VKS Cable Schedule Bay-01 (Update)

This document appears to be a table listing cable connections for panel E01. It includes 14 cables connecting various power sources and circuit breakers to the panel. The cables are various types and sizes, connecting items like DC and AC power sources, main breakers, and circuit breakers for different loads, with labeling of terminals at both ends to indicate the connections.

Uploaded by

Tien Dat Tran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
57 views8 pages

VKS Cable Schedule Bay-01 (Update)

This document appears to be a table listing cable connections for panel E01. It includes 14 cables connecting various power sources and circuit breakers to the panel. The cables are various types and sizes, connecting items like DC and AC power sources, main breakers, and circuit breakers for different loads, with labeling of terminals at both ends to indicate the connections.

Uploaded by

Tien Dat Tran
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

TABLE 3:

BNG U CP NH TH CHO NGN E01

U CP NGUN
Cable Type - Cores x
Order Cable Wire From Ref. To Ref.
Section
REMARK
Nr. Number Name Item Item Designation
Drawing Drawing
Designation
C101 DC /CRP 1-01 Cu/PVC/PVC-2Cx4.0 sq.mm DCBD = CRP E01
1 X1:11 /23 X03:07 /36
2 X1:12 /23 X03:08 /36 DC supply Source -01
C102 DC /CRP 1-02 Cu/PVC/PVC-2Cx4.0 sq.mm DCBD = CRP E01
1 X1:59 /27 X03:09 /36
2 X1:60 /27 X03:10 /36 DC supply Source -02
C103 AC /CRP 1-01 Cu/PVC/PVC-2Cx4.0 sq.mm ACDB = CRP E01
1 X14:3 /26 X03:5 /40
2 X14:4 /26 X03:6 /40 AC supply 230V
CA101 AC /MK 1-01 Cu/PVC/PVC-2Cx4.0 sq.mm ACDB = MK E01
1 X14:1 /26 X1:1 /11
2 X14:2 /26 X1:3 /11 AC supply 230V to MCB F201
C1201 MK 1/MK 2-01 Cu/PVC/PVC-2Cx4.0 sq.mm = MK E01 = MK E02
1 X1:2 /11 X1:1 /10
2 X1:4 /11 X1:3 /10 AC Supply to BMK-02
C104 MK 1/Q0 1-01 Cu/PVC/PVC-2Cx4.0 sq.mm = MK E01 = CB Q0 E01
1 MK1-X12:1 /12 X1:7
230V AC supply for Q0
2 MK1-X12:11 /12 X1:8
C105 MK 1/Q7 1-01 Cu/PVC/PVC-2Cx4.0 sq.mm = MK E01 = DS Q7 E01
1 MK1-X12:2 /12 401
230V AC supply for Q7
2 MK1-X12:12 /12 403
C106 MK 1/Q761-01 Cu/PVC/PVC-2Cx4.0 sq.mm = MK E01 = ES Q76 E01
1 MK1-X12:3 /12 401
230V AC supply for Q76
2 MK1-X12:13 /12 403
C107 MK 1/Q751-01 Cu/PVC/PVC-2Cx4.0 sq.mm = MK E01 = ES Q75 E01
1 MK1-X12:4 /12 401
230V AC supply for Q75
2 MK1-X12:14 /12 403
C108 MK 1/Q1 1-01 Cu/PVC/PVC-2Cx4.0 sq.mm = MK E01 = DS Q1 E01
