IEEE Guide For Power Station Control
IEEE Guide For Power Station Control
Put)llshed by
Thr Institute o f Elcctrical and Electroidcs Engincws, Inc
,\
Sponsor
@ Copyright 1985
Contributions from the following individuals who were associated with the
working group in the development of this guide are acknowledged here by the
IEEE:
D. F. Beals H. B. Hollowood
T. Driscoll H. E. Lokay
J. Feinstein J. McCabe
S. Z. Haddad S. R. Sirota
A. W. Hagstrom F. J. Wells
E. Harbist E. M. Wood
When the IEEE Standards Board approved this standard on June 23, 1983, it
had the following membership:
James H. Beall, Chairman Edward Chelotti, Vice Chairman
Sava I. Sherr, Secretaly
J. J. Archambault Donald N. Heirman John P. Riganati
John T. Boettger Irvin N. Howell, Jr Frank L. Rose
J. V. Bonucchi Joseph L. Koepfinger: Robert W. Seelbach
Rene Castenschiold Irving Kolodny Jay A. Stewart
Edward J. Cohen George Konomos Clifford 0. Swanson
Len S. Corey R. F. Lawrence Robert E. Weiler
Donald C. Fleckenstein John E. May W. B. Wilkens
Jay Forster Donald T. Michael* Charles J. Wytie
*Member emeritus
IEEE Standards documents are developed within the Technical Commit-
tees of the IEEE Societies and the Standards Coordinating Committees of
the IEEE Standards Board. Members of the committees serve voluntarily
and without compensation. They are not necessarily members of the In-
stitute. The standards developed within IEEE represent a consensus of the
broad expertise on the subject within the Institute as well as those activi-
ties outside of IEEE which have expressed an interest in participating in
the development of the standard.
Use of an IEEE Standard is wholly voluntary. The existence of an IEEE
Standard does not imply that there are no other ways to produce, test,
measure, purchase, market, or provide other goods and services related to
the scope of the IEEE Standard. Furthermore, the viewpoint expressed at
the time a standard is approved and issued is subject to change brought
about through developments in the state of the art and comments received
from users of the standard. Every IEEE Standard is subjected to review at
least once every five years for revision or reaffirmation. When a document
is more than five years old, and has not been reaffirmed, it is reasonable to
conclude that its contents, although still of some value, do not wholly
reflect the present state of the art. Users are cautioned to check to deter-
mine that they have the latest edition of any IEEE Standard.
Comments for revision of IEEE Standards are welcome from any inter-
ested party, regardless of membership affiliation with IEEE. Suggestions
for changes in documents should be in the form of a proposed change of
text, together with appropriate supporting comments.
Interpretations: Occasionally questions may arise regarding the meaning
of portions of standards as they relate t o specific applications. When the
need for interpretations is brought to the attention of IEEE, the Institute
will initiate action to prepare appropriate responses. Since IEEE Standards
represent a consensus of all concerned interests, it is important to ensure
that any interpretation has also received the concurrence of a balance of
interests. For this reason IEEE and the members of its technical commit-
tees are not able to provide an instant response to interpretation requests
except in those cases where the matter has previously received formal
consideration.
Comments on standards and requests for interpretations should be ad-
dressed to:
Secretary, IEEE Standards Board
345 East 47th Street
New York, NY 10017
USA
Contents
SECTION PAGE
1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1.1 Establishment of Noise-Control-Design Objectives . . . . . . . . . . . . . . . . 13
1.2 Prediction/Determination of Power-Station Noise . . . . . . . . . . . . . . . . . 14
1.3 Specifications of Equipment Sound Levels and Noise Reduction . . . . 14
1.4 Evaluation of the Noise-Control Measures ....................... 14
1.5 Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
1.6 References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2. Fundamentals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.2 Characteristics of the Noise Source ............................. 19
2.3 Sound Power, Sound Intensity, and Sound Pressure . . . . . . . . . . . . . . . 20
2.4 Sound Fields . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
2.5 Sound Propagation Outdoors ................................... 43
3 . Laws and Regulations ..................... ................... 47
3.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Federal Laws . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
3.3 Representative State and Local Regulations ...................... 48
3.4 Local Ordinances ....................... ................... 48
3.5 Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
4 . Measurement of Sound . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
4.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
4.2 Power-Plant Environments ..................................... 51
4.3 Types of Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
4.4 Recording the Acoustic Environment and Test Equipment
Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
4.5 Instrumentation for the Measurement and Analysis of Sound . . . . . . . 55
5. Sources of Noise and Spectra Examples ............................. 59
5.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
5.2 Plant Noise Sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
5.3 Rotating Turbo-Machinery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
5.4 Flow or Aerodynamic Action . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
5.4.1 Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
5.4.2 Piping . . . . . . . . . . . . . . ................................ 70
5.5 Electric Machinery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
5.6 Combustion Processes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
5.7 Cooling Towers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
5.8 Noise-Spectra Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
5.9 Conclusions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
SECTION PAGE
FIGURES
. . . . . .....
FIGURES PAGE
TABLES
1. Introduction
Environmental noise and occupational noise exposure are a matter of increas-
ing public concern. Legislation requiring assessment, control, and abatement of
noise has been enacted on all governmental levels. This guide provides guidance
to control electric power-plant noise emissions to acceptable limits.
There has been an increase in the noise emissions from power plants with the
use of larger, more intensely used, machinery. To reduce this noise emission,
power-plant engineers need to become familiar with noise-control principles.
Noise control for new plants is usually expensive and may cost up to 4% of the
total cost of the plant. It is necessary that noise-control planning be done prior
to constructing a new plant or to modernizing an existing plant so as to elimi-
nate or minimize excessive retrofit costs.
A typical noise-control program consists of the following subsections:
13
IEEE
Std 640-1985 IEEE GUIDE FOR
1.4 Evaluation of the Noise-Control Measures. Once the new plant, designed
with noise-control considerations, is in operation or the noise-control measures
are installed in an existing plant, a follow-up sound survey should be made to
evaluate the noise-control program. If the noise levels fail to meet the selected
design objectives, the reasons should be traced and corrected. See Section 7.
This guide supports the program and addresses alternate noise-control methods
for noise-emission problems generally encountered in fossil and nuclear power
plants.
The noise-control techniques reviewed in this guide are not intended to be
applicable to other power generating facilities such as combined cycle, diesel,
gas turbine, hydro-electric, and solar power plants.
Information presented in this guide was obtained from published national
standards, technical papers, and the experience from the installation and evalua-
14
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
1.5 Definitions. The following definitions apply to the subject matter presented
in this guide.
absorption coefficient. The ratio of the energy absorbed by the surface to the
energy incident upon it.
sound power. The total sound energy radiated by a source per unit time.
sound pressure. The instantaneous pressure measured in a sound wave, that is,
the variation in atmospheric pressure.
[31 ANSI S1.4-1983, American National Standard Specification for Sound Level
Meters.
[41 ANSI S1.8-1969 (R 1974), American National Standard Preferred Reference
Quantities for Acoustical Levels.
15
IEEE
Std 640-1985 IEEE GUIDE FOR
[6] ANSI S1.13-1971 (R 1976), American National Standard Methods for the
Measurement of Sound Pressure Levels.
[7] ANSI/ASC S1.6-1984, American National Standard Preferred Frequencies,
Frequency Levels, and Band Numbers for Acoustical Measurements.
[8] IEEE Std 85-1973 (R 1980), IEEE Test Procedure for Airborne Sound Mea-
surements on Rotating Electric M a ~ h i n e r y . ~
1131 State and Local Noise Regulations, 1973, ch 8. Illinois Pollution Control
Board.
[14] Sound and Vibration (Magazine).
[15] 24 CFR 51 HUD, Environmental Criteria and Standards for Housing and
Urban Development.8
IEEE publications are available from IEEE Service Center, 445 Hoes Lane, Piscataway, NJ 08854.
NEMA publications are available from National Electrical Manufacturers Association, 2101 L
Street, NW, Suite 300, Washington, DC 20037.
NUREG publications are available from Superintendent of Documents, US Government Printing
Office, Washington, DC 20402.
'This publication is available from Department of Environmental Control, Chicago, IL.
HUD publications are available from Superintendent of Documents, US Government Printing
Office, Washington, DC 20402.
OSHA publications are available from Occupational Safety and Health Administration, US
Department of Labor, Washington, DC 20210 or from the nearest regional or area office of the
United States Department of Labor.
lo CFR publications are available from Superintendent of Documents, US Government Printing
Office, Washington, DC 20402.
16
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
17
IEEE
Std 640-1985
2. Fundamentals
2.1 Introduction. Sound waves are a form of elastic waves that can be propa-
gated through any medium exhibiting mass and elasticity. Mass, or inertia,
enables displaced particles of the medium to transfer energy. Elasticity enables
the disturbed particles to return to their original position, somewhat similar to a
spring.
Air has mass and elasticity and therefore can transmit sound waves. A noise
source sets adjacent air molecules in motion. This movement produces a varia-
tion in atmospheric pressure and this disturbance is propagated from molecule
to molecule. The instantaneous variation in atmospheric pressure is called
sound pressure. The speed of sound in a particular medium is defined as the
product of frequency and wavelength
c=fX (Eq 1)
where
c = speed of sound
f = frequency
A = wavelength
19
IEEE
Std 640-1985 IEEE GUIDE FOR
Table 1
Examples of Sources of Different Types of Noise
Steady Nonsteady
Without audible discrete tones Fluctuating
Distant city Heavy traffic (nearby)
Waterfall Pounding surf
Air-conditioning system
Impulsive
Isolated bursts
Drop forge hammer
Dog barking
Pistol shots
Door slamming
Electrical circuit breaker
Quasi-steady noise
Riveting
Pneumatic hammer
Machine gun
2.3 Sound Power, Sound Intensity, and Sound Pressure. Consider a point
source of noise suspended in free space. Sound waves will emanate as spherical
waves from this source. As the wave front progresses further from the source,
its area increases as the square of the distance since the area of a sphere is
477 r2. If the energy of the noise source remains constant, it is evident that the
sound power per unit area shall decrease. Thus, for a doubling of distance, the
available energy is spread over four times the area, or the sound intensity is
one fourth of its original value. This reduction in intensity with distance is
known in physics as the inverse square law. See 1.5, sound power and sound
intensity.
Measurements have shown that a soft whisper may produce a sound power of
W. A jet engine at its exhaust can develop lo4 W. This indicates the wide
range of sounds (low to 1) which can occur in our environment. To avoid use of
such large numbers, acoustical engineers have borrowed a term from electrical
engineering, that is, the decibel. See 1.5, decibel.
20
IEEE
POWER-STATION NOISE CONTROL Std 64@1986
Electrical engineers have long used the decibel to describe the gain of
amplifiers.
Thus, assume that an amplifier has an input of W, and an output of W2. The
gain of the amplifier can be expressed as shown in Eq 2.
w2
Gain = 10 log -
W,
where
W , = 1 mW
W2 = 10 mW
10
Gain = 10 log - = 10 dB
1
From Eq 2 it can be noted that the decibel is a relative quantity. When used
to express noise level, a reference quantity is usually stated or implied.
In acoustics, the reference power is taken as W. Thus, the term sound
power level (PWL) can be defined as in Eq 3.
where
PWL = sound-power level
W = sound power, watts
For example, if
W=lOW
PWL = 10 log 10+120
= 10+120
= 130 dB (ref W)
It is also convenient to use the decibel scale to express the ratio between any
two sound pressures. Sound-pressure level (SPL) is defined in Eq 5.
P2 P
SPL = 10 log - = 20 log -
P2ref Pref
21
IEEE
Std 640-1985 IEEE GUIDE FOR
Therefore
where
SPL = sound-pressure level
P = sound pressure, Pa
NOTE: See Figs 1 and 2 for typical sound power and sound-pressure levels for various acoustic
sources.
The instrument used to measure sound-pressure level consists of a micro-
phone, attenuator, amplifier, and indicating meter. This instrument shall have an
overall response that is uniform @ut) as a function of frequency, and the instru-
ment is calibrated in decibels according to Eq 6.
The position of the selector switch of the instrument for this measurement is
often calledmt or 20-20 000 kHz to indicate the wide frequency range that is
covered. The result of a measurement of this type is also called the overall
sound-pressure level.
2.3.1 Sound Level. The apparent loudness that we attribute to a sound var-
ies not only with the sound-pressure level but also with the frequency (or pitch)
of the sound. If this effect is taken into account to some extent for pure tones,
by weighting networks included in an instrument designed to measure sound-
pressure level, then the instrument is called a sound-level meter. ANSI S1.4-1983
[3] requires that three alternate frequency response characteristics be provided
in instruments designed for general use (see Fig 3 and Table 2). These three
responses are obtained by weighting networks designated as A, B, and C.
Responses A, B, and C selectively discriminate against low and high frequencies.
Whenever one of these networks is used, the reading obtained should be
described as
(1) The A-weighted sound level is 45 dB
(2) Sound level (A) = 45 dB
(3) SLA = 45 dB
In a table, the abbreviated form LA with the unit dB is suggested, or where
exceptional compactness is necessary, dB(A). The form dBA has also been used,
but this notation implies that a new unit has been introduced and is therefore
not recommended. Note that when a weighting characteristic is used, the read-
ing obtained is said to be the sound level. Only when the overall frequency
response of the instrument is flat are sound pressure levels measured. Since the
reading obtained depends on the weighting characteristic used, the char-
acteristic that was used shall be specified or the recorded level may be useless.
It is often recommended that readings on all noises be taken with all three
weighting positions. The three readings provide some indication of the fre-
quency distribution of the noise. If the level is essentially the same on all three
networks, the frequencies of the predominate sounds are probably above
600 Hz. If the level is greater on the C network than on the A and B networks
by several decibels, much of the noise is probably below 600 Hz.
22
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
ACOUSTIC POWER
POWER POWER LEVEL SOURCE
(WATTS) dB (ref 10-12 W)
1000 150
4-PROPELLER AIRLINER
100 140
75PIECE ORCHESTRA
10 130 PIPE ORGAN } PEAK RMS LEVELS IN
Q SECOND INTERVALS
SMALL AIRCRAET
1 120 LARGE CHIPPING HAMMER
0.1 110
IANo
TUBA
) PEAK RMS LEVELS IN
A SECOND INTERVALS
BLARING RADIO
CENTRIFUGAL VENTILATING FAN (13 000 ft3/min)
0.0 1 100 4 ft LOOM
AUTO ON HIGHWAY
0.0001 80
0.000001 60
0.0000001 50
0.000 000 01 40
NOTE: These levels bear no simple relation t o the sound levels of Fig 2
Fig 1
Typical Power Levels for
Various Acoustic Sources
23
IEEE
Std 640-1985 IEEE GUIDE FOR
AT A GIVEN DISTANCE
FROM NOISE SOURCE dB(A) ENVIRONMENTAL
dB (ref 20 pPa)
140
THRESHOLD O F HEARING
YOUTHS - 1000 HZ - 4000 HZ
NOTE: These values are taken from the literature. Sound-level measurements give only part of the
information usually necessary t o handle noise problems, and are often supplemented by analysis of
the noise spectra.
Fig 2
Typical A-Weighted Sound Levels
Measured with a Sound-Level Meter
24
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
Table 2
A, B, and C Electrical Weighting Networks
for the Sound-Level Meter*
1000 0 0 0
1250 +0.6 0 0
1600 +1.0 0 -0.1
2000 + 1.2 -0.1 -0.2
'500 + 1.3 -0.2 -0.3
25
-
IEEE
Std 640-1985 IEEE GUIDE FOR
Fig 3
Frequency-Responses for SLM Weighting Characteristics
See ANSI S1.4-1983 [31
26
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
The spectra will help in providing data for later comparisons when conditions
change or if better evaluation techniques are developed.
The limitations of the simple, weighted measurement should be recognized
when plans for sound measurements are made.
2.3.4 Analysis in Frequency Bands. To make an analysis in the frequency
domain, the signal energy is electrically separated into various frequency bands,
for example, octave bands, each of which covers a 2:l range of frequencies. The
analysis yields a series .of levels, one for each band, called band levels, or for
octave bands, octave band levels or octave band sound-pressure levels. Here it
is apparent that the band in which a reading of level is obtained shall be spec-
ified if the information is to be of value.
2.3.5 Octave Bands. The preferred series of octave bands for acoustic mea-
surements [ANSI/ASC S1.6-1984 [7]] covers the audible range in ten bands. The
center frequencies of these bands are 31.5 Hz, 63 Hz, 125 Hz, 250 Hz,
500 Hz, 1000 Hz, 2000 Hz, 4000 Hz, 8000 Hz, and 16 000 Hz. The actual nominal
frequency range of any one of these bands is 2:l; for example, the effective
band for the 1000 Hz octave band extends from 707 Hz to 1414 Hz (see Table 3).
Another series of octave bands has been widely used in the past. The older bands
were a 75 Hz low-pass filter, and the octave bands of 75 Hz to 150 Hz, 150 Hz to
300 Hz, 300 Hz to 600 Hz, 600 Hz to 1200 Hz, 1200 Hz to 2400 Hz, 2400 Hz to 4800 Hz,
and a 4800 Hz high-pass filter, but these are no longer preferred. This older series is
still specified in a number of test codes and the published data obtained with this
series is extensive.
NOTE: For a method of converting octave-band levels measured with this older series to levels for the
new series, see ANSI S1.ll-1966 (R 1976) [5] and Appendix A. It should be noted that this conversion
method applies only t o broadband noise.
27
IEEE
Std 640-1985 IEEE GUIDE FOR
Table 3
Center and Approximate Cutoff Frequencies for
Standard Set of Contiguous-Octave and One-Third Octave
Bands Covering the Audio-Frequency Range
Frequency (Hz)
Octave One-Third Octave
18 44 63 88 56.2 63 70.8
19 70.8 80 89.1
20 89.1 100 112
28
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
w
>
w
Fig 1
A Plot of the Octave-Band Analysis of
Noise from a Calculating Machine
29
IEEE
Std 640-1985 IEEE GUIDE FOR
0
W
0
0
a
0
zw
m
v)
-I
W
>
W
-I
0
F
2
w
w
3
t,
m
m
-U
w
0
Z
w
a:
W
U
U-
0
30
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
*From Fig 5
If these values are combined by the more rigorous method, the answer will
also be 99.9 dB(A).
A s a practical consideration, sufficient accuracy can be obtained by dropping
any correction due to a difference of 10 dB or more. A similar procedure may
be used to convert flat octave-band data t o equivalent A-weighted values. See
Table 4.
Table 4
Conversion to Equivalent A-Weighted Values
31
IEEE
Std 640-1985 IEEE GUIDE FOR
where
PWL = sound power, dR (ref 10-l2 W)
SPL = sound pressure (ref 20 FPa)
r = distance (meters) from the point source to the point where the
sound-pressure level is measured
32
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
BAND NO
Fig 6
Comparison of Linear Versus A-Weighted
Octave Bands for Pulverizers-Bowl Mills
33
IEEE
Std 640-1985 IEEE GUIDE FOR
2.4.1.3 Power Level in Hemispherical Space. For the more usual case,
the source may be located far from other objects but close to the ground or
floor. In this case, the sound source will radiate into hemispherical space as
defined by the area above the ground plane. Since the intensity of the sound
source radiating into a hemisphere is twice as great as that radiating into a
sphere (see 2.4.1.2), the SPL measurement will be greater by 3 dB. In this
idealized case, the sound-power level for hemispherical space is given by Eq 9.
where
PWL = sound power, dB (ref 10-l2 W)
SPL = sound pressure (ref 20 pPa)
r = distance (meters) from the point source to the point where the
sound-pressure level is measured.
2.4.2 Directional Source. In actual practice, noise sources are not as simple
as point sources. The sound is not radiated uniformly in all directions, either
because the shape of the sound source is not spherical, or because the ampli-
tude and time phase of the vibrations of the different parts are not uniform, or
both. The net result is that more sound is radiated in some directions than in
others. In other words, the sound-pressure level for a given distance is different
in different directions.
