SDH2-Chapter 14-Design of Structures With Seismic Isolation PDF
SDH2-Chapter 14-Design of Structures With Seismic Isolation PDF
Key words: Base Isolation, Damage Control, Design Examples, Damping, Earthquake Engineering, Energy Dissipation,
Feasibility of Isolation, Friction Devices, High-Damping rubber bearings, IBC-2000, Lead-Rubber Bearings,
New Construction, Preliminary Design, Response Spectrum Analysis, Seismic Isolation, Seismic
Rehabilitation, Static Analysis, Time-History Analysis.
Abstract: This chapter surveys the principles, benefits, and the feasibility of seismic isolation. The basic principles of
seismic isolation are introduced first. Contrary to a perception held by many engineers, neither the concept
of seismic isolation is new nor its application is necessarily complex. What is new is the availability of
relatively new materials and devices worked to perfection over the last two decades and advances in
computational techniques now commonly in use by practicing engineers. Force-deflection characteristics ot
commonly used isolation devices are introduced next followed by guidelines for evaluation of the feasibility
of seismic isolation as an alternative for a given project. The differences in approach to new construction
and rehabilitation of existing structures are highlighted. The building code provisions for seismic isolation
are covered next. The very recently released year 2000 edition of the International Building Code (IBC-
2000) takes a much more simple approach to seismic isolation than did its direct predecessor, the 1997
edition of the Uniform Building Code (UBC-97). This is true even though the theory and objectives
implemented in both of these codes are the same. The simplification is largely due to incorporation of
spectral hazard maps in IBC-2000. A very practical side-effect of this incorporation is elimination of near-
fault factors from the design process simply because now they are explicitly contained in the map. In many
cases, design according to the new IBC-200 requirements will result in smaller displacement and force
demands on the isolation system and the structure above the isolation plane. This in terms mean that seismic
isolation can be implemented much more economically than it was possible under UBC-97. The IBC-2000
design provisions for seismic isolation are discussed in detail. A simple preliminary design procedure is
provided to aid engineers in initial sizing of the isolation devices. Several examples are provided to illustrate
the practical application of the material covered in this chapter.
723
724 Chapter 14
14. Design of Structures with Seismic Isolation 725
the cocktail-party level: why not detach the thereby providing protection to the building
building from the ground in such a way that the contents and components (Figure 14-2).
earthquake motions are not transmitted up
through the building, or are at least greatly
reduced? This conceptually simple idea has
required much research to make it feasible, and
only with modern computerized analysis has
become possible. Application has depended on
very sophisticated materials research into both
natural and composite materials in order to
provide the necessary performance.
the principles of seismic isolation. Kelly(14-6), the results provide an opportunity to validate
Buckle and Mayes(14-7) and Naeim and Kelly(14-8) computer modeling techniques which are then
provide an excellent history of world overview. used on full-size structures.
Other references containing overview material A third important development is in the skill
are given in references 14-25 and 14-41. of the engineering seismologist in estimating
The advantages of seismic isolation include ground motions at a particular site. Recent
the ability to eliminate or very significantly advances in seismology have given more
reduce structural and nonstructural damage, to confidence in site-specific ground motions
enhance the safety of the building contents and which take into account fault distances, local
architectural facades, and to reduce seismic and global geology, and return periods. These
design forces. These potential benefits are design motions are basic input to the computer
greatest for stiff structures fixed rigidly to the modeling of seismically isolated systems and
ground, such as low- and medium-rise are a vital step in the estimation of system
buildings, nuclear power plants, bridges, and performance.
many types of equipment. Some tectonic and In summary then, five recent developments
soil-foundation conditions may, however, are together responsible for elevating seismic
preclude the use of seismic isolation. isolation from fantasy to practical reality:
The design and manufacture of high-quality
14.1.1 An Idea Whose Time Has Come elastomeric (rubber) pads, frequently called
bearings, that are used to support the weight of
The elastomeric bearing and the mechanical the structure but at the same time protect it from
damper are fundamental components in many earthquake-induced forces.
seismic isolation schemes. But it is not just the The design and manufacture of mechanical-
invention of the elastomeric bearing and the energy dissipaters (absorbers) and high-
energy dissipater which has made seismic damping elastomers that are used to reduce the
isolation a practical reality. Three other parallel, movement across the bearings to practical and
but independent, developments have also acceptable levels and to resist wind loads.
contributed to its success. The development and acceptance of
The first of these was the development of computer software for the analysis of
reliable software for the computer analysis of seismically isolated structures which includes
structures so as to predict their performance and nonlinear material properties and the time-
determine design parameters. Work has been in varying nature of the earthquake loads.
progress for more than 25 years on the software The ability to perform shaking-table tests
for inelastic analysis of structural systems, and using real recorded earthquake ground motions
there are many available programs. Application to evaluate the performance of structures and
to seismically isolated structures is provide results to validate computer modeling
straightforward, and correlation studies with techniques.
model tests show many software systems to be The development and acceptance of
soundly based. procedures for estimating site-specific
The second development was the use of earthquake ground motions for different return
shaking tables which are able to simulate the periods.
effects of real recorded earthquake ground
motions on different types of structures. The 14.2 CONSIDERATIONS FOR
results of shaking-table tests over the last 20 SEISMIC ISOLATION
years (see Reference 14-16 to 14-22 and 14-31
to 14-40) have provided another mechanism to The need for seismic isolation of a structure
enhance confidence in the way buildings may arise if any of the following situations
respond during real earthquakes. In addition, apply:
728 Chapter 14
P ier
A n ch o r
E lasto m eric
B earin g
L ead
A rticu lated
S p h erical S lid er
C o n cav e
S u rface
Figure 14-9. Idealized force response spectrum
P T F E B earin g
M aterial
Figure 14-8. Most popular building isolation devices
(Top: the high damping rubber device; Middle: the lead-
rubber device; Bottom: the friction pendulum device).
measure of the energy dissipated during one with, say, a lead-rubber elastomeric bearing or
cycle of motion. Mechanical devices which use supplemental viscous dampers.
friction or the plastic deformation of either mild Friction is another source of energy
steel or lead to achieve this behavior have been dissipation which is used to limit deflections.
developed (14-9 to 14-14), and several mechanical- However, with the exception of the friction
energy dissipation devices developed in New pendulum system, it can be a difficult source to
Zealand are shown in Figure 14-13. quantify. A further disadvantage is that most
frictional devices are not self-centering, and a
permanent offset between the sliding parts may
result after an earthquake. The friction
pendulum system overcomes this problem by
using a curved rather than flat surface on which
the friction occurs. In proportioning a lead-
rubber system or a friction pendulum system
care must be exercised in design to ensure that
the restoring force during expected seismic
events would overcome the resistance of the
device to self-centering. In practice it is
common to compliment lead-rubber bearings
with ones without a lead core and this approach
Figure 14-11. Hysteretic force-deflection curve has proved to be very successful.
