................... 15
Bus Topology and EOL Terminations.......................................................................................... 16
Data Bus Shield Grounding Requirements ................................................................................. 19
Using Repeaters to Extend the Data Bus .................................................................................... 20
Device Addressing ....................................................................................................................... 23
Inter-Building BACnet Connection ............................................................................................... 30
Power Supply Requirements ....................................................................................................... 31
Typical Device BACnet MS/TP LAN and Power Wiring Diagram ............................................... 35
CHAPTER 3 ......................................................................................................................................... 36
LonWorks Communication Bus Fundamentals ............................................................................ 36
Network Architecture ................................................................................................................... 37
EC-NetAX Network Architecture ................................................................................................. 37
TP/FT-10 Network Topologies..................................................................................................... 38
Bus Topology............................................................................................................................. 38
Free Topology ........................................................................................................................... 38
Network Cables ......................................................................................................................... 40
TP/FT-10 Cable specifications .................................................................................................. 40
Extending the Network ................................................................................................................ 42
Grounding a Network ................................................................................................................... 43
Grounding Shielded Twisted Pair Cable ................................................................................... 43
Building Entrance Protection ..................................................................................................... 43
Power Supply Requirements ....................................................................................................... 44
CHAPTER 4 ......................................................................................................................................... 46
Subnetwork Installation Guidelines ............................................................................................... 46
About the Subnetwork Bus .......................................................................................................... 47
ECx-4XX Subnetwork Bus........................................................................................................... 48
ECx-4XX Subnetwork Bus Physical Specifications and Cable Requirements ......................... 48
ECx-4XX Subnetwork Bus Topology and End-of-Line Terminations ........................................ 48
ECx-4XX Subnetwork Bus Shield Grounding Requirements .................................................... 50
ECx-4XX I/O Extension Module Addressing ............................................................................. 50
Power Supply Requirements ..................................................................................................... 51
EC-Smart-Vue Subnetwork Bus .................................................................................................. 52
Network Guide 3
EC-Smart-Vue Subnetwork Bus Cable Requirements.............................................................. 52
EC-Smart-Vue Subnetwork Bus Topology and End-of-Line Terminations ............................... 54
Commissioning with an EC-Smart-Vue ..................................................................................... 55
Connecting to the LAN through an EC-Smart-Vue ................................................................... 57
CHAPTER 5 ......................................................................................................................................... 60
BACnet Troubleshooting ................................................................................................................ 60
CHAPTER 6 ......................................................................................................................................... 66
LonWorks Troubleshooting ............................................................................................................ 66
CHAPTER 7 ......................................................................................................................................... 70
ECx-400 Series I/O Extension Module Specific Troubleshooting ............................................... 70
CHAPTER 8 ......................................................................................................................................... 71
EC-Smart-Vue Troubleshooting ..................................................................................................... 71
APPENDIX A ....................................................................................................................................... 73
Typical BACnet EIA-485 Data Bus Transmission Example ......................................................... 73
APPENDIX B ....................................................................................................................................... 75
How to Set a DIP Switch .................................................................................................................. 75
APPENDIX C ....................................................................................................................................... 76
Metric Conversions for Wire Gauge ............................................................................................... 76
APPENDIX D ....................................................................................................................................... 77
Documentation Improvement Form ............................................................................................... 77
4 Network Guide
CHAPTER 1
INTRODUCTION
This section provides an overview of the user guide.
In This Chapter
Topic Page
Introduction 6
About This User Guide 7
Acronyms and Abbreviations Used in this Document 9
Network Guide 5
Introduction
Introduction
This document describes best practices, specifications, wiring rules, device termination, and
application information to implement robust and reliable communications networks.
About BACnet
The BACnet ANSI/ASHRAE Standard 135-2008 specifies a number of Local Area
Network (LAN) transport types. Distech Controls controllers use both BACnet IP and
BACnet Master-Slave/Token-Passing (MS/TP) communications bus (based on EIA-485) as
a local network for internetworking of supervisory controllers and field controllers.
About LonWorks
The LONWORKS standard ANSI/CEA-709.1-B specifies a number of Local Area Network
(LAN) transport types. Distech Controls controllers use a twisted pair "free topology"
communications bus operating at 78 kbit/s as a local network for internetworking of
supervisory controllers and field controllers.
LONWORKS is one of several network types of the BACnet ANSI/ASHRAE Standard;
however, no Distech Controls controllers are compatible with this network type except for an
EC-NetAX.
About Subnetworks
Distech Controls controllers also support the following types of subnetworks:
ECx-4XX subnetwork bus that is used to connect ECx-4XX Series I/O Extension
Modules to an ECB-600 or ECL-600 controller.
EC-Smart-Vue Subnetwork bus is used to connect EC-Smart-Vue sensors to any
Distech Controls ECB series controller or ECL series controller.
6 Network Guide
Introduction
For BACnet
This User Guide describes the best practices for installing a BACnet MS/TP LAN
and reviews the specifications, device limits, BACNET MS/TP LAN cable
requirements, best wiring practices, the importance of rigorous grounding practices,
24 volt power supply wiring requirements, BACnet MS/TP bus termination, setting
the MAC address and Device Instance for devices on a BACnet MS/TP LAN, and
finally LAN troubleshooting.
This user guide is intended to provide BACnet LAN information to instruct a user to
install and configure a BACnet MS/TP LAN. However, this guide is not intended to
instruct the user on how configure the devices connected to the LAN, to use network
management tool software, to program a device to share points on the network, or
the procedure to install a given device. For this information, refer to the devices
hardware installation guide and its related programming user guide.
For LONWORKS
This User Guide describes the best practices for installing a LONWORKS LAN and
reviews the specifications, device limits, LAN cable requirements, best wiring
practices, grounding practices, 24 volt power supply wiring requirements,
LONWORKS network termination, and finally LAN troubleshooting.
This user guide is intended to provide LONWORKS LAN information to instruct a user
to install and configure a LONWORKS LAN. However, this guide is not intended to
instruct the user on how configure the devices connected to the LAN, to use network
management tool software, to program a device to share points on the network, or
the procedure to install a given device. For this information, refer to the devices
hardware installation guide and its related programming user guide.
For Subnetworks
This user guide also describes the best practices for installing the subnetwork used
for Distech Controls I/O Extension Modules and EC-Smart-Vue; cable requirements,
best wiring practices, bus termination, and device addressing.
Intended Audience
This user guide is intended for system designers, integrators, electricians, and field
technicians who have experience with control systems, and who want to learn about how to
make a successful BACnet MS/TP LAN installation. It is recommended that anyone installing
and configuring the devices specified in this user guide have prior training in the usage of
these devices.
Network Guide 7
Introduction
Related Documentation
Refer to the Hardware Installation Guide for the devices you are installing.
8 Network Guide
Introduction
Network Guide 9
CHAPTER 2
BACNET MS/TP COMMUNICATION BUS
FUNDAMENTALS
This chapter describes the BACnet MS/TP Communications Bus operating principals.
In This Chapter
Topic Page
BACnet MS/TP Data Transmission Essentials 11
Bus Topology and EOL Terminations 16
Using Repeaters to Extend the Data Bus 20
Data Bus Devices and Baud Rate 13
Data Bus Physical Specifications and Cable Requirements 15
Data Bus Shield Grounding Requirements 19
Device Addressing 23
Inter-Building BACnet Connection 30
Power Supply Requirements 31
Typical Device BACnet MS/TP LAN and Power Wiring 35
Diagram
Network Guide 10
BACnet MS/TP Communication Bus Fundamentals
Network Guide 11
BACnet MS/TP Communication Bus Fundamentals
Table 2-1: Common Identification Labels for BACnet MS/TP Data Bus Polarity
Device Manufacturer Data Bus Connections
Inverting Non-inverting Reference
Distech Controls Controllers NET NET + 24V COM
EC-BOS + S
Thermostat + Ref
Repeater Data Data+ (B)GND
Data1 Data1+
BACnet/IP RT RT+ COM
to MS/TP
Adapter
BACnet/IP + SC
to MS/TP
Router
Common identification labels for B A SC
BACnet MS/TP data bus polarity + G
by other Manufacturers
TxD/RxD TxD+/RxD+ GND
U U+ COM
RT RT+ REF
Sig Sig+
Data Data+
Except for an EC-BOS, never connect the shield of the BACnet MS/TP data bus to
the Reference terminal. See Data Bus Shield Grounding Requirements on page 19
for more information.
When interfacing with BACnet MS/TP devices from other manufacturers, refer to the
documentation for the device to correctly wire the device.
12 Network Guide
BACnet MS/TP Communication Bus Fundamentals
Network Guide 13
BACnet MS/TP Communication Bus Fundamentals
that the maximum number of devices on each separate data bus is not exceeded. See Using
Repeaters to Extend the Data Bus on page 20.
Baud Rate
Most devices will have a range of baud rate settings and possibly an AUTO setting that
detects the baud rate of other devices transmitting on the data bus and adjusts the baud rate
of the device accordingly. Typical baud rates are 9600, 19 200, 38 400, and 76 800. The
baud rate setting determines the rate at which data is sent on the data bus. All devices on
the data bus must be set to the same baud rate. Therefore, the chosen baud rate must be
supported by all devices connected to the data bus.
Distech Controls devices must be power cycled after changing a baud rate setting for it to
take effect.
The recommended baud rate for Distech Controls devices is 38 400.
To set the baud rate, see Setting the BAUD Rate for ECB-Series Controllers (optional) on
page 56.