When such a directional sound source is far from any other object it behaves
in some ways like a point source. For example, the sound-pressure level
decreases 6 dB for each doubling of distance, provided measurements are
started at a distance away from the source that is several times the largest
dimension of the source, and moved directly away from the source. In actual
practice this idealized behavior is upset by the effects of variation in terrain,
atmospheric conditions, and the interference of nearby objects.
2.4.2.1 Near Field and Far Field. At locations close to a directional
source equal sound-level contours are different in shape from those at a dis-
tance. Furthermore, there is no apparent center from which the 6 dB drop for
each doubling of distance is found. Consequently, this nearzfield behavior can-
not readily be used to predict the behavior at a distance. For the near-field
effect to be minimized, the location should be at least one wavelength away
from the source. This dimension should be determined on the basis of the
lowest frequency of interest. For example, if the lowest frequency of sound of
interest is 120 Hz, the wavelength is approximately 10 ft.
Another factor that enters into the differences between the near-field and far-
field behavior is the way the sound waves spread out from a source. The sound
waves from a large source vary with distance differently from waves produced
by a small source. But at a distance of several (three to four) times the largest
dimension of the radiating source, spherical spreading is said to exist, and the
behavior is then nearly independent of the size of the source.
34
IEEE
POWER-STATION NOISE CONTROL Std 640-1986
DI
Q = antilog-
10
where
Q = directivity factor
DI = directivity index
For a point source located in the center of a large room, Q = 1 since the
sound radiates uniformly in all directions. For other typical values of Q, refer to
Fig 7.
Fig 7
Typical Values of Directivity Factor Q for
Different Locations of a Sound Source in a Large Room
Location Q
-
Center 1
A 2
B 4
C 8
35
IEEE
Std 640-1985 IEEE GUIDE FOR
where
DI = directivity index
- = sound-pressure level at a distance T in the desired direction
SPL
SPL = mean sound-pressure level around the source at distance r
where
SPL = octave-band sound-pressure level at a distance r in the desired
direction
-
SPLH = average octave-band sound-pressure level measured on a test hemi-
sphere around a source at distance r
-
+ SPL
antilog -
10
where -
SPL = mean sound-pressure level
SPL, . . . SPLM = level in dB of each measurement
n = number of measurements
36
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
\
\
c- -\
\
"!- n
cb
+--
c
t- W
L
n
\
\
\
37
IEEE
Std 640-1985 IEEE GUIDE FOR
(2) For summing decibels which differ by 5 dB to 10 dB, take the arithmetic
average and add 1 dB
2.4.2.5 Equivalent Radius. Instead of making measurements on a true herni-
spherical surface, see IEEE Std 85-1973 (R 1980) [8], 2.6 and 2.7, which proposes
that measurements be made on a prescribed surface surrounding the machine.
Also see Figs Wa), (b), and ( c ) which show the prescribed measurement points.
2.4.2.6 Sound-Pressure Level for a Directional Source. When we know
the directivity factor for the direction of interest, we can use it as a multiplying
factor on the power. Expressed in terms of level, Eq 14 is as follows:
SPL = PWL+lO log Q -20 log r -11 dB (Eq 14)
Fig 8
( c ) Prescribed Points, Large Horizontal Machines
h = shaft height or 0.3 m, whichever is greater
x= key measuring points
O = measuring points marked off at intervals of 1 m t 0.25 m from key points
d = 1 m or greater from major machine surfaces
(c)
38
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
Equation 15 relates the power level of the source, the sound-pressure level in
a given direction at a distance T meters from the source, and the directivity
index for that direction.
2.4.3 Effect of Reflections in a Room. The sound that a noise source radi-
ates in a room is reflected by the walls, floor, and ceiling. The reflected sound
will again be reflected when it strikes another boundary, with some absorption
of energy. at each reflection. The result of these reflections is that the sound-
pressure level measured at a distance from the source is different from that
predicted by Eqs 8 and 9.
Close to the source of sound there is little effect from these reflections, since
the direct sound dominates. But far from the source, unless the boundaries are
very absorbing, the reflected sound dominates, and this region is called the
reverberant field. The sound-pressure level in this region depends on the acous-
tic power radiated, the size of the room, and the acoustic absorption char-
acteristics of the materials in the room. These factors and the directivity
characteristics of the source also determine the region over which the transition
between reverberant and direct sound occurs.
A second effect of reflected sound is that measured sound does not necessar-
ily decrease steadily as the measuring position is moved away from the source.
At certain frequencies in a room with hard walls, marked patterns of variations
of sound pressure with position can be observed. These patterns are called
standing waves. They are noticeable mainly when the sound source has strong
frequency components in the vicinity of one of the very many possible reso-
nances of the room. They also are more likely to be observed when a frequency
analysis is made; and the narrower the bandwidth of the analyzer, the more
marked these variations will be.
The acoustical boundary conditions of ordinary rooms are extraordinarily
complicated, and most sound sources are also complicated. The result of this
complexity is that without advanced computer methods, only an average type of
description can be used. Even a rough approximation can be useful, however,
and we shall review briefly some of the work on room characteristics as it
applies to the sound produced by a source in a room.
2.4.4 Effective Room Absorption and Absorption Coefficient. To simplify
the analysis of the effect of the room, it is assumed that enough measurements
are made so that any standing wave patterns can be averaged. A number of
other assumptions are made, and then a relation of the form shown can be
developed.
where
Q = directivity factor
r = distance from the sound source, m
R = effective room absorption (room constant), square meters or metric
sabins and defined by Eq 17.
39
IEEE
Std 640-1985 IEEE GUIDE FOR
where
S = room area (m2)
-
E = average absorption coefficient
-
x = x, SI+ x 2 s, + . . . . . . . . . . . . . . x n Sn
s, +s,+ .............. Sn
where
absorption coefficients of all materials in the room
m I , x,, x n =
S,, S,, S , = corresponding areas of various materials
When a sound wave strikes a surface, a certain portion of the incident energy
is absorbed. The sound-absorbing ability of a material is called the absorption
coefficient. By definition true absorption coefficients range from 0 to 1. When
E = 0 all the energy is reflected, when 0~ = 1 all the energy is absorbed.
Table 5
Absorption Coefficients of Various Materials
Used in Acoustical Wall Treatment
40
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
enough to affect the room constant appreciably. This absorption increases with
frequency, and it varies markedly with humidity and temperature. The absorp-
tion at normal room temperatures is a maximum at relative humidities in the
range of 10%-30%.
Another item that affects the absorption properties of a material is the
method of mounting. For a porous-type absorber, the space between it and the
wall will increase the absorption as the space is increased.
If the absorption coefficients of the materials in the room are not known, the
room constant can be determined from measurements of the reverberation time
of the room. The reverberation time is the time for the sound-pressure level in a
room to deteriorate by 60 dB or of its original value. The value of R is given
by Eq 19.
R = 0.16 ( V / T )
where
V = volume of the test room, m3
T = reverberation time of the test room, s
The relation given in Eq 16 can be shown grar ically in Fig 9 for the non-
Fig 9
Sound-Pressure Level (SPL) Relative to the Power Level (PWL)
for a Nondirectional Source for Different Values of the Room
Constant R , as a Function of the Distance from the Source
METERS
+5
0
v)
w
m
U
-5
I
U
_I
-10
::
21
m_I
E& -lE
0
z
3
w
w -2c
?
4
= -2
-3c
05 07 1 2 3 4 5 7 10 20 30 40 50 70 100
41
IEEE
Std 640-1985 IEEE GUIDE FOR
METERS
2 5 10 20
05 0.7 1 2 3 4 5 7 10 20 30 40 50 70 100
DISTANCE FROM ACOUSTIC CENTER
O F A S O U R C E IN F E E T = r
NOTE: The relation is shown for three different values of the room constant R, and for
the six different values of the directivity factor 9.
Fig 10
Sound-Pressure Level (SPL) Relative t o t h e Power Level (PWL)
for a Directional Source as a Function of t h e Distance
from t h e Source
directional source and in Fig 10 for the directions having the labeled values of
directivity factor.
2.4.5 Reverberant Field. The graphs of Figs 9 and 10 show that close to the
source the sound-pressure level tends to vary with the distance from the source
as it does under free-field conditions (R = CO).But far from the source the
sound-pressure level becomes independent of the directivity of, and the distance
to, the source. This region is called the reverberant field, Here, the level is
determined by the acoustic power radiated by the source and the acoustic char-
acteristics of the room. The region through which the transition between the
free field and the reverberant field gradient occurs is determined by the direc-
tivity factor and the effective room absorption.
In terms of Eq 16 in the reverberant field, far from the source, T is large and
therefore the directivity term can be neglected; Eq 16 becomes, for such a field
42
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
4
SPL = PWL+lO log - dB
R
2.5 Sound Propagation Outdoors. Sound waves travel from source to receiver
outdoors through an atmosphere that is in constant motion. Turbulence, temper-
ature and wind gradients, viscous and molecular absorption, and reflection from
the earths surface all affect the amplitude and create fluctuations in the sound
received. The longer the transmission path through the atmosphere, the less
certain the average amplitude and the greater the fluctuations in the sound
receive d.
In addition to the effect of hemispherical divergence (see Eq 9), the excess
attenuation owing to environmental and other conditions may include the fol-
lowing topics given in 2.5.1 through 2.5.5.
NOTE: Frequently it may be difficult to obtain the information needed to determine these excess
attenuation effects. In such cases, it is always conservative practice not to include such effects.
43
IEEE
Std 640-1985 IEEE GUIDE FOR
I l l l I
RELATIVE
OCTAVE BAND HUMIDITY
RELATIVE
HUMIDITY
2o 1 1000 HZ
OCTAVE BAND
1
10 I OCTAVE BAND
- 2000Hz
2o
I OCTAVE BAND
1
0 20 40 60 80 100 0 20 40 60 EO 100
TEMPERATURE ( O F )
Fig 11
Atmospheric Absorption Coefficients for Octave Bands of Noise
for Different Temperatures and Humidities
44
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
PATHS OF
SO UN D WAVES
SHADOW
ZONE
SOURCE
WIND DIRECTION
SHADOW
ZONE
Fig 12
(a) Influence of Negative Temperature Gradient (Cooler Air
Above) on Bending of Sound Waves Upward (b) Influence of
Positive Temperature Gradient (cooler air below) on
Bending of Sound Waves Downward (c) Influence of Wind
Direction on Bending of Sound Waves, Assuming Typical
Wind Speed Increase with Height Above the Ground
45
IEEE
Std 640-1985 IEEE GUIDE FOR
46
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
47
IEEE
Std 640-1985 IEEE GUIDE FOR
ch 3, par 2; Section 4.1, p 4.2-15, ch 4, par 2; and Table 3, p 4.2-55, 4.2.1 and
4.3.1. These sections require an examination of the local population and an iden-
tification of the impact on their environment due to noise.
3.2.5 Department of Housing and Urban Development Environmental
Criteria and Standards [15]. This department provides environmental stan-
dards, criteria, and guidelines for determining project acceptability and for nec-
essary mitigating measures to ensure suitable noise environments. See [ 151.
3.2.6 Environmental Protection Agency [MI. Guidelines to rate the noise
in various receiving areas are provided by the Public Health and Welfare Cri-
teria for Noise. Information on Levels of Environmental Noise Requisite to Pro-
tect Public Health and Welfare with an Adequate Margin of Safety is also
provided.
48
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
3.5 Summary. For the construction and operation of power generating sta-
tions, there are two types of noise regulations with which the designer should
become familiar
(1) In-plant or occupational noise regulations to prevent noise-induced hear-
ing loss
( 2 ) Out-plant or community regulations to limit the effects of site noise on
the noise environs of the surrounding community
Occupational noise regulations specify limits of exposure to A-weighted sound
levels, require reduction of noise exposure by engineering controls (reduce
level) or administrative controls (reduce exposure time), and allow provision
and use of hearing protection devices. Community regulations limit noise emis-
sions from a building or site, specify C-weighted/A-weighted or octave-band lev-
els, and can include provisions for various types of noise such as impulse, tonal,
and steady. The trend in community regulations is toward more restrictive lev-
els and more detailed measurements. In addition to the specification of permis-
sible levels at the plant boundaries, some provisions are made to examine the
existing ambient levels, to determine the statistical distribution of these levels
with frequency of occurrence, and to predict the effects of plant operation on
ambient environmental noise. Conformance with these regulations does not
guarantee freedom from complaints, especially where noise sources exhibit
strong tonal characteristics. The first step in developing noise-control procedures
for a power station should be an examination of applicable noise regulations.
49
IEEE
Std 640-1985
4. Measurement of Sound
4.1 Introduction
4.1.1 Audible sound data in and around power stations are obtained primarily
(1) To determine if sound levels are excessive for employees hearing and
comfort
(2) To control exterior noise to avoid community annoyance
(3) To identlfy the sources of noise in a given acoustic environment
4.1.2 The basic considerations when measurements of sound are made are as
follows:
(1) Sound level and its frequency
(2) Characteristics of the noise source, steady or nonsteady; directivity of the
source
(3) Acoustic environment and measurement locations
In outdoor measurements, wind is an additional factor to be considered. The
measurements should be made while the source is operating at its normal oper-
ating condition. The normal operating condition may vary with the time of day
and night and also the time of year (summer - winter).
51
IEEE
Std 640-1985 IEEE GUIDE FOR
52
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
sound-power level of the source, they still provide very useful sound-level data.
The sound levels measured within a distance of 0.25 m from the major surfaces
of the source can be considered as near-field measurements.
Another technique to reduce the contribution of reverberant noise and at the
same time minimize the influence of nearby noise sources is to use directional
microphones. A directional microphone has the same response as the conven-
tional, omnidirectional microphone for sound waves which are incident perpen-
dicular to its diaphragm. Its response falls off for oblique incidences. Thus even
for measuring locations in the semireverberant field, the microphone will essen-
tially sense the direct sound field if it is pointed at the acoustic center of the
source.
Such a microphone however needs to be used with some degree of caution.
The frequency response of directional microphones is typically not as good as
that of conventional microphones. Therefore, some low- and high-frequency
sounds may not be accurately sensed. The user shall be aware of the frequency-
response limitations of any unit used so as to judge its adequacy for the
intended applications. Also, there are no convenient on-site calibrators that can
be used to adjust the microphone amplifiers to read out absolute sound levels.
A correction chart, tailored to each microphone system, can be used to facilitate
determination of these levels. The greatest utility of directional microphones is,
thus, for the identification of noise sources and relative measurements of the
noise levels of several sources.
4.3.1.3 Measurement Locations. Measurement locations depend on the
reasons for obtaining the data, which usually are
(1) To determine compliance with a purchase specification
(2) To determine the contributions of the equipment to the overall noise level
To determine the compliance with a purchase specification, the measure-
ments should be made according to the appropriate noise standard. In a case
when an existing standard is not suitable for equipment operating in a power-
plant noise environment, or there is no suitable standard for the equipment, the
measurement locations and the operating conditions should be agreed upon
beforehand. Near-field in-situ measurements under normal operating conditions
will suffice in these conditions.
In general, measurements to determine the contribution of the equipment to
the overall noise level will depend upon the equipment itself, the overall noise
level, and the ability to determine the background noise. Equipment noise
should be measured in its direct field, if possible, at meaningful locations. For
example, for rotating machinery, measurements are recommended on its axis
level, at the shaft ends, on top of the machine, and on both sides of the machine
on its center line perpendicular to the axis. A series of sound-level contours are
also recommended around the machine by recording levels at various distances
in all directions. If these contours exhibit a directional pattern, some additional
measurements should be taken to understand the cause of directionality. On
large equipment, for example, turbine generators and boilers, some additional
measurements may be needed near the couplings, burners, steam leaks, etc.
53
IEEE
Std 640-1985 IEEE GUIDE FOR
Hence, the measurement locations vary with the sources and their environment.
There are published standards that can serve as a guide to determine the
number of key measuring positions around a piece of equipment, microphone
location, and its height above the floor. In most cases, the maximum sound level
of the machinery has to be determined. This can be done by walking around the
equipment holding the microphone at approximately 1.5 m above the ground,
and observing the scale for the maximum reading. Caution shall be exercised
when measuring equipment, such as boiler feed pumps, which produces audible
discrete tones. Standing-wave interferences or large spatial variations in sound
pressure are frequently produced by sound sources that radiate audible tones,
and these are particularly pronounced in indoor locations. To reduce the influ-
ence of localized interferences, the microphone may be moved rapidly (a mini-
mum of 1 cycle per second) in a vertical plane approximately -1-0.3 m from each
location.
4.3.2 Noise Exposure Measurements Related to Personnel. The measure-
ments are made primarily to determine the noise exposure of plant personnel
and therefore should concentrate on the major noisy areas which are critical,
that is, 90 dB(A) and higher. According to current OSHA regulations, the guiding
factor in establishing the noise exposure measuring locations in the plant area
should be the path traveled most frequently by the personnel who get most
noise exposure in the plant.
4.3.3 Measurements Related to Community Annoyance. Sound will usually
be measured at the power-plant property boundaries or at the points of com-
plaint or annoyance. There are no set rules established to determine how many
measuring locations are required around the plant perimeter, although four loca-
tions are considered the minimum. The number depends upon the location and
orientation of the plant, local regulations, and the proximity of the residential
areas.
The purpose of the measurements is to characterize the noise at the selected
locations. Measurements shall be made over a period of time sufficient to reflect
the true time variation of the noise level. Statistical distribution noise measure-
ments may be made manually or by using automatic equipment. A manual
method of statistical noise measurement is described in [20]. Automatic
monitoring equipment is available on the market.
The following descriptors are used to describe the temporal distribution of
noise with time:
(1) Decile 4 is a noise level exceeded a given percentage of time with the
percentage indicated by the subscript
( 2 ) Equivalent sound L,Q is the continuous noise energy average of a fluctuat-
ing noise level
(3) Day-night sound bNis the halevel over a 24 h period with a weighting
factor applied for nighttime levels between the hours of 10 pm and 7 am
(4) Community noise equivalent level (CNEL) is the LQlevel over a 24 h
period with a weighting factor applied for evening hours from 7 pm to 10 pm
and another weighting factor applied for the period from IO pm to 7 am
54
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
Scheme A
Microphone
Sound level meter Octave band or one- Readout
or its equivalent third octave-band
filter set
55
IEEE
Std 640-1985 IEEE GUIDE FOR
Scheme B
Microphone
Sound-level meter
or its equivalent Tape recorder
Frequency analyzer Display
The instrumentation should meet the requirements of the latest edition of
applicable ANSI or ASA standards.
4.5.1 Sound-Level Meter. The sound-level meter is the basic instrument for
measuring sound levels. It consists of a microphone, an amplifier, an attenuator,
and an indicating meter. Most sound-level meters provide filter networks so that
the A-, B-, and C-weighted levels can be read off the meter. Some sound-level
meters have data analyzing capacity in one or one-third octave bands, can meas-
ure impulse noise, and can be used in conjunction with a tape recorder to store
the data.
Various degrees of precision and accuracy are required in practical measure-
ment of sounds of various kinds for different purposes. There are three basic
types of sound-level meters
Type 1 - Precision
Type 2 - General purpose
Type 3 - Survey
Their performance requirements become progressively less stringent, proceeding
from Type 1 to Type 3. The sound-level meters should meet the requirements of
ANSI S1.4-1983 [3].
The microphone should be carefully selected to suit the acoustic environ-
ment. Consideration should be given to the environment, the expected range of
sound-pressure levels, the desired frequency response, directional char-
acteristics of the microphone, and its physical size and shape. For most of the
acoustic measurements in power plants, a + inch condenser microphone or
equivalent is suitable. Sometimes it is impossible or impractical for an observer
to be near the microphone. In such cases, an extension cable is used to connect
the microphone to the instrument. To minimize the cable effects, the micro-
phone should be mounted directly on a preamplifier, and the sound-level meter
should be calibrated as a system, including the cables.
4.5.2 Frequency Analyzers. The distribution of sound energy versus fre-
quency is needed for identifying the noise-generation mechanism, or for pre-
scribing the noise-control treatment and to evaluate its effectiveness, or both.