Hydraulic damping has been used
Many engineering materials are hysteretic by successfully in some bridges and a few special-
nature, and all elastomers exhibit this property purpose structures(14-7). Potentially high
to some extent. By the addition of special- damping forces are possible from viscous fluid
purpose fillers to elastomers, it is possible to flow, but maintenance requirements and high
increase their natural hysteresis without unduly initial cost have restricted the use of such
affecting their mechanical properties(14-10). Such devices.
a technique gives a useful source of damping, Rigidity for low lateral loads and flexibility
but so far it has not been possible to achieve the for high seismic loads is very desirable. It is
same level of energy dissipation as is possible clearly undesirable to have a structural system
732 Chapter 14
which will vibrate perceptibly under frequently seismic isolation systems require a wind
occurring loads such as minor earthquakes or restraint device for this purposetypically a
wind loads. rigid component designed to fail under a given
Lead-rubber bearings, well designed high level of lateral load. This can result in a shock
damping rubber bearings, as well as other loading being transferred to the structure due to
mechanical-energy dissipaters provide the the sudden loss of load in the restraint.
desired low load rigidity by virtue of their high Nonsymmetrical failure of such devices can
elastic stiffness (Figure 14-14). Some other also introduce undesirable torsional effects in a
14. Design of Structures with Seismic Isolation 733
after repeated earthquake cycles is highly for a rock site if the structure has sufficient
dependent on the vibratory characteristics of the elastic strength to resist this level of load. The
ground motion and may exceed the design lowest curve shows the forces which a typical
displacement. Consequently, minimum design code(14-28) requires a structure to be designed
requirements do not adequately define the peak for, and the second-lowest curve shows the
seismic displacement for seismic isolation probable strength assuming the structure is
systems governed solely by friction forces. The designed for the corresponding code forces. The
value of the coefficient must be high enough to probable strength is typically about 1.5 to 2.0
resist the wind forces. times higher than the design strength because of
the design load factors, actual material strengths
14.5 SEISMIC-ISOLATION which are greater in practice than those
DESIGN PRINCIPLES assumed for design, conservatism in structural
design, and other factors. The difference
The design principles for seismic isolation between the maximum elastic force and the
are illustrated in Figure 14-16. The top curve of probable yield strength is an approximate
this figure shows the realistic forces based on a indication of the energy which must be
5% ground response spectrum which will be absorbed by ductility in the structural elements.
imposed on a non-isolated structure from When a building is isolated, the maximum
typical code forces(14-28). The spectrum shown is elastic forces are reduced considerably due to
period shift and energy dissipation, as shown in
14. Design of Structures with Seismic Isolation 735
Figures 14-10 and 14-12. The elastic forces on 14.6.1 New Construction
a seismically isolated structure are shown by
the dashed curve in Figure 14-16. This curve Structure The first consideration in
corresponds to a system with as high as 30% assessing the suitability of a new project is the
equivalent viscous damping.(14-29) structure itself. Seismic isolation achieves a
If a stiff building, with a fixed-base reduction in earthquake forces by lengthening
fundamental period of 1.0 sec or less, is the period of vibration at which the structure
isolated, then its fundamental period will be responds to the earthquake motions. The most
increased into the 1.5- to 2.5-sec range (Figure significant benefits obtained from isolation are
14-10). This results in a reduced code design in structures for which the fundamental period
force (Figure 14-16), but more importantly in of vibration without base isolation is short
the 1.5- to 2.5-sec range the probable yield less than 1 sec. The natural period of a building
strength of the isolated building is generally increases with increasing height.
approximately the same as the maximum forces Taller buildings reach a limit at which the
to which it will be subjected. Therefore, there natural period is long enough to attract low
will be little or no ductility demand on the earthquake forces without isolation.
structural system, and the lateral design forces Therefore seismic isolation is most
can be theoretically reduced by approximately applicable to low-rise and medium-rise
50%, if the building code permits such a buildings and becomes less effective for high-
reduction. rise ones. The cut-off depends mainly on the
type of framing system. Shear-wall structures
14.6 FEASIBILITY OF SEISMIC and braced-frame structures are generally stiffer
ISOLATION than moment frames of equivalent height, and
so, for shear walls and braced frames isolation
Structures are generally suitable for seismic may be effective up to 12 to 15 stories, whereas
isolation if the following conditions exist: with moment frames the cut-off is generally
The subsoil does not produce a about 8 to 10 stories. These numbers are only
predominance of long period ground motion generalizations and there are, of course,
such as that obtained in Mexico City. exceptions, as discussed to the retrofits of the
The structure has two stories or more (or is 19-story Oakland City Hall and the 28-story
unusually heavy). Los Angeles City Hall. The isolation system
The site permits horizontal displacements at must also resist maximum lateral loads from
the base of the order of 8 in. or more. other sources without yielding in order to avoid
The structure is fairly squat. unacceptable displacements and vibrations
Wind lateral loads and other non-earthquake under service loads, such as wind. Therefore, if
load are less than approximately 10% of the these service lateral loads exceed about 10% of
weight of the structure. the structures weight, the building should not
Each project must be assessed individually be isolated.
and early in the design phase to determine its Soil Conditions The second consideration
suitability for seismic isolation. For this when assessing the suitability of a structure for
assessment, there are differences between new seismic isolation is the soil condition and the
construction and the retrofit of the existing geology of the site. Generally, the stiffer the
structures. The following sections provide some soil, the more effective the isolation.
guidelines for each of the situations. The flexibility of the structure determines
how it will respond to a given earthquake
motion. However, the form of the earthquake
motion as it arrives at the base of a structure
may be modified by the properties of the soil
736 Chapter 14
through which the earthquake waves travel. If earthquake safety of existing buildings without
the soil underlying the structure is very soft, the the addition of new structural elements which
high frequency content of the motion may be detract from the features which originally make
filtered out, and the soil may produce long- the building worth preserving. Although
period motions. An extreme example of this seismic isolation reduces earthquake forces, it
was seen in the 1985 Mexico City earthquake. does not eliminate them. Consequently, the
Lengthening the period of a stiff structure in strength and ductility of an existing structure
these lake-bed soil conditions will amplify must at least be sufficient to resist the reduced
rather than reduce the ground motions, and forces that result from isolation. If the strength
hence for sites such as Mexico City seismic of the existing structure is extremely low (less
isolation should not be considered. than 0.05 of the weight of the building), then
Another geologic consideration is the additional strengthening versus some
distance from a major fault. For near-fault strengthening and the provision of isolation will
situations, generally the design forces and need to be studied.