14 Network Guide
BACnet MS/TP Communication Bus Fundamentals
Network Guide 15
BACnet MS/TP Communication Bus Fundamentals
Typical BACnet Device Typical BACnet Device Typical BACnet Device Typical BACnet Device Typical EC-BOS Device
EOL ENABLED: For the
EOL ON EOL OFF EOL OFF EOL OFF
EC-BOS as a first or last
daisy-chained device:
- OPTIONALLY set the
NET+
NET+
NET+
NET+
NET-
NET-
NET-
NET-
12
0
Electrical
Data Bus: Shielded Twisted Pair Cable System
First and last daisy-chained device: Ground
- EOL Jumpers are ENABLED
OR EOL resistor is installed
All other Devices:
- EOL Jumpers are DISABLED
Figure 2-1: EOL Terminations Must be Enabled at Both the First and Last Device on
the Data Bus
Devices are factory-set with the EOL termination disabled by default.
The BACnet/IP to MS/TP Adapter does not have EOL Termination (and BACnet
MS/TP Data Bus biasing) capabilities to be used at the end of a BACnet MS/TP
data bus. Instead, use the BACnet/IP to MS/TP Router for this application.
When to use EOL Terminations with BACnet MS/TP Thermostats
BACnet MS/TP thermostats support external EOL termination resistors only. When a
BACnet MS/TP thermostat is the first or last daisy-chained device, add a 120 Ohm resistor
across the and + BACnet MS/TP data bus connections.
The BACnet MS/TP data bus must be biased. This bias can only be provided by built-in EOL
termination resistors (ones set with a jumper). If a BACnet MS/TP data bus has a BACnet
MS/TP thermostat at one end of the BACnet MS/TP data bus and an EC-BOS at the other
end, you must set the internal EOL jumper in the EC-BOS so that proper biasing is provided
to the BACnet MS/TP data bus.
16 Network Guide
BACnet MS/TP Communication Bus Fundamentals
Typical Typical Typical Typical EOL ENABLED: Use the Typical EC-BOS Device
BACnet BACnet BACnet BACnet EC-BOS as a first or last
Device Device Device Device daisy-chained device:
No Built-in EOL No Built-in EOL No Built-in EOL No Built-in EOL The internal EOL jumper EOL ON
Jumper Jumper Jumper Jumper
MUST be set to ON to
NET+
NET+
NET+
NET+
provide bias to BACnet
NET-
NET-
NET-
NET-
MS/TP Data Bus AND - + S
add a 120 Ohm resistor
as shown here
12 12
0 0
Electrical
Data Bus: Shielded Twisted Pair Cable System
EOL: Add a 120
Ground
Ohm resistor as
First and last daisy-chained device:
shown here
- EOL Jumpers are ENABLED
at one end, and EOL resistor is
installed at other end.
All other Devices:
- EOL Jumpers are DISABLED.
Figure 2-2: Typical EOL Terminations with BACnet MS/TP Thermostats with Biasing
Provided by the EC-BOS Internal EOL Jumper set to ON
When a BACnet MS/TP data bus has a BACnet MS/TP thermostat at one end of the BACnet
MS/TP data bus and an EC-BOS at the other end without its internal EOL jumper enabled,
fish-tail the BACnet MS/TP data bus back to a controller in which the built-in EOL termination
can be set. This will provide the necessary biasing to the BACnet MS/TP data bus.
NET+
NET+
NET+
NET-
NET-
NET-
NET-
EOL jumper internally
- + S
- AND add a 120 Ohm
resistor as shown here
12
0
Electrical
Data Bus: Shielded Twisted Pair Cable System
Ground
First and last daisy-chained device:
Fish-tail the Data Bus back to a controller - EOL Jumpers are ENABLED
that has a built-in EOL Jumper making it OR EOL resistor is installed
the last device on the Data Bus All other Devices:
- EOL Jumpers are DISABLED
Figure 2-3: Fish-tailing the BACnet MS/TP Data Bus to use a Controller with Built-in
EOL Termination that will Provide Biasing to the BACnet MS/TP Data Bus
Only a Daisy-Chained Data Bus Topology is Acceptable
Use a daisy-chained BACnet MS/TP data bus topology only. No other data bus topology is
allowed.
Network Guide 17
BACnet MS/TP Communication Bus Fundamentals
- Data Bus Management
- Alarm - Data Bus Integration - User Interface
- Trend Log - Device Configuration and - Remote Access
- Schedule programming - Embedded EC-NetAX Pro
- Graphical Interface
EC-NetAX Supervisor Configuration EC-NetAX Pro Web Browser
EC-BOSAX
Maximum of 32 nodes and 1200 meters.
EOL Terminator Maximum is 50 nodes when using
MS/TP Data Bus Segment
Distech Controls devices exclusively
Segment 1
EOL
ON
Figure 2-4: Typical BACnet MS/TP LAN Topology Showing How Devices are Daisy-
Chained Together with One Data Bus Segment
Only linear, daisy-chained devices provide predictable data bus impedances
required for reliable data bus operation.
Only a daisy-chained data bus topology should be specified during the planning
stages of a project and implemented in the installation phase of the project.
A spur is only permitted when it is connected to the bus through a repeater (refer
to Using Repeaters to Extend the Data Bus on page 20).
Star and ring topologies are not supported because signal reflections on the data bus may
not be sufficiently dampened by the standard EOL termination resistors supplied by device
manufacturers, as these resistors may present excessively high or low termination
impedance. These topologies have more complex electrical characteristics that require
advanced analysis to determine the appropriate termination resistances to ensure error-free
data transmission on the data bus.
EC-BOSAX EC-BOSAX
Spur / Backbone
Star Topologies are
Topologies are
Unsupported
Unsupported
18 Network Guide
BACnet MS/TP Communication Bus Fundamentals
Bus Master (Building Controller) Typical BACnet Device Typical BACnet Device Typical BACnet Device Typical BACnet Device
NET+
NET+
NET+
NET+
NET-
NET-
NET-
NET-
The shield of the data bus
must be connected to the S + -
electrical system ground at
one point only usually at
the Building Controller,
when present
Data Bus Shields: Twist Data Bus Shields: Twist Data Bus Shields: Twist Data Bus Shield:
together and Isolate together and Isolate together and Isolate Isolate with
Electrical with electrical tape with electrical tape with electrical tape electrical tape
System
Ground
Figure 2-6: Typical Cable-Shield Grounding Requirements for a BACnet MS/TP Data
Bus Segment with a Building Controller located in the End of the Data Bus
NET+
NET+
NET+
NET-
NET-
NET-
NET-
electrical system ground
at one point only usually S + -
at the Building Controller,
when present
Data Bus Shield: Data Bus Shields: Twist Data Bus Shields: Twist Data Bus Shield:
Isolate with together and Isolate Electrical together and Isolate Isolate with
electrical tape with electrical tape System with electrical tape electrical tape
Ground
Figure 2-7: Typical Cable-Shield Grounding Requirements for a BACnet MS/TP Data
Bus Segment with a Building Controller located in the Middle of the Data Bus
Typical BACnet Device Typical BACnet Device Typical BACnet Device Typical BACnet Device Typical BACnet Device
NET+
NET+
NET+
NET+
NET+
NET-
NET-
NET-
NET-
NET-
Data Bus Shield: Data Bus Shields: Twist Data Bus Shields: Twist Data Bus Shields: Twist Data Bus Shield:
Isolate with together and Isolate together and Isolate together and Isolate Isolate with
electrical tape with electrical tape with electrical tape with electrical tape electrical tape
Figure 2-8: Typical Cable-Shield Grounding Requirements for a BACnet MS/TP Data
Bus Segment without Building Controller
Network Guide 19
BACnet MS/TP Communication Bus Fundamentals
MS/TP Data Bus Segment: MS/TP Data Bus Segment: MS/TP Data Bus Segment:
- 1220 m (4 000 ft) Maximum - 1220 m (4 000 ft) Maximum - 1220 m (4 000 ft) Maximum
EOL Terminators
EOL Terminator
20 Network Guide
BACnet MS/TP Communication Bus Fundamentals
MS/TP Data Bus Segment:
- 1220 m (4 000 ft) Maximum
- 50 Connected Devices Maximum Total
EOL Terminator
EOL
EC-BOSAX ON
NET+
NET+
NET+
NET-
NET-
NET-
NET-
The data bus shield must be connected to the electrical system ground at
< 7.6 m one point only usually at the Building Controller, when present
< 25 ft
Figure 2-11: Repeater Connections when it is the First or Last Device on its
Respective Data Bus Segment
The BACnet MS/TP Data Bus must be biased. This bias can only be provided by built-in
EOL termination resistors (ones set with a jumper). When a repeater is the first or last device
on its respective data bus segment, use the following methods to provide MS/TP Data Bus
biasing and EOL termination as applicable to your situation:
1. On the BACnet MS/TP data bus segment shown in Figure 2-11, bias and EOL
termination is provided by a controllers internal EOL jumper being set to ON. In this
case the connection to the repeater cannot be more than 7.6 meters (25 feet) from this
controller.
2. On the BACnet MS/TP data bus segment shown in Figure 2-11, a 120 EOL
Termination resistor is added to the repeaters terminals. Biasing for this BACnet MS/TP
Network Guide 21
BACnet MS/TP Communication Bus Fundamentals
data bus segment is provided by the internal EOL Jumper being set to ON at the last
controller at the other end of this data bus.
