Ac Stress Distribution in The Insulation Single Core Screened Xlpe Cable - 132 KV 300 MM

This document discusses the stress distribution in the insulation of a single core screened XLPE cable rated for 132kV 300mm^2. It provides the electrical and cable dimensions, and calculates the stress distribution (Ex) at different points (x) within the insulation using the given equation. Tables show the calculated normal stress distribution under nominal operating voltage and short duration power frequency withstand voltage, with the maximum and minimum stresses reported.

Uploaded by

john
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
78 views2 pages

Ac Stress Distribution in The Insulation Single Core Screened Xlpe Cable - 132 KV 300 MM

This document discusses the stress distribution in the insulation of a single core screened XLPE cable rated for 132kV 300mm^2. It provides the electrical and cable dimensions, and calculates the stress distribution (Ex) at different points (x) within the insulation using the given equation. Tables show the calculated normal stress distribution under nominal operating voltage and short duration power frequency withstand voltage, with the maximum and minimum stresses reported.

Uploaded by

john
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

AC STRESS DISTRIBUTION IN THE INSULATION

SINGLE CORE SCREENED XLPE CABLE - 132 kV 300 mm 2

ELECTRICAL DATA
U Phase to Phase Nominal Voltage (kV) 132
U0 Phase to Earth nominal Voltage (kV) 76
Uip Impulse Voltage (kV) 650
Upf Short Duration Power Frequency Withstand Voltage (kV) 275

CABLE DIMENSIONS
d Nominal Diameter of Conductor (mm) 20.60
tcs Nominal Thickness of Conductor Screen (mm) 1.20
D Nominal Diameter over Insulation Screen (mm) 60.20
tis Thickess of Semi Conductor screen over insulation (mm) 1.20
X Thickness of Insulation 17.40

CALCULATION OF STRESS DISTRIBUTION

Ex = V/{[(d/2)+tcs+x)]*ln[(D-2*tis)/(d+2*tcs)]} kV/mm

Where,
Ex : Stress Distribution at point X of inslulation (kV)
V : Potential applied between Conductor and Metalic Sheath (kV)
x: Distance from conductor screen at point X of insulation (mm)

Stress at Conductor + Screen

Semi Conductive Insulation Screen Stress at Sheath + Screen

XLPE Insulation

Conductor

Semi Conductive Conductor Screen Potential Difference = V


U0 (kV) Upf (kV) STRESS DISTRIBUTION
Increment
x (mm) 76 275
No.
Normal Stress
Ex0 (kV) Expf (kV)
8.0
1 0.00 7.192 25.950 7.0
2 0.92 6.661 24.036 6.0
5.0
3 1.83 6.204 22.385

kV
4.0
4 2.75 5.805 20.946 3.0

5 3.66 5.454 19.681 2.0


1.0
6 4.58 5.144 18.560
0.0
7 5.49 4.866 17.560
8 6.41 4.618 16.662 THICKNESS (mm)
9 7.33 4.393 15.852
10 8.24 4.189 15.116
STRESS DISTRIBUTION
11 9.16 4.003 14.446
12 10.07 3.834 13.833 SHORT DURATION PF VOLTAGE
13 10.99 3.677 13.270
30.0
14 11.91 3.534 12.750 25.0
20.0
15 12.82 3.400 12.270
kV

15.0
16 13.74 3.277 11.825 10.0
5.0
17 14.65 3.162 11.411
0.0
18 15.57 3.055 11.025
19 16.48 2.955 10.664
THICKNESS (mm)
20 17.40 2.862 10.326

Maximum Insulattion Stess at Conductor + Screen at Nominal Operating


7.19
Voltage (kV)

Maximum Insulation Stess at Conductor + Screen at Short Duration Power


25.95
Freq. Withstand Voltage (kV)

Minimum Insulattion Stess at Conductor + Screen at Nominal Operating


2.86
Voltage (kV)

Minimum Insulation Stess at Conductor + Screen at Short Duration Power


10.33
Freq. Withstand Voltage (kV)