1 MK1-X12:5 /13 401
230V AC supply for Q1
2 MK1-X12:15 /13 403
C109 MK 1/Q151-01 Cu/PVC/PVC-2Cx4.0 sq.mm = MK E01 = ES Q15 E01
1 MK1-X12:6 /13 401
230V AC supply for Q15
2 MK1-X12:16 /13 403
C110 DC /MK 1-01 Cu/PVC/PVC-2Cx4.0 sq.mm DCDB = MK E01
1 X2:1 /23 X2:1 /14
2 X2:2 /23 X2:3 /14 DC DUPPLY TO BMK-01
C111 MK 1/Q0 1-02 Cu/PVC/PVC-2Cx4.0 sq.mm = MK E01 = CB Q0 E01
1 MK1-X21:1 /14 X1:5
110V DC Q0 Breaker Spring charge Motor
2 MK1-X21:6 /14 X1:6
U CP DNG, P
C113A1 #N/A CVV-S -4Cx4.0 sq.mm = MK E01 = CT BOX A E01
MK1/CTA2-02 1 CTTB2:1 /41 1S4
R-Phase- Core-1 Distance protection(REL670)
2 CTTB2:3 /41 1S1
3
Core -02 Spare, 2S4-2S1 Spare and Ground
4
C113A2 #N/A CVV-S -4Cx4.0 sq.mm = MK E01 = CT BOX A E01
A2-01 1 CTTB4:1 /44 3S4
R-Phase- Core-3 Back Up protection(REF615)
2 CTTB4:3 /44 3S1
3 CTTB1:1 /40 4S4
R-Phase -Core-04 Metering Protection
4 CTTB1:3 /40 4S1
C113B1 #N/A CVV-S -4Cx4.0 sq.mm = MK E01 = CT BOX B E01
B2-02 1 CTTB2:4 /41 1S4
Y-Phase- Core-1 Distance protection(REL670)
2 CTTB2:6 /41 1S1
3
Core -02 Spare, 2S4-2S1 Spare and Ground
4
C113B2 #N/A CVV-S -4Cx4.0 sq.mm = MK E01 = CT BOX B E01
B2-01 1 CTTB4:4 /44 3S4
Y-Phase- Core-3 Back Up protection(REF615)
2 CTTB4:6 /44 3S1
3 CTTB1:4 /40 4S4
Y-Phase -Core-04 Metering Protection
4 CTTB1:6 /40 4S1
C113C1 #N/A CVV-S -4Cx4.0 sq.mm = MK E01 = CT BOX C E01
C2-02 1 CTTB2:7 /41 1S4
B-Phase- Core-1 Distance protection(REL670)
2 CTTB2:9 /41 1S1
3
Core -02 Spare, 2S4-2S1 Spare and Ground
4
C113C2 #N/A CVV-S -4Cx4.0 sq.mm = MK E01 = CT BOX C E01
C2-01 1 CTTB4:7 /44 3S4 B-Phase- Core-3 Back Up protection(REF615)
2 CTTB4:9 /44 3S1
3 CTTB1:7 /40 4S4
B-Phase -Core-04 Metering Protection
4 CTTB1:9 /40 4S1
C114 CRP 3/CRP 1-01 CVV-S -4Cx4.0 sq.mm = CRP E03 = CRP E01
1 L-X12:1 /43 X12:1 /41
2 L-X12:2 /43 X12:2 /41
BUS PT Voltage Metering Core-02
3 L-X12:3 /43 X12:3 /41
4 L-X12:4 /43 X12:4 /41
C115 CRP 3/CRP 1-02 CVV-S -4Cx4.0 sq.mm = CRP E03 = CRP E01
1 L-X12:5 /43 X12:5 /41
2 L-X12:6 /43 X12:6 /41
BUS PT Voltage Protection Core-03
3 L-X12:7 /43 X12:7 /41
4 L-X12:8 /43 X12:8 /41
C116 MK 1/CRP 1-01 CVV-S -4Cx4.0 sq.mm = MK E01 = CRP E01
1 CTTB1:1 /40 X01:11 /42
2 CTTB1:4 /40 X01:12 /42
Metering Core4 - CRP-01
3 CTTB1:7 /40 X01:13 /42
4 CTTB1:9 /40 X01:14 /42
C117 MK 1/CRP 1-02 CVV-S -4Cx4.0 sq.mm = MK E01 = CRP E01
1 CTTB2:1 /41 X01:1 /46
2 CTTB2:4 /41 X01:2 /46
REL670 Distance protection Core-01