Instruments performing this function are known as analyzers. Analyzers deter-
mine the sound-pressure levels in different frequency bands covering the audio
range. The bands are usually identified by their center frequencies. Most com-
mon-frequency analyzers are of the constant percentage bandwidth type. These
include octave, one-half octave, and one-third octave band analyzers, the band-
width decreasing progressively from octave to one-third octave bands. If further
detailed analysis of the data is required, a constant bandwidth can be selected
between 2 Hz and 200 Hz, and the whole audio range traversed. The choice of
the analyzer used depends upon the information required. For example, if the
56
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
57
IEEE
Std 640-1985
5.2 Plant Noise Sources. Sound sources in and around power stations contrib-
ute to the overall plant noise level with different energy levels, spectra, and
radiation characteristics. Power-plant noise sources can be produced in some
instances and locations within the plant by a single piece of equipment or any
array of different pieces or multiple pieces of essentially identical equipment.
Table 7 lists sound producing equipment which make up a power station and
attempts to identify the major noise-producing components, their internal and
external contribution to the plant, sound producing mechanisms, and opera-
tional period of significant sound contribution.
Specific sources of noise and the contribution of these sources to the A-
weighted sound level require extensive engineering noise surveys using fre-
quency selective instruments which include octave, one-third octave, and
narrow-band analyzers. The octave-band analysis may describe the inherent
sound characteristics of a single piece of equipment. However, when multiple
pieces of equipment, pure tones, or widely varying levels are involved, the pre-
ferred method is the use of one-third octave band analysis or narrower-band
analysis. An example of different types of analyses for the same sound source is
provided in Fig 31.
The most significant contributors to overall power-plant noise and personnel
noise exposure are coal mills, boiler feed pumps, forced draft fans, induced
draft fans, seal air fans, primary air fans, air compressors, pressure-reducing
stations, turbine-generators with accessories, and in some cases auxiliary equip-
ment drives such as motors and turbines. In any plant survey and noise-control
program, it is important to isolate and identify the noise sources and significant
noise problem contributors. Identification and an understanding of the noise-
producing mechanism in the various equipment will be beneficial.
59
IEEE
Std 640-1985 IEEE GUIDE FOR
U
C
.r
c
.r
a
+
a
a
5
L
2
ec, 'i
2
=+
a,
C
.r
i
cr
c
n
.r
E
s
60
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
m
5
n
5
2
P
2
$
Y
g
2
'C
U
U
I!
b
d
4
4
e-
'+
U
gI!
c
W
k
R
U
d
61
IEEE
IEEE GUIDE FOR
Std 640-1985
ww
I- I
nn nnn nn nnnnn n n
4 4 4 4 4 4 4 4 4 4 4 4 44 4 4
62
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
E E E E
a a a a
rn r
n rn rn
n n n n
c c c 4
4
a
d
z
n v a
63
IEEE
Std 640-1985 IEEE GUIDE FOR
G.
n n
4 4
VI
64
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
h
-
-n n c n n
- w
W
C
-
4 4
*
W
3
5
Y
I
d r i d d a;&
65
IEEE
Std 640-1985 IEEE GUIDE FOR
radial), axial forced draft fans, steam turbines, boiler feed pumps, air com-
pressors, and various pumps. Generally, the forced draft fans and boiler feed
pumps are the noisiest pieces of equipment in the power plant although the
main turbo-generator contributes significantly to the overall indoor plant noise
environment and air compressors and pumps influence more localized areas in
the plant.
5.3.1 Fans. Fan noise occurs when blades exert fluctuating forces on the air.
Each time a blade passes a point on its rotational path, an impulse is delivered
to the air at that point. The repetitive rate of this impulse called the blade
passing frequency determines the fundamental tone of this type of noise. This
rotation, or blade noise, is basic to all types of fans. Fan blades are also a major
source of vortex noise. When a blade moves through the air, a pressure gradient
is built up across the blade causing separation and giving rise to eddy formation
and vortex shedding. The first mechanism forms a discrete noise related to rev-
olutions per minute (r/min) and the second forms a more random noise which
is primarily associated with turbulence and a resultant broadband noise spec-
trum. The same mechanisms apply to all centrifugal fans; however, radial blade
fans are generally noisier and exert a predominant blade frequency tone that
can be extremely objectionable. The fundamental tone or 1st harmonic of the
axial flow fan is usually twice the frequency of an equivalent centrifugal fan.
Airborne noise generated by the fan impeller radiates through the intake and
discharge openings and the fan housing. Noise may also be radiated as a result
of resonance of fan housings and ducts since the aerodynamic noise from the
fan contains all possible frequencies in the audible range with which to excite
any mechanical resonant system at its natural frequencies of vibration.
5.3.2 Steam Turbine-Generator. The steam turbine is a significant noise
contributor in the power plant. Due to its size, operating environment, and mul-
titude of potential sources, its generated noise is particularly difficult to assess.
Identification of major sources of sound produced by fossil or nuclear steam
turbine-generator units can be found within the steam admission valves, steam
piping, turbines, couplings, generator, and exciter.
Most steam turbine-generator noise is created by friction, impact, turbulence,
imbalanced rotating parts, pressure drops, mass flow, magnetic attraction, or
other motions related to the change in velocity of moving parts. Flow-related
sources account for the majority of middle-to-high frequency noise emitted by a
turbine-generator. Low-frequency noise is created by rotor imbalance and fluc-
tuating electromagnetic forces.
The sound-pressure levels near the low-pressure turbine and generator vary
only a few decibels with load. Near the high-pressure turbines larger variations
are possible.
High-pressure ratios across the turbine-control valves will produce very high
sound levels near the high-pressure turbine. As the load on the unit increases,
the pressure ratio across the valve decreases until, at some point, the steam
noise produced is primarily the result of flow noise instead of valve noise in the
piping system.
66
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
Near the low-pressure turbine and generator, the sound levels remain fairly
constant with load. The constant volumetric steam-flow through the crossover
pipes (if used) across the entire load range sets the sound level in these areas.
Valves and piping systems radiate sound in the most sensitive frequency
ranges of 250 Hz-4000 Hz. Steam-turbine control valves of fossil turbines gen-
erally have not proven to be a dominant noise source, although noise problems
have existed, such as valve instabilities leading to chattering and mechanically
generated noise. The first generation nuclear turbine control valves produced
high noise levels when the valves were operating under choked conditions and
have become more prominent than fossil turbines. This is due partly to differ-
ences between partial-load characteristics of fossil and nuclear turbines and
their respective operating procedures. Largely, it is due to differences between
fossil and nuclear control-valve construction.
The typical fossil turbine with partial arc admission has two steam chests,
each containing three or four control valves. Each valve feeds one segment of
the nozzle chamber in the turbine. The throat diameter of these valves is typ-
ically in the range of 100 mm-150 mm. Structural walls are very thick. Full arc
admission, throttle control valves on the larger supercritical fossil turbines are
similar to nuclear turbine valve arrangements but still exhibit the thicker wall
characteristics of fossil turbines.
The first generation nuclear turbines, with their much lower steam pressures,
require approximately five times as much volumetric flow as fossil turbines of
the same power output. Because of this increased flow rate, a completely differ-
ent configuration had to be chosen. The nuclear turbines have four individual
control valves and comparatively their walls are much thinner than fossil
valves. The throat diameter of these valves presently ranges up to approx-
imately 500 mm.
Turbine-control valve noise is a function of the velocity immediately down-
stream from its throat and the mass flow. The noise generated within the valve
propagates down the pipe toward the turbine, and exhibits essentially a line
source of sound power per unit length.
Steam piping is one of the major sources of turbine-generator system noise.
Piping systems not only radiate sound produced by valves, they also radiate the
hydrodynamic pressure fluctuations impinging on their walls due to the tur-
bulent fluid. Steam flow through a complex piping system involving joints,
bends, constrictions, etc, may result in fluid excitation that can cause structural
resonances in the piping system.
The moisture separator-reheater is also a possible source of noise in nuclear
units. This stationary device mechanically separates moisture from the steam
and then reheats and discharges it to the low-pressure turbine inlet. Airborne
sound is generated by the flow of steam through this device.
The basic generators of noise inside the steam turbine are rotor imbalance
and the interaction between rotating and stationary blades. As the rotating
blades in a turbine pass the upstream stationary blades, they are acted upon by
a periodic steam force at the stationary blade passing frequency. This force may
67
IEEE
Std 640-1985 IEEE GUIDE FOR
68
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
low speed for compressors and because compressors are usually more efficient
noise generators than pumps.
69
IEEE
Std 640-1985 IEEE GUIDE FOR
pressure drop). The second comes from the general turbulence of the fluid
boundary and is effective above and below choked flow in the valve orifice.
Regardless of the generating mechanism, the in-pipe valve-generated noise
field is propagated downstream and upstream, and decays very slowly with dis-
tance from the valve. Generally, the mass of the valve wall tends to attenuate
noise generated in the valve. As a result, the piping system itself often becomes
the prime source of externally radiated noise.
5.4.2 Piping. Excluding valve, orifice, or equipment noise the most common
pipeline noise source is the fluid flow itself, particularly with compressible fluids
such as steam and air. The higher the fluid or gas velocity and the lower its
viscosity, the louder the noise. From a system approach, velocity in valves and
piping are contributing factors and lack of design consideration in one area can
negate efforts in the other. Also, contributing to noise sources in piping systems
but usually to a lesser extent are
(1) Water hammer
( 2 ) Valve cavitation
(3) Mechanical vibration
Within the fluid itself, noise originates from either pulsating flow, fluid-wall
interaction, fluid mixing, or shock waves.
Pulsating flow causes the pipe wall to radically expand and contract and thus
generate noise when the pulse cycling falls in the audible range. Common
causes of the pulsations are reciprocating compressors, unstable valves, or sim-
ilar devices.
Fluid-wall interaction occurs when a turbulent steam or gas flow strikes a
pipe or fitting wall and creates a fluctuating force that causes the pipe to
vibrate. This force is usually minor in long, straight pipe runs. Projections or
discontinuities can produce turbulent wakes leading to serious noise conditions.
Fan noise is an example of fluid interaction with a solid surface.
Turbulent mixing of fluids creates a sound that travels outward to the pipe
wall, causing it to vibrate and generate noise. Usually, this occurs downstream
of an orifice or valve where a high-velocity jet mixes with a lower-velocity fluid.
Shock waves, other than those resulting from valves and orifices, can occur in
steam or gas lines when the pressure drop across a restriction exceeds a limit
known as critical pressure drop. Under this so-called choked flow condition,
flow at the vena contracta is sonic and shall inevitably slow down and mix with
the normal-velocity fluid somewhere downstream. This takes place in a short
space, creating a shock wave. Normally, the shock wave fluctuates in intensity
and position, giving rise to vibrations that carry through the pipe wall in the
form of noise.
70
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
71
IEEE
Std 640-1985 IEEE GUIDE FOR
bearings are not a noise contributor, but antifriction bearings may be. The con-
tact between the rolling parts and the stationary parts generates noise at gener-
ally predictable frequencies. The condition of the bearing parts and the
clearances between them are very important considerations. Brush noise is
another mechanical sound determined by the condition and quality of the brush,
its holder, and the rotating contact surface. This may be the prime noise source
in dc motors because of their slotted commutators. Brush noise in large motors
and generators may also be a factor in synchronous machines, but usually it is
of secondary importance.
Typically, the higher speed motors have higher noise levels. This is an effect
of higher peripheral velocities of rotating parts and thus, more windage noise. In
slower speed machines, the noise level is more electromagnetic in origin.
Motor noise level is a function of basic machine parameters. With all other
parameters constant - a higher speed motor will have a higher noise level, a
larger machine will be noisier than a smaller one, and a more enclosed machine
will be quieter than an open noise source.
The type of machine enclosure has a significant influence on the radiated
sound. A totally enclosed fan-cooled motor is the noisiest enclosure because it
utilizes a large external fan for cooling. The dripproof enclosure ranks second
because of the generally exposed parts. The weather protected Type I1
enclosure is quite effective in providing a quieter machine because its air paths
can be effectively treated.
The driven equipment should be a part of the consideration in evaluating the
noise sources present in a power train. In the power-station environment, the
driven equipment includes small generators, pumps, compressors, fans, and in
some cases, a gear box.
Gears tend to produce pure-tone noise in the 500 and 1000 octaves. Friction is
one of the major sources of gear noise. Gear frequency noise consists of the
tooth-passing frequency and a number of higher harmonics, plus other compo-
nents associated with the impacts and structural resonances.
Sound produced by small generators is similar to that of motors and the same
criteria generally apply.
72
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
sound depends on the pattern of vibration on its surface at the frequency con-
cerned.
The cooling system on large transformers also produces some noise; however,
it is of low magnitude and normally not a problem.
5.7 Cooling Towers. The power industry commonly uses hyperbolic natural
draft (counterflow or crossflow) and rectangular multicell or round multifan
mechanical draft cooling towers of the wet evaporative type for the power-plant
condenser cooling. The high degree of splashing inherent in cooling-tower oper-
ation is an important source of noise and is reminiscent of a waterfall. The air
induction fans used in mechanical draft towers are also a potential source of
noise.
In a natural draft crossflow, tower noise is generated by water cascading
73
IEEE
Std 640-1985 IEEE GUIDE FOR
through the packing which is similar in style and arrangement to that of the
mechanical draft tower packing.
In the counterflow natural draft tower, the packing or fill is contained within
the shell of the tower and most of the noise is generated by the water falling
from the bottom of the packing into the basin of the tower.
The tower water-splash noise is generally composed of high-frequency sounds
and increases with increasing water-flow rates. Typical operation of cooling
towers at power stations is at a constant flow rate; therefore, the tower presents
a very constant source of noise. The overall sound power radiated by a mechan-
ical induced-draft cooling tower is determined almost entirely by fan noise and
is related to the power of the tower fans. Total noise radiated by these types of
towers is therefore composed of fan noise at low frequencies and water-splash
noise at high frequencies. For a propeller fan used on cooling towers, the peak
noise level should occur in the frequency band containing the blade passing
frequency which is typically in the lower frequency bands. Round mechanical
draft towers have a concentration of fans at the center that may tend to have a
greater low-frequency influence on the sound spectrum than the fans of a
mechanical rectangular tower.
Fig 13
Turbine Admission Valves
NOTE: The changing frequency characteristic of the noise from turbine
admission valves is illustrated as a function of load or valve position.
Lowest sound levels are produced at full open valves.
10 dB
T--
w
IX
2w
v)
a
a
w -
zk
w
4 __ -~ -
a
FREQUENCY (Hz)
74
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
Fig 14
Turbine Admission Valves
NOTE: The increase in noise levels near the valve is illustrated after one
valve is closed to a 20% throttling position.
L I
lOdB m
U
FREQUENCY ( H z )
4 VALVES 100% -
3 VALVES 100%
1 VALVE 20% __--
IEEE
Std 640-1985 IEEE GUIDE FOR
10 dB
I l0,dB
-1,
GENERATOR
M LP TURBINE
I , i , ) r("i?
LP T U R B I N E
L-44
IPTURBINE Q
I :
m
HP TURBINE
NOTE: The noise is generally broadband NOTE: The noise is generally broadband
for turbine-generators with some char- for turbine-generators with some char-
acteristic peak at running speed of unit, at acteristic peak at running speed of unit, at
power frequency and at excitation fre- power frequency and at excitation fre-
quency. The data is illustrated in f octave quency. The data is illustrated in f octave
since octave-band data would diop out since octave-band data would diop out
rotational and excitation frequency peak. rotational and excitation frequency peak.
Fig 15 Fig 16
Steam Turbine-Generator Steam Turbine-Generator
Fossil-Fired Plant Nuclear Plant
76
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
10 dB
a
w
L
I I L
l-
a
1 '1
w
[ r ' 4 ,
I I 1 1
Fig 17
Pulverizers
t
lOdB
T-2 W
1
W
[r
3
v)
W
v)
a
LII
W
L
k
W
4
n
31.5 63 125 250 500 1000 200040008000 16000
FREQUENCY (Hz)
Fig 18
Boiler Feed Pump
77
. ..
IEEE
Std 640-1985 IEEE GUIDE FOR
NOTE: The variation in noise spectra from two different motor drives. The
small unit actually produced higher sound levels and several pure tones
are evidenced by the sawtooth spectra.
Fig 19
Boiler Feed Pump
lOdB Z
D
T-g w
J
w
K
3
v)
w
v)
m.
n
w
3
t
4
w
m
FREQUENCY (Hz)
NOTE: The variation in noise spectra from two different motor drives. The
small unit actually produced higher sound levels and several pure tones
are evidenced by the sawtooth spectra.
Fig 20
Boiler Feed Pump
78
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
lOd8
-m
U
I
t> J
W
w
J
W
Lf
3
07
w
(0
Lf
a
w
+I
QI
-
w
Lf
FREQUENCY ( H r )
NOTE: The relatively broadband spectrum on noise at the inlet t o this type
fan is illustrated with the somewhat tonal spectrum of noise from the
motor in the 1 kHz and 2 kHz octave.
Fig 21
Forced Draft Fan
t
10 dB
FREQUENCY (Hz)
Fig 22
Induced Draft Fan
79
IEEE
Std 640-1985 IEEE GUIDE FOR
5
J
w
CT
3
v)
W
v)
n
a
w
2
I-
4
w
CT
FREQUENCY (Hz)
Fig 23
Axial Flow Fan
L
lOdB
7:
>
w
J
Fig 24
Axial Flow Fan
80
. . _.
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
Fig 25
Soot-Blowing Air Compressor
100 METERS -
1000 METERS ____
NOTE: Octave-band spectrum illustrated during a venting or relief condi-
tion. The effect on spectrum due t o excess atmospheric attenuation at
frequencies above 500 Hz is very evident at remote measured location.
Fig 26
Boiler Drum Safety Valves
81
IEEE
Std 640-1985 IEEE GUIDE FOR
FREQUENCY (Hz)
LOWER DECK----
UPPER DECK -
FREQUENCY (Hz)
NOTE: Burner noise for two different fuels is illustrated. The low-
frequency rumble of the oil-fired burner is quite evident. The coal-fired
burner does not exhibit such low-frequency peak characteristics. The peak
a t 8 kHz is the result of nearby steam or air leak.
Fig 27
Furnace Burners
82
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
t
10 dB
T--
FANSON -
FANS OFF -- - -
NOTE: Octave-band illustrates the predominant noise in the 125 Hz octave.
The effect of noise from fans is most evident above 500 Hz.
Fig 28
Transformer
83
IEEE
Std 640-1985 IEEE GUIDE FOR
F R E Q U E N C Y (Hz)
FREQUENCY (Hz)
Fig 29
N D Cooling Towers
84
IEEE
POWER-STATION NOISE CONTROL Std 64@1985
NOTE: Rectangular tower of 5 cells handling 90 000 g/m. Round towers handling
172 000 g/m with 16 fans in tower center. Measurements at a distance of 24 m.
Fan noise is quite evident at the low frequencies.
Fig 30
M D Cooling Towers
85
IEEE
Std 640-1985
87
IEEE
Std 640-1985 IEEE GUIDE FOR
(6) Sound radiation from the equipment. These data may be obtained from
manufacturers or measurements on similar installations
(7) Absorption on interior surfaces and transmission loss of plant construc-
tion
(8) Possibility of using noise-control measures such as mufflers, enclosures,
design, and supplier options
(9) Economic considerations, including
(a) Cost of buying low-noise machinery
(b) Administrative controls
(c) Economic feasibility of acquiring enough land surrounding the plant
site, if needed, for required noise attenuation
Though construction of such a model is outside the scope of this guide, the
participation of the inputs and their interactions are discussed in the following
subsections to present their influence on the optimum solutions.
6.4.1 Plant Location. After the general location of the plant site has been
decided, the specific location of the facilities on the site shall be considered and
also the noise emission of the plant. The community requirements and the sen-
sitive noise receptors of the community shall be identified. The location of the
plant on the site should be selected so that the noise impact on the surrounding
community is minimized.