displacements are amplified to allow for the In addition to the conditions discussed
recently observed fling or pulse effect of near- above from new buildings, the issues to be
fault ground motions. addressed in the seismic isolation retrofit of an
Adjacent Structures A third consideration existing structure are:
in assessing suitability is any constraints Is there sufficient clearance with adjacent
imposed by adjacent structures at the proposed buildings to permit a movement of 6 to 24
site. As discussed earlier, the basic concept of inches?
seismic isolation systems minimize these Do the building and its existing foundations
displacements, but nevertheless base have sufficient strength and ductility to
displacements of the order of 8 to 20 in. resist the reduced seismic forces?
generally occur. If the site is very confined due What is the appropriate level for the plane of
to neighbouring buildings built on the isolationfoundation level, basement level,
boundary, it may not be possible to ground level, or the top, bottom, or mid-
accommodate these displacements. height of the columns?
The pros and cons with regard to the plane
14.6.2 Retrofit of Existing Structures of isolation are:
Any structure with a full subbasement or
Retrofit of existing structures to improve basement that can be temporarily disrupted
their earthquake safety involves additional is a good isolation candidate, since the work
considerations, compared with new can be confined to that area.
construction, because of the constraints already A structure with piled foundations can be
present. Some structures are inherently more more easily retrofitted at the foundation
suitable for retrofit using seismic isolation than level than one with spread footings.
others. For example, bridge superstructures are Provisions for the zone of isolation at the
generally supported on steel bearings. top, bottom, or mid-height of the basement-,
Replacement of these bearings with elastomeric first-, or second-level columns requires a
ones is a fairly simple, low-cost operation that detailed evaluation of the column capacities.
will lead to a reduction in earthquake forces and If the strength of the column is not sufficient
allow the option of redistributing forces away to resist the reduced isolation forces, three
from the weak substructures into abutments potential options exist. First, the column
more capable of sustaining them(14-30). may be strengthened and act as a cantilever.
Buildings are often more difficult to retrofit Second, a new framing system with stiff
than bridges. However, seismic isolation may beams may be developed at the plane of
often be an effective solution for increasing the isolation to reduce the column forces. Third,
14. Design of Structures with Seismic Isolation 737
the mid-height column solution may be before significant softening of the bearing
considered, since it reduces the column occurs.
moments significantly. Therefore, if uplift is indicated in an isolated
In summary, seismic rehabilitation of an structure, detailed analysis must be performed
existing structure provides the ability to confine to quantify the vertical displacements for
most of the construction work to the level connection design. This involves a nonlinear
where the plane of isolation is to be provided, analysis with realistic maximum credible
whereas conventional methods generally earthquake records and requires significant
require the addition of structural elements to all analytical effort.
levels of the building. This trade-off can be To avoid this, the optimum strategy is to
very important if continued use of the facility is avoid or minimize uplift. This is done by
desired, as in hospitals or command and control careful configuration of the lateral load-
centers. resisting elements. The important parameters
are the height-to-width ratio of the lateral load-
14.6.3 Uplift and Overturning resisting system and the amount of gravity load
carried by these elements. Another alternative is
In many types of structural systems to utilize the loose-bolt connections which
increasing lateral forces will induce net tensions permit certain amount of isolator uplift without
in elements once the axial loads caused by the subjecting the bearing to net tension. Such
overturning moment exceeds the gravity loads. connections have been successfully
This may occur for example at the edges of implemented in several major buildings in
shear walls or the columns in braced or southern California such as the Los Angeles
moment-resisting frames. City Hall seismic retrofit and the Lake
In conventional design this tension is Arrowhead and Saint John new hospital
resisted in the base connections and buildings.
foundations, although only if it occurs under the
code levels of the earthquake lateral loads. The 14.7 DESIGN CODE
more severe loading occurring under actual REQUIREMENTS
maximum earthquakes will produce overturning
moments much greater than the design value, By the time this book reaches the market the
and therefore tension forces will be induced design of new seismically isolated buildings in
even where none are indicated under code United States will be probably governed by the
loading. In this case, it is assumed that the International Building Code 2000 (IBC-
structural detailing and redundancies are 2000)(14-42). It is likely, however, that design in
sufficient to prevent failure due to the uplift. some jurisdictions will be still controlled by the
More recent studies(14-16) have indicated that provisions of the IBC-2000 predecessor, (UBC-
uplift may in fact be beneficial in reducing 97)(14-43). As documented by Naeim and
earthquake forces in conventional structures. In Kelly)(14-8) UBC-97 is an unnecessarily
Fact, at least two actual structures in New complicated and conservative as far as seismic
Zealand have been explicitly designed for uplift isolation design is concerned. Therefore, in this
as a form of seismic isolation: a stepping bridge section we limit our discussion to the provisions
and a chimney stack. of IBC-2000. Readers who are interested in
For a structure isolated on elastomeric learning more about UBC-97 and its
bearings, the effects of uplift must be examined predecessors are referred to the referenced
more carefully, since the elastomeric bearing is textbook by Naeim and Kelly.
not suitable for resisting large tensile loads. For Primarily intended to regulate the design of
a fully bolted connection, an elastomeric new buildings, the IBC-2000 does not really
bearing can resist 250 to 300 psi in tension cover the retrofit of existing buildings using
738 Chapter 14
isolation, although most retrofit projects do Notice that this is different from UBC-97
follow either the IBC or UBC regulations definition of MCE which was 10%
closely. IBC-2000 regulations are written in probability of being exceeded in 100 years
such a way as to be nonspecific with respect to (1000-year return period earthquake)
isolation systems. No particular isolation
systems are identified as being acceptable, but 14.7.1 Design Methods
the regulations require that any isolation system
should be stable for the required displacement, Static Analysis: For all seismic isolation
provide increasing resistance with increasing designs it is necessary to perform a static
displacement, and have properties that do not analysis. This establishes a minimum level for
degrade under repeated cyclic loading. design displacements and forces. The static
The underlying philosophy is that an analysis is also useful both for preliminary
isolated building designed using IBC-2000 will design of the isolation system and the structure
out-perform fixed-base construction in when dynamic analysis is required and for
moderate and large earthquakes. It is not the design review; under certain circumstances it
intent of the code to reduce the construction may be the only design method used.
cost but to minimize damage to isolated Static analysis alone will suffice if:
structures and their contents. 1. The structure is located at a site with S1 <
Increasingly, the seismic upgrade design of 0.60g. S1 is determined using the spectral
existing structures is influenced by the NEHRP acceleration maps published as a part of
Guidelines for the Seismic Rehabilitation of IBC-2000.
