Ga Drawing For Local Control Panel For Area BF, Hm1, Hm2, LD, CH, Op, SP, SM, Co & RM Bulding

1) The document is a drawing for a local control panel for various building areas including HM1, HM2, LD, CH, OP, SP, SM, CO, and RM. 2) It shows the layout of the panel including components like MCCBs, busbars, HMI displays, and cable entries. 3) Key specifications are provided like the degree of protection being IP-52, fabrication from CRCA sheet metal according to GTS standards, and 100A TPN aluminum busbars rated for 50kA for 1 second.

Uploaded by

Nitin Bihani
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
3K views16 pages

Ga Drawing For Local Control Panel For Area BF, Hm1, Hm2, LD, CH, Op, SP, SM, Co & RM Bulding

1) The document is a drawing for a local control panel for various building areas including HM1, HM2, LD, CH, OP, SP, SM, CO, and RM. 2) It shows the layout of the panel including components like MCCBs, busbars, HMI displays, and cable entries. 3) Key specifications are provided like the degree of protection being IP-52, fabrication from CRCA sheet metal according to GTS standards, and 100A TPN aluminum busbars rated for 50kA for 1 second.

Uploaded by

Nitin Bihani
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 16

GA DRAWING FOR LOCAL CONTROL PANEL

FOR AREA BF, HM1, HM2, LD,


CH, OP, SP, SM, CO & RM BULDING

01 OF 16
PANEL PANEL
DOOR LOCKS MTG. LUGS
(4Nos.) (4Nos.)

R Y B
DEGREE OF PROTECTION IP-52
INDOOR TYPE APPLICATION
MCCB MCCB MCCB TIC HIC FABRICATION MATERIAL:- CRCA SHEET
ON OFF TRIP
AS PER GTS STANDARD
ON OFF ON OFF ON ON
M1 M2 M3

0-500V 0-100A
H1 H2 H3 H4 H5 H6 BUSBAR :- 100A TPN ALUMINIUM BUSBAR-50KA-1SEC.
PAC-1 PAC-2 HTR HUMD
PAC-1 PAC-2 ON OFF 25 x 5mm AL. PHASE
V A
SS2 SS3 25 x 5mm AL. NEUTRAL
ON OFF
25 x 5mm AL. EARTHING
PB1 PB2
PAC-1/2
ON OFF TRIP ON OFF TRIP COLOUR:- POWDER COATED RAL-7035
VSS ASS H7 H8 H9 H10 H11 H12 CABLE ENTRY:- BOTTOM
PUMP-1 PUMP-2
PUMP-1 PUMP-2

1250
ON
SS4 OFF

PB3 PB4
PUMP-1/2
ON OFF TRIP ON OFF TRIP
100A, TPN
MCCB H13 H14
CT-1
H15 H16 H17
CT-2
H18

INCOMER ON OFF ON OFF

PB5 PB6 PB7 PB8


CT-1 CT-2
CONTROL
ON
SS1

CHANGE OVER
SWITCH
100A TPN
50

400 800
300
1200

FRONT ELEVATION SIDE VIEW


PANEL
EARTHING
CONN.
(2Nos.)
300

GLAND PLATE
200 300 300 300 300 x 70 X 3mm Thk.
=

BOTTOM VIEW 02 OF 16
R R
Y Y
B B
N N
S1
0-100A
S3 A
S5
S A
CT S
100/5A
CL-1 CTS

100A, TPN MCCB


INCOMER

MCCB MCCB
AUX. TRIP
CONTACT CONTACT
INCOMER CIRCUIT DIAGRAM
M1 M2 M3
CF-1-3
2A
R
0-500V
Y V
B S V
100A TPN S
ALUMINIUM BUS BAR N
WITH H.S. SLEEVE NL-1
50KA-1Sec.
R Y B

