0% found this document useful (0 votes)
103 views1 page

Illumination Level Calculation: Lamp Fixture Utiliz Mainte Hight Down Sym - Ation - Nance F (LM) BLE Room Index Reflectance

This document provides calculations for illumination levels in three rooms - Manual Packing 1 and 2, and an Office - under both original and proposed lighting designs. The original design uses FL 14W-4 fluorescent fixtures while the proposed design uses LED 7W-4 fixtures. For each room and design, it lists the lamp lumens, designed lux level, room dimensions and area, fixture details, reflectance values used in calculations, and the results for number of fixtures needed and actual lux level. The goals are to determine the number of new LED fixtures required to meet or exceed illumination levels of the original designs while improving energy efficiency.

Uploaded by

Adi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
103 views1 page

Illumination Level Calculation: Lamp Fixture Utiliz Mainte Hight Down Sym - Ation - Nance F (LM) BLE Room Index Reflectance

This document provides calculations for illumination levels in three rooms - Manual Packing 1 and 2, and an Office - under both original and proposed lighting designs. The original design uses FL 14W-4 fluorescent fixtures while the proposed design uses LED 7W-4 fixtures. For each room and design, it lists the lamp lumens, designed lux level, room dimensions and area, fixture details, reflectance values used in calculations, and the results for number of fixtures needed and actual lux level. The goals are to determine the number of new LED fixtures required to meet or exceed illumination levels of the original designs while improving energy efficiency.

Uploaded by

Adi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

ILLUMINATION LEVEL CALCULATION

PROJECT NAME : SAMPOERNA LOT-17 KR01 27/10/2017


*
LAMP ROOM SIZE DESK FIXTURE ROOM INDEX REFLECTANCEUTILIZ MAINTE No.OF DESIGN
F.L ROOM NAME TYPE OF FIXTURE LUMENS LUX WIDTH DEPTH AREA HIGHT HIGHT DOWN K SYM- C W F -ATION -NANCE N.L N.F E REMARKS
SYMBOL F(lm) E(lx) X(m) Y(m) A(m2) Z(m) h1(m) h2(m) H(m) INDEX BLE (%) (%) (%) U M N(SET) SET (lx)

1 MANUAL PACKING-1 (ORIGINAL


C DESIGN)
FL 14W-4 Recessed w/Louver 5400 280 18,0 9,0 162,00 3,00 0,00 0,00 3,00 2,00 70 50 10 0,75 0,75 14,9 15 281

2 MANUAL PACKING-2 (ORIGINAL


C DESIGN)
FL 14W-4 Recessed w/Louver 5400 400 6,5 4,4 28,97 3,00 0,00 0,00 3,00 0,88 70 50 10 0,47 0,75 6,1 6 394

3 OFFICE (ORIGINAL DESIGN)C FL 14W-4 Recessed w/Louver 5400 150 12,0 4,4 53,28 3,00 0,00 0,00 3,00 1,08 70 50 10 0,55 0,75 3,6 4 167

1 MANUAL PACKING-1 A LED 7W-4 Recessed w/Louver 3200 280 18,0 9,0 162,00 3,00 0,00 0,00 3,00 2,00 70 50 10 0,61 0,90 25,8 15 163

2 MANUAL PACKING-2 A LED 7W-4 Recessed w/Louver 3200 400 6,5 4,4 28,97 3,00 0,00 0,00 3,00 0,88 70 50 10 0,40 0,90 10,1 6 239

3 OFFICE A LED 7W-4 Recessed w/Louver 3200 150 12,0 4,4 53,28 3,00 0,00 0,00 3,00 1,08 70 50 10 0,45 0,90 6,2 4 97

Fixture Hight H = Z - ( h1 + h2 ) SYMBOL A B C D E F G H I J E*A


No. of Lighting Fixture N[set] =
ROOM 4.5 4.5 3.5 2.75 2.25 1.75 1.38 1.12 0.9 0.7 F*U*M
Room Index K = ( X * Y ) / { H * ( X + Y ) } INDEX RANGE OVER | | | | | | | | UNDER F*N*U*M
Lux E[lx] =
3.5 2.75 2.25 1.75 1.38 1.12 0.9 0.7 A