3 CTTB2:7 /41 X01:3 /46
4 CTTB2:9 /41 X01:4 /46
C118 MK 1/CRP 1-03 CVV-S -4Cx4.0 sq.mm = MK E01 = CRP E01
1 MK1-X8:1 /43 X02:1 /47
Line CVT Incomer-01
2 MK1-X8:2 /43 X02:2 /47
3
4
C119 MK 1/CRP 1-04 CVV-S -4Cx4.0 sq.mm = MK E01 = CRP E01
1 CTTB4:1 /44 X01:6 /60
2 CTTB4:4 /44 X01:7 /60
REF615 Back Up Protection Core-03
3 CTTB4:7 /44 X01:8 /60
4 CTTB4:9 /44 X01:9 /60
C120 #N/A CVV-S -4Cx4.0 sq.mm = MK E01 = VTB BOX B E01
1 MK1-X8:1 /43 1a
2 MK1-X8:2 /43 1n Line-01 CVT Core-01
3
4
U CP IU KHIN
C121 MK 1/CRP 1-05 CVV-S -12Cx1.5 sq.mm = MK E01 = CRP E01
1 MK1-X1:13 /17 52X04:15 /80 Common positive +DC
2 MK1-X1:16 /17 52X04:16 /80 Breaker open position NC
3 MK1-X1:17 /17 52X04:17 /80 Breaker open position NO
4 MK1-X1:15 /17 52X04:18 /80 Spring charge indication
5 MK1-X1:14 /17 52X04:19 /80 SF6 Pressure Blocking
6 MK1-X1:18 /17 52X04:12 /50 Common positive +DC
7 MK1-X1:19 /17 52X04:13 /50 Breaker open position NC to REL670
8 MK1-X1:20 /17 52X04:14 /50 Breaker open position NO TO REL670
9 MK1-X1:21 /17 X04:01 /48
SF6 Gas Replisnish ment Alarm
10 MK1-X1:22 /17 X04:02 /48
11
12
C122 MK 1/CRP 1-06 CVV-S -7Cx1.5 sq.mm = MK E01 = CRP E01
1 MK1-X7:1 /39 X04:6 /48
Field MCB TRIP/OFF
2 MK1-X7:11 /39 X04:7 /48
3 MK1-X4:14 /29 X04:114 /86
4 MK1-X4:15 /29 X04:115 /86 OVH LINE DEAD IOM BO.12
5 MK1-X1:27 /14 52X04:22 /83
Breaker Local position Indication LAMP
6 MK1-X1:29 /14 52X04:23 /83
7
C123 CRP 3/CRP 1-03 CVV-S -12Cx1.5 sq.mm = CRP E01 = CRP E03
1 X04:36 /54 X04:27 /73
2 X04:37 /54 X04:28 /73 CRP-01,50 BF OPERATED to CRP-03 Trip coil-01
3 X04:38 /54 X04:29 /74
4 X04:39 /54 X04:30 /74 CRP-01,50 BF OPERATED to CRP-03 Trip coil-02
5 X04:77 /70 LBB-X04:1 /59
6 X04:78 /70 LBB-X04:2 /59 CRP-03,50 BF OPERATED to CRP-01 Trip coil-01
7 X04:83 /71 LBB-X04:3 /59
8 X04:84 /71 LBB-X04:4 /59 CRP-03,50 BF OPERATED to CRP-01 Trip coil-02
9
10
11
12
C124 MK 1/CRP 1-07 CVV-S -7Cx2.5 sq.mm = MK E01 = CRP E01
1 MK1-X5:1 /31 X03:1 /65
2 MK1-X5:3 /31 X03:2 /65 DC Supply 110V - Q1
3 MK1-X5:7 /31 89X04:1 /65 Common
4 MK1-X5:6 /31 89X04:2 /65 Remote open
5 MK1-X5:5 /31 89X04:3 /65 Remote Close
6 MK1-X5:8 /32 89X04:4 /65
7 MK1-X5:9 /32 89X04:5 /65 Interlock coil
C125 MK 1/CRP 1-08 CVV-S -7Cx2.5 sq.mm = MK E01 = CRP E01
1 MK1-X2:1 /19 X03:3 /67
2 MK1-X2:3 /19 X03:4 /67 DC Supply 110V - Q7
3 MK1-X2:7 /19 89X04:11 /67 Common
4 MK1-X2:6 /19 89X04:12 /67 Remote open