CHANGE OVER
SWITCH
R Y B N 100A R Y B N 03 OF 16

INCOMER-1 INCOMER-2
R
3.6.A Y
5.1.A
B
N

MPCB-1 MPCB-2 MCB


20-25A 20-25A 10A-3P

6.3.E 6.4.E 6.4.E

C1 C2 C3

N N N

HEATER
(As per Location
Requirement)
PAC-1 PAC-2
11 TR/5.5 TR 11 TR/ 5.5 TR

CONTROL CIRCUIT DIAGRAM 04 OF 16


4.8.A
9.1.A

MPCB-3 MPCB-4 MPCB-5 MPCB-6


4-6.3A 4-6.3A 1-1.6A 1-1.6A MCB MCB
4A-2P 10A-2P

7.3.D 7.3.D 7.4.D 7.5.D 6.1.A 6.1.A

220V. AC
C5 C6 C7 C8

N N N N
C9 C9

10.7.D 10.7.D

DAMPER DAMPER
CONTROLLER CONTROLLER

FD-1 FD-2

PUMP-1 PUMP-2 COOLING COOLING


2.2 KW 2.2 KW TOWER-1 TOWER-2
0.55 KW 0.55 KW

CONTROL CIRCUIT DIAGRAM 05 OF 16


PHASE
5.8.B 7.1.A
SS1

INTERLOCK
PLC

OFF

PLC
STOP

ON PLC R1

10.4.B TIC-1 C1 C2

SS2

PAC-1 PAC-2

R3 R4
8.3.D 8.4.D

R1 C1 C2 C3
PAC-1 PAC-2 HEATER
11 TR/ 11 TR/ (As per Location
5.5TR 5.5TR Requirement)
5.8.B 7.1.E

CONTROL CIRCUIT DIAGRAM 06 OF 16


6.6.A
10.1.A
PHASE

R2 MPCB-5 MPCB-6

SS4
STOP PUMP-1 PUMP-2 STOP STOP

PLC PLC PLC


STOP STOP STOP

MPCB-3 MPCB-4
PLC PLC PLC
START R2 C7 C8
START START START START
START

R5 R6
8.6.D 8.7.D

R2 C5 C6 C7 C8
COOLING COOLING
TOWER-1 TOWER-2
6.6.F
10.1.D
NEUTRAL

CONTROL CIRCUIT DIAGRAM 07 OF 16


9.2E +
24V. DC

9.2E _
FROM PS1
FLOW FLOW LEVEL LEVEL
SWITCH SWITCH SWITCH SWITCH
PACKAGE PACKAGE C/T-1 C/T-2
UNIT-1 UNIT-2

R3 R4 R5 R6

CONTROL CIRCUIT DIAGRAM 08 OF 16


5.8.A
11.1.A

6A-MCB-2P 6A-MCB-2P 2A-MCB-2P 2A-MCB-2P

220V. AC 220V. AC 220V. AC 220V. AC

DC POWER DC POWER
PS1 SUPPLY PS2 SUPPLY

24V. DC 24V. DC

+ _ + _

8.1.A 8.1.A 10.1.D 10.1.D

CONTROL CIRCUIT DIAGRAM 09 OF 16


7.6.A 12.1.A

9.5.D 9.7.D MCB 2A-2P

+ 6.2D + 11.5.C
TIC-1 HIC-1
_ 6.2.D
_ 11.5.C SIGNAL
FROM
FIRE
SYSTEM
TIC HIC

9.5.D
9.7.D

FROM PS2
9.4.E +
24V. DC 4 TO 20mA
9.4.E
_
C9
TEMPERATURE
& RH SENSOR

7.6.E 12.1.D

TEMP./RH CONTROLLER CIRCUIT DIAGRAM

10 OF 16
9.8.A

MCB-6A-3P
SS3
MCB-6A-2P
OFF ON

LEVEL SWITCH THERMOSTAT-1

C4

10.6.B HIC-1
THERMOSTAT-2 500W-HEATER

HEATER
(As per Location
Requirement)

IN HUMIDIFIER TERMINAL BOX

HUMIDIFIER CIRCUIT DIAGRAM


11 OF 16
10.8.E
10.8.A
PHASE
2A
CF

NL-1
220V. AC

NEUTRAL
CONTROL SUPPLY C1

H1
PACKAGE UNIT-1 ON
C1

H2
PACKAGE UNIT-1 OFF
C2

H3
PACKAGE UNIT-2 ON
C2

H4
PACKAGE UNIT-2 OFF
C3

H5
HEATER - ON
C4

H6

HUMIDIFIER - ON
C5

H7

PUMP-1 ON

INDICATION LAMP CIRCUIT DIAGRAM


H8
C5

PUMP-1 OFF
H9

PUMP-1 TRIP
MPCB-3
C6

H10

PUMP-2 ON
C6

H11

PUMP-2 OFF
H12

PUMP-2 TRIP
MPCB-4
C7

H13

C/T-1 ON
C7

H14

C/T-1 OFF
H15

C/T-1 TRIP
MPCB-5
C8

H16

C/T-2 ON
C8

H17

C/T-2 OFF
H18

C/T-2 TRIP
MPCB-6
12 OF 16
TERMINAL
220V.AC TO FIRE
TO C9 PANEL
O/L-1 PAC-1

24V DC TO TEMP/RH SENSOR


+ TEMP + TEMP
+ RH + RH
TO TIC/HIC FROM TEMP/RH SENSOR
- (COM) - (COM)
O/L-2 PAC-2
SPARE
TERMINALS
+24V DC
PAC-1 FS
TO R3
+24V DC
O/L-3 PUMP-1 PAC-2 FS
TO R4
+24V DC
CT-1 LS
TO R5
+24V DC
O/L-4 PUMP-2 CT-2 LS
TO R6
PAC-PLC
INTERLOCK
O/L-5 COOLING PAC-PLC STOP
TOWER-1
PAC-PLC START