If a power plant is located within a few hundred feet of a residential area, it
can meet some current noise limits only by building it entirely inside a building
using only acoustically controlled openings. On the other hand, many plants are
located on large plots to provide for cooling towers or lakes, coal and ash
storage, and large extra-high voltage (EHV) switchyards. A totally outdoor plant
may meet community requirements if located 3000 ft to 4000 ft from the prop-
erty line. Between these extremes, the ability of a plant to meet the applicable
neighborhood noise criteria can only be determined by design calculations.
6.4.2 General Arrangement of Plant. The boiler side of the plant should be
located away from the closest property line, if practical, because large fans and
their ductwork are major sources of noise. Other sources of noise, such as
cooling towers, transformers, gas regulating stations, and car dumpers should be
located as far from property lines as practical.
If offices and shops cannot be located remote from the main plant, transmis-
sion of noise into these areas should be controlled. Airborne noise transmission
may be controlled adequately by using masonry walls between the quieter and
noisier parts of the plant. Major process pipes and ducts should not penetrate
the walls or be supported on structural elements common to the offices. Any
penetration that does exist shall be sealed airtight to prevent a noise leakage
between the opening and the pipe. Mechanical equipment should not be located
on the roof of a noise-sensitive area or immediately adjacent to the walls.
6.4.3 Building Design. Conventional masonry and double-panel metal siding
generally provide adequate noise reduction properties for the control of exterior
noise. However, openings such as windows, roof vents, and overhead doors
transmit noise to the outside; therefore, if the plant is located close to the prop-
88
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
erty line, the noise emanating from these openings may have to be controlled to
achieve the required noise level at the property line. Ventilating louvers with
sound-attenuating properties are available. For the control of interior noise,
sound-absorption material on the interior surfaces should be considered.
6.4.4 Design Approaches. Some items of mechanical and electrical equip-
ment can be specified with regard to sound level performance by referring to
industry standard test codes. There are economic considerations in buying
quieter equipment.
There are two primary approaches for designing a power plant to meet the
desired indoor noise levels. The first could best be described as a single noise-
level approach. Here, the increase in sound-pressure levels due to reverberation
and multiple sources is estimated. The maximum free-field sound-pressure level
from any specific equipment is so specified that the combined sound level does
not exceed the OSHA requirement (see [16]). The current eight-hour limit of
90 dB(A) is often specified for all areas of the plant.
The second approach is described as a multinoise-level approach. From the
OSHA noise requirement [ 161, the maximum permissible levels in various areas
of the power plant are determined. Allowing for reverberation, the relative con-
tribution of the major sources to the existing/projected noise levels in these
areas is estimated. With this information, an individual noise level is specified
for each of the major sources. With this approach, some retrofit noise-control
measures may be needed, but the total cost of power-plant noise control is
minimized.
It is difficult to outline a specific procedure for designing a power plant to
meet the exterior noise requirements. The sound field around a power plant
depends on its layout (that is, its location and orientation with respect to the
surrounding community). The exterior levels may depend on the type of fuel the
plant uses, which governs the choice of some of the auxiliaries, and whether or not
the plant is fully or partially enclosed. Each plant has to be designed individually.
89
.
IEEE
Std 640-1985 IEEE GUIDE FOR
system. All three sources shall be given consideration for effective noise con-
trol.
Depending on the type of building and the fan location, it is sometimes possi-
ble to provide a separate fan room with muffled inlets to the room. Reverberant
sound buildup inside the room can be reduced by using sound-absorbing mate-
rial on its walls and ceilings. Provisions have to be made for relieving pressures
and maneuvering and transporting the equipment.
An alternate noise-control procedure is to use insulation and lagging, and to
install inlet and ducting silencers.
6.5.2 Primary Air Fans. If the primary air fans have open inlets, they may
have to be enclosed or the housing changed to accommodate inlet ducting and
mufflers. An acceptable sound level should be specified by the purchaser since
most fan manufacturers can now predict the sound-power level of their equip-
ment for its noisiest operating mode. With this information, the acoustical
engineers can determine the dynamic insertion loss (DIL) required for the inlet
silencer and whether or not the inlet, outlet, and fan housing require normal
thermal insulation or the addition of acoustical insulation. An alternate
approach is to enclose an open inlet fan and use silencers with the enclosure.
6.5.3 Induced-Draft Fans. Induced-draft fans and boiler gas recirculation
fans have ducted inlets and outlets with thermal insulation on the ducts and fan
casings, They may however produce excessive noise levels. The specification
should state the intent of having the sound-pressure levels no greater than spec-
ified at some designated distance from the fan, including the attenuating effect
of the duct wall and insulation. Octave-band sound power or pressure levels
should be specified in the manufacturers proposal so the design engineer can
evaluate the resulting sound-pressure level.
In addition to the near-field noise the induced-draft fan system may radiate
noise from the top of the stack. To control this noise a specification should be
adopted that defines either the allowable sound power radiating from the stack
or acceptable noise level at some far field such as a distance of 1000 ft.
If the sound-pressure level is specified, an acceptable measurement procedure
shall be agreed upon to check compliance.
6.5.4 Roof and Wall Vent Fans. Roof and wall vent fans should be specified
to meet the octave-band sound-power levels necessary to meet the neigh-
borhood and OSHA criteria. They can be tested in accordance with AMCA STD
300-67 [l].
6.5.5 Air Conditioning and Ventilating Fans. Air conditioning and ventilat-
ing fans should be specified to meet octave-band sound-power levels that will
limit the noise in the occupied area to the noise-control criteria selected for the
particular area. They can be tested in accordance with AMCA STD 300-67 [l].
Some sound attentuation is provided by the ductwork, filters, and coils in the
ducts.
6.5.6 Motors. The free-field sound-pressure levels from electric motors can
be specified in accordance with IEEE Std 85-1973 (R 1980) [8].
6.5.7 Control Valves. Control valves can produce excessive noise under
90
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
some operating conditions. Quieter valves with special quiet trim can be
obtained, or the valve body and adjacent piping can be covered with acoustical
insulation to reduce noise. However, the cost of doing this is expensive if it is
done for all control valves. A better procedure is to ask the valve supplier for
the sound level and spectra of the valves and then provide quieter valves or
covering for only those valves and their adjacent piping which are likely t o
produce excessive sound levels.
6.5.8 Boiler Feed Pumps. Boiler feed pumps and their drives can be housed
in enclosures. These enclosures may be modules or permanent construction.
The many appurtenances on the equipment can make the application of
enclosures difficult. Enclosures around each pump and its drive allow mainte-
nance work on one unit without noise exposure from the other pump.
6.5.9 Main Turbine Generators. The main turbine generators are well cov-
ered with metal enclosures and generally produce noise levels of approximately
95 dB(A) or less in conventional turbine rooms for medium-size turbine gener-
ators, without any sound-absorbing materials on the walls or ceiling.
6.5.10 Burners. The noise levels due to the burners and the boiler are not
excessive because the normal insulation and metal lagging on the boiler walls
provide reduction in noise.
6.5.11 Piping. Noise associated with fluid flow may be transmitted through
pipe walls. Fuel gas piping can be covered with acoustical insulation in addition
to the usual antisweat insulation, if it is found to be a noise problem after the
plant is in service. The same is true of condensate piping. A high-temperature,
high-pressure pipe has heavier walls and heavier thermal insulation but may
need acoustical treatment if the velocity and pressure drops are high.
6.5.12 Cooling Towers. Blower fans and falling water are the main sources
of noise in cooling towers. The manufacturer can provide representative values
of sound levels which should be reviewed with regard for neighborhood criteria.
Relocating the cooling towers is one of the solutions if a problem exists. Two-
speed fan motors can be provided and operated at lower speed under low-load
conditions at night where the criteria are more stringent.
6.5.13 Soot Blowers. Soot blowers will usually produce noise levels above
90 dB(A). However, their intermittent operation prevents them from overexpos-
ing plant personnel. If need be, some attentuation of noise can be achieved
through quiet valves, larger piping, and better fitting wall boxes.
6.5.14 Pulverizers. Pulverizers and their motors can be noisy. To date, the
only noise control that has been applied has been to enclose the pulverizers as
a group in one room. It may not be practical to acoustically insulate them.
6.5.15 Aspirators. The airflow through opened aspirator doors will usually
produce excessive noise levels. The only practical solution is personal hearing
protection.
6.5.16 Safety Valves. Unmuffled safety valves when operated can produce
excessive noise levels in the surrounding community. While their operation is
infrequent, in some installations it may still be advisable to provide muffling.
Muffling may also be provided for steam blow-off operations,
91
IEEE
S M 640-1985 IEEE GUIDE FOR
92
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
7. Noise-Control Techniques
93
IEEE
Std 640-1985 IEEE GUIDE FOR
Table 8
Case I, Cumulative Overexposure
Allowable
Noise Level at Exposure Time
Work Location HourslDay Work Location HourslDay C"/T"
C" dB(A) T" Noise Rating
Control room 3 < 90 >a 0
94
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
Table 9
Case 11, Cumulative Underexposure
Allowable
Noise Level a t Exposure Time
HoursIDay Work Location HourslDay C/T
Work Location C dB(A) T Noise Rating
Control room 7 < 90 > 8 0
95
IEEE
Std 640-1985 IEEE GUIDE FOR
includes noise sources which may have noise levels of 90 dB(A) and above,
such as
(1) Forced draft fans and motors
( 2 ) Boiler feed pumps
(3) Steam dump valves
(4) Pulverizers and turbine-generators
In addition, it is useful to measure noisy areas where plant operators move
around and are consequently exposed t o noise, such as: compressor building,
demineralizer building, and ground floor elevation. The guiding factor in estab-
lishing the noise-exposure measuring locations in the plant area should be the
path traveled most frequently by one or more persons in the plant, such as the
auxiliary operators and the yard persons.
A very critical noise source is the steam dump to the atmosphere which can
be released unexpectedly and create a severe noise hazard to plant personnel.
This type of noise is particularly offensive in nuclear plants where the discharge
to the atmosphere can last for long periods of time and may pose a community
annoyance problem. Thus, near-field and far-field sound measurements should
be taken from this noise source.
The two most difficult problems in obtaining true sound readings during a
plant survey are the isolation of individual pieces of machinery from the other
plant equipment and the determination of the influence of room acoustical char-
acteristics on the measured sound levels.
The first problem can be resolved by taking sound measurements during out-
ages. Equipment such as forced-draft fans, compressors, and pumps should be
operated alone and can be measured with a good degree of isolation.
During normal plant operation, sound measurements taken at various dis-
tances from equipment with a one-third octave-band analyzer will help reveal
tones that are often the most predominant noise sources in the area. Acoustical
treatment of these tones will contribute much towards an effective sound-
control program.
The influence of room acoustics will be evident at higher sound levels in
highly reverberant rooms. This fact should be kept in mind when correlating a
manufacturers noise rating of equipment and measurements taken during a field
survey. It indicates that any noise-reduction effort shall consider the building
acoustics, particularly where a sheet metal or concrete building is used.
Some standards recommend four key-measuring positions in a rectangular
array around the plant equipment for sources which are not highly directional.
When the source is highly directional, measurements at more than 20 different
locations may be required. The preferred height of the microphone above the
floor is approximately 1.5 m.
7.2.4 Selection of Measuring Locations and Time of Survey at the Plant
Property Line. Measuring points should be established around the plant prop-
erty and measurements should be taken, preferably during the day and at night.
There are no set rules which establish how many measuring locations are
required around the plant perimeter. This depends upon the location and orien-
96
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
tation of the plant, local regulations, and the proximity of residential areas.
Since wind can upset the sound-level readings, it is good practice to take meas-
urements when there is minimum wind. Wind screens have been devised to
reduce microphone sensitivity to wind noise, but their usefulness is limited to
velocities below 20 mi/h. A good practice is to carry an anemometer when taking
outdoor measurements, thus eliminating the need to estimate wind velocity.
The sound level is affected by atmospheric pressure; therefore, if the
atmospheric pressure at the site is significantly different from 760 mm of mer-
cury a correction shall be made to the measurements.
A minimum of A-weighted network and octave-band readings are recom-
mended for indoor and outdoor plant measurements. For most cases a range of
63 Hz-8000 Hz center frequencies for the octave-band spectra will be sufficient.
The 16 Hz and 31.5 Hz bands have received attention due to complaints about
low-frequency noise from residents bordering industrial sites and should be con-
sidered when residents are located close to the plant.
7.2.5 Selection of the Plant Load. Some noise sources produce their high-
est noise level at a high load and other sources at a low load. For example, a
boiler feed pump coupling produced a 4 dB(A) higher sound level at a station
load of 550 M W than at 350 MW. Conversely, the turbine control valves pro-
duced a 4 dB(A) higher sound level at a load of 350 MW than at a station load
of 550 MW.
A sound survey should include measurements taken at different loads, both
in-plant and at the boundary line, to pinpoint the highest noise level emanating
from a particular piece of equipment. This is important for base load plants that
may operate at a variable output because of maintenance problems.
Subsequent acoustical treatment of plant equipment will be based on the
most frequently occurring high noise level found during the variable load opera-
tion.
97
IEEE
Std 640-1985 IEEE GUIDE FOR
3
3
2
3
0
3
2
-
N
I
>Uz
w
3
E
U
0
0
0
cf
0
0
0
N
98
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
Table 10
Correction for Ambient Sound-Pressure Levels
Difference Decibels (dB)
Between SPL measured with
sound source operating and
ambient SPL alone (dB) 4.0 5.0 6.0 7.0 8.0 9.0 10.0
Correction
Subtracted from source operat-
ing to obtain SPL due to sound
source alone (dB) 2.2 1.7 1.3 1.0 0.8 0.6 0.4
99
IEEE
Std 640-1985 IEEE GUIDE FOR
100
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
/f WALL
94 dB ( A ) -/
92 d8 ( A ) J'
Fig 32
Sound Contours
E G 3 3f
EG33 GENERATOR AND TURBINE --
Fig 33
Turbine-Generator and Boiler Feed Pump
Measurements Locations
101
IEEE
Std 640-1985 IEEE GUIDE FOR
t
10 dB
W L . .
2
1
n
z
2
W
>
Q
I
k
U I
0
FREQUENCY (HZ)
Fig 34
Octave-Band Analyses at Three
Locations on Turbine Deck
102
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
Fig 35
A-Weighted Octave-Band Analyses at
Three Locations on Turbine Deck
A closer look at the data however shows that this peak is not of primary
concern when the goal is in compliance with personnel noise-exposure regula-
tions. These regulations are concerned with the A-weighting scheme applied at
each octave band. Under these criteria it is seen in Fig 35 that high-frequency
noise from the boiler feed pump (1000 Hz-8000 Hz) is pushing up the overall
A-weighted sound level in the room. To reduce the A-weighted sound level, the
boiler feed pump is considered first even though the initial inclination may be to
work on the main turbine because of its size.
7.3.2.5 Load Dependent Noise Sources. Noise levels can vary with the
load on the unit. Some noise sources produce their highest noise level at a high
load and other sources at a low load. For example, a boiler feed pump pro-
duced a 4 dB higher sound level at a station load of 550 MW than it did at a
103
IEEE
Std 640-1985 IEEE GUIDE FOR
FREQUENCY (Hz)
Fig 36
Boiler Feed Pump
FREQUENCY (Hz)
Fig 37
Turbine Control Valve Chest
104
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
station load of 350 MW, as shown in Fig 36. Conversely, the turbine-control
valve chest produced a 4 dB higher sound level at a load of 350 MW than at a
station load of 550 MW, as shown in Fig 37. Thus, a sound survey should
include measurements takert at different plant loads to pinpoint the highest
noise level emanating from a particular piece of equipment.
7.3.2.6 Narrow-Band Analysis. Since a noise measurement taken in an
operational power plant can contain contributions from a number of sources, it
is important to be able to locate the source of discrete frequency noise. Narrow-
band analysis can be a useful tool in identifying noise sources.
As an example, this technique is used inside a 750 MW plant. An extensive
sound survey is conducted on the turbine deck and on lower levels. One meas-
urement location is 3 ft from a valve on a lower plant level. Two other points
are on the turbine deck, 3 ft from the turbine, as illustrated in Fig 38. Figure 39
shows data from these three points displayed as narrow-band spectrum plots.
Fig 38
Location of Measuring
Points on Turbine Deck
105
IEEE
Std 640-1985 IEEE GUIDE FOR
Fig 39
Narrow-Band Spectrum Plots
As can be seen in Fig 39, all three measurement locations show significant
peaks at 2600 Hz intervals. For each of these peaks the valve shows consistently
higher sound levels. For example, at the 2600 Hz peak, the valve sound level
is approximately 9 dB higher than the level associated with the low-pressure
turbine.
Since the peaks are of the greatest magnitude in the vicinity of the valve, it is
a good indication that the peaks are characteristic of the valve. Even though the
valve is located on a lower level, it has a significant influence on the sound
levels associated with the main turbine-generator on the turbine deck. This can
be accounted for because an open well is located on the high-pressure end of
the machine which permits valve noise to emanate up into the turbine hall. The
sound spectrum recorded near the low-pressure turbine then shows the smallest
peaks at 2600 Hz intervals because it is farthest away from the well. Noise
traversing from floor to floor will tend to be a universal problem when attempt-
ing to obtain accurate noise measurements because open wells are rather com-
mon in power plants.
7.3.3 Data Interpretation of Community Noise. Power-plant noise sources
that influence community ambient-noise levels shall be identified. The first step
in this process is the collection of noise data at the complaint location or at a
position prescribed by local code for the accurate measurement of ambient-
noise levels. The next step is the interpretation of this data.
106
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
70
60
m
a
3.
0
N
r
L
-
m 50
-
U
J
w
>
w
J
w
K
2 40
rn
w
LT
4
0
2
3
a
0
z 30 NOISE \
4.
cp \
w \
> \
<
+
U
0
20
10 I 1 I 1 I 1 I
31.5 63 125 250 500 1000 2000 4000 8000
OCTAVE BAND CENTER FREQUENCY (Hz)
Fig 40
Sound-Pressure Level of Complaint and
Residual Ambient Noise as a Function of
Frequency in Octave Bands
(Distance from Plant is 2000 ft)
107
IEEE
Std MO-1985 IEEE GUIDE FOR
60
I D F A N TONES
10 I I I I I I 1
100 200 300 400 500 600 700 800
FREQUENCY ( H I )
A N A L Y S I S BANDWIDTH 6 Hr
Fig 41
Narrow-Band Analysis of Complaint Noise
with Sound-Pressure Level Plotted
as a Function of Frequency
108
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
Fig 42
Variation of Background Noise Caused by
Meteorological Conditions
(a) Noise Recorded Near Power Plant
(b) Noise Recorded During Same Time Span
but in a Residential Area Some Distance
from the Plant
meteorological conditions is illustrated in Fig 42(a) and (b). In Fig 42(a) the
noise recorded close to the plant is plotted as a function of time, while in Fig
42(b) the noise level is recorded in a nearby residential area as a function of
time. Note that while the plant noise is steady, the residential recorded noise
varies significantly.
The load level of the power plant can also affect community noise levels.
Normally the plants contribution to community noise levels is greater at higher
loads: During nighttime operation, load demands are usually less than daytime
output requiring the throttling of valves. Consequently, more pronounced pure
tones may be generated.
The type and magnitude of noise on which a complaint is lodged is important.
Whether it is a pure tone or a pulsating noise may be indicative of the source.
The time and date of the initial complaint should also be noted. Knowing
whether the noise repeats at the same time every night or occurs only on week-
ends is very important in determining the source. The geographical relationship
between the power plant and the complaint location is also of importance. For
example, a transformer was determined to be the source of complaint even
though it was 10 000 ft from the lone complaining resident. The noise emanating
from the transformer funneled through valleys, was reflected by the atmosphere,
and finally propagated to the general location of the complaint.
109
IEEE
Std 6440-1985 IEEE GUIDE FOR
110
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
111
IEEE
Std 640-1985 IEEE GUIDE FOR
112
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
NEMA TR1-1980[91 but lower noise-level transformers can be obtained from the
manufacturer at a higher initial price. In many control valve applications, the
valve body can be designed to accommodate various forms of special trim
which reduce noise by controlled multipath expansion and therefore reduce
velocity and noise.