5 MK1-X2:5 /19 89X04:13 /67 Remote Close
6 MK1-X2:8 /20 89X04:14 /67
7 MK1-X2:9 /20 89X04:15 /67 Interlock coil
C126 MK 1/CRP 1-09 CVV-S -7Cx2.5 sq.mm = MK E01 = CRP E01
1 MK1-X6:7 /35 89X04:6 /66 Common ------Q15
2 MK1-X6:6 /35 89X04:7 /66 Remote open
3 MK1-X6:5 /35 89X04:8 /66 Remote Close
4 MK1-X6:8 /36 89X04:9 /66
5 MK1-X6:9 /36 89X04:10 /66 Interlock coil
6
7
C127 MK 1/CRP 1-010 CVV-S -7Cx2.5 sq.mm = MK E01 = CRP E01
1 MK1-X3:7 /23 89X04:16 /68 Common ------Q75
2 MK1-X3:6 /23 89X04:17 /68 Remote open
3 MK1-X3:5 /23 89X04:18 /68 Remote Close
4 MK1-X3:8 /24 89X04:19 /68
5 MK1-X3:9 /24 89X04:20 /68 Interlock coil
6
7
C128 MK 1/CRP 1-011 CVV-S -7Cx2.5 sq.mm = MK E01 = CRP E01
1 MK1-X4:7 /27 89X04:21 /69 Common ------Q76
2 MK1-X4:6 /27 89X04:22 /69 Remote open
3 MK1-X4:5 /27 89X04:23 /69 Remote Close
4 MK1-X4:8 /28 89X04:24 /69
5 MK1-X4:9 /28 89X04:25 /69 Interlock coil
6
7
C129 MK 1/CRP 1-012 CVV-S -12Cx2.5 sq.mm = MK E01 = CRP E01
1 MK1-X1:1 /15 52X04:1 /72
2 MK1-X1:2 /15 52X04:2 /72 DC Supply 110vdc breaker Q0
3 MK1-X1:8 /16 52X04:3 /72 Remote Trip /TC-1
4 MK1-X1:10 /16 52X04:4 /72 Pre-Close TC-01 Supervision
5 MK1-X1:9 /16 52X04:5 /72 Post-Close TC-01 Supervision
6 MK1-X1:7 /16 52X04:6 /73 Remote Trip /TC-2
7 MK1-X1:12 /16 52X04:7 /73 Pre-Close TC-02 Supervision
8 MK1-X1:11 /16 52X04:8 /73 Post-Close TC-02 Supervision
9 MK1-X1:30 /15 52X04:25 /73 DC supply-02
10 MK1-X1:04 /15 52X04:10 /74 Auto Recloser
11 MK1-X1:05 /15 52X04:11 /74 Remote/ Manual Close
12
C130 MK 1/CRP 1-013 CVV-S -7Cx1.5 sq.mm = MK E01 = CRP E01
1 MK1-X5:26 /34 89X04:26 /80 Common
2 MK1-X5:27 /34 89X04:27 /80 Q1-Isolator open position NC
3 MK1-X5:28 /34 89X04:28 /80 Q1- Isolator Close position NC
4 MK1-X2:22 /22 89X04:29 /80 Common
5 MK1-X2:23 /22 89X04:30 /80 Q7-Isolator open position NC
6 MK1-X2:24 /22 89X04:31 /80 Q7- Isolator Close position NC
7
C131 MK 1/CRP 1-014 CVV-S -12Cx1.5 sq.mm = MK E01 = CRP E01
1 MK1-X6:26 /38 89X04:32 /81 Common
2 MK1-X6:27 /38 89X04:33 /81 Q15-Earth Switch open position NC
3 MK1-X6:28 /38 89X04:34 /81 Q15- Earth Switch Close position NC
4 MK1-X3:16 /26 89X04:35 /81 Common
5 MK1-X3:17 /26 89X04:36 /81 Q75-Earth Switch open position NC
6 MK1-X3:18 /26 89X04:37 /81 Q75- Earth Switch Close position NC
7 MK1-X4:16 /30 89X04:38 /81 Common
8 MK1-X4:17 /30 89X04:39 /81 Q76-Earth Switch open position NC
9 MK1-X4:18 /30 89X04:40 /81 Q76- Earth Switch Close position NC