Buildings (FEMA-273) and its commentary 2. The site soil is classified as Class A, B, C,
(FEMA- 274), which are published by the or D (see Chapter 3).
Federal Emergency Management Agency(14-44, 3. The structure above the isolation plane is
14-45)
. FEMA-273 provisions are very similar to not more than four stories or 65 feet in
those of the IBC-2000 with one exception: height.
FEMA-273 permits a new analysis approach 4. The effective period at maximum
called Static Nonlinear Analysis or the displacement of the isolated system, TM,
Pushover method (see Chapter 15). does not exceed 3.0 seconds.
A 1986 document published by a 5. The effective period at design displacement,
subcommittee of the Structural Engineers TD, is greater than three times the elastic,
Association of Northern California (SEAONC) fixed-base period of the structure.
and generally referred to as the Yellow Book(14- 6. The structural system above the isolation
26)
has served as the backbone of all new code plane is regular.
provisions. 7. The effective stiffness of the isolation
The seismic criteria adopted by current system at design displacement is greater
model codes involve a two-level approach to than one third of the effective stiffness at
seismic hazard, which are as follows: 20% of design displacement.
The Design Basis Earthquake (DBE): That 8. The isolation system can produce the
level of ground shaking that has a 10% restoring force requirements mandated by
probability of being exceeded in 50 years the code (IBC-2000 Sec. 1623.5.1.4).
(475 year-return period earthquake) 9. The force deflection characteristics of
The Maximum Considered Earthquake isolation system are independent of rate of
(MCE): The maximum level of ground loading, vertical load, and bilateral load.
shaking that may ever be expected at the 10. The isolation system does not limit MCE
building site. MCE is taken as 2% displacements to less than SM1/SD1 times the
probability of being exceeded in 50 years total design displacements.
(2500-year return period earthquake).
14. Design of Structures with Seismic Isolation 739
Dynamic Analysis: Dynamic analysis may isolated periods at design displacement and
be used in all cases and must be used if the maximum displacement, respectively.
requirements mentioned for adequacy of static 6. Each pair of time histories is to be applied
analysis are not satisfied. Dynamic analysis simultaneously to the model considering the
may take the form of response spectrum most disadvantageous location of mass
analysis or time-history analysis. eccentricity. The maximum displacement of
Response spectrum analysis would suffice if the isolation system is to be calculated from
requirements number 2 and 7-10 as mentioned the vectorial sum of the two orthogonal
for static analysis, are satisfied. Otherwise, a components at each time step.
time-history analysis will be required. Use of 7. The parameters of interest are calculated for
more than 30% critical damping is not each time-history analysis. If three time
permitted in response spectrum analysis even if history analyses are performed, then the
the system is designed to provide for more. maximum response of the parameter of
Regardless of the type of dynamic analysis interest is to be used for design. If seven or
to be performed a site-specific design spectra more time histories are used, then the
corresponding to DBE and MCE events must be average value of the response parameter of
developed and used (instead of the code interest may be used.
published default spectra) if: As Naeim and Kelly have pointed out (14-8),
The structure is located on a Class E or F this formulations contains implicit recognition
site, or of the crucially important fact that design
The structure is located at a site with S1 < spectra are definitions of a criteria for structural
0.60g. analysis and design and are not meant to
If time history analysis is to be performed, represent characteristics of a single event.
then a suite of representative earthquake ground
motions must be selected that satisfy the 14.7.2 Minimum Design Displacements
following requirements:
1. At least three pairs of recorded horizontal Four distinct displacements calculated using
ground motion time-history components simple formulas and used for static analysis,
should be selected and used. also serve as the code permitted lower bound
2. The time histories should be consistent with values (subject to some qualification) for
the magnitude, fault distance, and source dynamic analysis results. These are:
mechanisms that control the DBE and/or DD: the design displacement, being the
MCE events. displacement at the center of rigidity of the
3. If appropriate recorded time-histories are isolation system at the DBE;
not available, appropriate simulated time- DM: the displacement,at the center of rigidity
histories may be used to make up the the of the isolation system at the MCE;
total number of required records. DTD: the total design displacement, being the
4. For each pair of horizontal ground motion displacement of a bearing at a corner of the
components, the square root sum of the building and includes the component of the
squares (SRSS) of the 5 percent-damped torsional displacement in the direction of DD
spectrum of the scaled horizontal DTM: same as DTD but calculated for MCE.
components is to be constructed. DD and DM are simply spectral displacement
5. The time-histories are to be scaled such that values calculated assuming constant spectral
the average value of the SRSS spectra does velocity from code published spectral maps and
not fall below 1.3 times the 5 percent- adjusted for damping.
damped design spectrum (DBE or MCE) by
more than 10 percent over a range of 0.5TD
to 1.25TM where TD and TM are effective
740 Chapter 14
g S M 1TM 1
DM = 2 (14-2) = 0.25(1 ln ) (14-7)
4 BM B
where g is the gravitational acceleration, SD1 where is given as the fraction of critical
and SM1 are spectral coefficients, TD and TM are damping (not as a percentage).
isolated periods, and BD and BM are damping
coefficients corresponding to the DBE and 14.7.3 Effective Isolated System Periods
MCE level responses, respectively.
SD1 and SM1 are functions of two parameters: The effective isolated periods TD and TM
S1, the MCE 5% damped spectral corresponding to the DBE and MCE response
acceleration for the site available from the are computed from
maps accompanying the IBC-2000 and also
available on Internet via the USGS and W
CDMG web sites, and TD = 2 (14-8)
Fv, the site coefficient defined for various
K D min g
site classes and acceleration levels (see
Chapter 3).
Such that W
TM = 2 (14-9)
K M min g
S M 1 = Fv S1 (14-3)
where
W = the weight of the building
2
S D1 = SM1 (14-4) g = gravity
3 KDmin = minimum effective horizontal stiffness
of the isolation system at the design
The effective damping in the system, , at displacement (DBE).
the DBE and MCE response levels (referred to KMmin = minimum effective horizontal stiffness
as D and M are computed from of the isolation system at the maximum
displacement (MCE).