See When to use EOL Terminations on page 16 for more information. Follow shielding and
grounding recommendations: See Data Bus Shield Grounding Requirements on page 19.
22 Network Guide
BACnet MS/TP Communication Bus Fundamentals
Device Addressing
Device addressing allows the coordinated transfer of messages between the intended
devices on the BACnet MS/TP data bus and with devices connected to the internetwork. For
this, each device connected to the BACnet MS/TP data bus is identified by a MAC address,
a Device Instance number, and a Network Number:
The MAC Address uniquely identifies a device on a Network (identified by a Network
Number). Devices on another Network can have the same MAC Address as messages
are not passed at the internetwork level using the MAC Address. The MAC Address also
defines the devices on the data bus that are Masters and Slaves, among other
categories (see Table 2-6). The MAC Address is also used to share data bus bandwidth
between devices through token passing between Master devices.
The Device Instance uniquely identifies a device across the BACnet internetwork. The
Device Instance is any number between 0 and 4 194 303. It is with the Device Instance
that messages are exchanged between BACnet devices. The Device Instance is also
used by routers to forward messages to devices located elsewhere in the internetwork.
Unlike a MAC Address, a Device Instance cannot be reused elsewhere in the BACnet
internetwork (it must be unique).
The Network Number is any number between 1 and 65 534. A network number identifies
a LAN for routing purposes.
Both the MAC Address and the Device Instance must be set for each device and are
essential for proper BACnet LAN operation.
For an example of how MAC address, Device Instance number, and Network Number apply
to a typical BACnet network, see Figure 2-16.
About the MAC Address
The MAC Address is a number from 0 to 255; however we recommend reserving some MAC
Addresses for common commissioning and maintenance tasks. For example, when a
portable adaptor is set to use one of these reserved MAC Addresses, it can be temporarily
connected with certainty to any data bus of any site without conflicting with other devices
already connected to the data bus.
MAC Addresses should be used as shown in the following table.
Network Guide 23
BACnet MS/TP Communication Bus Fundamentals
Table 2-6: Recommended BACnet MS/TP Bus MAC Address Values / Ranges for
BACnet MS/TP Bus Devices
MAC Address Usage Devices
Value / Range
0 Bus Master EC-BOS
(Building Controller) This address is invalid for Distech Controls
ECB devices
1 Temporary Portable adaptor MAC Address for a
commissioning temporary commissioning and maintenance
connection connection
2 Reserved Other
3-127 Master Range Master devices: All Distech Controls
devices are master devices and should be in
this MAC Address range
128-254 Slave Range Slave devices and network sensors
255 Broadcast Do not apply address 255 to any device.
BACnet MS/TP Data Bus Token-Passing Overview
The BACnet MS/TP data bus protocol is a peer-to-peer, multiple-master protocol that shares
data bus bandwidth by passing a token between Master devices on the data bus that
authorizes the device that is holding the token to initiate communications on the data bus.
Once the device has completed its request(s), it closes the communications channel, passes
the token to the next Master device (making it the current Master), and liberates the data
bus.
The token is passed through a short message from device to device on the BACnet MS/TP
data bus in consecutive order starting from the lowest MAC address (MAC Address = 0) to
the next MAC Address.
Gaps or pockets of unassigned device MAC Addresses should be avoided as this reduces
bus performance. Every 50 requests, each master must poll for the next master that may
exist on the Data Bus. It is the timeout for each unassigned MAC Address that slows down
the data bus.
The way MAC Addresses are assigned is not a physical requirement: Devices can be daisy-
chained on the data bus in any physical order regardless of their MAC Address sequence.
The goal is to avoid gaps in the device MAC Address range.
Slave devices cannot accept the token, and therefore can never initiate communications. A
Slave can only communicate on the data bus to respond to a data request addressed to it
from a Master device. Gaps in slave device MAC Addressing have no impact on BACnet
MS/TP data bus performance.
24 Network Guide
BACnet MS/TP Communication Bus Fundamentals
No MAC Address Gaps MAC Address Gaps
MS/TP MS/TP
EOL Terminator Network # 10 EOL Internally Set EOL Terminator Network # 10 EOL Internally Set
EOL EOL
EC-BOSAX ON EC-BOSAX ON
MAC: 0 MAC: 3 MAC: 4 MAC: 5 MAC: 6 MAC: 0 MAC: 3 MAC: 4 MAC: 25 MAC: 26
DI: 10 000 DI: 10 003 DI: 10 004 DI: 10 005 DI: 10 006 DI: 10 000 DI: 10 003 DI: 10 004 DI: 10 025 DI: 10 026
MS/TP
EOL Terminator Network # 10 EOL Internally Set
EOL
EC-BOSAX ON
Figure 2-12: Setting the Max Master on the Bus Master (Building Controller) to the
Highest MAC Address Used on the BACnet MS/TP Data Bus
About Tuning the Max Info Frames Parameter
Once a device has the token, it can make a number of information requests to other devices
on the BACnet intranetwork. The maximum number of requests is limited by the
Max Info Frames parameter. Ordinary BACnet MS/TP devices should have the
Max Info Frames parameter set to between 2 and 4. The Bus Master (Building Controller)
should have the Max Info Frames parameter set to 20.
About Tuning the Max Master Parameter
To prevent the passing of the token to unused MAC Addresses situated after the final Master
device, the Max Master must be set. By default, the Max Master for the Bus Master (Building
Controller) is set to 127 which allows for the theoretical maximum of 127 devices besides the
Bus Master to be connected to the data bus.
In practice, the actual number of devices connected to a data bus is far less, resulting in a
gap between the highest MAC Address of any device connected to the data bus and the
value set for Max Master. This gap unnecessarily slows-down the data bus with Poll for
Master requests.
When commissioning a BACnet MS/TP Data Bus, it is useful to start with the Max Master set
to 127 so as to be able to discover all devices connected to the data bus. Then, once all
devices have been discovered and the MAC Addressing is finalized by eliminating any gaps
in the address range, set the Max Master (maximum MAC Address) in the EC-BOS
(Building Controller) to the highest Master devices MAC Address number to optimize the
efficiency of the data bus.
Network Guide 25
BACnet MS/TP Communication Bus Fundamentals
Setting the Max Master and Max Info Frames
The Max Master and Max Info Frames are parameters used to optimize a BACnet MS/TP
Data Bus. This is set in the Bus Master (EC-BOS Building Controller) for the MS/TP port of
the Bus Master and for each BACnet MS/TP device connected on that port.
A Configure MS/TP Devices tool is available to automate this task. This tool:
Can only be used with a live database during commissioning. If you add more devices to
the data bus, you must run this tool again.
Automatically calculates the value for the Max Master by finding the highest Master
device MAC Address on the connected BACnet MS/TP data bus plus 1.
Sets the Max Master for all master devices including the Bus Master (EC-BOS).
Sets the Max Info Frames for all master devices excluding the Bus Master (EC-BOS).
For the Bus Master (EC-BOS), set the Max Info Frames to 20 in the screen shown in Figure
2-15 as this is a device that will make more requests for service from other devices on the
network. In general, according to the way a device is programmed, the Max Info Frames
may have to be set to a higher value than for other devices. For example, when Roof Top
Unit Controllers are used with VAV controllers that use gfxApplications code, they should
also have their Max Info Frames set to a higher value such as 5, as Roof Top Unit
Controllers poll VAV controllers for information.
Set the Max Master and Max Info Frames as follows.
1. Right-click the Link node in the Nav tree and select Ms/Tp Configuration.
26 Network Guide
BACnet MS/TP Communication Bus Fundamentals
Figure 2-14: Setting the Max Master on the Bus Master (EC-BOS) to the Highest MAC
Address Used on the BACnet MS/TP Data Bus
3. A confirmation message is shown.
4. Set the Max Info Frames to 20 for the Bus Master (EC-BOS) as shown in the screen
below.
Figure 2-15: Setting the Max Info Frames on the Bus Master (EC-BOS)
Default Device Instance Number Numbering System for Distech Controls controllers
By default, controllers from Distech Controls automatically self assign a Device Instance
number generated from the unique MAC Address assigned to the controller during
installation. The Device Instance number is calculated as follows:
Device Instance number = 364 X 1000 + MAC Address
Where 364 is Distech Controls unique BACnet Manufacturer ID.
This Numbering system is sufficient for a BACnet network that has only one Building
Controller. For larger BACnet networks that have more than one Building Controller (to form
a BACnet intranetwork), set the MAC Addresses, Device Instance Numbers and Network
Numbers according to the numbering scheme below.
Adopting a Numbering System for MAC Addresses, Device Instance Numbers, and
Network Numbers
Good network planning requires a well thought-out numbering scheme for device MAC
Addresses, Device Instance Numbers (DI), and Network Numbers. We recommend the
Network Guide 27
BACnet MS/TP Communication Bus Fundamentals
following scheme, as it reuses the MAC Address and Network Number in the Device
Instance number to make it easier for a network administrator to know where a device is
located in the network. This is shown below.
Table 2-7: Recommended Numbering Scheme for MAC Addresses, Instance Numbers,
and Network Numbers
Description Range Example
BACnet/IP Network Number 0 to 65 534 1
Building Controller BACnet/IP Device Instance 10 000 to 10 000
Numbers: Multiples of 10 000 4 190 000 20 000
BACnet MS/TP Network Number: Building Controller 10 to 4190 10
BACnet/IP Device Instance Number/1000 + 0,1,2,3,4 11
(for each LAN) 20
BACnet MS/TP Device Instance Number = 10 000 to 10 007 where
EC-BOS BACnet MS/TP Network Number * 1000 + 4 190 256 MAC = 7
MAC Address
An example of this numbering system is shown below.