10
11
12
C132 CRP 3/CRP 1-04 CVV-S -7Cx1.5 sq.mm = CRP E03 = CRP E01

C133 MK 1/Q0 1-03 CVV-S -12Cx2.5 sq.mm = MK E01 = CB Q0 E01


1 MK1-X1:1 /15 X1:1
2 MK1-X1:2 /15 X1:2 DC Supply 110vdc breaker Q0
3 MK1-X1:8 /16 X1:10 Remote Trip /TC-1
4 MK1-X1:10 /16 X1:13 Pre-Close TC-01 Supervision
5 MK1-X1:9 /16 X1:12 Post-Close TC-01 Supervision
6 MK1-X1:07 /16 X1:11 Remote Trip /TC-2
7 MK1-X1:12 /16 X1:15 Pre-Close TC-02 Supervision
8 MK1-X1:11 /16 X1:14 Post-Close TC-02 Supervision
9 MK1-X1:30 /15 X1:3 DC Supply -2
10 MK1-X1:04 /15 X1:4 Auto Recloser
11 MK1-X1:05 /15 X1:9 Remote/ Manual Close
12
C134 MK 1/Q0 1-04 CVV-S -12Cx2.5 sq.mm = MK E01 = CB Q0 E01
1 MK2-X1:13 /17 X1:30 Common positive +DC
Loop
(X1:30,X1:32,
X3:106,X3:108)
2 MK2-X1:14 /17 X1:29 Loop SF6 Pressure Blocking
3 MK2-X1:15 /17 X1:31 (X1:30,X1:32, Spring charge indication
4 MK2-X1:16 /17 X3:105 X3:106,X3:108) Breaker open position NC
5 MK2-X1:17 /17 X3:107 Breaker open position NO
6 MK1-X1:18 /17 X3:102 Common positive +DC
Loop
7 MK1-X1:19 /17 X3:101 Breaker open position NC to REL670
(X3:102,X3:104)
8 MK1-X1:20 /17 X3:103 Breaker open position NO TO REL670
9 MK1-X1:21 /17 X1:18
SF6 Gas Replisnish ment Alarm
10 MK1-X1:22 /17 X1:19
11
12
C135 MK 1/Q0 1-05 CVV-S -7Cx2.5 sq.mm = MK E01 = CB Q0 E01
1 MK1-X1:6 /15 X1:46
2 MK1-X1:7 /15 X1:47 Not required
3 MK1-X1:23 /18 X1:26
SH:02 Local Interlock
4 MK1-X1:26 /18 X1:27
5
6
7
C136 MK 1/Q0 1-06 CVV-S -12Cx1.5 sq.mm = MK E01 = CB Q0 E01
1 MK1-X1:27 /15 X3:151 Common
2
3 MK1-X1:29 /15 X3:152 Local Selector switch
4 MK1-X2:19 /21 X3:109 Breaker AUX Contact NC-Normal Condition used for Q7
5 MK1-X2:18 /21 X3:110 Local Interlock
6 MK1-X5:19 /33 X3:113 Breaker AUX Contact NC-Normal Condition used for Q1
7 MK1-X5:18 /33 X3:114 Local Interlock
8 MK1-X7:1 /39 X1:40
9 MK1-X7:11 /39 X1:39 F3 MCB Aux.Contact Trip for Q0 Breaker
10 MK1-X7:2 /39 X1:38
11 MK1-X7:12 /39 X1:37 F11 DC MCB Contact trip for Q0 Breaker
12
C137 MK 1/Q7 1-02 CVV-S -12Cx2.5 sq.mm = MK E01 = DS Q7 E01
1 MK1-X2:1 /19 410
2 MK1-X2:3 /19 418 DC Supply 110V - Q7
3 MK1-X2:7 /19 431 Common
4 MK1-X2:6 /19 432 Remote open
5 MK1-X2:5 /19 430 Remote Close
6 MK1-X2:8 /20 440
7 MK1-X2:9 /20 441 Interlock coil
8 MK1-X2:12 /21 437
9 MK1-X2:19 /21 438 Local Interlock
10
11
12
C138 MK 1/Q7 1-03 CVV-S -7Cx1.5 sq.mm = MK E01 = DS Q7 E01
1
2
3
4 MK1-X7:3 /39 455
Local CONTROL PANEL MCB Trip/OFF