COOLING PUMP 1/2


O/L-6
TOWER-2 PLC-STOP
PUMP 1/2
PLC-START
C3 TO STRIP
CT-1
PLC-STOP
TO PLC TERMINAL DIAGRAM
HEATER
N CT-1
PLC-START
CT-2
PLC-STOP
C4
TO CT-2
N HUMIDIFIER PLC-START
4-20mA, +
MCB FROM TIC -
4-20mA, +
DC-1 FD-1 SUPPLY FROM HIC -

DC-2 FD-2 SUPPLY


13 OF 16
- NC CONTACT
A - AMMETER

- CONTACTOR COIL
V - VOLTMETER

- PUSH BUTTON
- INDICATING LAMP LED TYPE
WITH NO LEMENT

- PUSH BUTTON
- PUSH BUTTON
WITH NC LEMENT
- CURRENT TRANSFORMER

- CT SHORTLINK TERMINALS
- AUTO / MANUAL
SELECTOR SWITCH
- AUX RELAY
- TPN MCCB
- HUMIDITY IND. CONTROLLER
HIC

- CONTROL FUSE
- TEMP. IND. CONTROLLER
TIC

- O/L RELAY

- NEUTRAL LINK
LEGEND
- NO CONTACT

14 OF 16
NMDC ELECTRICAL BOQ FOR AC BUILDINGS
S. NO. ITEM DESCRIPTION RATING MAKE QTY .
CHANGE OVER SWITCH TPN/4POLE 100 Amp. C&S/SCHNEIDER/L&T
1 1
WITH ROTARY HANDLE
MCCB TPN /4-POLE (50KA FOR1Sce.) WITH 1C/O
2 100 Amp. SCHNEIDER/L&T/BCH/ SIEMENS 1
AUX. CONTACT, TRIP CONTACT (LV510487)
3 ROTARY HANDLE FOR MCCB - SCHNEIDER/L&T/BCH/ SIEMENS 1
4 SPREADER TERMINALS FOR MCCB - SCHNEIDER/L&T/BCH/ SIEMENS 2-SET
5 MPCB, WITH 1NO+1NC FRONT CONTACT 20-25 Amp. SCHNEIDER/L&T/BCH/ SIEMENS 2
6 MPCB, WITH 1NO+1NC FRONT CONTACT 4-6.3 Amp. SCHNEIDER/L&T/BCH/ SIEMENS 2
7 MPCB, WITH 1NO+1NC FRONT CONTACT 1-1.6 Amp. SCHNEIDER/L&T/BCH/ SIEMENS 2
8 MCB, 3-POLE 10 Amp. SCHNEIDER/L&T/SIEMENS 1
9 MCB, 3-POLE 6 Amp. SCHNEIDER/L&T/SIEMENS 1
10 MCB, 2-POLE 10 Amp. SCHNEIDER/L&T/SIEMENS 1
11 MCB, 2-POLE 6 Amp. SCHNEIDER/L&T/SIEMENS 3
12 MCB, 2-POLE 4 Amp. SCHNEIDER/L&T/SIEMENS 1
13 MCB, 2-POLE 2 Amp. SCHNEIDER/L&T/SIEMENS 3
CONTACTOR, 3-POLE (AC-3 DUTY) COIL 240V AC 40 Amp. SCHNEIDER/L&T/SIEMENS/BCH
14 2
WITH 2NO+2NC AUX. CONTACT
CONTACTOR, 3-POLE (AC-3 DUTY) COIL 240V AC 25 Amp. SCHNEIDER/L&T/SIEMENS/BCH
15 6
WITH 2NO+2NC AUX. CONTACT
CONTROL (AUX.) CONTACTOR COIL 240V AC 4 Amp. SCHNEIDER/L&T/SIEMENS/BCH
16 1
WITH 2NO+2NC CONTACT
17 SELECTOR SWITCH 2POLE, 2-WAY SALZER/KAYCEE 4
18 VOLT METER SELECTOR SWITCH SALZER/KAYCEE 1
19 AMP. METER SELECTOR SWITCH SALZER/KAYCEE 1
20 INDICATION LAMP-RED LED TECNIC/L&T/SIEMENS/BCH 8
21 INDICATION LAMP-YELLOW LED TECNIC/L&T/SIEMENS/BCH 6
22 INDICATION LAMP-GREEN LED TECNIC/L&T/SIEMENS/BCH 9
23 INDICATION LAMP-BLUE LED TECNIC/L&T/SIEMENS/BCH 1
24 PUSH BUTTON START SCHNEIDER/L&T/SIEMENS/BCH 4
25 PUSH BUTTON STOP SCHNEIDER/L&T/SIEMENS/BCH 4
26 RELAY MODULE, 24V, 8-WAY/2C/O REPUTED MAKE 1
27 AMMETER ANALOGUE TYPE 100 Amp. AE/MECO 1
28 VOLTMETER ANALOGUE TYPE 0-500 V AE/MECO 1
1200 x 1250 BCH/VENUS/MEDITRON/
29 PANEL SCHNEIDER/SEN &SINGH 1
x 300
30 BUS BAR ALUMINIUM 50KA FOR 1Sec. 25 x 5 mm REPUTED MAKE 1-Lot
31 220 V. AC TO 24 V. DC SUPPLY 2 Amp. SCHNEIDER/SIEMENS 2
32 CT, CL-1 100/5 Amp. KAPPA/PRAGATI/REPUTED 3
33 CONTROL FUSE WITH BASE 2 Amp. CONNECT WELL/REPUTED 4
34 CT SHORTING TERMINAL REPUTED MAKE 4
35 FIRE DAMPER CONTROLLER SYSTEM AIR 2
36 TEMPURATURE/RH CONTROLLER 96x96mm MASIBUS/PEPL/HONEYWELL/CHINO 2
37 NEUTRAL LINK REPUTED MAKE 4
38 WIRE FOR CONTROL CIRCUIT WIRING POLYCAB/KEI/BCH 200Mtr.
39 WIRE FOR POWER CIRCUIT WIRING POLYCAB/KEI/BCH 100Mtr.
40 TERMINALS CONNECT WELL/ WAGO/ELMEX 36
41 TERMINALS CONNECT WELL/ WAGO/ELMEX 64
42 LUG TERMINAL, INSULATOR PANEL HARDWARE - REPUTED 1-LOT