Treatment of internal equipment noise generated by friction, impact, tur-
bulence, imbalance of rotating parts, fluid cavitation, pressure drops, mass flow,
magnetic attraction, or other motions due to change in velocity of moving parts
is most effectively done and generally more economical during preliminary
design, before the new or modified machine leaves the drawing board. For exist-
ing power-plant equipment, changing to a quieter design by modification or
retrofit, or by replacing partially depreciated equipment with new quiet equip-
ment, if available, is often very expensive, inconvenient, and sometimes impossi-
ble from a practical viewpoint.
7.4.2.2 Path Treatment. Sometimes it is impossible to reduce sound levels
of high horsepower and high-speed machinery to acceptable levels by internal
design changes alone. Compromises on size, weight, accessibility for mainte-
nance, and convenience in operation may also fail to reduce noise to acceptable
levels. In this case, additional sound control will be necessary after the machine
has been built. In general, any method which is prescribed to reduce noise
between the origin or source and a microphone or the ear of the listener
(receiver) is defined as path treatment.
Some of the main devices which are being used for path treatment are
(1) Acoustical enclosures
(2) Mufflers
(3) Plenums
(4) Lagging
(5) Acoustical shields or barriers
(6) Absorbent coatings and ceiling septums
(7) Vibration isolation
(8) Vibration damping
(9) Various combinations of these devices
Selection and usage of a particular type of path treatment is often a difficult
task and depends on the sound spectrum being radiated from the source and
the nature of the path it takes to the ear of the receiver.
7.4.2.2.1 Acoustical Enclosures. An acoustical enclosure may consist of
a single solid, laminated, multilayer, or sandwich-type panel which has a solid
outer shell, space for one or more fibrous or l i m p mass inner fillers, and an
absorbent liner with a retainer for holding the liner or filler in place. The liner
may consist of a perforated inner sheet which has sufficient strength to be self-
supporting or it may be a soft, porous material which adheres to or is attached
to the existing structure.
For maximum attenuation, the shell that blocks the transmission of noise
shall be nearly airtight with a sealant or flexible material used around all piping,
electrical, or other penetrations to minimize noise leaks. Thinner shells may be
113
IEEE
Std 640-1985 IEEE GUIDE FOR
114
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
115
IEEE
Std 640-1985 IEEE GUIDE FOR
For existing power plants, it may be the only economically feasible method of
employee protection from intermittent exposure to high noise levels.
Personal protection devices consist of ear plugs of various types, ear muffs,
or earphones. Properly fitted ear plugs and muffs can provide up to 25 dB
attenuation in some frequency bands.
Another personal protection measure which may infringe on path treatment
instead of receiver treatment is to enclose the operator(s) of a piece of equip-
ment in an air-conditioned enclosure, such as a cab or booth. A three-sided
partial enclosure with a top and windows for viewing is an effective technique.
After source and path treatment, the two major categories for the engineering
methods of noise control, have proven to be unfeasible or unpracticable, the
next step in a noise-control program is administrative controls. See 7.7.
7.5 Selection of Noise Reduction Schemes for Different Noise Sources. The
acoustical engineer selects the most appropriate attenuation device for a spe-
cific area, room, or individual piece of equipment after identifying the noise
source by analysis of data obtained during a sound-level survey, determining
acceptable noise criteria, and reviewing probable attenuation techniques. The
most logical device from a noise-reduction viewpoint may not be economically
feasible or practical from a field-erection standpoint. The space available in an
existing plant, multiple penetrations (such as pipes, conduits, and cable trays)
that cannot be sealed airtight, the risk of overheating existing equipment, and
any acoustical device shall be partly removed or disassembled for inspection
and periodic maintenance of equipment are a few of the design parameters that
often prevent use of the most logical acoustical device. All of the design param-
eters should be considered in the selection of any noise attenuation device.
The attenuation techniques listed in Table 11 may be used as a guide in
selecting a device for the reduction of noise from equipment of like size and
type, and similarly located and mounted in a system where projected field use is
the same.
Table 11
Possible Sources of Noise and Possible Methods of Noise Reduction
1. Air Equipment
a. Compressors - acoustical block or paneled enclosure
Air intake and discharge - mufflers
Intake and discharge piping - lagging
Relief valves and vents - quiet trim or in-line silencers
h. Ejectors - lagging, mufflers
c. Open-air jets - quiet trim valves or mufflers
2. Boilers
a. Aspirated doors - wear hearing protectors when doors are opened
3. Coal Handling Equipment
a. Car shakers - provide acoustical booth for operator
h. Coal crushers - enclosure and vibration isolators
c. Feeder vibrators - enclosure
d. Mills or oulverizers - enclosure
116
IEEE
POWER-STATION NOISE CONTROL Std 64@1985
Table 11 (Continued)
Possible Sources of Noise and Possible Methods of Noise Reduction
4. Engines
a. Emergency power diesel generator - enclosure
Intake and exhaust - muffler
Cooling fan - shroud intake or exhaust, or both
b. Fire pump diesel - same as above (This is an intermittent duty item.)
5. Electrical Equipment
a. Circuit breakers - mufflers
b. Motors (large) - enclosure and mufflers
c. Transformers - barrier or enclosure (Install in vault with sound absorption.)
6. Fans
a. Forced draft - enclosure, lagging, or duct silencers
i. Open Inlet. Enclosure or acoustical plenum with or without inlet silencers. Configuration
with fans on base slab and inlet ducted from opening near top of boiler may not require
inlet silencers. Air preheater and boiler act as noise sink for airborne noise traversing the
length of the duct. Lagging reduces radiated noise.
ii. Closed Inlet. Lagging or lagging and duct silencers, or both
b. Induced draft - lagging (A silencer may be required to reduce tonal noise.)
c. G a s recirculating - lagging
d. Primary air - lagging and inlet and discharge silencers (Use enclosure if inlets are open.)
e. Ventilating air - louvers and silencers
7. Precipitators
a. Rapper and vibrators - lagging and enclosures
8. Pumps
a. Ash sluice - lagging and enclosure
b. Boiler feed - located operating floor - enclosure
Located base slab - numerous penetrations and maintenance costs affect economic
feasibility of an enclosure in this case.
c. Condensate - lagging and enclosure
d. Condensate booster - lagging and enclosure
e. Fire - lagging and enclosure
9 Soot Blowers
a. Air flow - redesign of some of piping and valves which contribute to noise. Closer fitting
wall box on furnace.
b. Steam flow - same as above
c. Air motor drive - exhaust mufflers
10. Turbogenerators
a. Bearings - walk-in lagging and enclosure
b. Exciter brushes - lagging and enclosure
C. Exciter gears - enclosure
d. Exciter vent fans - install silencers in air inlet and discharge
e. LP turbine casing - seal openings in existing housing
f. Steam control valves - insulate with fiberglass and impervious covering
23. Reduction gearing - enclosure
h. Steam piping - reduce velocity, reduce number of bends and install acoustical/thermal
insulation.
11. Vacuum System
a. Cleaners - lagging and enclosure
b. Ejectors - lagging
c. Pumps - lagging and enclosure
117
IEEE
Std 640-1985 IEEE GUIDE FOR
Table 11 (Continued)
Possible Sources of Noise and Possible Methods of Noise Reduction
12. Valves
NOTE: Quiet trim is usually limited t o replacement items or new facilities.
a. Pressure reducing - quiet trim, multiple step pressure reduction, in-line silencers, lagging,
heavier wall pipe, enclosures
b. Pressure relief - quiet trim, silencers, bell mouth, or tapered exit
c. Steam dump - quiet trim, silencer, heavier wall pipe, and lagging
d. Vent - quiet trim and silencers and plenums
13. Miscellaneous
a. Piping - heavier wall and lagging. Delete discontinuities such as sharp bends, and large
divergent sections. Provide quiet valves or silencers for atmospheric releases. Lower
velocity.
b. Ducting - lagging, turning vanes, addition of stiffeners, and heavier wall thickness
c. Intakes - silencer and louvers
d. Vents - silencers, quiet trim valves, and plenums
e. Housing and panels - lag or damp emitting housing and panels
f. Air and steam leaks - improve maintenance to minimize leaks
118
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
7.8 Summary. The basic methods and techniques for noise reduction (see 7.4)
may be used not only in and around power plants, but also in and around other
industrial plants to produce a quieter environment.
Under engineering control for noise abatement, the two major categories of
treatment, source and path, have been discussed and the conclusion drawn that
source treatment is generally the most economical approach to noise reduction.
However, from the standpoint of an overall noise-control program, receiver
treatment through the application of administrative control is quite important
and shall be considered.
Numerous probable sources of noise and known attenuation techniques for
each have been listed and discussed. Experience has shown that once a noise
attenuation method has been employed, a follow-up sound-level survey should
be made to ascertain its effectiveness. Analysis of the follow-up data will aid in
the continuing search for more economical methods, techniques, and devices for
noise reduction in power plants.
The application of known techniques, the analysis and study of the results
achieved, and the reapplication of modified or improved methods to similar
noise problems is a process which shall be continued if the noise problems are
to be resolved effectively.
119
IEEE
Std 640-1985
12 1
IEEE
Std 640-1985 IEEE GUIDE FOR
of environmental noise (that is, noise emitted beyond the plant property line)
and in-plant noise (that is, noise within the property line). For either of these
two concerns, the development of realistic design objectives can follow a logical
four-step process
(1) Establish ideal noise-control objectives
(2) Determine conceptual noise-control procedures that are probable to
achieve the ideal noise-control objectives
(3) Evaluate the conceptual noise-control procedures and determine those
procedures that are feasible and, if required, will be implemented
(4) Determine realistic design noise-control objectives based upon the limita-
tions established by design procedures considered not feasible
The following subsections outline what is involved in each of the four steps:
8.2.1 Ideal Noise-Control Design Objectives. The purpose of developing
ideal noise-control design objectives is to generate a baseline for preliminary
evaluation of the impact of designing for noise control. These objectives set
forth numerical values with which to compare expected equipment noise emis-
sions and determine probable design noise-control procedures. The required
design procedures are conceptual in nature at this point and generally do not
consider feasibility from aspects other than acoustical. They do however serve
the important functions of allowing those responsible for making design deci-
sions to grasp the potential impact of noise control on the project and providing
the basis for evaluating the feasibility of potential noise-control/design features
from other aspects, such as cost, safety, maintenance, and operations.
Ideal noise-control design objectives are numerical limits that are selected to
ensure that the new power plant will not experience any noise problems at all;
neither from the standpoint of legal requirements nor from the standpoint of
annoyance. Ideal environmental design objectives should consider
8.2.1.1 Legal Requirements. The status of noise regulations that may
affect the new plant should be thoroughly investigated at federal, state, county,
and municipal levels (see Section 3). Ideal design goals should be based upon
existing noise regulations and on regulations that either have been proposed or
are likely to be proposed by governmental bodies.
8.2.1.2 Interference with Activities. Plant noise emissions should not
interfere with activities of surrounding neighbors. Major consideration should be
given to noise-sensitive activities such as sleeping, conversing, or activities
requiring concentration (for example, studying). In determining normal activities
which will be conducted around the new site, possible land use changes around
the site should be considered.
8.2.1.3 Ambient Noise Increases. Neighbors, particularly those in residen-
tial areas, will look upon excessive increases in ambient noise levels as a pollu-
tant that degrades the value and full enjoyment of their property. Ambient noise
surveys should always be taken around a new plant site that has existing neigh-
bors and these results should be weighed in setting ideal noise design objec-
tives. This is also important if there is a possibility of new neighbors moving in
prior to the completion and operation of the plant.
122
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
123
IEEE
Std 640-1985 IEEE GUIDE FOR
achieved. Because of the total absence of any benefits gained by reducing levels
due to secondary noise sources much below these limits, it is important to
determine these limitations. Those design procedures judged to be unfeasible
will determine the practical noise-control design objectives to be used for the
project.
124
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
9. Bibliography
125
IEEE
Std 640-1985 IEEE GUIDE FOR
126
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
Appendixes
(These Appendixes are not a part of IEEE Std 640-1985, IEEE Guide for Power-Station Noise Control.)
Appendix A
Noise Legislation
130 125
w
J 120
2
120 115
a
U:I
3
ul
110
UI
a:
a 110
n 105
z
3
100
100
95
90
90
30
The numbers in brackets preceded by the letter B correspond to those of the References listed
in A4. of Appendix A.
127
IEEE
Std 640-1985 IEEE GUIDE FOR
graph and noting the A-weighted sound level corresponding to the point of high-
est penetration into the sound level contours. This equivalent A-weighted sound
level, which may differ from the actual A-weighted sound level of the noise, is
used to determine exposure limits from Table A-1.
(b) (1) When employees are subjected to sound levels exceeding those listed
in Table A-1, feasible administrative or engineering controls shall be utilized. If
such controls fail to reduce sound levels within the levels of Table A-1, personal
protective equipment shall be provided and used to reduce sound levels within
the levels of the table.
(2) If the variations in noise level involve maxima at intervals of 1 second
or less, it is to be considered continuous.
When the daily noise exposure is composed of two or more periods of noise
exposure of different levels, their combined effect should be considered rather
than the individual effect of each. If the sum of the following fractions: CUT1 +
C2/T2.. . . Cn/Tn exceeds unity, then, the mixed exposure should be considered
to exceed the limit value. Cn indicates the total time of exposure at a specified
noise level, and Tn indicates the total time of exposure permitted at that level.
Exposure to impulsive or impact noise should not exceed 140 dB peak sound
pressure level.
NOTE: Section 1910.95(c) through ( s ) and Appendixes A through I describe the hearing conserva-
tion program. These amendments are still under administrative review prior to final issuance.
128
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
129
IEEE
Std 640-1%5 IEEE GUIDE FOR
Table 1
Permissible Noise Exposures'
Sound level
db(A) slow
Duration per day, hours response
8 90
6 92
4 95
3 97
2 100
1% 102
1 105
% 110
Yi or less 115
'When the daily noise exposure is composed of two or more
periods of noise exposure at different levels, their combined effect
should be considered, rather than the individual effect of each. If
the sum of the following fractions: CUT1 + C2/T2 . . . . Cn/Tn
exceeds unity, then, the mixed exposure should be considered to
exceed the limit value. Cn indicates the total time of exposure at a
specified noise level, and Tn indicates the total time of exposure
permitted a t that level.
90dB, a second machine of the same kind placed next to it will result in a
combined noise level of 93 dB, rather than 180 dB, which might be expected.
( 3 ) Exposures at Different Sound Levels. Table 1 describes the method by
which several separate exposures to different sound levels during a day are to
be treated in determining whether or not the combined exposure is within per-
missible limits.
For example, assume that an employee works most of the day in an area in
which the sound level is 90 dB(A), but for 105 min out of each of 8 h, he is in
an area of 100 dB(A), and for one 15 min period each day, he is in an area of
105 dB(A).
This adds up to 6 at 90 dB(A): permissible duration of exposure, 8 h; 1: h at
100 dB(A): permissible exposure 2 h; and t h at 105 dB(A): permissible expo-
sure, 1 h. Tabulating it, we have:
130
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
-6 + +175
+ - = -025
+ + + 6- = 7 2 15
-=1.87
8 2 1 8 8 8 8
This is greater than unity and therefore not permissible. Either the exposure to
the 100 dB(A) levels have to be eliminated or the exposure to 105 dB(A) elimi-
nated and the exposure to 100 dB(A) reduced to 0.5 h or 30 min so as not to
exceed the permissible total exposure. In addition; no further exposure at the
90dB(A) level is allowed.
0.25 = -2.0
6 + -
- = 6 + -
1 or - 0.50 = _
2.0= 1
8 1 2 8 2 2
(4) Impulse o r Impact Noise. The last sentence of Sections 50-204.10 [B6]
and 1910.95 [B6] states
Exposure to impulsive or impact noise should not exceed 140 dB peak sound
pressure level.
This sets the upper limit of sound level to which a person should be exposed,
regardless of the brevity of the exposure.
In contrast with the 115 dB(A) upper limit for steady noise, the higher inten-
sity for impact noise is permissible because the noise impulse resulting from
impacts, such as hammer blows or explosive processes, is past before the ear
has time to react fully. Impact noise levels are to be measured only with an
impact meter or an oscilloscope.
(5) Converting Octave-Band Analyzer Readings. Many plants have done
much noise-control work based on measurements taken with the type of instru-
ment that measures the sound level at each of a number of frequencies, or
pitches, of the sounds produced rather than the overall total noise, as measured
by the sound-level meter. A chart is provided in the regulations to permit read-
ings obtained from an octave-band analyzer to be converted to corresponding
values as indicated in Table 1.
Sections 50-204.10 [B6] and 1910.95 [B6] (a) state
When noise levels are determined by octave-band analysis, the equivalent A-
weighted sound level may be determined as follows:
Equivalent sound level contours. Octave band sound pressure levels may be
converted to the equivalent A-weighted sound level by plotting them on this
graph and noting the A-weighted sound level corresponding to the point of high-
est penetration into the sound level contours. This equivalent A-weighted sound
level, which may differ from the actual A-weighted sound level of the noise, is
used to determine exposure limits from Table 1.
Figure A2 illustrates, in a general way, the response of a sound-level meter
working on the A scale. It minimizes, as does the ear, the low-frequency sounds
and emphasizes, as does the ear, the high-frequency sounds. Thus, a 90 dB read-
ing on the A scale may include as hlgh as 103 dB at 125 Hz, but will not accept
more than 85 dB at 2000 Hz and 4000 Hz.
131
IEEE
Std 640-1985 IEEE GUIDE FOR
140
125
120
115
0
z
3
110
105
100
z
A
W
Y 95
> a
2 2
3
0 Y
90
Fig A2
Band Center Frequency (Hz)
132
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
Where the sound-level meter on the A scale, at slow response, moves up from
a generally steady reading, for example, from 88 dB to 92 dB, at intervals of 1 s
or less, the high reading shall be taken as that to be used in Table 1.
As a corollary, intermittent sounds of brief duration at intervals greater than
1 s should, as far as practical, be measured as to intensity and duration, and the
total duration over a day be ascertained. This total should be entered in the
equation given in Table 1, Footnote 1, to determine the permissible limit. These
intermittent sounds, which can be measured with a sound-level meter, should
not be confused with impulse sounds of very short duration resulting from
impacts or explosions.
(7) Control Measures. Sections 50-204.10(b) [B6] and 1910.95 (b) [B6] refer
to control measures to be taken:
(b) When employees are subjected to sound exceeding those listed in the
Table of Permissible Noise Exposures, feasible administrative or engineering
controls shall be utilized.. . .
The Department of Labor considers feasible to mean Capable of being done,
accomplished or carried out; capable of being dealt with successfully [B8].
(8) Engineering Noise-Control Measures. Engineering controls are those
which reduce the sound intensity either at the source of the noise or in the
hearing zone of the workers. For example,
(a) Maintenance
(i) Replacement or adjustment of worn and loose or imbalanced parts
of machines
(ii) Lubrication of machine parts and use of cutting oils
(iii) Properly shaped and sharpened cutting tools
(b) Substitution of machines
(i) Larger, slower machines for smaller, faster ones
(ii) Step dies for single operation dies
(iii) Presses for hammers
(iv) Rotating shears for square shears
(v) Hydraulic for mechanical presses
(vi) Belt drives for gears
(e) Substitution of processes
(i) Compression for impact riveting
(ii) Welding for riveting
(iii) Hot for cold working
(iv) Pressing for rolling or forging
(d) Vibration dampening
(i) Increase mass
(ii) Increase stiffness
(iii) Use rubber or plastic bumpers or cushions
(iv) Change size to change resonance frequency
(e) Reducing sound transmission through solids
(i) Flexible mountings
(ii) Flexible sections in pipe runs
133
IEEE
Std 640-1985 IEEE GUIDE FOR
134
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
135
IEEE
Std 640-1985 IEEE GUIDE FOR
but shall be fitted to the individual. In addition, plugs, and any other type of
protector inserted into the ear, shall be issued by a physician or by a trained
person under the direction of a physician. Frequent checks shall be made to see
that the plugs are being properly inserted.