1 total area of hysteresis loop The values of KDmin, and KMmin are not
D = (14-5) known to the engineer during the preliminary
2 K D 2
D , max D design phase. The design procedure will begin
with an assumed value which is obtained from
previous tests on similar components or by
total area of hysteresis loop using the material characteristics and a
1 (14-6)
M =
schematic of the proposed isolator. After the
2 K M , max D 2
M preliminary design is satisfactorily completed,
prototype isolators will be ordered and tested,
KDmax and KMmax are effective stiffness terms and the values of KDmin, KDmax, KMmin, and KMmax
defined in Section 14.7.3. The damping will be obtained from the results of the
reduction factors BD for the DBE and BM for the prescribed program of tests on the prototypes.
MCE are given in a tabular form (IBC-2000,
14. Design of Structures with Seismic Isolation 741
This is so, although the seismic isolation theory considered whenever the interstory drift ration
suggests a uniform distribution of forces over exceeds 0.010/RI.
the height of the superstructure. Therefore, the
lateral force at level x, denoted by Fx, is 14.7.7 Peer Review
computed from the base shear, VS, by
IBC-2000 similar to its predecessors
hx w x requires the design of the isolation system and
Fx = Vs (14-15) the related test programs to be reviewed by an
i =1 wi hi
N
independent team of registered design
professionals and others experienced in seismic
where wx and wi are the weights at level i or x analysis methods and theory and application of
and hx and hi are the respective heights of seismic isolation. The scope of this review
structure above isolation level. includes, but is not limited to the following
items:
14.7.6 Drift Limitations 1. Review of site-specific design ground
motion criteria such as design spectrum and
The maximum interstory drift (relative time-histories as well as other project-
displacement of adjacent floors) permitted by specific information.
the IBC-2000 is a function of method of 2. Review of the design criteria and the
analysis in that more drift is permitted when preliminary design procedures and results.
more sophisticated analyses are performed. 3. Overview and observation of the prototype
Static Analysis: The drift at any level x is testing program.
calculated from Equation 14-16 and should not 4. Review of the final design of the entire
exceed 0.015hsx (hsx is the story height below structural system and supporting analyses
level x). and calculations.
5. Review of the isolation system quality
RI se control and production testing program.
x = (14-16)
IE
14.7.8 Testing Requirements for
Isolators
where se is the drift determined by an elastic
analysis and IE is the occupancy importance Code testing requirements of the isolator
factor for the building as defined in Chapter 5. units before they can be accepted are contained
Response Spectrum Analysis: The drift at in Section 16.23.8 of IBC-2000. The code
any level x calculated from response spectrum requires that at least two full-sized specimens of
analysis should not exceed 0.015hsx. each type of isolator be tested. The sequence
Time-History Analysis: The drift at any and the necessary number of cycles of testing
level x calculated from a time-history analysis vary with the amount of deformation the
considering the nonlinear behavior of the isolators are subjected to. For example, twenty
isolators should not exceed 0.020hsx. The code fully reversed cycles of loading is to be
has an additional paragraph stating that this performed at a displacement corresponding to
drift should be calculated using Equation 14-16. the wind design force.
However, the relevance of such a provision to The tests required are a specified sequence
nonlinear time-history analysis is not clear and of horizontal cycles under D + 0.5L from small
this may be just a printing error in the very first horizontal displacements up to DTM. The
edition of the IBC that has just been released at maximum vertical load used during testing is
the time of this writing. P- effects must be 1.2DL + 0.5LL + Emax, and the minimum is
0.8DL - Emin where Emax and Emin are the
14. Design of Structures with Seismic Isolation 743
Figure 14-17. Bearings located at top of basement Figure 14-19. Bearings located at top of first story
columns columns
746 Chapter 14
2. The connections must have the capacity for weight while the bearing is removed, and (ii) a
transferring maximum seismic forces means of removing the bearing without undue
between the substructure and the damage to the connections.
superstructure. The ease of meeting this first requirement
3. Ease of construction must be kept in mind to will depend on the location of the bearings and
insure access for installation and, in the case type of backup safety system used. In a
of a retrofit, temporary support for the subbasement, jacks can generally be used
superstructure. between the foundation and basement floor to
support the bearing load. If a backup safety
The most common bearing construction has system is used (as described in the following
outer load plates of - 1 in. steel covered by section), provision for jacking may be
1/8 in. rubber layers. During the manufacture, incorporated into the design. Bearing locations
holes for bolts or dowels are formed through at the top of columns will require shoring to be
the outer rubber layers and load plates. Exterior erected around columns to provide a jacking
cover plates with bolts or dowels are then added platform if a backup system has not been
to the bearing prior to installation. These provided.
exterior plates may be either welded or bolted The removal of the bearing once the load is
to the structure. It is important to insure that the removed will be simplified if bolted
bolts or dowels do not intrude into the internal connections are used to connect to the structure.
rubber layers. Figure 14-20 is an example of a For example, the connection detail shown in
connection detail using dowels. The more Figure 14-20 could be modified to simplify
common trend is to use fully bolted rather than bearing removal. In this modification, double
dowelled connections. plates would be added at the bottom of the
bearing as shown in Figure 14-21. The bearing
14.8.3 Provision for Bearing Removal complete with dowel plates could then be
removed. For a welded connection, removal
Where practical, provision should be made would entail cutting the welds.
to ease removal and replacement of the bearings A combination of a removal and backup
should this ever be necessary. This requires two safety-system detail is shown in Figure 14-22.
things: (i) a means of supporting the building
14. Design of Structures with Seismic Isolation 747
One of the most important parameters in For bearings with very large shape factors the
design of elastomeric bearings is the shape compressibility of rubber affects the value of
factor, S, defined as Ec. In such cases a more accurate estimate of Ec
may be obtained from
14. Design of Structures with Seismic Isolation 749
4Qd (D Qd 9 K u )
eff = (14-25)
2 (K u D + Qd )D
W
KH = (14-26)
R
R
T = 2 (14-27)
g
Figure14-25. Typical bilinear hysteresis loop
The characteristic strength, Qd, can be The effective (peak-to-peak) stiffness of the
accurately estimated as being equal to the yield isolator is given by
force of the lead plug. The yield stress of lead is
about 1,500 psi. The effective stiffness of the W W
K eff = + (14-27)
lead-plug bearing, Keff, at a horizontal R D
750 Chapter 14
where is the friction coefficient and all other The average sustained load on an interior
terms are defined previously. The friction isolator is 500 kips.
coefficient has been shown to be independent of The fixed-base period of the super-structure
velocity for pressures of 20 ksi or more on the is estimated to be about 0.70 seconds.
articulated slider(14-8). The damping provided by From IBC-2000 for this site, SD1=0.56
the system, , is a function of horizontal Estimate the size of isolators needed for each of
displacement and may be obtained from the three alternatives and the corresponding
seismic design base shears so that the architect
2 and engineers could make substantial progress
= (14-28) while you are performing your final design of
+D R
the isolators and preparing for procurement and
prototype testing process.