Figure 2-16: BACnet MS/TP Numbering System for MAC Addresses, Device Instance
Numbers, and Network Numbers
When discovering devices with an EC-BOS which has the routing option
configured, it will discover all BACnet devices connected to all EC-BOSes. Make
sure to add only the devices connected to the MS/TP port of the specific EC-BOS
being configured. Using this numbering system will greatly help to identify those
devices that should be added to a given EC-BOS.
Setting the MAC Address
The MAC Address on most devices can be set through a DIP switch located on its faceplate,
or though the software interface of a handheld device for example.
An example of how to set the devices MAC Address DIP switch is shown below for a
Distech Controls ECB-203 (and higher) controllers.
28 Network Guide
BACnet MS/TP Communication Bus Fundamentals
ON
Must be set to the
OFF (0) position
Network Guide 29
BACnet MS/TP Communication Bus Fundamentals
Building #1 Building #2
KEY:
DI: Device Instance
EOL: End of Line
MAC: Media Access Control
30 Network Guide
BACnet MS/TP Communication Bus Fundamentals
Power Supply
AC Power BACnet Device
Fuse: 4A Max.
Source
Fast Acting
24 / 120 / 208 / 24V AC/DC
240 / 277 / 347 / 24 VAC
480 VAC, 1 24V COM
Figure 2-19: The 24V COM / C Terminal of all Devices must be Connected to the
Grounded Power Supply Bus
The table below lists Distech Controls recommended power cable.
Network Guide 31
BACnet MS/TP Communication Bus Fundamentals
Table 2-8: Distech Controls Recommended Power Cable
Cable Type Non-Plenum Applications Plenum Applications
AWG (FT4) (FT6)
Number of Part Number O.D. () Part Number O.D. ()
Conductors
18-2 07CBL-W181P-1002 5.0mm 07CBL-W181P-2051 5.0mm
0.20in. 0.20in.
16-2 07CBL-W161P-1031 4.8mm / 07CBL-W161P-2062 4.8mm /
0.19in. 0.19in.
14-2 07CBL-W141P-1081 7.2mm / 07CBL-W141P-2013 7.2mm /
0.29in. 0.29in.
Avoid Ground Lift
Power wiring runs should not be too long, nor have too many devices connected to it. Wiring
used to supply power to devices has a resistance that is proportional to the length of the
wiring run (see Table 2-9).
Table 2-9: Resistance of Common Copper Wire Sizes
AWG Diameter () Area Copper wire resistance
(inch) (mm) (kcmil) (mm) (/km) (/1000 ft)
14 0.0641 1.628 4.11 2.08 8.286 2.525
16 0.0508 1.291 2.58 1.31 13.17 4.016
18 0.0403 1.024 1.62 0.823 20.95 6.385
If the power run from the power supply is relatively long and it supplies power to many
devices, a voltage will develop over the length of wire. For example, a 1000 ft of 18 AWG
copper wire has a resistance of 6.4 Ohms. If this wire is supplying 1 Ampere of current to
connected devices (as shown in Figure 2-20), the voltage developed across it will be 6.4
volts. This effect is called ground lift.
32 Network Guide
BACnet MS/TP Communication Bus Fundamentals
Use a heavier gauge wire.
Add more wire runs. Connect these wire runs to the power supply in a star pattern.
For controllers that accept DC power (without triac outputs): Specify a 24 DC power
supply. The continuous and even voltage of a DC power supply makes more efficient
use of the power handling capabilities of a power run. A 24 DC power supply eliminates
the 2.5 multiplication factor associated with the peak AC current being 2.5 times the
average RMS AC current. See below.
Peak Current
Particular attention should be paid to the peak current absorbed by devices that are powered
by an AC circuit. All Distech Controls devices use half-wave rectifiers to supply their onboard
electronics (this is common with most controls manufacturers). With this configuration, the
peak AC current is approximately 2.5 times the average RMS AC current.
Transformer Selection and Determining the Maximum Power Run Length
Distech Controls devices are Class 2 Products. To conform to Class 2 installation
requirements, only use transformers of 100VA or less to power the device(s).
For VAV devices, determine the maximum number of VAVs that can be supplied by a single
power run cable supplied by a 100 VA transformer, according to the cables wire gauge and
the total cable length from the following table.
Table 2-10: Maximum Number of VAV Devices on a Power Run
AWG Power Run Total Maximum Maximum Maximum
Cable Length Number of Number of Number of
Devices @ 7 Devices @ 10 Devices@ 15
VA per device1 VA per device2 VA per device3
144 75M (250 feet) 4 2 1
14 60M (200 feet) 5 3 2
14 45M (150 feet) 5 4 3
14 30M (100 feet) 5 5 4
16 60M (200 feet) 3 2 1
16 45M (150 feet) 5 3 2
16 30M (100 feet) 5 4 3
18 45M (150 feet) 3 2 1
18 30M (100 feet) 5 3 2
1. Typical VAV with 1 EC-Smart-Vue and actuator activated. No external loads.
2. Typical VAV with 1 EC-Smart-Vue, 2 triac loads (1.6 VA each), 1 analog output (20 mA), and actuator
activated.
3. Typical VAV with 1 EC-Smart-Vue, 4 triac loads (1.6 VA each), 2 analog outputs (20 mA each), and
actuator activated.
4. Device terminals are not capable of accepting two 14 AWG wires (when daisy-chaining devices). Use a
wire nut with a pig tail to make such a connection.
Any installation condition that is outside of the parameters of Table 2-10 should be avoided.
For non-VAV devices, determine the appropriate size transformer for the job as follows:
1. Add up the power requirements of all devices plus all connected output loads. Multiply
the total power needed by a multiplier of 1.3, as a security margin. For example, to
power five devices (15 VA each), the total load is 75 VA multiplied by 1.3 is 98 VA.
Choose a size of transformer just over this amount: For example, a 100 VA model.
2. When the total load of a number of devices requires a transformer with a rating greater
than 100 VA, use two or more transformers. Ensure that the load to be connected to
each transformer follows the guideline of Step 1 above.
Network Guide 33
BACnet MS/TP Communication Bus Fundamentals
Always use a separate transformer for each ECB-600 series controller and its
associated I/O Extension Modules.
Use an external fuse on the 24VAC side (secondary side) of the transformer, as shown in
Figure 2-19, to protect all controllers against power line spikes.
Maintain consistent polarity when connecting controllers and devices to the transformer, as
shown in Typical Device BACnet MS/TP LAN and Power Wiring Diagram on page 35. That
is, the 24V COM terminal of each controller and each peripheral must be connected to the
same terminal on the secondary side of the transformer. This transformer terminal must be
connected to the buildings ground. This ensures that the 24V COM terminals of all devices
connected to any BACnet MS/TP bus in the building are at the same potential.
34 Network Guide
When two or more devices share a single
Beware of Ground Lift. Too much current
power source, maintain polarity between
over long wire runs can raise the ground
devices. For example, the 24V AC/DC
reference at the 24V COM terminals,
terminal of all devices must be connected
causing data bus transmission errors.
to the same power supply bus.
Network Guide
Fuse: 4A Max. Power
Fast Acting Typical EC-BOS Device Module
AC Power
Source 24 VAC EC-NPB-PWR
(Mains) EC-NPB-PWR-
UN
Power
RS-485 Input
Equivalent
Fuse: 4A Max.
Wiring Diagram
24V COM
24V COM
24V COM
24V COM
24V AC/DC
24V AC/DC
24V AC/DC
24V AC/DC
24 VDC Fast Acting
+ Typical BACnet Device Typical BACnet Device Typical BACnet Device Typical BACnet Device
DC Power
Source EOL ENABLED: For the
EOL ON EOL OFF EOL OFF EOL OFF
EC-BOS as a first or last
daisy-chained device:
Electrical OPTIONALLY set the
System EOL jumper internally
NET-
NET+
NET-
NET+
NET-
NET+
NET-
NET+
Ground S - +
AND add a 120 Ohm
resistor as shown here
Data Bus Shields: Twist Data Bus Shields: Twist Data Bus Shields: Twist
Electrical
together and Isolate together and Isolate together and Isolate
Data Bus Shield: System Ground 0
with electrical tape with electrical tape with electrical tape 12
Isolate with
electrical tape
Data Bus: Shielded Twisted Pair Cable
Data Bus Shield: Connect
to the S terminal
AC Power
An overview of the BACnet MS/TP LAN and power wiring is shown below.
35
LonWorks Communication Bus Fundamentals
CHAPTER 3
LONWORKS COMMUNICATION BUS
FUNDAMENTALS
This chapter describes the LONWORKS Communications Bus operating principals.
In This Chapter
Topic Page
Network Architecture 37
TP/FT-10 Network Topologies 38
Network Cables 40
Extending the Network 42
Grounding a Network 43
Power Supply Requirements 44
36 Network Guide
LonWorks Communication Bus Fundamentals
Network Architecture
EC-NetAX Network Architecture
Single-Segment EC-NetAX Network
A single-segment EC-NetAX Network shown with EC-NetAX Supervisor and EC-NetAX Pro.