5 MK1-X7:13 /39 454
6
7
C139 MK 1/Q7 1-04 CVV-S -12Cx1.5 sq.mm = MK E01 = DS Q7 E01
1 MK1-X1:25 /18 27
Q7 NC contact for LC /Closing CKT Q0
2 MK1-X1:26 /18 28
3 MK1-X2:22 /22 24 Common
4 MK1-X2:23 /22 23 Q7-Isolator open position NC Contact
5 MK1-X2:24 /22 25 Q7- Isolator Close position NC Contact
6 MK1-X3:14 /25 31 Q7 Isolator Aux Contact open position NC contact used for
7 MK1-X3:15 /25 32 Local Interlock Q75
8 MK1-X4:13 /29 35 Q7 Isolator Aux Contact open position NC contact used for
Local Interlock Q76
Q7 Isolator Aux Contact open position NC contact used for
9 MK1-X4:14 /29 36 Local Interlock Q76
10 MK1-X6:14 /37 55 Q7 Isolator Aux Contact open position NC contact used for
11 MK1-X6:15 /37 56 Local Interlock Q15
12
C140 MK 1/Q1 1-02 CVV-S -12Cx2.5 sq.mm = MK E01 = DS Q1 E01
1 MK1-X5:1 /31 410
2 MK1-X5:3 /31 418 DC Supply 110V - Q1
3 MK1-X5:7 /31 431 Common
4 MK1-X5:6 /31 432 Remote open
5 MK1-X5:5 /31 430 Remote Close
6 MK1-X5:8 /32 440
7 MK1-X5:9 /32 441 Interlock coil
8 MK1-X5:12 /33 437
9 MK1-X5:19 /33 438 Local operation Interlock
10
11
12
C141 MK 1/Q1 1-03 CVV-S -7Cx1.5 sq.mm = MK E01 = DS Q1 E01
1 MK1-X5:29 67
2 MK1-X5:30 68 Q1 Aux contact used in E03 Q16 closing CKT.
3
4 MK1-X7:6 /39 455
Local CONTROL PANEL MCB Trip/OFF
5 MK1-X7:16 /39 454
6
7
C142 MK 1/Q1 1-04 CVV-S -12Cx1.5 sq.mm = MK E01 = DS Q1 E01
1 MK1-X1:23 /18 27
Q1 NC contact for LC /Closing CKT Q0
2 MK1-X1:24 /18 28
3 MK1-X5:26 /34 24 Common
4 MK1-X5:27 /34 23 Loop 24&26 Q7-Isolator open position NC Contact
5 MK1-X5:28 /34 25 Q7- Isolator Close position NC Contact
6 MK1-X3:12 /25 31
7 MK1-X3:13 /25 32 Isolator OFF position NC contact for Local Interlock
8 MK1-X4:11 /29 35
9 MK1-X4:12 /29 36 Isolator OFF position NC contact for Local Interlock
10 MK1-X6:12 /37 55
11 MK1-X6:13 /37 56 Isolator OFF position NC contact for Local Interlock
12
C143 MK 1/Q751-02 CVV-S -12Cx2.5 sq.mm = MK E01 = ES Q75 E01
1 MK1-X3:7 /23 431 Common ------Q75
2 MK1-X3:6 /23 432 Remote open
3 MK1-X3:5 /23 430 Remote Close
4 MK1-X3:8 /24 440
5 MK1-X3:9 /24 441 Interlock coil
6 MK1-X3:3 /23 418
7 MK1-X3:1 /23 410 DC Supply 110V - Q75
8 MK1-X3:12 /25 437
9 MK1-X3:15 /25 438 Local operation Interlock
10
11
12
C144 MK 1/Q751-03 CVV-S -7Cx1.5 sq.mm = MK E01 = ES Q75 E01
1
2
3
4 MK1-X7:4 /39 455
Local CONTROL PANEL MCB Trip/OFF
5 MK1-X7:14 /39 454
6
7
C145 MK 1/Q751-04 CVV-S -12Cx1.5 sq.mm = MK E01 = ES Q75 E01