An estimate of the rise of the structure
(vertical displacement) as a result of movement SOLUTION
along the curved surface of the isolator may be
obtained from
TD 3T fixed base = 3(0.7) = 2.1 sec.
1 D2
V (14-29) T be on the safe side, take TD=2.5 sec for
2 R preliminary design. The reduction fact, RI for
the superstructure is calculated from Eq. 14-14
as
14.9.4 Design Example
3
Assume you are in charge of designing a 1.0 RI = (6) = 2.25 2.0 RI = 2.0
four story isolated building. The owner, a 8
public entity, requires that the design
accommodate competing isolation systems to a) High-Damping Rubber Isolators
bid on the job. The architect needs to know the To be conservative we size the isolator
maximum dimensions of the isolators so that under largest sustained load. That is an interior
she can complete her schematic design. Your isolator under 500 kips of load. We take
engineering team needs to know the design base damping to be 10% subject to verification.
shears for proportioning the structural system Therefore, from Eq. 14-17 or from Table
above and the elements below the isolation 1623.2.2.1 of IBC-2000, BD=1.20.
surface. You would like to estimate these We take a typical high damping rubber
values for three alternative isolation systems: compound with G=145 psi and K=300 ksi.
a) a high damping rubber system Therefore, our first estimate for the horizontal
b) a lead-rubber system which may or may not stiffness of the isolator is obtained from Eq. 14-
be complimented by ordinary low-damping 8 as
isolators, and
2 2
c) a friction pendulum system. W 2 500 2
The following information is also available KH = = = 7.35 k/in.
gT 386 2.5
to you at this time.
The structural system above the isolation
The design displacement is obtained from
plane is a shear wall system with R = 6.
Eq. 14-1
The total weight of the building is 14,120
kips.
There are a total of 60 support points (i.e., g (0.56 )(2.5)
DD = 2 = 11.43 in.
60 isolators). 4 1.20
14. Design of Structures with Seismic Isolation 751
Usually we want to achieve this Let us now estimate the base shear coefficient
displacement at about 150% shear strain. From for design of the superstructure, Cs, and the
Eq. 14-19 , we can estimate the total rubber corresponding value for the base, Cb.
thickness required
Vb K H D 8.65(11.43)
D 11.43 Cb = = = 0.20
= tr = = 7.6 in. W W 500
tr 1.50 C
Cs = b 0.10
RI
Now we calculate the cross-sectional area
and the required diameter of the bearing from
b) Lead-Rubber Isolators
Eq. 14-18
It is usually more beneficial to begin
designing isolation systems using LRB isolators
K H tr 7.33(7.6 )
A= = = 384 in 2 as a system and then assign individual isolator
G 0.145 properties. The reason is that often the best
4A 4(384) solution is a combination of LRB isolators and
= = = 22.12 in low damping rubber isolators (i.e., isolators
without the lead plug).
Use = 24 in. In LRB isolators since damping comes from
the lead core, usually there is no need to use
Now we re-calculate A, KH and TD based on high damping rubber and therefore ordinary
this bearing diameter: rubber is generally used. Given the solution in
Part (a) of this problem, it is obvious that we do
2 (24)
2
not need a large amount of damping here.
A= = = 452 in 2 Therefore, we use 15% critical damping subject
4 4
to verification and a rubber compound with a
K H = 7.35(452 384) = 8.65 k/in shear modulus of G=60 psi.
TD = 2.50 (7.33 8.65) = 2.3 sec f 2.1 sec
The same target period of 2.5 seconds is
maintained. Either from Eq. 14-17 or from
Selecting a shape factor of S=10, from Eq. 14-
Table 1623.2.2.1 of IBC-2000, for =15%,
17 we can calculate the thickness of individual
BD=1.35 and from Eq. 14-1
rubber layers, t
g (0.56)(2.5)
t= =
24
= 0.6 in, say 5 8 " DD = 2 = 10.16 in.
4 S 4(10 ) 4 1.35
7 .6
number of layers = = 12.1, say 12 Treating the entire isolation system as a unit,
58 the required stiffness corresponding to this
t r = 12(5 8) = 7.5 in period is
2 2
Using 0.1in thick steel shim plates and one inch W 2 14,120 2
KH = = = 231 k/in.
top and bottom end plates, the total height of gT 386 2.5
the bearing is
The energy dissipated per cycle is
h = 7.5 + 2(1.0 ) + 11(0.1) = 10.6 in
752 Chapter 14
= 22,462 k - in Qd 578
K pb = = = 57 k - in
D 10.16
The area of the hysteresis loop, however, is
also given by
and the remainder of required stiffness has to be
WD = 4Qd (D D y )
provided by rubber. Therefore,
Qd 552
and if ignore Dy because of its relatively small K rubber = K H = 231 = 176 k - in
D 10.16
size
The total cross sectional area of the rubber is
W 22,462
Qd D = = 552 kips
4 D 4(10.16) (24)
2
Arubber = 60 385 = 26,744 in 2
4
Now, we can estimate Kd from Eq. 14-23:
and from Eq. 14-18, we can now establish the
Q 552
K d = K eff d = 231 required total rubber thickness, tr, as
D 10.16
= 176 kips/in
tr =
GA
=
( )
60 10 3 (26,744 )
K rubber 176
and since
= 9.1 in
Qd
Dy = and K u 10 K d , then Therefore, assuming 1.0 inch thick top and
Ku K d bottom end plates and steel shims, our isolators
Qd 552 will have a height of less than 12 inches.
Dy = = 0.35 in.
9 K d 9(176) The seismic shear coefficients are calculated
as in Part (a):
The total cross sectional area of the lead 231(10.16)
plug area needed for the entire isolation system Cb = = 0.167
is 14,120
0.17
Cs = = 0.083
Qd 552 2
pb =
Atotal pb
= = 368 in 2
Fy 1.5
c) Friction Pendulum System
For the sake of simplicity, we keep the Using the same target period of 2.5 seconds,
diameter of all isolators the same at =24 in. from Eq. 14-27
Using 3.5 inch diameter lead cores in 40 of the
60 isolators provides a lead cross sectional area R
2.5 = 2 R = 61.23 in
of slightly more than 385 square inches. Now 386
we have to recalculate Qd based on this new
area of lead Eq. 14-28 indicates that effective damping
and maximum displacement are inter-related.