Ear muffs, though relatively expensive, may be issued by any designated per-
son in the plant, as the only fitting required is adjustment of the headband. This
makes it very easy for the supervisor to check on proper use of the muffs. Long
hair and spectacle or goggle temples will interfere with the seal made by the
cushioned edges of the muffs and will correspondingly reduce the actual
attenuation as stated by the manufacturer.
Regardless of the type of ear protector decided upon, its attenuation, as
stated by the manufacturer, shall be sufficient to reduce the noise level in the
workers ear to the level and for the duration prescribed in Table 1. The manu-
facturers stated values are determined under ideal conditions and therefore, as
a precaution, it is wise to assume that the attenuation actually attained in use in
the shop will be at least 5 dB less than the stated value.
The Department of Labor strongly recommends that any employee who is
exposed to high sound levels and requests ear protection be provided with it,
even if the duration of exposure is within the limits prescribed by Table 1.
(13) Definitions.
continuing. A program will be in effect and in use for the duration that noise
levels above 90 dB(A) occur in the plant.
effective. Employees exposed to those noise levels above 90 dB(A) will not
suffer continuing deterioration of hearing acuity because of the exposure, and
incipient loss of hearing will be detected and necessary steps taken to prevent
further deterioration before serious hearing loss has occurred.
136
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
137
IEEE
Std 640-1985 IEEE GUIDE FOR
movement and bending of cord, wire, and lead; knob turning, switch actuating,
and button pushing to ensure that there are no sounds other than the test tones.
A log of these checks shall be maintained and available for inspection.
(c) Records. In addition to the certificates and logs referred to in (13) (b), a
record of each audiogram made on each individual tested shall be available for
inspection. Records of audiometric tests shall indicate whether readings are
based on ANSI S2.45-1983/ASA 51 [B4] (IS0 R389-1964 [B5]). The complete
records on each employee required to be tested shall be retained for 1 year
following termination of employment or transfer to an area in which noise lev-
els above 90 dB(A) do not exist.
The records will be examined for evidence of any deterioration of hearing
acuity and of action taken to prevent further deterioration in those employees
found to suffer some loss of acuity. Conclusions as to the effectiveness of con-
trol measures taken will be based on examination of a significant number of
audiograms and not upon the basis of one or two cases.
(d) Audiometric Tests Outside of the Plant. If audiometric tests are done
outside the plant, the Department of Labor representative will also inspect the
facilities and test records and the same standards will apply.
Plant management will make arrangements for such inspection with the per-
son conducting the audiometric tests and may accompany the representative in
the inspection and review of records.
(15) Noise Surveys. A noise survey of each area in the plant in which sound
levels exceed 90 dB(A) shall be made at least once each year to ensure that
sound levels have not increased above those originally existing. The survey may
also establish that noise levels in some areas have been reduced to levels below
90 dB(A) and thereby justify discontinuing application of requirements for
administrative controls, ear protection, and audiometric tests of individuals in
such areas.
A noise survey of an area is recommended whenever a change is made in
either equipment or type of operations, so that significant changes in noise level
will be acted upon immediately.
Tests of noise levels will be made with a sound-level meter on the A-scale,
slow response. The use of octave-band analyzers or impact meters for control
or other purposes shall be in addition to, not in place of, tests made with the
sound-level meter.
The sound-level meter used will be one meeting the specifications in ANSI
S1.4-1983 [Bl].
Records will be made of such surveys showing
(a) The instrument used
(b) Date
(c) The time and location of such tests
(d) The machinery or equipment generating the noise
(e) The name of the person making the test
Test records shall be kept readily available for inspection for 1 year or until a
subsequent survey is made, if done more frequently.
138
IEEE
POWER-STATION NOISE CONTROL Std 640-1986
139
IEEE
S M 640-1985 IEEE GUIDE FOR
Agency (EPA). The legislation also called for public hearings of environmental
noise and a special report to the Congress on the problem, incorporating the
results of the public hearings and other special studies. Information from this
EPA report and extensive Congressional hearings formed the basis of the Noise-
Control Act of 1972.
(2) The Effects of Noise. Half of the some 80 million people significantly
affected by noise (from transportation, construction activities, and other engine-
powered equipment and devices) are exposed to levels that can damage their
hearing or otherwise affect their health. Noise also interferes with communica-
tion and interrupts sleep-generally adding to the stress of modern life-with
some of the resulting physiological responses apparently chronic. For the aver-
age urban dweller, the fact that noise impinges upon the quality of the environ-
ment is probably the most impelling reason for quieting things.
( 3 ) The Noise-Control Act of 1972. The Noise-Control Act of 1972 represents
the first major federal attempt to eliminate excess noise at the design stage of a
wide variety of new consumer products.
The administrator of the EPA is required to develop and publish information
regarding permissible levels of noise, and then to set noise standards for prod-
ucts that have been identified as major sources of noise.
While aircraft noise control remains under the administration of the FAA, the
law gives the EPA an advisory role in formulating criteria and standards for
controlling this source of noise.
(4) Major Provisions. The EPA is directed to develop and publish information
on the noise limits required for protecting the public health and welfare and a
series of reports to identify products that are major sources of noise and to give
information on the techniques for controlling noise from such products.
Using the criteria thus developed, the EPA administrator is required to set
noise-emission standards for products that have been identified as major
sources of noise and for which standards are deemed feasible. The law requires
such standards to be set for products in the categories of construction equip-
ment, transportation equipment (except aircraft), all motors and engines, and
electrical and electronic equipment. It also grants authority to set standards
deemed feasible and necessary to protect public health and safety for other
products.
The EPA has authority to require the labeling of domestic or imported con-
sumer products as to their noise-generating characteristics or their effectiveness
in reducing noise. Manufacturers or importers of nonconforming or mislabeled
products are subject to fines of up to $25000 per day for each violation and to
imprisonment for up to one year. Manufacturers must issue warrants that at the
time of sale their regulated products comply with federal standards. They are
also required to maintain records and provide information, including production
samples, if requested by the EPA.
The EPA administrator also is to prescribe noise-emission standards for the
operation of equipment and facilities of interstate railroads, ,trucks, and buses.
All federal agencies are directed to use the full extent of their authority to
140
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
ensure that purchasing and operating procedures conform to the intent of the
law. The EPA may certify low-noise emission products for purchase by the
federal government.
(5) Some of the Common Noisemakers. Aircraft, transportation equipment
(most notably trucks), and construction equipment are major sources of
environmental noise. Recently, the booming recreation industry has added a
new dimension to the problem as snowmobiles, trailbikes, and other engine-
powered devices have become more and more popular. By the end of 1970,
there were approximately two and one-half million motorcycles in the United
States, five times the number in use in 1960. The growing number of power
tools and devices in use in the home (manufacturers of power lawn-mowing
equipment have shipped nearly 89 million units since 1946) are also adding to
the din. It is not surprising, then, that from 22 to 44 million people have lost
part of the use of their homes because of aircraft and transportation noise.
(6) Aircraft Noise. Under the Noise-Control Act of 1972, the EPA administra-
tor was required by mid-1973 to make a comprehensive study of aircraft noise
and cumulative noise exposure around airports. Using this information, the EPA
is to submit to the FAA proposed regulations to control aircraft noise and sonic
booms. After a hearing and further consultation with the EPA, the FAA may
adopt or modify the proposed regulations. The FAA may reject the proposals if
it believes they are unsafe, technologically or economically infeasible, or not
applicable to certain aircraft. However, it must publicly explain its specific rea-
sons for rejection. A continuing review and consultation role is provided for the
EPA.
( 7 ) Citizen Suits. Any person may start a civil action on hidher own behalf
against any person or the United States and any other governmental agency for
violation of this act. Similarly, civil action may be brought against the adminis-
trator of the EPA or the FAA for failure to perform any nondiscretionary duty
under this law. Rights which a person may have under different statutes or the
common law to enforce a noise-control requirement are not restricted by this
law.
(8) An End to Noise Pollution. The comprehensive nature of the Noise-
Control Act of 1972 brings under federal regulation, for the first time, nearly all
of the major new sources of noise. An incentive now exists for the full employ-
ment of noise-control technology that is already available, and the day when
quiet is restored appears closer.
141
IEEE
Std 640-1985 IEEE GUIDE FOR
142
IEEE
POWERSTATION NOISE CONTROL Std 640-1985
lowing set of values: 20, 25, 31.5, 40, 50, 63, 80, 100, 125, 160, 200, 250, 315, 400,
500, 630, 800, 1000, 1250, 1600, 2000, 2500, 3150, 4000, 5000, 6300, 8000, 10000,
12500.
(n) Prominent discrete tone: Sound, having a one-third octave-band sound-
pressure level which, when measured in a one-third octave band at the pre-
ferred frequencies, exceeds the arithmetic average of the sound-pressure levels
of the two adjacent one-third octave bands on either side of such one-third
octave band by:
(1) 5 dB for such one-third octave band with a center frequency from
500 Hz to 10 000 Hz, inclusive. Provided: such one-third octave-band sound-pres-
sure level exceeds the sound-pressure level of each adjacent one-third octave
band, or;
(2) 8 dB for such one-third octave band with a center frequency from 160
Hz to 400 Hz, inclusive. Provided: such one-third octave-band sound-pressure
level exceeds the sound-pressure level of each adjacent one-third octave band,
or;
(3) 15 dB for such one-third octave band with a center frequency from
25 Hz to 125 Hz, inclusive. Provided: such one-third octave-band sound-pressure
level exceeds the sound-pressure level of each adjacent one-third octave band.
(0)Property-line-noise-source: Any equipment or facility, or combination
thereof, which operates within any land used as specified by Rule 201 of this
Chapter. Such equipment or facility, or combination thereof, must be capable of
emitting sound beyond the property line of the land on which operated.
(p) SLUCM: The Standard Land Use Coding Manual (1969, United States
Government Printing Office) which designates land activities by means of
numerical codes.
(q) Sound: An oscillation in pressure in air.
(r) Sound level: In decibels, a weighted sound-pressure level, determined
by the use of metering characteristics and frequency weightings specifled in
ANSI S1.4-1983, Specification for Sound-Level Meters.
(s) Sound-pressure level: In decibels, 20 times the logarithm to the base 10
of the ratio of the magnitude of a particular sound pressure to the standard
reference pressure. The standard reference pressure is 20 micronewtons per
square meter.
(t) Unregulated safety relief valve: A safety relief valve used and designed
to be actuated by high pressure in the pipe or vessel to which it is connected
and which is used and designed to prevent explosion or other hazardous reac-
tion from pressure buildup, rather than being used and designed as a process
pressure blowdown.
143
IEEE
Std 640-1985 IEEE GUIDE FOR
144
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
inclusive, 7223 and 7311 used for automobile and motorcycle racing and 811
through 890 inclusive.
(d) A parcel or tract of land used as specified by SLUCM Code 81, 83, 91
or 922, when adjacent to Class B or C land may be classified similarly by action
of a municipal government having zoning jurisdiction over such land. Notwith-
standing any subsequent changes in actual land use, land so classified shall
retain such B or C classification until the municipal government removes the
classification adopted by it.
Rule 202: Sound Emitted to Class A Land During Daytime Hours. Except
as elsewhere in this Part 2 provided, no person shall cause or allow the emis-
sion of sound during daytime hours from any property-line-noise-source located
on any Class A, B or C land to any receiving Class A land which exceeds any
allowable octave band sound pressure level specified in Table 1, when measured
at any point within such receiving Class A land, provided, however, that no
measurement of sound pressure levels shall be made less than 25 feet from
such property-line-noise-source.
Table 1
Octave Band Allowable Octave Band Sound Pressure Levels (dB) of Sound
Center Frequency Emitted to any Receiving Class A Land from
(Hertz) Class C Land Class B Land Class A Land
31.5 75 72 72
63 74 71 71
125 69 65 65
250 64 57 57
500 58 51 51
1000 52 45 45
2000 47 39 39
4000 43 34 34
8000 40 32 32
Rule 203: Sound Emitted to Class A Land During Nighttime Hours. Except
as elsewhere in this Part 2 provided, no person shall cause or allow the emission
of sound during nighttime hours from any property-line-noise-source located on
any Class A, B or C land to any receiving Class A land which exceeds any allow-
able octave band sound pressure level specified in Table 2, when measured at any
point within such receiving Class A land, provided however, that no measurement
of sound pressure levels shall be made less than 25 feet from such property-line-
noise-source.
145
IEEE
Std 640-1985 IEEE GUIDE FOR
Table 2
Allowable Octave Band Sound Pressure Levels (dB) of Sound
Octave Band
Emitted to any Receiving Class A Land from
Center Frequency
(Hertz) Class C Land Class B Land Class A Land
31.5 69 63 63
63 67 61 61
125 62 55 55
250 54 47 47
500 47 40 40
1000 41 35 35
2000 36 30 30
4000 32 25 25
8000 32 25 25
Rule 204: Sound Emitted to Class B Land. Except as elsewhere in this Part
2 provided, no person shall cause or allow the emission of sound from any
property-line-noise-source located on any Class A, B or C land to any receiving
Class B land which exceeds any allowable octave band sound pressure level
specified in Table 3, when measured at any point within such receiving Class B
land, provided, however, that no measurement of sound pressure levels shall be
made less than 25 feet from such property-line-noise-source.
Table 3
Allowable Octave Band Sound Pressure Levels (dB) of Sound
Octave Band
Emitted to any Receiving Class B Land from
Center Freauencv
(Hertzj Class C Land Class B Land Class A Land
31.5 80 79 72
63 79 78 71
125 74 72 65
250 69 64 57
500 63 58 51
1000 57 52 45
2000 52 46 39
4000 48 41 34
8000 45 39 32
Rule 205: Sound Emitted to Class C Land. Except as elsewhere in this Part
2 provided, no person shall cause or allow the emission of sound from any
property-line-noise-source located on any Class A, B, or C land to any receiving
Class C land which exceeds any allowable octave band sound pressure level
specified in Table 4, when measured at any point within such receiving Class C
land, provided however, that no measurement of sound pressure levels shall be
made less than 25 feet from such property-line-noise-source.
146
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
Rule 206: Impulsive Sound. No person shall cause or allow the emission of
impulsive sound from any property-line-noise-source located on any Class A, B,
or C land to any receiving Class A, B or C land which exceeds the allowable
dB(A) sound level specified in Table 5, when measured at any point within such
receiving Class A, B, or C land, provided however, that no measurement of
sound levels shall be made less than 25 feet from the property-line-noise-source.
Table 5
Allowable db(A) Sound Levels of Impulsive Sound Emitted to
Classification of
Designated Classes of Receiving Land
Land on Which Property-Line-
NoiseSource is Located Class C Land Class B Land Class A Land
Daytime Nighttime
Class A Land 57 50 50 45
Class B Land 57 57 50 45
Class C Land 65 61 56 46
147
IEEE
Std 640-1985 IEEE GUIDE FOR
148
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
ducted between 8:OO am and 5:OO pm local time, at specified hours previously
announced to the local public.
(g) Every owner or operator of Class C land now and hereafter used as
specified by SLUCM Code 4112 shall have three years from the effective date of
this Chapter to bring the sound from railroad car coupling in compliance with
Rule 206.
(h) Every owner or operator of Class C land on which forging operations
are now conducted shall have three years from the effective date of this Chap-
ter to bring sound from the impact of forging hammers into full compliance
with the limits specified in Rule 206 for emissions to any receiving land.
(i) Every owner or operator of Class C land now and hereafter used as
specified by SLUCM Code 291 shall comply with the standards and limitations
of Part 2 of this Chapter on and after two years from the effective date of this
Chapter.
0) Every owner or operator of Class C land now and hereafter used as
specified by SLUCM Code 7223 and 7311 when used for automobile and motor-
cycle racing shall comply with the standards and limitations of Part 2 of this
Chapter on and after two years from the effective date of this Chapter.
149
IEEE
Std 640-1985 IEEE GUIDE FOR
(8) The term noise sampling location means the general area containing the
specific sampling points at which measurements are taken.
(b) The information on present environmental sound required by subdivi-
sions (a) and (b) of section 75.2 shall:
(1) Include data collected during noise sampling time periods within 18
months prior to the date on which the application is filed;
(2) Be based upon generally accepted measuring and recording techniques;
(3) Contain a statement of the bases for determining the number and loca-
tion of noise sampling points adequate to determine that the measurements
taken are representative of the site and area of noise impact;
(4) Contain a statement of the bases for determining the number of observa-
tions made at each sampling location adequate to determine that the data is
statistically reliable;
(5) Be based upon data collected in weather conditions which do not create
a bias in the data, such as winds, rain, sleet, hail, falling snow, or thunder;
(6) Be based upon field measurements made during normal ambient condi-
tions when significant temporary changes in sound patterns have not occurred,
such as transportation strikes and closed streets, except that this restriction
shall not apply if there is a generally acceptable method for adjusting data to
reflect any temporary change in sound patterns; and
(7) Unless circumstances indicate or require that measurements should be
made at a greater height or closer to a vertical reflecting surface, be based upon
measurements taken four to five feet above the ground and at least 12 feet from
a vertical sound reflecting surface.
(c) In providing the information on present environmental sound levels
required by subdivision (b) of section 75.2, the applicant shall indicate:
(1) The time, location and date of measurement;
(2) Appropriate meteorological data, including air temperature, relative
humidity, and wind speed and direction; and
(3) The name and pertinent training and experience of the persons respon-
sible for the measurement.
(d) (1) For each instrument and microphone combination used to measure
sound level or frequency, the applicant shall state the:
(i) Name;
(ii) Make;
(iii) Type; and
(iv) Method and date of calibration.
(2) Only measurements from sound measuring equipment that meets the
Type 1 specifications of the American National Standards Institute (S1.4-1971)
may be used to satisfy the requirements of this Part.
150
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
(b) For the noise sampling area for each noise sampling time period at each
location, the applicant shall submit, in tabular form and, with the exception of
the information required by paragraph (3), graphic form, a summary of the
results of observations showing:
(1) The frequency occurrence distribution, with a class interval or cell size of
five decibels or less;
( 2 ) A cumulative percentage curve;
(3) The peak sound measured in decibels on the A weighted scale, slow
response; and
(4) The frequency, duration, and octave band pressure level of any pure tone.
(c) The applicant shall submit an overlay or overlays showing each noise
sampling location and each noise sensitive land use within the noise sampling
area.
151
IEEE
Std 640-1985 IEEE GUIDE FOR
Table L-1
Noise Sampling Periods
Season Day Time
Winter Monday through Friday Daytime
Winter Monday through Friday Evening
Winter Monday through Friday Nighttime
Winter Saturday or Sunday Daytime
Winter Saturday or Sunday Evening
Winter Saturday or Sunday Nighttime
Summer Monday through Friday I Daytime
Summer Monday through Friday I Evening
Summer Monday through Friday I Nighttime
Summer Saturday or Sunday Daytime
Summer Saturday or Sunday Evening
Summer Saturdav or Sundav Nighttime
The requirement is for any of the five weekdays
152
-
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
111 43 12 26 42 22
93 17 6 5 55
M 4? U1 508 442 509
1970
Jurisdiction Powlation
I7 412
8?.3ai
10 487
e? 973
28.691
Lorn l a 19.783
long 8zac11 358 633
tns Altos H , I b 6.853
Lcr ingeler 2.816.05i
Los Banor 9.188
Lywood 43.353
IN?ONA Yarlcca 13.845
llajrlah
Phoenn. .
26.177
581.55?
0
c
-- J
c
-
K
-- -- -- -- Uen'o Pail
Yonwe,
26 826
26 302
Tempt
Tucsm
..
.
.
_.
.. .
...
62.s37
262.93;
P
0
0
E
m - - L - -
- - - - - -
Nerark
N r r ~ o i lBeach
27,153
49 422
hcrito 31.0%
ARKANSS 361,561
Litfir Rock
rlhr 81.11
..... 132,125
57.389
E
2 -
-- -- -- -- -- -- 77.365
36 02J
55.SSF.