1 MK1-X2:14 /21 27
2 MK1-X2:15 /21 28 Earth Switch OFF position NC contact for Local Interlock
3 MK1-X3:16 /26 24 Common
4 MK1-X3:17 /26 23 Loop 24&26 Q75-Earth switch OFF position NC Contact
5 MK1-X3:18 /26 25 Q75-Earth switch OFF position NO Contact
6 MK1-X5:14 /33 31
7 MK1-X5:15 /33 32 Earth Switch OFF position NC contact for Local Interlock
8
9
10
11
12
C146 MK 1/Q761-02 CVV-S -12Cx2.5 sq.mm = MK E01 = ES Q76 E01
1 MK1-X4:7 /27 431 Common ------Q76
2 MK1-X4:6 /27 432 Remote open
3 MK1-X4:5 /27 430 Remote Close
4 MK1-X4:8 /28 440
5 MK1-X4:9 /28 441 Interlock coil
6 MK1-X3:2 /23 410
7 MK1-X3:4 /23 418 DC Supply 110V - Q76
8 MK1-X4:11 /29 437
9 MK1-X4:15 /29 438 Local operation Interlock
10
11
12
C147 MK 1/Q761-03 CVV-S -7Cx1.5 sq.mm = MK E01 = ES Q76 E01
1
2
3
4 MK1-X7:5 /39 455
Local CONTROL PANEL MCB Trip/OFF
5 MK1-X7:15 /39 454
6
7
C148 MK 1/Q761-04 CVV-S -12Cx1.5 sq.mm = MK E01 = ES Q76 E01
1 MK1-X2:17 /21 27
2 MK1-X2:16 /21 28 Earth Switch OFF position NC contact for Local Interlock
3 MK1-X4:16 /30 24 Common
4 MK1-X4:17 /30 23 Loop 24&26 Q76-Earth switch OFF position NC Contact
5 MK1-X4:18 /30 25 Q76-Earth switch OFF position NO Contact
6
7
8
9
10
11
12
C149 MK 1/Q151-02 CVV-S -12Cx2.5 sq.mm = MK E01 = ES Q15 E01
1 MK1-X6:7 /35 431 Common ------Q15
2 MK1-X6:6 /35 432 Remote open
3 MK1-X6:5 /35 430 Remote Close
4 MK1-X6:8 /36 440
5 MK1-X6:9 /36 441 Interlock coil
6 MK1-X6:3 /35 418
7 MK1-X6:1 /35 410 DC Supply 110V - Q15
8 MK1-X6:12 /37 437
9 MK1-X6:15 /37 438 Local operation Interlock
10
11
12
C150 MK 1/Q151-03 CVV-S -7Cx1.5 sq.mm = MK E01 = ES Q15 E01
1
2
3
4 MK1-X7:7 /39 455
Local CONTROL PANEL MCB Trip/OFF
Local CONTROL PANEL MCB Trip/OFF
5 MK1-X7:17 /39 454
6
7
C151 MK 1/Q151-04 CVV-S -12Cx1.5 sq.mm = MK E01 = ES Q15 E01
1 MK1-X2:12 /21 27
2 MK1-X2:13 /21 28 Earth Switch OFF position NC contact for Local Interlock
3 MK1-X6:26 /38 24 Common
4 MK1-X6:27 /38 23 Loop 24&26 Q75-Earth switch OFF position NC Contact
5 MK1-X6:28 /38 25 Q75-Earth switch OFF position NO Contact
6 MK1-X5:12 /33 31
7 MK1-X5:13 /33 32 Earth Switch OFF position NC contact for Local Interlock
8
9
10
11
12
C152 MK 1/Q163-01 CVV-S -7Cx1.5 sq.mm = MK E01 = ES Q16 E03
1 MK1-X5:17 /33 67
2 MK1-X5:16 /33 68 Earth switch OFF POSITION NC contact for Q1 Interlock
3 MK1-X5:29 34A
4 MK1-X5:30 35A Q1 Aux contact used in E03 Q16 closing CKT.
5
6
7