Computation of Loads
Computation of Loads
Ozamiz City
EE 513
Subject
PERSPECTIVE VIEW
COMPUTATION
SOLUTION
Examining the lighting plan and power plan, there are 26 light outlets, 17 convenience outlets,
and 1 aircon outlet. Split the 26 light outlets into four circuits (A, B, C, and D). Split the 17
convenience outlets into two circuits (E and F). 1 aircon oulet for one remaining circuit (G).
1. The Philippine Electrical Code provides that 100 watts be the maximum load per light outlet.
Thus, for 6 light outlets at 100 watts, multiply:
6 outlets x 100 watts = 600 Watts
1. The Philippine Electrical Code provides that 100 watts be the maximum load per light outlet.
Thus, for 6 light outlets at 100 watts, multiply:
6 outlets x 100 watts = 600 Watts
1. The Philippine Electrical Code provides that 100 watts be the maximum load per light outlet.
Thus, for 5 light outlets at 100 watts, multiply:
6 outlets x 100 watts = 600 Watts
1. The Philippine Electrical Code provides that 100 watts be the maximum load per light outlet.
Thus, for 5 light outlets at 100 watts, multiply:
8 outlets x 100 watts = 800 Watts
2. Compute the Current Load.
800 watts/230 = 3.47 Amperes
Section 3.3.1.2 of the Philippine Electrical Code specify 180 watts load limit per
conveniece outlet. Thus:
1. Find the number of appliance outlet and the current load
8 outlets x 180 watts .
8 x 180 = 1440 Watts
Divide: 1440 watts/230volts = 6.26 Amperes
2. Determine the Size of the Service Wire Conductor. Refer to Table 2-5 or 4-2
For the 3.13 amperes load, specify the minimum wire gauge for convenience outlet.
2 pieces 3.5mm2 THHN copper wire.
4. Solve for the Size or Rating of the Over Current Protective. Refer to Table 4-l.
For 3.13 amperes on 3.5 mm2 THHN copper wire specify:
Use 20 Amperes trip breaker.
Section 3.3.1.2 of the Philippine Electrical Code specify 180 watts load limit per
conveniece outlet. Thus:
2. Determine the Size of the Service Wire Conductor. Refer to Table 2-5 or 4-2.
For the 3.91 amperes load, specify the minimum wire gauge for convenience outlet.
2 pieces 3.5 mm2 THHN copper wire.
4. Solve for the Size or Rating of the Over Current Protective. Refer to Table 4-l.
For 3.91 amperes on 3.5mm2 THHN copper wire specify:
Use 20 Amperes trip breaker.
Article 6.7 of the Philippine Electrical Code (PEC) provides that:Branch Circuit conductor
supplying a motor shall have an ampacity not less than 125% of the flull load current."
5. Find the Size and Rating of the Branch Circuit Protection. The Code on branch circuit protection
for a single motor provides that: "It shall be increased by 250% of the full load current of the
motor. Thus:
6.07 x 250% = 15.175 amperes. From Table 4-1 for a continuous load
use 30 Amperes Trip Breaker
Calculating the Ampacity of the Service Entrance Conductor
and the Main Disconnecting Means
1. Find the total current load of circuit 1 to Circuit 7:
Lighting Load Ct. -1 and Ct 2 ------------------------ 2,600 Watts
Small appliance load Ct.-3 and Ct.-4 ------------------------ 3,060 Watts
TOtal load (except the Aircon unit) ------------------------ 5,560 Watts
2. From Table 4-4 of PEC, Optional Calculation for Dwelling Unit, apply demand factor (df).
2. Find the Size of Main Feeder and the Neutral From Table 4-2
use 2- 30 mm2 THHN copper wire.
3. The Neutral conductor of a 3-wire line to line supply system shall have an ampacity of not
less than 70% of the ungrounded (live wire) conductor or Two Trade size smaller
than the ungrounded conductor. (PEC Specifications).
Therefore: use 1 - 22 mm2 THW copper wire for the Neutral line.
4. Determine the .Size of the. Conduit Pipe. Refer to Table 2-9, use 25mm diameter pipe.
Summary:
The total load is 57.28 Amperes. From Table 4-2 the 30 mm2 THHN copper wire could be
used considering its 90 amperes ampacity. However, the National Electrical Code (NEC) provides
that: If the computed load exceeds 10,000 watts, the conductor and overcurrent protection shall be
rated not less than 100 amperes.
Therefore:
Use 2-30mm2 THHN copper wire for the Main Feeder and 100 Amperes for the
main breaker.
REFERENCE TABLE
Voltage Drop Calculation
Voltage drop can be calculated by:
VD = K P L I / A
where
K = specific resistivity ( circular mils/foot)
P = phase constant = 2 (for single phase) = 1.732 (for three phase)
L = wire length (ft)
A = wire area (circular mils)
Specific electric resistivity for different types of wire materials
Solid Copper, K = 11 (temp 77oF 121oF),
K = 12 (temp 122oF 167oF)
Solid Aluminum, K = 18 (temp 77oF 121oF),
K = 20 (temp 122oF 167oF)
Stranded Copper, K = 11 (temp 77oF 121oF),
K = 12 (temp 122oF 167oF)
Stranded Aluminum, K = 19 (temp 77oF 121oF),
K = 20 (temp 122oF 167oF)
SOLUTION:
VD = K P L I / A
= (11) (2) (65.09) (2.60) / (4110)
VD = 0.90 V
VD = K P L I / A
= (11) (2) (59.74) (2.60) / (4110)
VD = 0.83 V
VD = K P L I / A
= (11) (2) (47.67) (2.60) / (4110)
VD = 0.66 V
VD = K P L I / A
= (11) (2) (114.40) (3.47) / (4110)
VD = 2.12 V
E. Circuit-5 For Small Appliance Load (Convenience Outlet)
Single phase
Length of wire is 44.26 ft. VD% = [VD/Source Voltage] x 100
Wire # 12 3.5mm2 THHN = [0.93 V / 230 V] x 100
Stranded Copper wire VD% = 0.40%
Current = 6.26 Amperes
VD = K P L I / A
= (11) (2) (44.26) (6.26) / (6530)
VD = 0.93 V
VD = K P L I / A
= (11) (2) (65.25) (7.04) / (6530)
VD = 1.55 V
VD = K P L I / A
= (11) (2) (26.08) (4.86) / (10400)
VD = 0.27 V
H. Service Entrance
Single Phase
Length of wire is 59.05 ft. VD% = [VD/Source Voltage] x 100
Wire # 1 38mm2 TW = [0.89 V / 230 V] x 100
Solid Copper wire VD% = 0.39%
Current = 57.28 Amperes
VD = K P L I / A
= (11) (2) (59.05) (57.28) / (83700)
VD = 0.89 V