CT Test Procedure
CT Test Procedure
1. IS 2705 (1992)
3. BS 3938 (1973)
SUBHASH
S.NAGENDRA 14.10.2016 02
KULKARNI
Nature of modifications Dessin Vrifi Date Rev
Dsignation
: TEST PROCEDURE - CT
Emploi : Page : 1/9
Format chelle Dossier Repre Identification
The terminal markings of the CT should be verified as per the customer approved drawings.
Polarity test is done while doing determination of error test. If the polarity is incorrect the Transformer
accuracy bridge will show Reverse Polarity.
Acceptance criterion:
The error values are to be displayed. If the polarity reverse the meter will display Reverse Polarity
Purpose:
CONNECTION DIAGRAM:
Ensure the CT secondary terminals and ground terminals are solidly grounded.
Increase the voltage to specified power frequency voltage & maintain it for one minute. Decrease the
voltage to pre-stress level i.e. 80 % of power frequency voltage and maintain it for one min. Decrease the
voltage to Highest system voltage & note down the PD value further decrease the voltage to
1.2 Um / /3 & note down the PD value.
If the CT has more than one primary winding all the primary terminals to be shorted before HV & PD test.
SUBHASH
S.NAGENDRA 14.10.2016 02
KULKARNI
Nature of modifications Dessin Vrifi Date Rev
Dsignation
: TEST PROCEDURE - CT
Emploi : Page : 2/9
Format chelle Dossier Repre Identification
Acceptance criterion:
CT should withstand the applied PF test voltage without any flash over.
Measured Partial Discharge values should be less than 5 pC at 1.2 x Um /3 & 10 pC at Um Voltage. Um =
HSV
Purpose:
To check the P.F. voltage withstand level with respect to BIL of the system.
To check the Internal ionization caused by loose connections & any voids inside the CT
Correct the measured secondary resistance to 75 C by using the formula given below.
(234.5 + 75) x Rct
R75 =
234.5 + 1
Acceptance criterion:
Purpose:
To know CT internal burden for protection windings.
SUBHASH
S.NAGENDRA 14.10.2016 02
KULKARNI
Nature of modifications Dessin Vrifi Date Rev
Dsignation
: TEST PROCEDURE - CT
Emploi : Page : 3/9
Format chelle Dossier Repre Identification
CONNECTION DIAGRAM:
SUBHASH
S.NAGENDRA 14.10.2016 02
KULKARNI
Nature of modifications Dessin Vrifi Date Rev
Dsignation
: TEST PROCEDURE - CT
Emploi : Page : 4/9
Format chelle Dossier Repre Identification
CONNECTION DIAGRAM:
Acceptance criterion:
The raise in excitation current measured from 1.0 VK to 1.1 VK should be less than 50 %
At specified knee point voltage excitation current should be less than specified as per approved drg./GTP
Purpose:
To know the V-I characteristics of the CT secondary core.
SUBHASH
S.NAGENDRA 14.10.2016 02
KULKARNI
Nature of modifications Dessin Vrifi Date Rev
Dsignation
: TEST PROCEDURE - CT
Emploi : Page : 5/9
Format chelle Dossier Repre Identification
Connection diagram is same as clause 7. Connect only P class cores to the source and keep open all
secondary and primary winding.
Calculate the secondary limiting emf as per the formula given below:
Acceptance criterion :
Purpose: To know the characteristics of the core during the flow of fault current.
SUBHASH
S.NAGENDRA 14.10.2016 02
KULKARNI
Nature of modifications Dessin Vrifi Date Rev
Dsignation
: TEST PROCEDURE - CT
Emploi : Page : 6/9
Format chelle Dossier Repre Identification
CONNECTION DIAGRAM:
Connect the standard CT (N) and test CT (X) as shown above .CAUTION: The secondary winding
which is not under test should be short circuited.
Increase the input voltage gradually so as to pass the required current through the primary K-L and P1- P2.
This current will be indicated as a percentage of the Rated current (%In) in the transformer accuracy
bridge.
Note down the ratio error (R.E%) and Phase displacement error (P.E in Minutes).
Ensure proper burden (output) is connected to the test CT i.e as specified by the customer. After increasing
the current to the required level decrease the current slowly. Never switch of the supply suddenly.
Metering CT : For 0.5 and 1.0 class conduct the % RE and PDE from 20 % to 120 % or up to the
extended primary current specified by the customer at 25 % and 100 % burden. For accuracy less than 0.5,
conduct the % RE and PDE from 5 % , 20% , 100% , 120% or up to the specified extended current at 25 %
and 100% burden. The measured values should be within claimed accuracy class.
Note : while doing accuracy test as a type test the procedure mentioned for less than 0.5%
accuracy to be followed.
P- class cores: Measure the % RE and PDE at rated current and burden.
PS or X class core : Measure the % RE by TRE Method
Important points to be noted while doing accuracy test are as follows:
Set the ratio of the standard CT in line with test CT correctly.
Short circuit the secondary cores which are not under test before this test.
Acceptance criterion:
The measured accuracy values should be within class of accuracy / standard requirement & as per customer
specification.
Purpose:
To know the accuracy of each type of core to eliminate the errors in measuring / protection system.
SUBHASH
S.NAGENDRA 14.10.2016 02
KULKARNI
Nature of modifications Dessin Vrifi Date Rev
Dsignation
: TEST PROCEDURE - CT
Emploi : Page : 7/9
Format chelle Dossier Repre Identification
CONNECTION DIAGRAM:
Short circuit all the secondary windings individually and connect the HV terminal of the HV breakdown
tester to any one winding. Connect all remaining secondary windings which are not under test to ground
along with ground terminal of the HV breakdown tester.
Apply specified voltage for one minute. Repeat the above procedure for all cores.
Apply 3kV r.m.s as per IS 2705 (1992) , IEC 60044-1 (2003)
Apply 2kV r.m.s as per AS 1675 (1986) , BS 3938 (1973), CAN3- C13-M83
As per GTP & customer specification, whichever is applicable.
Acceptance criterion:
There should not be any disruptive discharge during the test
Purpose :
SUBHASH
S.NAGENDRA 14.10.2016 02
KULKARNI
Nature of modifications Dessin Vrifi Date Rev
Dsignation
: TEST PROCEDURE - CT
Emploi : Page : 8/9
Format chelle Dossier Repre Identification
CONNECTION DIAGRAM:
Short circuit all secondary windings which are not under test. Connect Peak voltmeter across the full
winding under test. Connect one end of the peak voltmeter to ground.
Pass the current through the primary winding in such a way that the induced voltage across the secondary
winding should be the specified voltage. Maintain the same for one minute.
4.5 kV peak - as per IS 2705 (1992) , IEC 60044-1 (2003)
Ten times the rated knee point e.m.f or 10 kV peak which ever is low as per AS 1675
(1986), BS 3938 (1973) , CAN3- C13-M83
If primary injection method is not possible then secondary injection method is to be followed in line with
procedure mentioned in relevant standards.
Acceptance criterion:
There should not be any disruptive discharge during the test
Purpose:
SUBHASH
S.NAGENDRA 14.10.2016 02
KULKARNI
Nature of modifications Dessin Vrifi Date Rev
Dsignation
: TEST PROCEDURE - CT
Emploi : Page : 9/9
Format chelle Dossier Repre Identification