Support Overload Manual
Support Overload Manual
ADOVERLOADSYSTEM
(UserGuide)
ADOverloadSystem 2
ADOverLoadSystem
Rapidinstallation
Costeffective
Immunetooutsidedisturbancesandvariationsinsupplyvoltage
Stablemeasurementsoverlongperiodsandinvariableconditions
FUNCTIONAL FEATURES:
Simulationofloadwithaknownweightcorrespondingtoatleast25%oftheoverload
2levelstobeselectedbyoperator
3pushbuttonsforlevelsetting,scaleandzerosetting
4digitsindicatingweightandlevels
Outputsoncleanrelaycontacts
2LEDstoviewstateofrelays
1powerLEDtoshowelectricalsupply
3LEDstoshowstate(weight,zerosetting,
Supplyinputandrelayoutputonconnectorspitch3,96mm
Eliminationofbriefvariationsinweightmeasure
Constantautomaticcalibrationofthedevice
Weightblockconnectiontoeliminateweightvariationsduringliftoperation
ELECTRICAL FEATURES:
MECHANICALINSTALLATION:
Themetalsensorplatemustbeinstalledonthetractionropes.Itcanbepositionednearthecarframe
asshowninthefigure.
1. Bring the comb near to the ropes, after having inserted them and to push it until the complete ropes
fitting.
2. Bring the sensor near to the comb in order to position the ropes between the sensor and the comb.
3. Insert the fixing bolts and the washers into the sensor holes.
4. Bring the comb near to the sensor and screw hardly the bolts into the comb's hole.
5. Continue to screw with the spanner until the sensor and the comb are parallel and then in contact
between them.
6. Screw tight the bolts.
ADOverloadSystem 4
Thecontrolunitlinkedtothesensorwithcablelength3m.mustbefixednearthesensor.Forthe
controlunitfixingusethesuitablescrews.
ADOverloadSystem 5
ELECTRICALINSTALLATION
Please follow the instruction below:
Make sure that your power supply fits the above values (230 AC, 50 Hz) and then connect it to the main
connector into the Overload System (Fig.).
2. RELAY CONNECTION :
Connect the outputs of the relays RELAY1 and RELAY2 to the control board in the most suitable way
for your installation, considering that the relay accept maximum 3A at 220V AC and 3A at 30V DC.
AD- Overload System has an electronic device measuring variations while lift is moving. With the
Measuring Block connections such variations can be completely eliminated. The detected weight will
be memorized while lift is moving. To activate the option Measuring Block proceed as follows:
When the lift doors are closed, the current to the terminals should be between 40mA and 4A AC/DC:
CONTROL UNIT will not to be affected by weight variations when lift moves. The car load variations do
not affect the status of relays RELAY1, RELAY2 (overload) and the weight indication on the displays.
CALIBRATION PROCEDURE
Calibration procedure for lift capacity EQUAL or INFERIOR than 999 kilos
1.After the perfect and careful Mechanical Installation of both Sensor and Control Unit as explained
above, Move the Lift from TOP to BOTTOM at least five times through its way for Mechanical Stress
Adjustment.
2.For calibration process stop the lift at CENTRE FLOOR and leave doors open. The units on the display
indicator are turned off.
5.Wait at least 10 minutes before to begin with calibration procedure (thermic settle).
ADOverloadSystem 6
AD Overload System is provided with ZERO SETTING When NO LOAD on the plate.
6. Now press UP , for the NEW ZERO SETTING process at Current Site Location.
( UP button has a dual function . It is used for Increment if in Edit Mode else for Zero Setting)
When unit is in Zero Setting mode then LED indicated by ZERO will start blinking. The reading on
display at that time is due to the Unloaded Cabin weight.
7.Now move the Zero Setting POT such a way that the reading will display 200 kg( because cabin-car
load is initially set at 200kg).
9. After Exit from Zero Setting Process the Display will indicate 00 .
COMPANY PASSWARD : P. 09