SMART Transmitter Power Supply KFD2-STC4-Ex1

Features Assembly

1-channel isolated barrier


24 V DC supply (Power Rail)
Front view
Input 2-wire and 3-wire SMART transmitters and 2-wire Removable terminals
blue
SMART current sources
Output 0/4 mA ... 20 mA
Terminals with test points
1 2 3
4 5 6
Up to SIL2 acc. to IEC 61508
KFD2-STC4-Ex1

Function
LED green:
PWR Power supply
This isolated barrier is used for intrinsic safety applications.
The device supplies 2-wire and 3-wire SMART transmitters in
a hazardous area, and can also be used with 2-wire SMART
current sources.
7 8 9
It transfers the analog input signal to the safe area as an 10 11 12
13 14 15
isolated current value.
Digital signals may be superimposed on the input signal in the
Removable terminals
hazardous or safe area and are transferred bi-directionally. green
If the HART communication resistance in the loop is too low,
the internal resistance of 250 between terminals 8 and 9
can be used.
Test sockets for the connection of HART communicators are
integrated into the terminals of the device.

Application

The device supports the following SMART protocols:


HART
BRAIN 2
Foxboro

Connection
Release date 2010-06-28 15:07 Date of issue 2010-06-28 122580_ENG.xml

KFD2-STC4-Ex1

1+ 7-
HART

HART

2- 8+

mA
3 9
250

5-
HART

mA

6+ 14+
15-
24 V DC

Zone 0, 1, 2 24 V DC Zone 2
Div. 1, 2 Power Rail Div. 2
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group Tel.: Germany +49-621-776-0 USA +1-330-4253555 Singapore +65-67-799091 Internet www.pepperl-fuchs.com 1
Technical data KFD2-STC4-Ex1

General specifications
Signal type Analog input
Supply
Connection Power Rail or terminals 14+, 15-
Rated voltage 20 ... 35 V DC
Ripple within the supply tolerance
Power loss 1.5 W
Power consumption 1.9 W
Input
Connection terminals 1+, 2-, 3 or 5-, 6+
Input signal 0/4 ... 20 mA
Voltage drop Ud 2.4 V at 20 mA (terminals 5, 6)
Input resistance 64 terminals 2-, 3 ; 500 terminals 1+, 3 (250 load)
Available voltage 16 V at 20 mA terminals 1+, 3
Output
Connection terminals 7-, 8+, 9
Load 0 ... 800
Output signal 0/4 ... 20 mA (overload > 25 mA)
Ripple 50 A rms
Transfer characteristics
Deviation at 20 C / 0/4 ... 20 mA
10 A incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage
Influence of ambient temperature 0.25 A/C
Frequency range hazardous area into the safe area: bandwidth with 0.5 Vss 0 ... 7.5 kHz (-3 dB)
safe area into the hazardous area: bandwidth with 0.5 Vss 0.3 ... 7.5 kHz (-3 dB)
Rise time 20 s
Start-up time 200 s
Electrical isolation
Output/power supply functional insulation, rated insulation voltage 50 V AC
Directive conformity
Electromagnetic compatibility
Directive 2004/108/EC EN 61326-1:2006
Conformity
Electromagnetic compatibility NE 21:2006
Protection degree IEC 60529
Ambient conditions
Ambient temperature -20 ... 60 C (-4 ... 140 F)
Mechanical specifications
Protection degree IP20
Mass approx. 200 g
Dimensions 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 in) , housing type B2
Data for application in connection
with Ex-areas
EC-Type Examination Certificate BAS 99 ATEX 7060 , for additional certificates see www.pepperl-fuchs.com
Group, category, type of protection II (1)GD, I (M1) [Ex ia] IIC, [Ex iaD], [Ex ia] I (-20 C Tamb 60 C) [circuit(s) in zone 0/1/2]
Input Ex ia IIC
Supply
Release date 2010-06-28 15:07 Date of issue 2010-06-28 122580_ENG.xml

Maximum safe voltage Um 250 V (Attention! The rated voltage can be lower.)
Equipment terminals 1+, 3-
Voltage Uo 25.4 V
Current Io 86.8 mA
Power Po 551 mW
Equipment terminals 2-, 3
Current Io/Current Ii 74 mA / 115 mA
Current Ii 115 mA
Voltage Uo 3.5 V
Current Io 74 mA
Power Po 64 mW
Equipment terminals 1+, 2 / 3-
Voltage Ui 30 V
Current Ii 115 mA
Voltage Uo 25.4 V
Current Io 115 mA
Power Po 584 mW
Equipment terminals 5-, 6+

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group Tel.: Germany +49-621-776-0 USA +1-330-4253555 Singapore +65-67-799091 Internet www.pepperl-fuchs.com 2
Technical data KFD2-STC4-Ex1

Voltage Ui 30 V
Current Ii 115 mA
Voltage Uo 8.7 V
Current Io 0 mA
Output
Maximum safe voltage Um 250 V (Attention! The rated voltage can be lower.)
EC-Type Examination Certificate DMT 01 ATEX E 133
Group, category, type of protection I (M1) [EEx ia] I
Statement of conformity TV 99 ATEX 1499 X , observe statement of conformity
Group, category, type of protection, II 3G Ex nA II T4 [device in zone 2]
temperature classification
Electrical isolation
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 94/9/EC EN 60079-0:2006, EN 60079-11:2007, EN 61241-11:2006 , EN 60079-15:2005
International approvals
UL approval
Control drawing 116-0173 (cULus)
General information
Supplementary information EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of
Conformity and instructions have to be observed where applicable. For information see www.pepperl-
fuchs.com.

Accessories

Power feed modules KFD2-EB2...


The power feed module is used to supply the devices with 24 V DC via the Power Rail. The fuse-protected power feed module
can supply up to 100 individual devices depending on the power consumption of the devices. A galvanically isolated mechanical
contact uses the Power Rail to transmit collective error messages.
Power Rail UPR-03
The Power Rail UPR-03 is a complete unit consisting of the electrical inset and an aluminium profile rail 35 mm x 15 mm. To
make electrical contact, the devices are simply engaged.
The Power Rail must not be fed via the device terminals of the individual devices!
Release date 2010-06-28 15:07 Date of issue 2010-06-28 122580_ENG.xml

Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group Tel.: Germany +49-621-776-0 USA +1-330-4253555 Singapore +65-67-799091 Internet www.pepperl-fuchs.com 3