100% found this document useful (2 votes)
2K views

Substation Earthing Design: Input Data

1) The document provides specifications for designing the earthing system for a 132kV substation, including conductor size, tolerable touch and step voltages, grid resistance, and maximum ground potential rise. 2) Key calculations are shown to determine the conductor size, tolerable touch and step voltages according to IEEE standards, and resistance of the earth grid and rods to obtain the total grid resistance and maximum GPR within safety limits. 3) The output confirms the final earthing system design is safe based on the specifications and calculations.

Uploaded by

pavan3961
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
100% found this document useful (2 votes)
2K views

Substation Earthing Design: Input Data

1) The document provides specifications for designing the earthing system for a 132kV substation, including conductor size, tolerable touch and step voltages, grid resistance, and maximum ground potential rise. 2) Key calculations are shown to determine the conductor size, tolerable touch and step voltages according to IEEE standards, and resistance of the earth grid and rods to obtain the total grid resistance and maximum GPR within safety limits. 3) The output confirms the final earthing system design is safe based on the specifications and calculations.

Uploaded by

pavan3961
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 12

SUBSTATION EARTHING DESIGN

Input data :-

1 Conductor material = Steel, 1020 18 Length of one earth mat cond

2 System Voltage = 132 kV 19 Width of one earth mat condu

3 Fault Current, If = 31.5 kA 20 Additional length of conduct

4 Fault Duration, tc = 1 sec 21 Grid conductor combined leng

5 Max. Allowable Temperature, Tm = 1510 0


C 22 Total no. of ground rods (Unt
SA
6 Ambient Temperature, Ta = 50 0
C Transformers (Body earthing)
Towers with peak
7 Reference temp for material constant,Tr = 20 0
C Switchyard corners
Additional ground rods
8 Thermal Co-eff.of resistivity at reference Total no of rods
Temperature, ar = 0.0016 23 length of each rod in m Lr
Total ground rod length, LR
9 Resistivity of Ground Conductor at ref.
Temperature, rr = 15.9 mW/cm3 24 Effective length of buried con
LT = LR + Lc
10 Thermal Capacity Factor, TCAP = 3.28 J/cm3/oC 25 Soil Resistivityconsidered for

11 K0 = (1/ar) -Tr = 605 26 Surface Resistivity, rs

12 Length of Earth grid = 100 metre 27 Spacing for Earthing Mat ,D

13 Width of Earth grid = 50 metre 28 Corrective weighting factor, K

14 Area of Earth grid, A = 5000 sq.metre 29 Reference Depth of grid, h0

15 Depth of burial w.r.t. ground level, h = 1 metre 29 Thickness of Concrete , hs

16 Calculate w.r.t to person weight(50/70) = 50 Kg 30 Fault Current division factor (

17 No. of conductors parallel to length side( nl = 25 31 No. of conductors parallel to w

Output:
Conductor size, A = 231 SQMM Effective Buried Length for m

By considering 30% allowance = 300 SQMM Effective Buried Length for st


A = 300 SQMM
Grid Resistance
Ground Potential Rise(GPR) = 4058.90 Volts

Tolerable Tolerable
Touch Voltage Etouch = 735 Volts Step Voltage Estep

Attainable Attainable
Touch Voltage Etouch = 701.21 Volts Step Voltage Estep

As per the above Design the System is SAFE


e earth mat conductor Lx = 100 metre

earth mat conductor Ly = 50 metre

ngth of conductor considered 12 metre

or combined length, Lc = 3162 metre

round rods (Untreated)


0
(Body earthing) 1
1
1
ound rods 1
4
h rod in m Lr = 3 meter
rod length, LR = 12 metre

gth of buried conductor = 3174 metre

tyconsidered for design, r = 49.12 W-meter

tivity, rs = 3000 W-meter

arthing Mat ,D = 4 meter

eighting factor, Kii = 1

pth of grid, h0 = 1 meter

Concrete , hs = 0.15 meter

division factor (Sf) = 0.5

ctors parallel to width side ( ns) = 13

ied Length for mesh voltage, LM = 3181 Meter

ied Length for step voltage, LS = 2382 Meter

= 0.26 Ohms
= 2447 Volts

= 379.06 Volts

AFE
Conductor Size :-

As per Eq.37 of IEEE Std 80-2000, conductor size is given by

tc ar rr x 104
TCAP
A = If Ko + Tm
ln 1 +
Ko + Ta

2.2) Calculation of Tolerable Etouch & Estep Voltage :

a) Tolerable Etouch :
From IEEE Std 80-2000
For 50 Tolerable Etouch50= [(1000 + 1.5CS rS) 0.116/ tS ] ( From eq.32of IEEE Std 80-2000 )
For 70 Tolerable Etouch70= [(1000 + 1.5CS rS) 0.157/ tS ]
Where,
Cs = Reduction factor for derating the nominal value of surface layer
resistivity.