15 OF 16
NOTES:-
1. THE PANEL SHALL BE SINGLE FRONT, OPERATION & MAINTENANCE ON FRONT SIDE.
2. THE PANEL SHALL BE DUST & VERMIN PROOF. (DEGREE OF PROTECTION IP-52)
3. THE LOAD BEARING SECTION, FRAME SHALL BE FABRICATED OUT OF 2.0MM, NON LOAD
BEARING SECTION DOORS, COVERS & PARTITIONS SHALL BE FABRICATED OUT OF 1.6MM
THICK & GLAND PLATES SHALL BE FABRICATED OUT OF 3.0MM THICK MS. CRCA SHEET.
4. THE PANEL SHALL BE POWDER COATED RAL-7035
5. ALL DOOR & COVER WILL BE FULLY GASKET WITH NEOPRENE RUBBER.
6. ALL THE DOORS SHALL BE EARTHING WITH 2.5 SSQ.MM Cu. WIRE.
7. THE SIZES FOR THE WIRING SHALL BE AS FOLLOWS:-
(a) AC POWER WIRING (415V AC) - BLACK - AS PER RATING.
(b) AC CONTROL WIRING (230V AC.) -PHASE-GREY, NEUTRAL - BLACK - 2.5 SQ.MM. ,1100V.
(c) CT WIRING - GREY - 2.5 SQ.MM.
(d) EARTHING WIRING - GREEN - 2.5 SQ.MM.
8. ALL TERMINATING WIRE ENDS OF CONTROL WIRING SHALL BE PROVIDED WITH THE
SLEEVE AND FERRULE NUMBER ON IT FOR WIRE IDENTIFICATION.
9. INSPECTION & TESTING:-
(a) PHYSICAL CHECKING.
(b) INSULATION RESISTANCE (100 MEGGER ).
(c) FUNCTIONAL TESTS INCLUDING CONTROL & INTERLOCK FUNCTIONS.
10. AREAS COVERED FOR ELECTRICAL PANELS BF,HM1,HM2,
LD,CH,OP,SP,SM,CO & RM BUILDING.

12. MCCB & CONTACTOR RATING SHALL BE AS PER TYPE 2 COORDINATION CHART.

16 OF 16