- Data Bus Management
- Alarm - Data Bus Integration - User Interface
- Trend Log - Device Configuration and - Remote Access
- Schedule programming - Embedded EC-NetAX Pro
- Graphical Interface
EC-NetAX Supervisor Configuration EC-NetAX Pro Web Browser
EC-BOSAX
IP Network # 1 IP Network # 3
AX
EC-BOS EC-BOSAX
Building #1 Building #2
Figure 3-2: Typical Inter-Building Connection Using IP/FOX
Network Guide 37
LonWorks Communication Bus Fundamentals
Bus Topology
A bus topology is a physical routing of the communication channel that includes a distinct
beginning and end. It is also known as a daisy-chain topology.
T T
...
Figure 3-3: Bus Topology
TP/FT-10 Bus Topology Network Termination
For bus topology type networks, use the following terminators at each end of the bus
topology channel (2 terminators per channel in total):
R1 = 105, 1%, W
+
Distech Controls Part Number:
R1
C1
C1 = 100F, 50V PDIDI-BT-TP10XX
C2
+ C2 = 100F, 50V
Free Topology
Free topology is a flexible wiring structure for communication channels that include ring, star,
loop and/or combination wiring structures. A free topology does not have restrictions such as
branching restrictions, stub length limits, device separation requirements or strict termination
guidelines. The free topology transmission specification only has two requirements that must
be met for proper system operation. The distance from each transceiver to all other
transceivers and to the termination must not exceed the maximum node-to node distance. If
multiple paths exist (i.e. a loop topology) then the longest path should be used for
calculations. The maximum total wire length is the total length of wire within a segment. See
the section for detailed information about wiring lengths and network cable considerations.
38 Network Guide
LonWorks Communication Bus Fundamentals
R1 = 52.3, 1%, W
+
Distech Controls Part Number:
R1
C1
C1 = 100F, 50V PDIDI-FT-TP10XX
C2
+ C2 = 100F, 50V
Network Guide 39
LonWorks Communication Bus Fundamentals
Network Cables
The following section identifies the type of cabling that may be used in a TP/FT-10 twisted
pair LONWORKS network. The recommendations presented herein are intended to assist
network integrators and OEMs and are provided for informational purpose only.
For more information and detailed explanations on network topology and wire length
restrictions refer to the Junction Box and Wiring Guideline for Twisted Pair LonWorks
Networks. These guides can be downloaded from Echelons web site at www.echelon.com.
As a general rule, the TP/FT-10 channel communication cables should not
be run close to high voltage power cables.
All wiring must comply with applicable national, state and local wiring
electrical codes, ordinances, and regulations.
Parameter Details
Nickname Free Topology
Raw Bit rate 78kbps
Packets per second 144/168
Peak traffic 180/210
Topology Free, Bus
Termination - One per segment in free topology
- Two per segment in bus topology
Maximum number of 64
devices per segment A maximum of 128 devices per channel can be
installed on a TP/FT-10 when a router or
repeater is used. See Extending the Network on
page 42 for more information.
Table 3-1 TP/FT-10 Channel Attributes
40 Network Guide
LonWorks Communication Bus Fundamentals
Untwisted wires or cables containing flat or parallel untwisted conductors must not
be used on an LONWORKS twisted pair channel. The use of theses wires/cables may
result in improper network operation and could, in certain circumstances, result in
damage to nodes connected to such a channel.
In a bus topology, the maximum wire length is 1400 meters (4593 feet). The maximum stub
length on a TP/FT-10 channel is 3 meters (10 feet). A stub is a section of unterminated
transmission line that branches off the main transmission line of interest. The branch line is
terminated as an open circuit.
In a free topology, the maximum length is 400 meters (1312 feet) node-to-node and 500
meters (1640 feet) total wire length.
In the event that the limits on the number of transceivers or total wire distance are
exceeded, then one FTT physical layer repeater can be added to interconnect two
segments and double the overall system capability.
Type 2:
16 AWG (1.3mm), 1 twisted pair (1P), stranded conductor (STR), tinned copper (TNC),
PVC insulation, PVC jacket, unshielded, plenum FT6, CSA 600V or UL 300V.
Parameter Details
Conductor Gauge (AWG) 16 AWG
Conductor Count 2 Conductors (twisted pair)
Conductor Type Stranded conductor
Material Tinned copper
Plenu: Plenum rated
NEC Rating UL listed art 800 plenum
CSA Flame rated
Table 3-3: TP/FT-10 Type 2 Cable Attributes
In bus topology, the maximum wire length is 2700 meters (8858 feet). The maximum stub
length on a TP/FT-10 channel is 3 meters (10 feet).
In free topology, the maximum length is 500 meters (1640 feet) node-to-node and 500
meters (1640 feet) total wire length.
For more information about extending the network to a sensor, see Connecting to
the LAN through an EC-Smart-Vue on page 57.
Network Guide 41
LonWorks Communication Bus Fundamentals
...
T T
Repeater
Bus Toplogy
Router
or
T Bus Toplogy
T
...
42 Network Guide
LonWorks Communication Bus Fundamentals
Grounding a Network
Grounding Shielded Twisted Pair Cable
When using Shielded Twisted Pair, terminate the twisted pair and ground the cable shield,
as shown in Figure 3-6.
Network Guide 43
LonWorks Communication Bus Fundamentals
Fuse: 4 A Max.
Controller 1 Fast Acting
24V AC
24V COM 24 VAC AC
Transformer
Controller 2
24V AC Electrical System Ground
24V COM - At Transformer Only
Figure 3-7: Power wiring AC: The 24V COM Terminal of all Devices must be
Connected to the Grounded Power Supply Bus
Fuse: 4 A Max.
Controller 1 Fast Acting
24V AC/DC
24V COM 24 VDC
Controller 2
24V AC/DC Electrical System Ground
24V COM - At Power Supply Only
Figure 3-8: Power wiring DC: The 24V COM Terminal of all Devices must be
Connected to the Grounded Power Supply Bus
The table below lists Distech Controls recommended power cable.
Table 3-4: Distech Controls Recommended Power Cable
Cable Type Non-Plenum Applications Plenum Applications
AWG (FT4) (FT6)
Number of Part Number O.D. () Part Number O.D. ()
Conductors
18-2 07CBL-W181P-1002 5.0mm 07CBL-W181P-2051 5.0mm
0.20in. 0.20in.
16-2 07CBL-W161P-1031 4.8mm / 07CBL-W161P-2062 4.8mm /
0.19in. 0.19in.
14-2 07CBL-W141P-1081 7.2mm / 07CBL-W141P-2013 7.2mm /
0.29in. 0.29in.
44 Network Guide
LonWorks Communication Bus Fundamentals
Table 3-5: Maximum Number of VAV Devices on a Power Run
AWG Power Run Total Maximum Maximum Maximum
Cable Length Number of Number of Number of
Devices @ 7 Devices @ 10 Devices@ 15
VA per device1 VA per device2 VA per device3
144 75M (250 feet) 4 2 1
14 60M (200 feet) 5 3 2
14 45M (150 feet) 5 4 3
14 30M (100 feet) 5 5 4
16 60M (200 feet) 3 2 1
16 45M (150 feet) 5 3 2
16 30M (100 feet) 5 4 3
18 45M (150 feet) 3 2 1
18 30M (100 feet) 5 3 2
1. Typical VAV with 1 EC-Smart-Vue and actuator activated. No external loads.
2. Typical VAV with 1 EC-Smart-Vue, 2 triac loads (1.6 VA each), 1 analog output (20 mA), and actuator
activated.
3. Typical VAV with 1 EC-Smart-Vue, 4 triac loads (1.6 VA each), 2 analog outputs (20 mA each), and
actuator activated.
4. Device terminals are not capable of accepting two 14 AWG wires (when daisy-chaining devices). Use a
wire nut with a pig tail to make such a connection.
Any installation condition that is outside of the parameters of Table 3-5 should be avoided.
For non-VAV devices, determine the appropriate size transformer for the job as follows:
1. Add up the power requirements of all devices plus all connected output loads. Multiply
the total power needed by a multiplier of 1.3, as a security margin. For example, to
power five devices (15 VA each), the total load is 75 VA multiplied by 1.3 is 98 VA.
Choose a size of transformer just over this amount: For example, a 100 VA model.
2. When the total load of a number of devices requires a transformer with a rating greater
than 100 VA, use two or more transformers. Ensure that the load to be connected to
each transformer follows the guideline of Step 1 above.
Always use a separate transformer for each ECL-600 series controller and its
associated I/O Extension Modules.
Use an external fuse on the 24VAC side (secondary side) of the transformer, as shown in
Figure 3-7 and Figure 3-8, to protect all controllers against power line spikes.
Maintain consistent polarity when connecting controllers and devices to the transformer.
That is, the 24V COM terminal of each controller and each peripheral must be connected to
the same terminal on the secondary side of the transformer. This transformer terminal must
be connected to the buildings ground.
Network Guide 45
Subnetwork Installation Guidelines
CHAPTER 4
SUBNETWORK INSTALLATION GUIDELINES
This chapter describes the Extension and Room Sensor Bus Installation Guidelines.