Qd = 385(1.5) = 578 kips For example, assuming a coefficient of friction
14. Design of Structures with Seismic Isolation 753
of =0.06 and a design displacement of D=12 States indicates that it depends on two primary
inches, we get variables: the design force level of the
conventional building and the location of the
2 0.06 plane of isolation. The theory of seismic
eff = = 15% isolation permits substantial cost savings for
0.06 + 12.0 61.23
isolated buildings compared to convention
construction. However, given the current code
The selected value of D=12 inches satisfies regulations, the initial cost for seismic isolated
the minimum code prescribed displacement of structures can be equal to or exceed the cost for
10.16 inches which was calculated for the same a similarly situated fixed base building by as
basic parameters (T=2.5 sec., =15%, B=1.35) much as 5%. However, one should keep in
in Part (b). mind that this is a very minor price to pay for
From Eq. 14-27 the effective total stiffness achieving a structures which will have a
of the FPS isolation system consisting of 60 substantially better seismic performance during
identical isolators will be major earthquakes. Simply stated, achieving the
level of performance provided by seismic
14,120 0.06(14,120 )
K eff = + = 301 k/in isolation is virtually impossible through
61.23 12.0 conventional construction.
For the retrofit of existing buildings, seismic
and the seismic base shear coefficients are isolation may only be technically applicable in
calculated as before: one out of approximately eight buildings. When
it is technically feasible it has the attractive
301(12.0)
K eff D feature that most of the construction work is
Cb = = = 0.25 confined to the basement area. Retrofit
W 14,120
construction costs, when compared to a
C 0.25 conventional code force level upgrade, have
Cs = b = = 0.125
RI 2 been shown to be comparable. In addition,
disruption to the operation of the facility may
be avoided during construction with the use of
seismic isolation.
14.10 CONCLUSIONS
One of the major difficulties in comparing
the costs and benefits of a conventional and an
Several practical systems of seismic
isolated structure is the significant difference in
isolation have been developed and implemented
their performance characteristics. In the only
in recent years, and interest in the application of
such design performed to date, a critical Fire
this technique continues to grow. Although
Command and Control Facility for Los Angeles
seismic isolation offers significant benefits, it is
County required both a conventional and an
by no means a panacea. Feasibility studies are
isolated two story structure to meet the same
required early in the design phase of a project to
stringent performance criteria. In this case the
evaluate both the technical and the economic
isolated design was shown to be 6% less
issues. If its inclusion is appropriate from a
expensive.
technical and first-cost perspective, then
If equivalent performance designs are not
significant life-cycle cost advantages can be
performed then the costs and benefits of
achieved. Thus, seismic isolation represents an
different structural design schemes can only be
important step forward in the continuity search
assessed by calculating and comparing the four
for improved seismic safety.
principal cost impact factors: 1) construction
The construction costs of incorporating
cost: 2) earthquake insurance premium: 3)
seismic isolation in new buildings in the United
physical damage that must be repaired and 4)
754 Chapter 14
disruption costs, loss of market share and the Fourth Conference on Structural Mechanics in
potential liability to occupants for their losses. Reactor Teachnology, San Francisco, Vol. K, No. 9/2,
1977
Earthquake damage studies have shown that
14-12 Castiglinoni, A., Urbano, C., and Stupazzini, B.,
seismic isolation can reduce the cost of Seismic Design of Bridges in High Activity Region,
earthquake damage factors of 4 to 7. Proceedings of the Seventh European Conference on
Furthermore, the estimated dollar value of Earthquake Engineering, Athens, Vol. 6, 186-203,
earthquake damage in an isolated building has 1982.
been shown to be less than the currently 14-13 Ikonomou, A.S., Seismic Isolation of Bridges with
the Alexisismon, Proceedings of the Conference on
available 10% earthquake insurance deductible. Short an Medium Span Bridges, Toronto, 141-153,
1982.
14-14 Robinson, W.H., Lead-Rubber Hysteretic
REFERENCES Bearings Suitable for Protecting Structures During
Earthquakes, J. Earthquake Eng. And Structural
Dynamics 10, 593-604, 1982.
14-1 Calantariants, J. A., improvements in and
14-15 Blakeley, R. W. G., et al., Recommendations for
Connected with Building and Other Works and
the Design and Construction of Base Isolated
Appurtenances to Resist the Action of Earthquakes and
Structures, Bull. New Zealand Nat. Soc. Earthquake
the Like, Paper No. 325371, Engineering Library,
Eng. 12, No. 2, 1979.
Stanford University, CA, 1909.
14-16 Kelly, J. M. and Tsztoo, D., Earthquake
14-2 deMontalk, Robert Wladislas, Shock Absorbing or
Simulation Testing of a Stepping Fram with Energy-
Minimizing Means for Buildings, U.S. Patent No.
Absorbing Devices, Report No. UCB/EERC-77/17,
1,847,820, 1932.
Earthquake Engineering Research Center, Univ. of
14-3 Bechtold, Jacob, Earthquake-Proof Building, US
California, Berkeley, 1977.
Patent No. 845,046, 1907.
14-17 Earthquake Simulator Tests of a Nine-Story Steel
14-4 Wright, F.L., An Autobiography: Frank Lloyd
Frame with Columns Allowed to Uplift, report No.
Wright, Horizon Press, New York, 1977.
UCB/EERC-77/23, Earthquake Engineering Research
14-5 Green, N.B., Flexible First Story Construction for
Center, Univ. of California, Berkeley, 1977.
Earthquake Resistance, Trans. Amer. Soc. Civil Eng.
14-18 Kelly, J. M., Eidinger, J. M., and Derham, C. J., A
100, 645, 1935.
Practical Soft Story System, Report No. UCB/EERC-
14-6 Kelly, J.M. Aseismic Base Isolation: Its History
77/27, Earthquake Engineering Research Center, Univ.
and Prospects, Joint Sealing and Bearing Systems for
of California, Berkeley, 1977.
Concrete Structures, Publication SP-70, American
14-19 Kelly, J. M., Beucke, K. E., and Skinner, M. S.,
Concrete Institute, 1982.
Experimental Testing of a Friction Damped Aseismic
14-7 Buckle, I.G. and Mayes, R.L., Seismic Isolation:
Base Isolation System with Fail-Safe Characeristics,
History, Application and Performance - A World
Report No. UCB/EERC-80/18, Earthquake Engineerig
View, Earthquake Spectra Journal, Theme Issue:
Research Center, Univ. of California, Berkeley, 1980.
