Itp DVM
Itp DVM
I. Introduction/Purpose
This plan covers the detailed test and commissioning of the Data Voice Multiplexer
(FOX515).
This plan/procedures document developed in accordance with the steps indicated for
testing as outlined in the SEC-EOA Scope of Work and Technical Specifications for this
contract.
The Test will be witnessed by SEC-EOA approved Third Party Inspector appointed by
the Main Contractor.
The basis of this test will be approved Detailed Design/Manufacturing Clearance from
SEC-EOA /Main Contractor.
The equipment should be pre-tested locally by ABB before offering for FAT. The Local
test results recorded on the Manufacturers recommended Test formats will be presented
to the SEC-EOA/Third Party Inspector for verification.
The SEC-EOA/Third Party Inspector will verify/test 20% of the equipment offered for
inspection.
- Multimeter
- PCM Tester
As part of performing final testing and commissioning of each FOX 515, ABB will be
providing the following test equipment, as outlined in the table below:
Refer the Test Plan/Procedure for Test Configuration Drawings, showing the scheme /
configuration of the test equipment interconnections along with the unit(s), or link(s) under
test.
ABB
Refer Drawing No. ED- 195447 Sht. 11 of 28 {Rackface Elevation for FOX515}
Refer Drawing No. ED- 195447 Sht. 12 of 28 {Rackface Elevation for FOX515}
Refer Drawing No. ED- 195447 Sht. 13 of 28 {Rackface Elevation for FOX515}
Refer Drawing No. ED- 195447 Sht. 14 of 28 {Rackface Elevation for FOX515}
Refer Drawing No. ED- 195447 Sht. 15 of 28 {Rackface Elevation for FOX515}
Refer Drawing No. ED- 195447 Sht. 16 of 28{Rackface Elevation for FOX515}
Refer Drawing No. ED- 195942 Sht. 04 of 05 {Rackface Elevation for FOX515}
Refer Drawing No. ED- 195942 Sht. 05 of 05 {Rackface Elevation for FOX515}
Refer Drawing No. ED- 196201 Sht. 06 of 08 {Rackface Elevation for FOX515}
Refer Drawing No. ED- 196201 Sht. 07 of 08 {Rackface Elevation for FOX515}
Refer Drawing No. ED- 196201 Sht. 08 of 08{Rackface Elevation for FOX515}