In This Chapter
Topic Page
About the Subnetwork Bus 47
ECx-4XX Subnetwork Bus 48
EC-Smart-Vue Subnetwork Bus 52
46 Network Guide
Subnetwork Installation Guidelines
EC-Smart-Vue Sub-Network Bus: 200 m (650 ft) ECx-4XX Sub-Network Bus: 300 m (1 000 ft)
Maximum Maximum
Typical ECB-600 / Typical ECx-4XX Series Extension I/O Modules For use
ECL-600 Controller with an ECB-600 / ECL-600 Series Controller Only
- Temporary
Commissioning and
Maintenance
Connection
- No EOL Resistors are
Necessary EC-Net Pro
Figure 4-1: Subnetwork Bus Overview Showing the EC-Smart-Vue Subnetwork Bus
and the ECx-4XX Subnetwork Bus
Subnetwork Bus Total Length
The total maximum length of all subnetwork buses, including both the length of the
EC-Smart-Vue subnetwork bus and the ECx-4XX subnetwork bus is 300 m (1 000 ft). The
maximum length of the EC-Smart-Vue subnetwork bus is 200 m (650 ft). The maximum
length of the ECx-4XX subnetwork bus is 300 m (1 000 ft).
Network Guide 47
Subnetwork Installation Guidelines
48 Network Guide
Subnetwork Installation Guidelines
When ECx-4XX I/O Extension Modules are installed with an ECB-600 / ECL-600, only the
EOL terminations of the ECB-600 / ECL-600 and the last ECx-4XX are set to ON. All other
ECx-4XX I/O Extension Modules must have their EOL terminations set to OFF. This is
shown below.
Typical ECB-600 / Typical ECx-4XX Series Extension I/O Modules For use
ECL-600 Controller with an ECB-600 / ECL-600 Series Controller Only
Inside Inside
ECx-4XX ECx-4XX
EOL OFF EOL OFF
EOL ON EOL ON
For ECx-4XX:
For ECB-600 / ECL-600, the - Last daisy-chained ECx-4XX:
Sub-Network EOL is set to ON EOL Jumper is ON
- All other ECx-4XX:
EOL Jumpers are OFF
Figure 4-2: Setting the EOL Terminations on the ECx-4XX Subnetwork Bus
When ECx-4XX I/O Extension Modules are installed with an ECB-600 / ECL-600 and with
EC-Smart-Vue sensor(s), only the EOL terminations the last ECx-4XX and the last EC Smart
Vue are set to ON. All other ECx-4XX I/O Extension Modules and EC-Smart-Vues must
have their EOL terminations set to OFF. This is shown below.
Typical ECB-600 / Typical ECx-4XX Series Extension I/O Modules For use
ECL-600 Controller with an ECB-600 / ECL-600 Series Controller Only
Inside
Back of ECx-4XX
EC-Smart-Vue EOL OFF
Figure 4-3: Setting the EOL Terminations on the ECx-4XX Subnetwork Bus when
EC-Smart-Vue Sensors are used
ECx-4XX devices and EC-Smart-Vue sensors are factory-set with the EOL set to OFF by
default.
Network Guide 49
Subnetwork Installation Guidelines
ECB-600
ECx-4XX ECx-4XX
ECL-600
SUBNET +
SUBNET +
SUBNET -
SUBNET -
SUBNET -
SUBNET+
50 Network Guide
Subnetwork Installation Guidelines
ON
Must be set to the
OFF (0) position
Figure 4-5: Typical I/O Extension Module Address DIP Switch Set to 2
Network Guide 51
Subnetwork Installation Guidelines
52 Network Guide
Subnetwork Installation Guidelines
Table 4-5: T568A and T568B Terminations for an RJ-45 Connector
Pin T568A (at both cable ends) T568B (at both cable ends)
Pair Color Pair Color
1 3 2
white/green stripe white/orange stripe
2 3 2
green solid orange solid
3 2 3
white/orange stripe white/green stripe
4 1 1
blue solid blue solid
5 1 1
white/blue stripe white/blue stripe
6 2 3
orange solid green solid
7 4 4
white/brown stripe white/brown stripe
8 4 4
brown solid brown solid
The final result of a crimped RJ-45 connector is shown graphically below.
T568A T568B
Key:
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8
Stripe Solid
Network Guide 53
Subnetwork Installation Guidelines
Bus and Cable Non-Plenum Applications (Use in Plenum Applications (FT6)
Type Conduit - FT4)
Part Number O.D. ()1 Part Number O.D. ()1
300 meters (1000 feet), 07CBL-W244P-1446WHTB 4.6mm (0.18in.) 07CBL-W224P-2176WHTB 4.6mm (0.18in.)
Cat 5e Cable Without
Connectors
100 Crimp RJ-45 07CBL-PATCHCONNECTOR N/A 07CBL-PATCHCONNECTOR N/A
Connectors
1 Outer Cable diameter This does not factor the RJ-45 connector.
Controller Series:
ECL-VAVS / ECL-VAV
ECL-103 Back of
ECL-203 EC-Smart-Vue
ECL-300
ECL-400
ECB-VAVS / ECB-VAV
ECB-103 EOL set to ON
ECB-203 at the last ON
EOL
Figure 4-7: Setting the EOL Terminations on the EC-Smart-Vue Subnetwork Bus for
the ECB-VAVS / ECB-VAV, ECB-103, ECB-203, ECB-400 Controller Series
When one or more EC-Smart-Vues are installed with an ECB-600 / ECL-600, only the EOL
terminations the ECB-600 / ECL-600 and the last EC Smart Vue are set to ON. All other
EC-Smart-Vues must have their EOL terminations set to OFF. This is shown below.
54 Network Guide
Subnetwork Installation Guidelines
Controller Series:
ECB-600
ECL-600 Inside
ECB/ECL-600 Back of
EC-Smart-Vue
EOL OFF
EOL ON
EOL set to ON
at the last ON
EOL
For ECB-600 / ECL-600, set the sensor at the
OFF
Sub-Network EOL to ON end of the Bus
Figure 4-8: Setting the EOL Terminations on the EC-Smart-Vue Subnetwork Bus
Network Guide 55
Subnetwork Installation Guidelines
2. Press and hold the Menu button for 5 seconds to enter the password menu. 10000 is
shown on the display.
3. Use the down button to set the number to 9995 (this is the default password).
4. Use the Menu button to select GEN CFG.
5. Press the down button once to enter the GEN CFG submenu. The MAC ADDRESS
menu is shown with the current controllers BACnet MAC Address.
6. Use the up and down buttons to set the controllers MAC Address. Only
addresses from 1 to 127 are recommended to be used.
7. Press the Menu button once to apply the value.
8. Press and hold the Menu button for 5 seconds to exit the configuration menu.
Once the BACnet MS/TP network is operational, the controller can be programmed with
EC-gfxProgram. For each EC-Smart-Vue, set its Subnet ID number to the block number of
its associated CommSensor block in EC-gfxProgram. This is done in the EC-Smart-Vues
GEN CFG menu under SUBNET ID.
Setting the BAUD Rate for ECB-Series Controllers (optional)
For information about what the BACnet MS/TP network baud rate should be set to, see Data
Bus Devices and Baud Rate on page 13.
By default, the BAUD rate for the controller is set to automatically detect the current
communication BAUD rate of the connected BACnet MS/TP network (AUTO). This is the
preferred setting for a controller. However, at least one controller on the BACnet MS/TP
network data bus must have its BAUD rate set. The preference is to set the building
controllers BAUD rate (if present). Otherwise, set the BAUD rate on one controller that will
set the BAUD rate for all other controllers (to act as the master for setting the BAUD rate).
When the Baud rate is set to AUTO, the controller cannot initiate any
communication until it has detected the baud rate of the BACnet MS/TP network.
If all controllers on the BACnet MS/TP network are set to AUTO, then all
controllers will not communicate.
Set the connected controllers BAUD rate as follows:
1. Connect an EC-Smart-Vue to the controller with a Cat 5e patch cable. Wait for the
display to show the room temperature.
2. Press and hold the Menu button for 5 seconds to enter the password menu. 10000 is
shown on the display.
3. Use the down button to set the number to 9995 (this is the default password).
4. Use the Menu button to select GEN CFG.
5. Press the down button once to enter the GEN CFG submenu. The MAC ADDRESS
menu is shown.
6. Use the Menu button to select BAUD RATE. The current controllers BAUD rate is
shown.
7. Use the up and down buttons to set the controllers Baud rate. AUTO detects and
uses the Baud rate currently being used by the BACnet MS/TP network.
8. Press the Menu button once to apply the value.
9. Press and hold the Menu button for 5 seconds to exit the configuration menu.
56 Network Guide
Subnetwork Installation Guidelines
Net to Subnet
Port Settings
Enable
Disable
Enable
Disable
Network Guide 57
Subnetwork Installation Guidelines
LAN Access
Connector
LON1
LON2
Shield
To Portable Router
- Temporary
Commissioning and
Maintenance
EC-Net Pro Connection
LON USB Network
Interface
BAC
LON
58 Network Guide
Subnetwork Installation Guidelines
Ensure the BAC/LON jumper in the EC-Smart-Vue is set to the BAC position (this is
the factory-set default jumper position).
BAC
LON
Network Guide 59
BACnet Troubleshooting
CHAPTER 5
BACNET TROUBLESHOOTING
Table 5-1: Troubleshooting ECB Device Symptoms
Symptom Possible Cause Solution
Device does not The device does not have See Power Supply Requirements on page 31.
communicate on power / poor-quality power.
the BACnet BACnet data bus polarity Ensure the polarity of the BACnet data bus is
MS/TP network reversed. always the same on all devices. See BACnet
MS/TP Data Bus is Polarity Sensitive on page
11.
Cut or broken wire. Isolate the location of the break and pull a
new cable.
The BACnet data bus has See Adopting a Numbering System for MAC
one or more devices with Addresses, Device Instance Numbers, and
the same MAC Address. Network Numbers on page 27.