Seismic Isolation, EERI, Vol. 6, No. 2, May 1990; and
14-20 Kelly, J. M., Beucke, K. E., and Skinner, M. S.,
Buckle, I.G., Development and Application of Base
Experimental Testing of an Energy-Absorbing Base
Isolation and Passive Energy Dissipation: A World
Isolation System, Report No. UCB/EERC-80/35,
Overview, Applied Technology Council Report 17,
Earthquake Engineering Research Center, University
Palo Alto, CA, Mar. 1986.
of California, Berkeley, 1980.
14-8 Naeim, F. and Kelly, J.M., Design of Seismic
14-21 Kelly, J. M., and Hodder, S. B., Experimental
Isolated Structures: From Theory to Practice, John
Study of Lead and Elastomeric Dampers for Base
Wiley and Sons, Inc., New York, 1999.
Isolation Systems, Report No. UCB/EERC-81/16,
14-9 Skinner, R.E., Tyler, R.G., Heine, A.J., and
Earthquake Engineering Research Center, Univ. of
Robinson, W.J., Hysteretic Dampers for the
California, Berkeley, 1981.
Protection of Structures from Earthquakes, Bull. New
14-22 Kelly, J. M., Buckle, I. G., and Tsai, H. C.,
Zealand Nat. Soc. Earthquake Eng. 13, No.1, Mar.
Earthquake Simulator Testing of a Base Isolated
1980.
Bridge Deck, Report No. UCB/EERC-85/09,
14-10 Way, D. and Lew, M., Design and Analysis of a
Earthquake Engineering Research Center, Univ. of
High Damping Rubber Isolation System, Applied
California, Berkeley, 1985.
Technology Council Report No. 17, Palo Alto, CA,
14-23 Structural Engineers Association of California,
1986.
Recommended Lateral Force Requirements and
14-11 Jolivet, F. and Richli, M., Aseismic Foundation
Commentary, San Francisco, 1983.
System for Nuclear Power Stations, Transactions of
14. Design of Structures with Seismic Isolation 755
14-24 Stanton, J. F. and Roeder, C. W., Elastomeric 14-37 Kell, J.M., Buckle, I.G. and Tsai, H.C. (1985),
Bearings: Design, Construction and Materials, Earthquake Simulator Testing of Base Isolated Bridge
NCHRP Report 248, Transportation Research Board, Deck, Report Bo UCB/EERC-85/09, Earthquake
Washington, 1982. Engineering Research Center, University of California,
14-25 Applied Technology Council, Proceedings of a Berkley.
Seminar and Workshop on Base Isolation and Passive 14-38 Mokha, A., Constantinou, M.C., and Reinhorn,
Energy Dissipation, ATC Report No. 17, Palo Alto, A.M., (1990), Teflon Bearings in Base Isolation I:
CA, 1986. Testing, Journal of Structural Engineering, ASCE,
14-26 Structural Engineers Association of Northern Vol. 116, No. 2, pp. 438-454.
California (1986), Tentative Seismic Isolation Design 14-39 Mohka, A., Constantinou, M.C., and Reinhorn,
Requirements, San Francisco, 1986. A.M., (1990), Teflon Bearings in a Seismic Base
14-27 Structural Engineers Association of Northern Isolation. Experimental Studies and mathematical
California, Tentative Lateral Force Requirements, San Modeling. Report No. NCEER-88-0038, National
Francisco, 1985. Center for Earthquake Engineering Research, State
14-28 International Conference of Building Officials, University of New York, Buffalo.
Uniform Building Code, Whittier, CA 1994. 14-40 Zayas, V., Low, S.S., and Mahin, S.A., (1987) The
14-29 Kelly, T. E., Mayes, R. L., and Jones, L. R., FPS Earthquake resisting System, Experimental
Preliminary Design Procedures for Seismically Report. Report No. UCB/EERC-87/01, Earth
Isolated Structures, Proceedings of a Seminar on Base Engineering Research Center, University of California,
Isolation and Passive Energy Dissipation, Report No. Berkeley.
17, Applied Technology Council, Palo Alto, CA, 1986. 14-41 Applied Technology Council, proceedings of a
14-30 Buckle, I.G. and mayes, R.L. (1990), The Workshop on Seismic Isolation, Passive Energy
Application of Seismic Isolation to Bridges, 14-42 International Code Council (2000), International
Proceedings ASCE Structures Congress: Seismic Building Code, March.
Engineering - Research and Practice, pp 633-642, May, 14-43 International Conference of Building Officials,
1990. Uniform Building Code, Whittier, CA 1997.
14-31 Chalhoub, M.S., and Kelly, J.M., (1989) 14-44 Federal Emergency Management Agency (1997),
Earthquake Simulator Evaluation of a Combined NEHRP Guidelines for the Seismic Rehabilitation of
Sliding Bearing and Tension Controlled Rubber Buildings, FEMA-273, Washington, D.C., October.
Bearing Isolation System. Proceeding, 1989 ASME 14-45 Federal Emergency Management Agency (1997),
Pressure Vessels and Piping Conference, American NEHRP Commentary on the Guidelines for the
Society of Mechanical Engineers, Hawaii, Vol. 181, pp Seismic Rehabilitation of Buildings, FEMA-274,
59-64. Washington, D.C., October.
14-32 Constantinou, M.C., Mokha, A., and Reinhorn, 14-46 Kelly, J.M. (1996), Earthquake-Resistant Design
A.M., (1990) Teflon Bearings in Base Isolation II: with Rubber, 2nd Edition, Springer-Verlag, London.
Modeling, Journal of Structural Engineering, ASCE,
Vol. 116, No. 2 pp. 455-474.
14-33 Griffith, M.C., Aiken, T.D., and Kelly, J.M. (1988)
Experimental Evaluation of Seismic Isolation of a
Nine-Story Braced Steel Frame Subject to Uplift.
Report No. UCB/EERC-88/05, Earthquake
Engineering Research Center, University of California,
Berkeley.
14-34 Kelly, J.M.., Eidenger, J.M. and Derham, C.J.
(1977) A Practical Soft Story System, Report No.
UCB/EERC-77/27, Earthquake Engineering Research
Center, University of California, Berkeley.
14-35 Kelly, J.M., Beucke, K.E. and Skinner, M.S.
(1980), Experimental Testing of an Energy-Absorbing
Base Isolation System, Report No. UCB/EERC-
80/35, Earthquake Engineering Research Center,
University of California, Berkley.
14-36 Kelly, J.M. and Hodder, S.B. (1981),
Experimental Study of Elastomeric Dampers for Base
Isolation Systems, Report No. UCB.EERC-81/16,
Earthquake Engineering Research Center, University
of California, Berkeley.
756 Chapter 14