0% found this document useful (0 votes)
67 views

Load Flow Spreadsheet

This document provides a listing of equipment loads, including absorbed power, rated power, load factor, power factor, and nature of load (continuous, intermittent, standby). It then calculates the maximum normal running load, peak load, maximum normal running load with a 10% growth factor, peak load with a 10% growth factor, and recommends a generator size based on 70% loading.

Uploaded by

Erdinc
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
67 views

Load Flow Spreadsheet

This document provides a listing of equipment loads, including absorbed power, rated power, load factor, power factor, and nature of load (continuous, intermittent, standby). It then calculates the maximum normal running load, peak load, maximum normal running load with a 10% growth factor, peak load with a 10% growth factor, and recommends a generator size based on 70% loading.

Uploaded by

Erdinc
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 1

LOAD LISTING, CALCULATIONS & GENERATOR SIZING

Absorbed Rated Load Nature Continous Intermittent Standby


Sr. Equipment Name Equip ID No Ef cos MCC Remarks
Power Power Factor of Load*
KW KVAR KW KVAR KW KVAR
1 Ana Motor M001 18 18 0.75 0.89 0.8 Main I 20.22 15.17 List
2 Aydnlatma M001 0.072 0.072 0.7 0.85 0.75 Main C 0.08 0.07 C
3 Istma M001 3 3 0.7 0.85 0.75 Main I 3.53 3.11 I
4 Kap Motor M001 0.75 0.75 0.7 0.85 0.75 Main S 0.88 0.78 S
150+KW

###
###
###

Sum 0.08 0.07 23.75 18.28 0.88 0.78

Maximum Load = 100% of continous load + 50% of Intermittent load + 10% of standby or biggest individual load (higher one)

KW KVAR KVA cos Amp Volts


Maximum of normal running load 12 9 15 0.7922 23 380
Peak load 13 10 16 0.7892 25 380

Maximum of normal running load with 10% Growth Factor 13.158 10.137 16.61 0.7922 25 380
Peak load with 10% Growth Factor 14.129 10.993 17.901 0.7892 27 380

Reccemended Generator Size when 70% loading 20.184 15.704 25.573 0.7892 39 380

You might also like