The BAUD rate for all At least one device must be set to a baud
devices are set to AUTO rate, usually the bus master.
The device is set to a MAC See if the STATUS led on the device is
Address in the range of 128 showing a fault condition. See Table 5-2 for a
to 255. list of fault codes.
This range is for slave devices that cannot
initiate communication. All Distech Controls
devices are master devices and must their
MAC Address set accordingly. See Device
Addressing on page 23.
The maximum number of Use a repeater to extend the BACnet data
devices on a data bus bus. See Data Bus Devices and Baud Rate on
segment has been page 13.
exceeded.
Max Master parameter Configure the Max Master to the highest MAC
Address of any device on the MS/TP data
bus. See Setting the Max Master and Max
Info Frames on page 26.
Absent or incorrect supply 1. Check if the device is showing the Poor-
voltage Quality Power status code. See Table 5-4 for
a list of fault codes.
2. Check power supply voltage between
24VAC 15% and COM pins and ensure that
it is within acceptable limits.
3. Check for tripped fuse or circuit breaker.
Overloaded power 1. Check if the device is showing the Poor-
transformer Quality Power status code. See Table 5-4 for
a list of fault codes.
2. Verify that the transformer used is powerful
enough to supply all controllers. See
Transformer Selection and Determining the
Maximum Power Run Length on page 33.
60 Network Guide
BACnet Troubleshooting
Network Guide 61
BACnet Troubleshooting
Symptom Possible Cause Solution
Hardware input Input wiring problem Check that the wiring is correct according to
is not reading this manual and according to the peripheral
the correct devices manufacturer.
value Open circuit or short circuit Using a voltmeter, check the voltage on the
input terminal. For example, for a digital input,
a short circuit shows approximately 0V and an
open circuit shows approximately 5V. Correct
wiring if at fault.
Configuration problem Using the controller configuration wizard,
check the configuration of the input. Refer to
the controllers user guide for more
information.
Over-voltage or over- An over-voltage or over-current at one input
current at an input can affect the reading of other inputs. Respect
the allowed voltage / current range limits of all
inputs. Consult the appropriate datasheet for
controller input range limits.
Hardware Fuse has blown (Auto reset Disconnect the power and outputs terminals.
output is not fuse) Then wait a few seconds to allow the auto-
operating reset fuse to cool down. Check the power
correctly supply and the output wiring. Reconnect the
power.
Output wiring problem Check that the wiring is correct according to
this manual and according to the peripheral
devices manufacturer.
Configuration problem Using the controller configuration wizard,
check the configuration of the output. Refer to
the controllers user guide for more
information.
0-10V output, 24VAC Check the polarity of the 24VAC power supply
powered actuator is not connected to the actuator while connected to
moving. the controller. Reverse the 24VAC wire if
necessary.
Wireless Device not associated to Using the device configuration wizard, check
devices not controller the configuration of the input. Refer to the
working devices user guide for more information.
correctly Power discharge 1. Recharge device with light (if solar-
powered) or replace battery (if battery-
powered).
2. Ensure sufficient light intensity (200lx for 4
hours/day).
Device too far from the Reposition the device to be within the range of
Wireless Receiver the Wireless Receiver. For information on
typical transmission ranges, refer to the Open-
to-Wireless Solution Guide.
Configuration problem Using the device configuration plug-in or
wizard, check the configuration of the input.
Refer to the Wireless Battery-less Sensors
and Switches Solutions Guide for more
information.
62 Network Guide
BACnet Troubleshooting
Table 5-2: Led Fault Condition Interpretation for ECB Devices
ECB Device Led Description Solution
Interpretation
RX LED not blinking Data is not being received from the BACnet If there is no
MS/TP data bus. communication, see
TX LED not blinking Data is not being transmitted onto the Table 5-1.
BACnet MS/TP data bus.
POWER constant on Power is available at the device. However If not lit, see Power
this does not mean that the quality of Supply Requirements
supplied power is good. Verify the STATUS on page 31 for the
led. See also Power Supply Requirements power requirements.
on page 31.
STATUS blinking See below.
Table 5-3: STATUS Led Interpretation for Normal Operation with ECB Devices
Device STATUS Led blink Status Description
patterns
Fast blink continuous: Initialization The device is starting up.
Network Guide 63
BACnet Troubleshooting
Table 5-4: STATUS Led Fault Condition Interpretation for ECB Devices
Device STATUS Led blink Possible Cause Corrective action
patterns every 2 seconds
(highest priority shown first)
Long Long Long blink Offline The device has not received a BACnet
token, and therefore cannot
(800ms On, 300ms Off, 800ms On, communicate on the network.
300ms Off, 800ms On)
Short Short Long blink Poor-quality The voltage at the 24VAC and 24VCOM
power. terminals was not at an acceptable level
(150ms On, 300ms Off, 150ms On, The device has during power up.
300ms Off, 800 ms On) browned-out.
Short Long blink Invalid MAC The devices MAC address is set to zero
address (0) or is set to an address higher than
(150ms On, 300ms Off) the Max Master. See BACnet MS/TP
Data Bus Token-Passing Overview on
page 24.
Long Short Short Short Short Backup and The controller is being backed-up or
Long Short: Restore. restored.
64 Network Guide
BACnet Troubleshooting
Table 5-5: Verify that the Following Recommendations have been Carried Out Before
Calling Technical Support
Recommendation Description
Properly terminate the BACnet MS/TP EOL terminations must be enabled / installed at either
data bus end of the data bus only. See Figure 2-1.
Avoid duplicate MAC Addresses Verify that no device has a duplicate MAC Address by
checking the MAC Address DIP switch settings on all
devices on the data bus, including segments
connected by a repeater.
If necessary, isolate devices from the data bus to
narrow-down the number of devices that may be at
fault.
All devices must be set to the same When all devices are set to AUTO BAUD rate, at least
baud rate one device must be set to a baud rate, usually the bus
master.
The bus is polarity sensitive Ensure that the polarity of all data bus wiring is
consistent throughout the network. See BACnet MS/TP
Data Bus is Polarity Sensitive on page 11.
Do not overload the data bus with COV reports create the most traffic on the BACnet
Change of Value (COV) reporting MS/TP data bus. Set the COV report rate to the largest
value that provides acceptable performance. Only map
COV reports for values that are necessary. For
mapped analog points that are continuously changing,
try increasing the COV increment on these points or
set the COV minimum send time flag to true to send
the value at a regular frequency.
Do not leave address holes in the Assign MAC Address to device starting at 3, up to 127.
devices MAC Address range Do not skip addresses. Set the maximum MAC
Address in the Bus Master (Building Controller) to the
final MAC Address number actually installed.
NOTE: The physical sequence of the MAC Address of
the devices on the data bus is unimportant: For
example, the MAC Address of devices on the data bus
can be 5, 7, 3, 4, 6, and 8.
Only daisy-chained devices are Eliminate T-taps and star configurations. Use a router
acceptable to connect a data bus spur.
Connect no more than five devices to a BACnet MS/TP devices require good power quality.
power supply transformer See Power Supply Requirements on page 31.
Network Guide 65
LonWorks Troubleshooting
CHAPTER 6
LONWORKS TROUBLESHOOTING
Table 6-1: Troubleshooting ECL Device Symptoms
Symptom Possible Cause Solution
Device does not The device does not have See Power Supply Requirements on page 44.
communicate on power / poor-quality power.
the LONWORKS Cut or broken wire. Isolate the location of the break and pull a
network new cable.
The maximum number of Use a repeater to extend the LONWORKS data
devices on a segment has bus. See Network Cables on page 40 and
been exceeded. also Extending the Network on page 42.
Absent or incorrect supply 1. Check if the device is showing the Poor
voltage Power Quality status code. See Table 6-4 for
a list of fault codes.
2. Check power supply voltage between
24VAC 15% and COM pins and ensure that
it is within acceptable limits.
3. Check for tripped fuse or circuit breaker.
Overloaded power 1. Check if the device is showing the Poor
transformer Power Quality status code. See Table 6-4 for
a list of fault codes.
2. Verify that the transformer used is powerful
enough to supply all controllers. See
Transformer Selection and Determining the
Maximum Power Run Length on page 44.
Network not wired properly Double check that the wire connections are
correct.
Absent or incorrect network Check the network termination(s). See TP/FT-
termination 10 Free Topology Network Termination on
page 39.
The STATUS The device has auto- See Table 6-2 for a list of fault codes.
led is blinking diagnosed a fault condition
Controller is Fuse has blown Disconnect the power. Check the fuse
powered but integrity. Reconnect the power.
does not turn on Power supply polarity Verify that consistent polarity is maintained
between all controllers and the transformer.
Ensure that the COM terminal of each
controller is connected to the same terminal
on the secondary side of the transformer. See
Power Supply Requirements on page 44.
Controller Network length Check that the total wire length does not
communicates exceed the specifications of the Network
well over a short Guide. See Network Cables on page 40.
network, but Wire type Check that the wire type - see Network Cables
does not on page 40.
communicate on
large network Network wiring problem Double check that the wire connections are
correct.
66 Network Guide
LonWorks Troubleshooting
Network Guide 67
LonWorks Troubleshooting
Symptom Possible Cause Solution
Wireless Device not associated to Using the device configuration wizard, check
devices not controller the configuration of the input. Refer to the
working devices user guide for more information.
correctly Power discharge 1. Recharge device with light (if solar-
powered) or replace battery (if battery-
powered),
2. Ensure sufficient light intensity (200lx for 4
hours/day).