'lliDi!4!A 112.951
&antra 62.125 24.610
16C.7M 16.6~5
43.Ti7 7.676
166 716 Pmr-rnind 79 043
33,416 ROSS 2.742
63 M6 Sarramcnto 254 413
ba.871 Salinas 56.633
19,580 San baclrno 13.031
72,fbU San Grmaidmo 104.251
2.oai San C m t n l c 17.063
18.216 Szn Dicpo 696.769
88.462 San irancsco 715 614
52.273 Sam MIIWS 3.8%
15 620 San lorc 445,779
1.834 Sin kanCro 66 698
31.826 San Matro 18 -1
165.172 San Rclac: 38.92
100.859 Sanla Barba a 7C.?15
Cirdwa 41,021 Sanata Clara 67.717
Grorm Crwz 121.371 slnla IC Svrinks I4 7%
CknEal* 132.752 M a Yana 32 i 4 9
Glendora 31,349 Santa 8oa 1 3 8a.289
Ya,irrL 93.058 Santa Rosa 50.0%
Hm4 12.252 Saurrltto 6.158
153
IEEE
Std 640-1985 IEEE GUIDE FOR
:: 2 a s
E
2 .EP E E
.
1970 f 1970 $ f
I'opuiation Z'WP I 8 P
.--
Jurisdiction Jurisdiction PoDulation
-
S m Yadey ..... 59 83L U - - MI& 3;619 c - -
- -
..
South tl hkmle. 13 442 U - - 72586
South Gale . . . .
Sunspalr . . . . . .
..
56.939
45 a3 E n - - -
TJIIU-'
I m p .~. . . . . . . . . . . . .
.m................
298.740 E -
<- --
--
hac, . . . . . .
Iwiancc . . . . . . . .
14.724
134 5&
-
m a n
0 - -
c -
E of8JSurtbkld . . . . . . . .
v m e . .~. . . ~. . . . . .
3.613
'6.878
14.211 E
-
Victomille . . 10.u5 U - - Vulmia Cndens . . . . . . . 2.592 2 - --
c -
COLOiiPOO
Amadz . . . . . . . . . . . . . 49.083
west urmi . . . . . . . . .
I& PJhn L a c h . . . . .
Wmtu Hawen . . .
5.989
27.132
16.136 o
0 - o
Aspen . . . . . 2,404
Aurora. . . . . . . . . 74 974 ctmu
Bould?r . . . . . . . . . 66.870 Alma ................. 3.156
Colorado Springs . . 135 NO UlJntl . . . . . . . . . . . . . . 697.421
Denver ......... 514.618 Clmllh . . . . . . . . . . 4.987
Orllon r....... I82 Cmolton . . . . . . . . . . 13 520
tnglewood . . . . . . . . . . . 33 695 Cbrton ................ 2.669
Fort Collins ....... 43.337 Colkge P J h ............ 18.203
LakewcDd .... 92.i81 tolumbus .............. 154. I68
Littlclon .............. 16.466
- Riape . . .
y..heat 3.795
krdele . . . . . . . . . . . .
DJC& . . . . . . . . . . . . . .
10.733
782
COI!NCCTlCUT Oanielsrille . . . . . . . 310
Errlin . . . . . . . . 16149 U
a n
--
- -- -- m-- m--
- Decatur . . . . . . . . . .
D m ............
21.943
220
Bridgeport . . . . 156,542 E
- -- --- --
farnqton . 14390 0 P 0 FlOnIY %Jnch. ........ 161
tlarllord . . . I58017
- -- -- 2- fwesl Park, . . . . . . . . . .
6nIlin . . . . . . . . .
19.994
22.134
Ne* daven . . . . 137.707 0 0
Slontng!on . . . . issgn I I I I I Hawilk . . . . . . . . . . . . 9,567
westpart . . . 27 414 Kinasland . . . . . . . . . . . 1.631
..........
Lake CiIy 2.306
.
OCUXPRE .........
Loultvllls 2.691
Wilnim&an 80386 U E 0 - - - - - Macon . . . . . . .
. . . . . . . .
HogntIt
122.423
16.4GO
DlSTFlCI 01 COLUYBll Nnnan . . . . . 11.205
0 t r t : ~ lof Columb,a 756.510 Cl 0 - - - - - Peazhtret . ,
City ,
RlncOn . . . . . . . .
753
1.854
1tERIOA Rimdale ...... 2.521
Anna Maria . 1,404 Savannah ........ 118.345
Allantis 844 ipnc .......... 136
Bal Harta Village 2.104 Warnu Robins .. ,.., 33.491
E J marbcr
~ 4,723 Wapeslmro 5.530
Ba) Lale 18
BKK~Raton 28 506 IIIWLII
Cape Cana.eral 5.131 ll0ffilUl" ......... 324.811 0 I - - - - -
.
C.eawz'rr 52.074
mulo
- - - - -
Cocca Beach I I 555
Car11 Cables
Dama
. 42.494
9 819
Boise . . . . . . . . .
Idaho Fills ......
14.9W
35.776
D
-
C
--
1
-- -- -- -- --
DayIona Beach ~7.6a2 sOCIttlb . . . . .. . 40,035 0
Decrlield k a c h 19 577
Deland . . . . . . . .
~ ~ 11.641
&IIJVBeach , , 19.915
CdWJ!Cr .... 3.3a
-
iM LsuCefdak
1 Ulers . . .
139.590
32.563
......
57239 - -- 8 E -
0 - - - - -
-
8 - - - - -
31.152 80.318 0
uJlrUlWlk
HJ!lJndJh
..........
.........
64,510
32,292
4,235
u.237 --
L
-- m- -- -- -- -- a-
Hialeah . . . . . . . . . . . . . . 102.452 27.291
- 6 - - 8 - -
-- 00 - -- -- 0- --
nlJl?tb C J l h S . . . 1.076 12.G6 0
n3llpxd . . . . . . . . 106.873 126.963 0
t&WSltJd . . . . . . . . 19 022 141.370 C
. . . . . .
l n a m ihofes 691 4942 0 - U - - - - -
hCbJsWl!k . . . . . 528.865 32.800 O P P Q - - I I -
LJke Bucna YlSIJ . . . . . 22
. -- - -
45 091 IXD11YA
---
Ldd~td
Lahe PJlk . . . . . . 7.921 lvmsnlk . . . . 138.i64 o n R U
. . -
Late Worlh . . . . . . .
LaudCrdak b~ l h r .
25.934
2.441 %mn6 '. . .
175.:15 D
1 0 7 . ~ 8 ~c
U
o
0
e m -- o- --
-- --
&J
LqhthJrsr Pam1 ..... I 1 160 In<ianapolis . . . 145.73
- - - - - 0
-
- - 0
UadurJ . . . . . . . . . . . . . . 4.169 Cqatr Ouner 982
Margate . . . . . . . . . . . . . 11,153 b d h Bcnd . . . . . . . . . 125.580 0 - 0 - -
Yelbvufn 40.236
MlMl . . . . . . . . . . . . . . IOWA
R -
--- --- o0 --
334.859
M.ml kach .......... t9.141 M a r falls.. . . 29.597 0 0 D
Ymmi S h o r t s . . . . . . . . 9.541 b n c n l Blulls . . . . . 60.3:8 D -- C i7
c - --
MtrJmJr . . . . . . . . . . . . .
13.384
21.132
0a.c:wt
DesMoines
........
. . .
91.459
2M.587
D
0 - E -
m -
-- -- 0- --
kW7h hJdCIdJk ....... 5.648 Dvbuque . . . . . . . . . . .
hllr . . . . . . . . . . . . . . . .
62.309
- -
0 0
m -
--- --- --- ---
h f l h Miami ............ 42.970 6.668
S ~ m C i l [ : . . . _ . .. . . . D -
D -
M h PJlm bJCh . , , . , . . 12.056 82.925 0 0
Oakland Park ...........
Oldmar ..............
19.lM)
2.090
Stmbe . . . . . . .
WJtCflOO . . . . . . . . . . . . .
8.591
15.533
0
0
B
- - - - - -
............. 12.924
...............
~~
OrMO 97.565
h l l J I I M . ........... 29.512
Plan1 C i r . ............. 15.781
h l l d J S Nk ........... 28.525
.
hk LXh bfdmt . . 8.315
h a D J m Buch ......... 3e.544 IfKWCKV
Cmengton . . . . . . . . . . . . - 0 0 - -- 0- --
- -- 0- - --
R n W J LaCb ........... 21.401 52.535 0
..........
Redinm ylorcr.. ......
..........
SL h N l l M l [
SJfJSOtI ..............
2.111
216.232
44.631
Lbi*gton
b ~ ~ ~ v . ~. l. l . e. . . . .
108,131
361.412
U
W -
M h0
- ......... 1.1125 LOUISIANA
t J t m Rouge.. .........
IlnOdem~ . .~. . . . . . . . .
165,963
593.471
0 - 0
0 G - - -
- 0 -- - --0
154
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
1970 1970
Jurisdiction mpulation Jurisdiction
___. --
YAWUNO
Baltimore 905 759
Cumb-rland 29 724
RKkVllk 41 54.4
tklLIus1n . . . . . . . .
YASUCllUSfTlS ~aCkinlJch . . .
Acton ............ 15.770 -mmonton . . . . .
Bustun . . . . . . . . Y1.070 wcr
COcCQtd . . . . . . 16.148
Fall " C l ... 96.898
Milford . . . . . . . . . 19.352
Mcwlon . . . . . . . . . . 91.163 O -
Ptllsf~eld . . . . . . 57.C20 - E
......
Springfield
6orceslcI . . . . . .
163.905
176.512
- I
- -
q 0 -
0 - 0 -
Ann Arbor 99 197 O D c -
Augusta lownshtv 1016 c - YJrta:e . . . . . . . . . . 3 -
Bewrl" YdIS 13.598 0 - Maynod.. . . . . . . . . . . c -
Bmtn'gham 26,170 0 - Morrlsto*n . . . . . . . C -
Cornslock 5.003 m - Naa? C -
Dearbarn lo4 199 0 - Newlin c -
1.512 893 0 -
(klroll
Farmm Ion
Grand gapids
10.329
197,649
0
0
-
0
l a t h ha'eoon
htrth WildiJDo - -
r , -
Wltlq . . . . . . 2 -
KalamazGo a5 555
23 817
0 0
B P
Ocean C n y . . . . . c -
Mcr#dmTo*nshv Orange G i l l . . . . .
Millord 0 699 -
n
I
i
Parsaic . . . . . . . . . . . . :I
Ponljac . . . . . . . 85.279 c -
Ravenna .......... 51 0 - 0 -
Sacinan . . . . 91 a43 E O
1rq . . . . . . . . . 39 419 0
u n
- :I
warre,, . . . . . . . . 179.260 C .
Vmtland . . . . . 86.749 K m m n
vlpn.,ng . . . . . . 5L 560 0 - C .
MlMllLSOli
B omin 81 970
c- -
tun
Cannon falls 2 155
u -
I D
Colvnibia Heqhls 23 837 m -
MlnncaFnlls
RQcheSle;
434.m
53 156
Svmwt
ltcnlari . . . . . -
n -
SI Paul 309.828 Vinelare . . . .
a
-
rl -
-
MISS1SSIPPI
Whn? c -
C -
Iachwn 153.~ m m
- m
MISSOURI
BridEeton 19.992 e :
Clldslsne 23.422
WmGaiidgt m -
Crandrlcr 17.456 YiIICO
lndewndenct 111,662
507.330
.i?"rfq"c . . c 2
trlltp II-
622.236 Lor !!.amor ..... i. -8
Irn.096
3.376
- 3
nut - m
nu 61 581 c -
b,eal falls 60 W1 u -
Helena 22 730 u -
w~saau!a 25 497 3 -
0 0
Ifll:su 3 -
Bra: sic I 2 187
Lmoh
McCnok
Id* 518
8 f85
us --
z n m
-
m
Omana 3Jb 929
Scuttshlu~l 14 507 -
- I
Sidnrr 6 258 U
r
-
- -
ULVLOA
u -
bs Vejar 125 787 0 - C
0 -
NEW "i*PSP'PE
Mancb*slrI 87 754 1,592 c l -
57.681 c -
.
MEW JERSLI 620 E -
P91KS6 . . . . . . . . 6 094 2 4.814 c -
Arbuq Pirk
8 nne
..... 16.533
12 703
- 2.167 c. -
c -
: h e
Y
8.754
BX"ll*. . , . .. 34.613 m Burlington 35.930 0 -
&rkeky Heighlr .... 13 078 Carolina Beach 1.663 n -
Bliljmbeld ...... 52,059 U Cnrbafo 3.412 0 -
konlon ......... 9.261 m C~UWIntii 25.537 D -
. . . .
Badentorn
& anlm . . . . . . .
4.490
6.741
0
0 - Concord
COWK
18,464
160
0
0
-
-
ditnmn . . . . . . . . . 11.991 0 Durham 95.438 0 -
CJlndcn . . . . . . . . . . . .
cape Y* . . . . . . . .
102.551
4.392
0
C - hytlltlmlk
Fwerl City
53.510
7.179
0
0
-
-
Cl,IlO" ........... 82.437 8 Franklin 2.336 0 -
Clmlon ..... 1.742 C luauar Varina 3.576 0 -
corbln ............. 2s a GJsJia ....... 47,I43 0 -
Dcm ............ 15.039 0 Gibsonvtlle , . . , 2.OIE 0 -
155
IEEE
Std 640-1985 IEEE GUIDE FOR
1970
Jurisdiction Jurirdlction Population
coldstoru
GreLnsbcrr. . . . .
26.8l(r
144076
0
i:
-- -
0
-- -- -- -- -- UMI C I l O U I I A
ColvmDia ............. 113.WZ
-- -- -- --
nicko 20569 U - - - - - - -
High?wni I..::'. : 63.204 U -- -- ---
ilorenii . . . . . . . . . . 25.937
Kingr Mountain 8(05
-- -- - - - - HLlll DAKOTA
--- --- --- --- --
Kinslon . . . . . . 72.33 c Lemm.7 . . . . . . . . . . . . . 2.456
*Ire 8cach ... 0
Laurmbu;g . . . . .
3q4
8.859 0
0
-
-
-- --
Sicux Falls ............. 72,486
Lumbcrloo . . . . . . . 16.961
- --- --- --- ---
---
RIXtt*LI
Mad son
Maitro
.....
. . .
2,081
541
2
0
--- -- t h l t l r s w ~ a .... . . . . . . .
Kiny.prt ..............
119.923
31.939
Marian . . . . . . . . . .
- - - -
0
Mom? . . . . . . . . . .
3.335
11.282 0 -
- -- -- -- -- -- Kmxntb ............... 276.293
MI. Pleasant . . . . . . . . . 1.174 U -- -
Nm@m . . . . . . . . . . . . .
llutlnlk ...............
621.530
44.003
...... ....
- - - -
2 0
Ner errn 1466@
- - --
--- --- --- ---
~
--
. . . . .
'
0 kanc . . . . . . . . . . . 117.548
Rocky Mount
..........
y.2Iy
649 0 - - - -
- - - - -- &r:.Ffntl
'. : ::::.:;.: 204.525
-- ---
ROW1 844.401
SalisbJr
seaboarg ..:.
Sllvel Cltj . .
' .
22.515
(11
4,689
2
0
0 - -- -- -- -- -
II
fell mr
..............
fIt0
.............
322.261
393.476
Sou!hem Pines
Staterwllt .
. . . .
. .
5.937
19.996
U
0
-- -- --- --- - -- - --- -
-
.............. 81.137
I1.232.0i
o 97 457
larboro
Thml,r,l,a
....
. . . . . .
9.423
15.230
3.182
0 -m-
--- -- -- -- -- -
--
3c.507
I h lI
--- - - - -
YaICrre 0
---
3,148 0 78.381
-- -- -- --
46.169
Winston-Salem
Winton
..
. .
132.913
917
0
U*-
B
-
E
- nu
Ogdm............... 69,478
hrp ................. 9.131
ROZlM DAKOTA
Bisnlark ..... 34,703 2 - - - - - - - b m n ........
&H bM City . . . . . . . . .
2.005
175,865
OHl9
A h " 215.525 0 110.927 - 0 -
9,902 C 174.284 . E -
152.5?4 0 89.580 0 - -
m
.--
750 903 0 Hamplan . . . . . . . . . . . . . 125.779 c c 0
YO 075 0 a Yorpolt "5. ........ 1% I 7 1 a
- - -
.
243.bC1 a
12.367
.-.
hdblk . . . . . . . . . . . . . . .
Rctunond . . . . . . . . . . .
307.951
249.621
--
U
0
-
-
-
36.306 d
Vir#inii k a c h ..... 172.106
.
6: 941 0
.
383 818 3 WASMUCM
1).05; U blterve . . 61.102 m - -
Calitls P I x e 4.510 G - 0 -
Meefia . . . . . . 3.455 - 0 -
D
0 - Pd:r,afi
Rti:lind
......
......
X.W
26.2SJ
o
m - -
c -
kaWt -
.
532,531 - I -
0 0
hohawh
Smtrsc
5.114
IlO.S!i
E E C -
c - - - -
I! TacmJ
Wall. Walla
154.581
25.619
= : c -
u -
6
.
- 4a ' -
C
- Irkma 45.w - c -
1W.571
12 686
129.231
2 631
0
U
0
(I
D
--
--
---
--
---
rnCElStN
Mahn .
IIbIwYUkee
RKcm
5 p
. . . . .
........
...............
~ .U. . . . . . . . . . . . .
113.258
711 372
95,162
6.258
E
cl
8
3
.;-
.
0
-
E
.
L,
-
-
-
--
-.-
i.w.o5a ?!Is
uO.ll7 =Pet ............ 39.361 5 - -
102.564
i8.070 - - ;beyeme . . . . . . . . . . .
Lrnk . . . . . . . . . . .
(0.914
7.112
m
3
-
-
a
D
-
-
I& .......... 4.w7
MOM ISUED
Crinrtm ...... m -- -- lmrtan ,. . . . . . . . . . . . .
lrlrd . . . . . . . . . . . .
7.95
s.m5 - - -
b s l RandcMe ...... B
......... m M* ....... a,m,en
!!
-- --
?mUcbet E 0
ho*.J?Kt. . . . . . . . .
WY*Tk . . . . . . . . . . . .
-
NOTE: The current list of municipalities with noise regulations are available at any public library in the
United States. The listing has been reproduced here for the convenience of the users of this guide.
156
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
Motorcycles
Manufacture Date Noise Limit bv dB(A1
Before Jan 1, 1970 92
After Jan 1, 1970 88
After Jan 1, 1973 86
After Jan 1, 1975 84
After Jan 1, 1980 75
157
IEEE
Std 640-1985 IEEE GUIDE FOR
Snowmobiles
Manufacture Date Noise Limit by dB(A)
After Jan 1, 1971 86
After June 1, 1972 82
After June 1, 1974 73
158
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
Noise Responsibility Does Not End with Manufacturer. Under the ordinance
the manufacturer is required to turn out products that will meet prescribed
noise levels. The user of these products is also subject to limitations. He must
see that the product is kept in good working condition so that it will not give
off more noise than the manufacturer intended. He cannot modify or change the
product to make it louder, and in operating the following restrictions must be
met. These restrictions apply to the total noise from a vehicle or any combina-
tion of vehicles. Noise limits will be measured at a distance of 50 feet from the
following vehicles.
Restrictions by Speed for Operation of Motor Vehicles with Manufacturers
Gross Volume Weight of 8000 lb or more, and Any Combination of Vehicles
Towed by Same
Motorcycles
Noise Limit bv dB:A>
For Posted SDeed Limits
Date 35 mi/h or Less Over 35 mi/h
Before Jan 1, 1978 82 86
After Jan 1, 1978 78 82
Any other Motor Vehicle and Any Combination of Vehicles Towed by Same
Noise Limit bv dB(AI
For Posted Speed Limits
Date 35 milh or Less Over 35 mi/h
After Jan 1, 1970 76 82
After Jan 1, 1978 70 79
159
IEEE
Std 640-1985 IEEE GUIDE FOR
160
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
A4. References
[Bl] ANSI S1.4-1983, American National Standard Specification for Sound-Level
Meters.'2
[B2] ANSI S3.1-1977, American National Standard Criteria for Permissible
Ambient Noise During Audiometric Testing.
