Thermal Overload Parameter Values (Range) Unit Step Default
Thermal Overload Parameter Values (Range) Unit Step Default
FUNCTION 0-1-2 1 1
T6 3-40 Sec 1 6
STALL PROTECTION
Parameter Values (Range) Unit Step Default
FUNCTION 0-1 1 1
FUNCTION 0-1 1 1
LOCKED ROTOR LEVEL 120-800 % 10 120
TRIP DELAY 0-250 SEC 0.1 10
TRIP RESET MODE 2-3-4 1 4
FUNCTION 0-1,3 1 0
ALARM 10-90 % 1 80
TRIP 10-90 % 1 70
TRIP DELAY 0-60 SEC 1 10
TRIP RESET MODE 2-3-4 1 4
UNBALANCE PROTECTION
FUNCTION 0-1,3 1 0
ALARM 50-90 % 1 90
TRIP 50-90 % 1 85
TRIP DELAY 0-60 SEC 1 10
TRIP RESET MODE 2-3-4 1 4
UNDERLOAD PROTECTION
FUNCTION 0-1,3 1 0
ALARM 20-90 % 1 30
TRIP 5-90 % 1 20
TRIP DELAY 0-1800 SEC 1 10
TRIP RESET MODE 2-3-4 1 4
FUNCTION 0-1,3 1 0
FUNCTION 0-1 1 0
0=DISABLED; 1= ENABLED; 2=
DISABLED DURING START
Description
0=DISABLED; 1= ENABLED;
2=LOCAL;3=REMOTE; 4= LOCAL/REMOTE
STALL PROTECTION TRIP
STALL AFTER START UP
Description
0=DISABLED; 1= ENABLED;
ROTOR LOCKED DURING START UP PROTECTION TRIP
LONG START UP TRIP DELAY
2=LOCAL;3=REMOTE; 4= LOCAL/REMOTE
Description
0=DISABLED; 1= ENABLED; 3=
ALARM ONLY
IL MIN/ILMAX
IL MIN/ILMAX
PHASE FAILURE TRIP DELAY
2=LOCAL;3=REMOTE; 4= LOCAL/REMOTE
Description
0=DISABLED; 1= ENABLED; 3=
ALARM ONLY
IL MIN/ILMAX
IL MIN/ILMAX
UNBALANCE PROTECTION TRIP DELAY
2=LOCAL;3=REMOTE; 4= LOCAL/REMOTE
Description
0=DISABLED; 1= ENABLED; 3=
ALARM ONLY
IL MAX/IRATED
IL MAX/IRATED
UNDERLOAD PROTECTION TRIP DELAY
2=LOCAL;3=REMOTE; 4= LOCAL/REMOTE
Description
0=DISABLED; 1= ENABLED; 3=
ALARM ONLY
I0
I0
EARTH FAULT TRIP DELAY
2=LOCAL;3=REMOTE; 4= LOCAL/REMOTE
Description
0=DISABLED; 1= ENABLED;