Device too far from the Reposition the device to be within the range of
Wireless Receiver the Wireless Receiver. For information on
typical transmission ranges, refer to the Open-
to-Wireless Solution Guide.
Configuration problem Using the device configuration plug-in or
wizard, check the configuration of the input.
Refer to the Wireless Battery-less Sensors
and Switches Solutions Guide for more
information.
Table 6-3: STATUS Led Interpretation for Normal Operation with ECL Devices
Device STATUS Led blink Status Description
patterns
Fast blink continuous: Initialization - Initialization: The device is starting up.
- Firmware upgrade in progress. Controller
(150ms On, 150ms Off, continuous) operation is temporarily unavailable. The
new firmware is being loaded into memory.
This takes a few seconds. Do not interrupt
power to the device during this time.
STATUS led is always OFF No anomaly Normal operation.
68 Network Guide
LonWorks Troubleshooting
Table 6-4: STATUS Led Fault Condition Interpretation for ECL Devices
Device STATUS Led blink Possible Cause Corrective action
patterns every 2 seconds
(highest priority shown first)
Long blink continuous: The controller is Commission the controller
unconfigured
(1s On, 1s Off, continuous)
Long Long Long blink The controller is Set the controller Online
offline
(800ms On, 300ms Off, 800ms On, 300ms Off,
800ms On)
Long Short Short Short blink The controller is in Set the controller Online
bypass mode
(800ms On, 300ms Off, 150ms On, 300ms Off, 150ms On,
300ms Off, 150ms On)
Short Short Long blink Poor-quality The voltage at the 24VAC and 24VCOM
power; The device terminals has gone below the devices
(150ms On, 300ms Off, 150ms On, 300ms Off, 800 ms On) has browned-out acceptable limit during power up.
Fast blink 12x: Wink The wink function is used to identify a
device.
(80ms On, 80ms Off, 12x)
Table 6-5: Verify that the Following Recommendations have been Carried Out Before
Calling Technical Support
Recommendation Description
Properly terminate the LONWORKS data EOL terminations must be enabled / installed at either
bus end of the data bus only. See TP/FT-10 Free Topology
Network Termination on page 39.
Connect no more than five devices to a LONWORKS devices require good power quality. See
power supply transformer TP/FT-10 Free Topology Network Termination on page
39.
Network Guide 69
ECx-400 Series I/O Extension Module Specific Troubleshooting
CHAPTER 7
ECX-400 SERIES I/O EXTENSION MODULE
SPECIFIC TROUBLESHOOTING
For general troubleshooting of an ECx-400 Series I/O Extension Module, first follow the
troubleshooting for a controller see BACnet Troubleshooting on page 60 and LonWorks
Troubleshooting on page 66. Then follow the troubleshooting tips shown below.
Table 7-1: Troubleshooting ECx-400 Series I/O Extension Module Device Specific
Symptoms
Symptom Possible Cause Solution
Device does not Cut or broken wire. Isolate the location of the break and pull a
communicate on new cable.
the subnetwork Network not wired properly Double check that the wire connections are
correct.
Absent or incorrect network Check the network termination(s). See
termination ECx-4XX Subnetwork Bus Topology and End-
of-Line Terminations on page 48.
There is another controller Each I/O Extension Module on the
with the same Subnet ID on subnetwork must have a unique Subnet ID.
the subnetwork Look at the Subnet ID DIP switch on the
faceplate of each I/O Extension Module. See
ECx-4XX I/O Extension Module Addressing
on page 50.
Network length Check that the total wire length does not
exceed specification shown in About the
Subnetwork Bus on page 47.
Wire type Check that the wire type agrees with the
specification shown in ECx-4XX Subnetwork
Bus Physical Specifications and Cable
Requirements on page 48.
70 Network Guide
EC-Smart-Vue Troubleshooting
CHAPTER 8
EC-SMART-VUE TROUBLESHOOTING
Table 8-1: EC-Smart-Vue Normal Operation
Symptom Status Description
When the Firmware upgrade in Wait for the upgrade to complete. Do not
EC-Smart-Vue is progress disconnect the EC-Smart-Vue from the controller
connected to a as the upgrade will only restart once it is
Controller, the LCD reconnected.
display on the
EC-Smart-Vue is
blank with the
backlight ON for
about 30 to 45
seconds
Table 8-2: Troubleshooting EC-Smart-Vue Symptoms
Symptom Possible Cause Solution
EC-Smart-Vue Is the EC-Smart-Vue Verify that the EC-Smart-Vue is connected to the
screen is blank & connected to the controller and that the patch cables are plugged-
back light is off controller? in to the connectors. Refer to EC-Smart-Vue
Subnetwork Bus on page 52 for more information.
Is power being There may be no power being supplied from the
supplied to the controller. Check if the controller has power or if
controller? the controllers internal fuses have blown or
tripped.
Is the cable Verify wiring.
connected to the
controller and
EC-Smart-Vue?
Is the address Each EC-Smart-Vue must be set to a unique
correctly set to a address for each controller. See Commissioning
unique address? with an EC-Smart-Vue on page 55.
Was the patch cable Verify that the RJ-45 crimp connectors were
was made onsite? installed on the cable correctly. See
EC-Smart-Vue Subnetwork Bus Cable
Requirements on page 52.
Device is not Is the device too far Verify the distance between the device and the
communicating from controller? controller. See Subnetwork Bus Total Length on
with controller page 47.
Is there a With EC-gfxProgram, check the configuration of
configuration the sensor, for example, is it enabled? Refer to
problem? the EC-gfxProgram User Guide for more
information.
Network Guide 71
EC-Smart-Vue Troubleshooting
Table 8-3: Error code Interpretation for EC-Smart-Vue Symptoms
Symptom Possible Cause Corrective action
Clock icon flashing for 15 Cannot Verify power at controller
seconds communicate with Verify wiring to controller
After 15 seconds: Error code 1 controller.
with Bell icon
Error code 2 with Bell icon Invalid In EC-gfxProgram, resynchronize the
configuration. code with the controller.
Contact Distech Controls Customer
Support.
Error code 3 with Bell icon EC-Smart-Vue is With EC-gfxProgram, check the
not configured in configuration of the sensor, for example,
the controller is it enabled? Refer to the
EC-gfxProgram User Guide for more
information.
72 Network Guide
Typical BACnet EIA-485 Data Bus Transmission Example
Appendix A
TYPICAL BACNET EIA-485 DATA BUS
TRANSMISSION EXAMPLE
The graph below shows electrical signals for the transmission of one byte of data
(hexadecimal D3, least significant bit first). Note that when idle, the BACnet MS/TP bus is
biased such that the Net + connection is positive with respect to the Net connection.
Space
Space
Mark
Mark Space Mark
Net + Mark Mark
Stop
1 1 0 0 1 0 1 1
Permissible
Range
+2 Volts Maximum
+0.2 Volts Transition Operating
Voltage VNet-,Net+ Voltage VNet-,Net+ Range
Region
-0.2 Volts
-2 Volts
Permissible
Range
-7 Volts -7 Volts
Network Guide 73
Typical BACnet EIA-485 Data Bus Transmission Example
Common Mode Noise Rejection
Noise induced onto the conductors of the data bus cable will be common to both Net + and
Net - data bus wires that is to say, the noise will be of the same amplitude and polarity as
the conductors in the cable are so close together. For this reason the EIA-485 data bus is
differential bus. The receiver nulls out common mode induced noise picked up on the data
bus wire by subtracting the negative input from the positive input. This greatly reduces the
impact that induced noise has on the bus.
Induced common-mode noise transient
Noise transient
attenuation
74 Network Guide
How to Set a DIP Switch
Appendix B
HOW TO SET A DIP SWITCH
DIP switches are used to set the address of a device. In the following table, A & B represent
the binary ON / OFF setting for the DIP switch required for a given decimal value shown in
the table.
B 000 001 010 011 100 101 110 111
A
0000 0 1 2 3 4 5 6 7
0001 8 9 10 11 12 13 14 15
0010 16 17 18 19 20 21 22 23
0011 24 25 26 27 28 29 30 31
0100 32 33 34 35 36 37 38 39
0101 40 41 42 43 44 45 46 47
0110 48 49 50 51 52 53 54 55
0111 56 57 58 59 60 61 62 63
1000 64 65 66 67 68 69 70 71
1001 72 73 74 75 76 77 78 79
1010 80 81 82 83 84 85 86 87
1011 88 89 90 91 92 93 94 95
1100 96 97 98 99 100 101 102 103
1101 104 105 106 107 108 109 110 111
1110 112 113 114 115 116 117 118 119
1111 120 121 122 123 124 125 126 127
ON
A B
For example
82 = A: 1010 & B: 010
Network Guide 75
Metric Conversions for Wire Gauge
Appendix C
METRIC CONVERSIONS FOR WIRE GAUGE
The following table provides information about metric wire equivalents for wire gauge.
76 Network Guide
Documentation Improvement Form
Appendix D
DOCUMENTATION IMPROVEMENT FORM
Is any part of this document not clear enough? Are there any comments about the content of
this document? Do not hesitate to use this form to send us comments and
recommendations, as there is always a drive to improve documentation to further satisfy
clients.
Please mail or fax this form to:
Network Guide 77
Distech Controls Inc
4005-B Boul. Matte
Brossard, QC J4Y 2P4
*05DI-UGBACNG-12*
Tel.: 1-800-404-0043 05DI-UGBACNG-12
Tel.: 1-450-444-9898
www.distech-controls.com