[B3] ANSI S3.6-1969 (R 1973), American National Standard Specifications for
Audiometers.
[B41 ANSI S2.45-1983/ASA 51, American National Standard Electrodynamic Test
Equipment for Generating Vibration - Methods for Describing Equipment Char-
acteristic~.~~
[B5] IS0 R389-1964, Standard Reference Zero for the Calibration of Pure-Tone
audiometer^.'^
[B61 29 CFR 1910.95 OSHA, Occupational Noise Standards.'j
[B7] 29 CFR Bulletin 334, Guidelines to the Department of Labor's Occupational
Noise Standards.
[B8] Webster's New Collegiate Dictionary. Springfield, MA: G. and C. Merriam
Company.
ANSI publications are available from the Sales Department, American National Standards
Institute, 1430 Broadway, New York, NY 10018.
This publication is available from the Sales Department, American National Standards Institute,
1430 Broadway, New York, NY 10018. Copies are also available from the Acoustical Society of Amer-
ica, 335 East 45th Street, New York, NY 10017.
l4 IS0 publications are available from the Sales Department, American National Standards
Institute, 1430 Broadway, New York, NY 10018.
l5 OSHA publications are available from Occupational Safety and Health Administration, US
Department of Labor, Washington, DC 20210 or from the nearest regional or area office of the
United States Department of Labor.
161
IEEE
Std 640-1985 IEEE GUIDE FOR
Appendix B
ABMA Procedure for the Measurement of Sound from Packaged Boiler Units.
The purpose of this procedure is to provide a standard test for the measure-
ment of airborne sound from packaged steam or hot water generators (boilers),
using water or other fluids, and from liquid phase heaters.
AGMA 297.0233, Sound for Enclosed Helical, Herringbone, and Spiral Bevel
Gear Drives. The purpose of this standard is to present the instrumentation and
procedure to be used for sound measurements of enclosed helical, herringbone,
and spiral bevel gear drives and to present typical maximum A-Weighted sound
levels. This standard includes the instrumentation and procedure necessary for
the determination of the gear unit sound level or octave-band sound-pressure
levels.
AGMA 298.01-1975, Sound for Gearmotors and In-Line Reducers and Increasers.
The purpose of this standard is to present the instrumentation and procedure to
be used for sound measurements of gearmotors and in-line reducers and
increasers and to present typical maximum A-weighted sound levels.
AMCA STANDARD 300-1967, Test Code for Sound Rating.I8 This code estab-
lishes a practical method of determining the sound-power level of an air-moving
l6ABMA publications are available from American Boiler Manufacturers Association, 950 N. Glebe
Rd, Suite 160, Arlington, VA 22203.
"AGMA publications are available from American Gear Manufacturers Association, 1901 North FY
Myer Drive, Suite 1000, Arlington, VA 22209.
'*AMCA publications are available from Air Movement and Control Association, 30 W. University
Dr, Arlington Heights, IL 60004.
162
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
device (AMD). The test set-ups are designed t o represent general usage of the
AMDs tested.
ANSI S1.2-1962 (R1976), American National Standard Method for the Physical
Measurement of Sound (Partially Revised-see S1.13-1971 and S1.21-1972). This
standard applies primarily to airborne sound produced by apparatus which nor-
mally operates in air. These sounds shall be nonimpulsive and of sufficient dura-
tion to be within the dynamic measuring capabilities of the instruments used.
ANSI S1.4-1983 (ASA 4783), Specification for Sound-Level Meters. This standard
provides the minimum requirements for three basic types of sound-level meters:
Types 1, 2, and 3 with performance requirements that become progressively less
stringent, proceeding from Types 1 to 3. Provision is made for a special purpose
sound-level meter-type S.
ANSI publications are available from the Sales Department, American National Standards
Institute, 1430 Broadway, New York, NY 10018.
163
IEEE
Std 640-1985 IEEE GUIDE FOR
ANSI S1.6-1984 (ASA 53-84), Preferred Frequencies, Frequency Levels, and Band
Numbers for Acoustical Measurements (Agrees with IS0 266-1975).
ANSI S1.10-1966 (R1976), American National Standard Methods for the Calibra-
tion of Microphones (see also IEC 327-1971). In this standard, methods are
described for performing absolute and comparison calibrations of laboratory
standard microphones.
ANSI S1.13-1971 (R1976), American National Standard Methods for the Measure-
ment of Sound-Pressure Levels. (Partial revision of S1.2-1962). The purpose of
this standard is to provide uniform guidelines for measuring and reporting
sound-pressure levels observed under different environmental conditions. This
standard is intended to assist in the preparation of test codes for
(1) Determining compliance with a specification, ordinance, or acoustical
criterion
(2) Obtaining information to assess the effects of noise on people or
equipment.
ANSI S5.1-1971, Test Code for the Measurement of Sound from Pneumatic
Equipment (see CAGI Test Code 1969).
ANSI S6.1-1973, Qualifying a Sound Data Acquisition System (see SAE 5184-1978).
164
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
ASHRAE 36-72, Methods of Testing for Sound Rating Heating, Refrigerating, and
Air-conditioning Equipment." This standard establishes a method of testing
heating, refrigerating, and air-conditioning equipment to determine the sound-
power levels in frequency bands.
ASTM C423-84, Standard Test Method for Sound Absorption and Sound Absorp
tion Coefficients by Reverberation Method.23This method covers the measure-
ment of the sound absorption of acoustical materials in a diffuse sound field.
When a material is in the form of an extended plane surface, such as an acous-
tical ceiling or wall treatment, the results shall be given as sound absorption
coefficients.
2o ARI publications are available from Air Conditioning and Refrigeration Institute, 1501 Wilson
165
IEEE
Std 640-1985 IEEE GUIDE FOR
ASTM E477-84, Standard Method of Testing Duct Liner Materials and Prefabri-
cated Silencers for Acoustical and Airflow Performance. This method covers the
laboratory testing of duct liner materials, integral ducts, and in-duct absorptive
silencers used in the ventilation systems of buildings.
CAGI TEST CODE (1969), CAGI-PNEUROP Test Code for the Measurement of
Sound from Pneumatic Equipment.24 (see ANSI S5.1-1979). The purpose of the
code is to provide standard test procedures for the measurement of airborne
sound from pneumatic equipment. This code applies to compressors and pneu-
matic equipment and specified procedures and operating conditions acceptable
and expedient for use by nonspecialists and by acoustical engineers.
DEMA TEST CODE (1972), for the Measurement of Sound from Heavy-Duty
Reciprocating Enginesz5 The purpose of this document is to establish a stand-
ard procedure for measuring, recording, and reporting data in acoustic surveys
at engine installations. This code applies to heavy-duty internal combustion
engines and driven equipment, such as generators, pumps, or compressors, and
specifies procedures and operating conditions acceptable and expedient for use
by nonspecialists and by acoustic engineers.
IEC 34-9 (1972), Rotating Electrical Machines, Part 9 Noise Limitsz6 A-weighted
sound levels have been adopted for this standard. When the machine being
tested emits one or more pure tones of significant intensity, the A-weighted
level is not sufficient and the recommendation provides for the use of fre-
quency band analysis in such cases. This recommendation covers rotating elec-
trical machines in the following power and speed ranges: 1 kW-400 kW and
600 r/min -3750 r/min.
24CAGI publications are available from Compressed Air and Gas Institute, 1230 Keith Blvd,
Cleveland, OH 44115.
29 DEMA publications are available from Diesel Engine Manufacturers Association, 14600 Detroit
Avenue, Suite 712, Cleveland, OH 44107.
26 IEC publications (International Electrotechnical Commission) are available from the Sales
Department, American National Standards Institute, 1430 Broadway, New York, NY 10018.
166
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
required. This recommendation does not apply to apparatus for measuring dis-
continuous sounds or sounds of very short duration.
IEC 179A (1973), First Supplement to Publication 179 (1973) Precision Sound
Level Meters, Additional Characteristics for the Measurement of Impulsive
Sounds. This recommmendation specifies the characteristics of an apparatus for
measuring sounds of short duration, single impulses, and sequences of impulses
(pulses).
IEC 225 (1966), Octave, Half-Octave and Third-Octave Band Filters Intended for
the Analysis of Sounds and Vibrations. See ANSI S1.ll-1966 (R1976).
IEC 327 (1971), Precision Method for the Pressure Calibration of One Inch
Standard Condenser Microphones by the Reciprocity Technique. See ANSI
S1.10-1966 (R1976).
IEC 402 (1972), Simplified Methods for Pressure Calibration of One-Inch Con-
denser Microphones by the Reciprocity Technique. The object of this recom-
mendation is to specify a method of absolute pressure calibration of one-inch
condenser microphones used in laboratories for conventional measuring pur-
poses, without requiring the highest obtainable accuracy.
IEC 486 (1974), Precision Method for Free-Field Calibration of One Inch Stand-
ard Condenser Microphones by the Reciprocity Technique. The object of this
recommendation is to specify methods of measuring certain characteristics of
standard condenser microphones with high accuracy, so that discussions
between testing authorities may be based on clearly expressed and reproducible
results.
IEEE Std 85-1973, IEEE Test Procedure for Airborne Sound Measurements on
Rotating Electric Ma~hinery.'~ This test procedure defines approved methods
for conducting tests and reporting results to effect the uniform determination of
rotating electric machine sound under steady-state conditions with an accuracy
of 3 dl3 tested in free field, reverberant field, and semireverberant field acous-
tical environments. This procedure assumes the presence of pure tones or the
predominance of discrete frequencies in the sound spectrum.
271EEE publications are available from IEEE Service Center, 445 Hoes Lane, Piscataway, NJ
08854.
28 IS0 publications are available from the Sales Department, American National Standards
167
IEEE
Std 640-1985 IEEE GUIDE FOR
IS0 R1680-1970, Test Code for the Measurement of the Airborne Noise Emitted
by Rotating Electrical Machinery. This recommendation was drafted in accord-
ance with IS0 R495-1966, and gives the detailed instructions for conducting and
reporting tests on rotating electrical machines, to determine the airborne noise
characteristics under steady-state conditions. This test code for the measure-
ment of noise applies to rotating electrical machines such as motors and gener-
ators of all sizes without limitation of output or voltage, when fitted with their
normal auxiliaries.
NEMA MGl-78 (Rev 8, Nov 84, Motors and Generators, Methods of Measuring
Machine Noise.29 (See IEEE Std 85-1973).
NEMA MG3-1974 (R1979), Sound Level Prediction for Installed Rotating Elec-
trical Machines. This document provides a method of predicting approximate
sound-pressure levels in industrial and commercial areas. The method is
2y NEMA publications are available from the National Electrical Manufacturers Association, 2101 L
168
IEEE
POWER-STATION NOISE CONTROL Std 640-1985
NEMA TR1-80 (Rev 2, Apr 1983), Transformers, Regulators, and Reactors (Sec-
tion 9-04 Audible Sound-Level Tests). This standard lists test conditions and
measurement procedures for determining the audible sound level associated
with transformers under field conditions.
SAE ARP 866A (1975), SAE Aerospace Recommended Practice, Standard Values
of Absorption as a Function of Temperature and Humidity for Use in Evaluating
Aircraft Flyover Noise.31 This document describes a method by which values
can be obtained for the absorption of sound in air over a wide range of temper-
ature and humidity conditions. The purpose here is to consider only the classi-
cal and molecular absorption of sound energy by the atmosphere.
SAE 5184 (1978), SAE Recommended Practice, Qualifying a Sound Data Acquisi-
tion System. See ANSI S6.1-1973. Various SAE vehicle noise standards require
use of a sound-level meter which meets the requirements of International Elec-
trotechnical Commission, IEC 179 (1973), Precision Sound-Level Meters, and
ANSI S1.4-1971 (R1976), American National Standard Sound-Level Meters. The
purpose of this recommended practice is to provide a procedure for determin-
ing if an acoustical data acquisition system has performance equivalent to such
a meter.
NFP(A) publications are available from the National Fluid Power Association, 3333 N. Mayfair
Road, Milwaukee, WI 53222.
"SAE publications are available from the Society of Automotive Engineers, 400 Commonwealth
Drive, Warrendale, PA 15096.
169
IEEE
Std 640-1985
A Analyzers
octave-band, 95, 96
Absorption Anemometers, 97
air, 43; Fig Aspirators, 91
as noise reduction method, 110, 113, Attenuators, 22, 56
115 Audiometry, 137, 138
atmospheric, 43; Fig 1 1 , 44
coefficient, 39, 40, 41
atmospheric, Fig 1 1 , 44
B
definition of, 15 Barrier, 100, 111, 113, 115
of various materials, Table 5 , 40 effects, 44
effective room, 39, 40, 42 Boilers, Table 7 , 64; 91; Table 11, 116
Acoustic Burners, Fig 27, 82; 91
absorption, 39, 40, 41
coefficient of materials used in,
Table 5 , 40; 41
C
of path, 110 Calibrators, 95
of receiver, 110 Case histories, 94; Table 9, 95
of source, 110 Circuit-breakers, Table 7 , 65;
characterization of rooms, 26, 39 Table 1 1 , 117
environment, 51, 52, 55, 56 Compressors, 59, 66, 68, 69; Fig 2 5 , 81;
shadow, 46 Fig 6, 60; 61; Table 7 , 63;
sources, 19, 62, 63, 64, 65 Table 1 1 , 116
treatment, 26
Air
absorption, 43; Fig 1 1 , 44 D
equipment, Table 1 1 , 116
Amplifiers, 22, 56 Damping
gain of, 21 constrained-layer, 112
Analysis Data
octave-band, 27, 59, 95, 97; Fig 31, 98; interpretation, 97, 99, 100, 103, 105,
99; Fig 3 4 , 102 106, 107, 108, 109, 110
A-weighted, 32; Fig 6, 33; reduction, 97, 98, 99
Fig 35, 103 Decibel, 20
center and cutoff frequencies for, combining readings, 29
Table 3 , 28 definition of, 15
combining readings for, 31 Design
converting to A-weighted values, building, 88, 89
Table 4, 31; 131, 132 Devices
of calculating-machine noise, hearing protection, 49, 116, 135, 136
Fig 4 , 29 personal protection, 116, 135, 136
one-third octave-band, 27, 59; Fig 3 1 , 98; Diffuse field, 51
99 Direct field, 32, 34, 51, 53, 54, 100
center and cutoff frequencies for, Directivity, 19, 20
Table 3 , 28 characteristics, 39
narrow-band, 27, 59; Fig S I , 98; 99, factor, 35, 38, 42
105, 106, 107; Fig 4 1 , 108 typical values of, Fig 7 , 35
IEEE
Std 640-1985 INDEX
172
IEEE
INDEX Std 640-1985
I control, 26, 97
administrative, 118, 119, 134, 135
Inhomogeneities cost of, 123, 124
atmospheric, Fig 1.2, 45; 46 design objectives for, 13, 121- 124
Inverse square law, 20 evaluations of measures for, 118
generalized model for, 87, 88, 89
L measures, 88, 133, 134
planning, 13, 87, 121
Labor program, 13, 14, 59, 83, 93, 116
Department of, 47 determination, 14
Lagging, 113, 115 distribution, 54
Legislation, 13, 47, 48, 49 duct, 71
emission, 13
energy, 26, 59
environmental, 13
Machine data interpretation for, 106- 110;
calculating, 29 Fig 40, 107; Fig 41, 108;
Machines, 26 Fig 42, 109
measurement points for, Fig 8, 37, 38 exposure to, 94, 95
calculating, Fig 4, 29 laws and regulations, 47
Magazine measurement of, 49, 52, 54, 55
Sound and Vibration Magazine, 48 noise-control design, 122
Meters noise-control planning, 87, 93
indicating, 22, 56 explosion, 59
Microphones, 22, 53, 54, 56 flame, 73
location of, 96, 100 flow-induced, Table 6, 61; 69, 70
wind screens, 95 generation, 59, 67, 68
Moisture separator-reheater, 67 impact, 59; Table 6, 61
Motors, 59; Table 6, 60; 90, 96; levels, 14
Table 11, 117 contribution to, 53, 54
Mufflers, 113, 114 combining, Fig 5 , 30
extrapolation of, 14
NEMA specifications, 112, 113
N nonsteady, 19
Noise offensive, 108
aerodynamic, 59, 68, 69 overexposure to, 94; Table 9, 95
ambient, 52, 53, 54; Table 10, 99; 100, prediction, 14
106; Fig 40, 107; 108; pulsating, 109, 110
Fig 42, 109; 122 reduction, 13, 14, 26, 52, 118
background, 52, 53, 54, 59, 100, 106, approaches to, 110, 112 - 116
107, 108, 109, 122 categories for noise-reduction
blade, 59 treatments, 112
broadband, 71 methods for, 110-112, 119
cavitation, 69, 70 selection of method for different
combustion, 59, 73 noise sources,
community, Table 11, 116-118
equivalent level (CNEL), 54, 55 source, 52, 53, 54
exposure, 13 sources, 19; Table 7, 62-65
complaint, 13 characteristics of, 19
IEEE
Std 640-1985 INDEX
174
IEEE
INDEX Std 640-1985
R limitations of, 26
measurement of, 26, 32, 97, 100,
Radiation 103, 127, 128
far field, 34, 35 occupational exposure to, 49
near field, 34, 35, 52, 53, 100 typical, Fig 2 , 24
Radius, equivalent, 38 near field, 34
Recorder power, 20
graphic level, 57 definition of, 15
Regulations, 47, 48, 49 pressure, 20
state and local, 48 definition of, 15
Resonances, 111 propagation, outdoors
Reverbant atmospheric absorption, 43
field, 42, 43, 51, 52 barrier effects, 44
rooms, 42, 43, 90, 96 foliage effect, 44
behavior of, 43 precipitation effects, 43, 44
Reverberation time refraction by atmospheric
definition of, 41 inhomogeneities, Fig 12, 45; 46
measurement of, 52 radiation, 19, 26, 59, 88
Rooms near-field, 34
acoustic characteristics of, 26, 39, 96 far-field, 34
reverberant, 42, 43, 90, 96 reflections, 39
Rotating turbo-machinery, 59, 66-69 spectra, 14, 97
definition of, 19
examples of, 74-85
S
measurement of, 26, 27, 56, 57, 59, 83
Septums transmission loss, 110, 111
ceiling, 113, 115 speed of, 46
Shields waves, definition of, 19
acoustical, 100, 110, 111, 113, 115 Sound level
Shock waves, 70 contours, 100; Figs 32 and 33, 101
SLM weighting characteristics, Fig 3 , 26 data forms, 95
Soot blowers, 91 measurement, 21, 22, 27, 29, 31, 32,
Sound 39, 43, 129, 130
absorption, 110 directivity factor in, 35, 36
atmospheric, 43; Fig 11, 44 effect of reflection on, 39
by atmospheric precipitation, 43, 44 environmental, 49, 52, 54, 55;
by foliage, 44 Fig 40, 107
by outdoor barriers, 44 far field, 34, 35
attenuation, 44 for directional source, 34, 38, 39
energy, 19 free-field, 32, 34, 51, 53, 54, 100
distribution as function of frequency, in hemispherical space, 34, 36
27 instrumentation for, 55, 57, 95
far field locations for, 53-55; Fig 38, 105
intensity, 20 mean, 36, 38
definition of, 15 near field, 34, 35, 52, 53, 100
measurement of, 21 occupational, 52, 54
isolation, 26, 110, 111 point sources, 32
levels, 22, 26 prescribed measurement points for
A-weighted, 59, 131, 132 machines, Fig 8, 37; 38
as single number rating, 26 reverberant field, 42, 43, 51
175
IEEE
Std 640-1985
176
.-