Test Report For Circuit Breaker: Customer

The document is a 6 page test report for a circuit breaker. It provides details of the circuit breaker such as the location, manufacturer, type, ratings, and test results. Key tests included insulation resistance testing, contact resistance testing, and time interval testing. All test results were found to be satisfactory and the circuit breaker was determined to be healthy.

Uploaded by

Subramaniam NP
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
118 views

Test Report For Circuit Breaker: Customer

The document is a 6 page test report for a circuit breaker. It provides details of the circuit breaker such as the location, manufacturer, type, ratings, and test results. Key tests included insulation resistance testing, contact resistance testing, and time interval testing. All test results were found to be satisfactory and the circuit breaker was determined to be healthy.

Uploaded by

Subramaniam NP
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 6

SHEET : 1 OF: 6

TEST REPORT FOR CIRCUIT BREAKER PAGE :


DATE : 24.03.2016
Customer :
Project:

1. Location : 1110 KV / 6.9 KV Switch yard

Feeder Name : 6.3 MVA Trafo.

2. Equipment Details :

Make Crompton Greaves


Type 120 SFM-32B
SI.No 34008C
Rated Voltage 145 KV
TESTED BY WITNESSED BY
SHEET : 2 OF: 6

TEST REPORT FOR CIRCUIT BREAKER PAGE :


DATE : 24.03.2016
Customer :
Project:

Rated Normal Current 1250


Frequency 50 Hz
Year 2011

3. General Inspection : OK

4. IR Test:

Measured Values (M)


Ref Applied Voltage (V)
R Y B
Pole to Pole 5 KV 517 717 515
TESTED BY WITNESSED BY
SHEET : 3 OF: 6

TEST REPORT FOR CIRCUIT BREAKER PAGE :


DATE : 24.03.2016
Customer :
Project:

Pole to Pole 5 KV 558 720 520


Pole to Earth 5 KV 415 516 489

5. Contact Resistance Test:

Ref Applied Current (A) Measured Resistance( )


R 200 89.2
Y 200 80.3
B 200 96.9

TESTED BY WITNESSED BY
SHEET : 4 OF: 6

TEST REPORT FOR CIRCUIT BREAKER PAGE :


DATE : 24.03.2016
Customer :
Project:

6. Time Interval Test:

Ref R Y B
Close 64 63 64
Open 23 24 24
Close-Open 22 22 21

TESTED BY WITNESSED BY
SHEET : 5 OF: 6

TEST REPORT FOR CIRCUIT BREAKER PAGE :


DATE : 24.03.2016
Customer :
Project:

TESTED BY WITNESSED BY
SHEET : 6 OF: 6

TEST REPORT FOR CIRCUIT BREAKER PAGE :


DATE : 24.03.2016
Customer :
Project:

7. Operational Checks : (Whether Operational Checks OK / Not OK / Not Available)

1 Manual (close/open) OK
2 Breaker Mechanical open & close indication properly working OK
3 Breaker Spring Charging Indication properly working OK

8. Comments : Nil

9. Remarks : Breaker found healthy.

TESTED BY WITNESSED BY