The Ziegler-Nichols method uses a closed controller loop & requires the following steps:
Bring system to steady state operation.
Put on P control. Introduce a set point change and vary gain until system
oscillates continuously. This frequency is CO and M is the amplitude ratio.
Compute the following:
1
Ultimate Gain K u
M
2
Ultimate Period Pu
CO
The original Z-N tuning settings are given in the following table.
Controller Kc I D
P K u /2
PI K u /2.2 Pu /1.2
PID K u /1.7 Pu /2 Pu /8
These controller settings were developed to give a 1/4 decay ratio. However, other
settings have been recommended that are closer to critically damped control (so that
oscillations do not propagate downstream). These PID controller settings are shown in the
following table.
Controller Kc I D
Original 0.6K u Pu /2 Pu /8
Some Overshoot 0.33K u Pu /2 Pu /3
No Overshoot 0.22K u Pu /2 Pu /3
The question becomes one of how to find these parameters when we dont have a real
process but rather the idealized transfer functions for the process.
Kp
R + Gc + Gp Y
1s 1 2 s 1 3 s 1
- +
As an example, let's assume we have a 3rd order overdamped system with negligible
dynamics in the final control & measurement elements. Then:
Kp
Gp s
1 s 1 2s 1 3s 1
G f s Gm s 1
The transfer function between the set point and the output under P control will be:
Kp
Kc
Gs
Gc Gp
1 s 1 2 s 1 3 s 1
1 Gc Gp Kp
1 Kc
1 s 1 2 s 1 3 s 1
KcK p
1 23 s 1 2 23 31 s 2 1 2 3 s 1 K p K c
3
1 23 s3 12 23 31 s 2 1 2 3 s 1 K pK c 0
will control the stability & oscillatory nature of the systems response. Undamped
oscillatory behavior occurs at the very edge of the systems stability limit.
Row
1 1 23 1 2 3
2 12 23 31 1 K pK c
3 1 23 1 K p K c
1 2 3
1 2 23 31
4 1 K pK c
1
1 K pK c 0 K c
Kp
which will be satisfied for any positive K c . The stability limit from the 3rd row is:
1 23 1 K p K c 1 2 3 12 23 31 1
1 2 3 0 Kc
1 2 23 31 K p 123 Kp
1 1 1 1 1
Kc 1 2 3
Kp 1 2 3 K p
1 1 1 1 1
K cu 1 2 3
Kp 1 2 3 K p
The period of oscillation at this ultimate gain must be calculated from the inverted Laplace
expression.
Direct Substitution. We could also use direct substitution to determine the stability limit for
this process. Substituting s j into the characteristic equation:
123 j 12 23 31 j 1 2 3 j 1 K pK c 0
3 2
1 23 3 j 12 23 31 2 1 2 3 j 1 K pK c 0
1 K K 23 31 2 1 2 3 1233 j 0 .
p c 1 2
1 2 3
1 2 3 u 1233u 0 u
1 23
and setting the real part to zero gives us the controller gain at the stability limit:
1 2 3
12 23 31 1
1 23
1 K K
p cu 1 2 23 31 2u 0 K cu
Kp
1 1 1 1 1
1 2 3
K p 1 2 3 Kp
(which is exactly the same as that given by the Routh array analysis).
1
Gp s
s 15s 10.2s 1
1 1 1 1 1
K cu 1 5 0.2 37.44
1 1 5 0.2 1
1 5 0.2
CO 2.48998
1 5 0.2
2
Pu 2.52339
CO
P control:
Ku
Kc 18.72
2
PI control:
Ku
Kc 17.02
2.2
P
I u 2.10
1.2
PID control:
Ku
Kc 22.02
1.7
P
I u 1.26
2
P
D u 0.32
8
Lets look at a step change to the load for PI control. The closed loop transfer function will
be:
Gs
Gp
s 15s 10.2s 1
1 Gc Gp 1 1
1 Kc 1
I s s 15s 1 0.2s 1
I s
I s s 15s 1 0.2s 1 K c I s 1
I s
I s 6.2I s 6.2I s 2 I 1 K c s K c
4 3
1
Y s
8.1039 18.0182s 6.2s2 6.2s3 s 4
Y t 0.00573006e 5.62165t 0.0626769e 0.495759t
e 0.0412961t 0.00204812sin 1.70472t 0.0569469cos 1.70472t
0.10
0.08
0.06
0.04
y(t) 0.02
0.00
-0.02
-0.04
-0.06
0 5 10 15 20
t
This figure shows the response to this disturbance. The controller settings are very
conservative there is very little damping to the response. In actual practice, these
settings would only be used as initial settings and additional tuning would be done.