Cs = 1 - 0.09 [(1-r/rs)/(2hs + 0.09)] ( From eq.27 of IEEE Std 80-2000 )

Cs = 0.7730
tS = Duration of shock current in seconds = 0.5
( from clause 16.2.2 of IEEE Std 80-2000 )
Substituting the above values,
Tolerable Etouch50 = 734.70 Volts
Tolerable Etouch70 = 994.38 Volts

b) Tolerable Estep (from eq.29 of IEEE Std 80-2000)


For 50 Tolerable Estep50 = [(1000 + 6CS rS) 0.116/ tS ]

For 70 Tolerable Estep70 = [(1000 + 6CS rS) 0.157/ tS ]

Substituting the values,


Tolerable Estep50 = 2446.65 Volts
Tolerable Estep70 = 3311.42 Volts

2.3) Calculation of Grid Resistance, Rg :

As per IEEE Std 80-2000,


R1 R2 - R m 2
The total system resistance, Rg =
R1 + R2 - 2Rm
Where,
R1 = Ground resistance of grid conductors in
R2 = Ground resistance of of all ground rods in
Rm = Mutual ground resistance between the group of grid conductors, R1 and
group of ground rods, R2 in

Ground resistance of the grid, R1

2 Lc k1 Lc
R1 = ln + - k2 From IEEE Std 80-2000
Lc a' A
a = 0.0195
Where,
r = Soil Resistivity in -m 49.12 ohm-m
Lc = Total length of all connected grid conductors in m 3162 m
a'
= a.2h for conductors buried at depth h in m 0.1977 m
2a = Diameter of conductor in m 0.0195 m
A = Area covered by conductors in m2 5000 m2
k1 = Coefficient from fig 25(a) of IEEE Std 80-2000 1.03
k1= -0.05*(Lx/Ly) + 1.13
k2 = Coefficient from fig 25(b) of IEEE Std 80-2000 4.30
k2= -0.05*(Lx/Ly) + 4.40
Coefficient K1 and k2 of schwarz's fromula IEEE Std 80-2000 )
R1 = 0.2578

Ground resistance of the rod bed, R2


From eq.55 of IEEE Std 80-2000
r 4 LR 2 k1 . Lr
R2 = ln -1 + ( nR - 1 ) 2
2p nRLR b A

Where,
Lr = length of each rod in m 3 m
2b = diameter of rod in m 0.020 m
nR = number of rods placed in area A 4
LR = Total length of ground rods 12
k1 = Coefficient from fig 25(a) of IEEE Std 80-2000 1.03
R2 = 1.236

Mutual ground resistance between the grid and the rod bed, Rm
From eq.56 of IEEE Std 80-2000

r 2 Lc k1 Lc
Rm = ln + - k2 + 1
p Lc Lr A

Rm = 0.2493
Subtituting the above values,
Rg = 0.2577

2.4) Calculation of Maximum Ground Potential Rise :


Max. Ground potential above remote earth, GPR = IG x RG Volts
Where,
IG = grid current = If x S f

IG = 15.75 KA
Substituting the values,

Ground Potential Rise, GPR = 4058.90 Volts

Since, GPR > Estep50 (as per Figure 33 of IEEE Std 80-2000),calculate Attainable Emesh and Attainable
Estep voltages

2.5) Calculation of Attainable Emesh Voltage :

From Eq.80 of IEEE Std 80-2000, for Grid rods in the periphery,
Emesh = [ r Km Ki IG / LM ]

Lr
LM = Lc + 1.55+1.22 Lr From eq.91 of IEEE Std 80-2000
L2x + L2y
Where,
Lr = Length of each ground rod = 3 m
Lx = Maximum length of grid conductor in x-direction 100 m
Ly = Maximum length of grid conductor in y-direction 50 m

IG = grid current = 15.75


Ki = corrective Factor, = 3.86
p1

LR = Total length of ground rods = 12 m


Subtituting the above values,

LM = 3180.99 m

As per Eq.81 of IEEE Std 80-2000, the Spacing Factor for Mesh Voltage,

1 D2 (D + 2h)2 h Kii 8
Km = ln + - + ln
2p 16hd 8Dd 4d Kh p(2n-1)

Equ. Diameter of Earth conductor, d = 0.0172 metre

K h = 1 + h / h0 ( From eq.83 of IEEE Std 80-2000 )

Kh = 1.41

No. of Parallel Paths, n = na nb nc nd (From eq.84 of IEEE Std 80-2000)

Where, From eq.85 to 88 of IEEE Std 80-2000 Lp


na = (2 Lc)/Lp nb =
4 A
0.7 A
Lx Ly Lx Ly Dm
nc = nd I
A L2x + L2y

Where,
Lp = Peripheral length of the grid = 300 m
Dm = Maximum distance between any two points
on the grid = 111.8 m
Substituting the above values,

na = 21.08 nb = 1.030

nc = 1 nd = 1.00

n = 21.71 = 22 Rounded of to nearest digit

As per Eq.89 of IEEE 80-2000,


The corrective Factor, Ki = 0.644 + ( 0.148 x n )From eq.89of IEEE Std 80-2000

= 3.86
Substituting the values,
Km = 0.7475

AttainableEmesh Voltage = 701.21 Volts

2.6) Calculation of Attainable Estep voltage :

From Eq.92 of IEEE Std 80-2000,


Attainable Estep = [ r Ks Ki IG / LS ] From eq.92 of IEEE Std 80-2000

As per Eq.94 of IEEE Std 80-2000, the Spacing Factor for Step Voltage,

1 1 1 1
Ks = + + (1 - 0.5n-2) From eq.94of IEEE Std 80-2000
P 2h D+h D

No. of Parallel paths, n = 22


n = 22
As per Eq.89 of IEEE 80-2000,
The corrective Factor, Ki = 0.644 + ( 0.148 x n )
Ki = 3.86

Ks = 0.3025

As per Eq.93 of IEEE Std 80-2000,

Ls = 0.75 Lc + 0.85 LR From eq.93of IEEE Std 80-2000


Lc = Total length of all connected grid conductors in m
LR = Total length of ground rods

Ls = 2381.7 m

Substituting the values,


Attainable Estep = 379.06 Volts

SAFE SAFE
NOT SAFE
ainable
Std 80-2000

Std 80-2000

You might also like