ERMLG
ERMLG
ERMLG Test block provides facilities for monitoring & secondary It is recommended that the protection scheme or relay is wired
injection testing of any power system protection scheme, when to the even numbers of the test modules. To ensure the scheme
used with the multi fingered test plug type ERMLB01. wiring is routed logically it is recommended that the ERMLG is
always positioned on the right-hand side of the relay, when
viewed from the front. The connections to other equipment
Description such as CTs, VTs, and dc supplies should be made to the odd
numbered terminals indicated on the ERMLG. This will ensure
ERMLG Test block removes the need to disturb protective system
that on connection of the ERMLB, the sockets on the even
wiring for testing.
numbered side of the test plug are the isolated relay circuits
The ERMLG Test Block is housed within an Epsilon enclosure. and the sockets on the odd numbered side are connected to the
potentially live supplies and shown in Figure 3.
The ERMLG Test Block has 14 pairs of spring loaded contacts
which are linked to a terminal block positioned at the rear of the
enclosure.
The short test finger in position 13-14 on the ERMLB 01 will open
contacts 13-14 in the test block after the other fingers have made
contact in all other positions. !
When the cover is removed a blue fascia is revealed which is
attached to the test block. This gives a visual indication and
warning that the protection scheme or relay is not in service.
Precautions
BEFORE inserting a Test Plug into a Test Socket carrying
current transformers secondary circuits. ENSURE that the Test
Plugs corresponding to the current transformers circuits are
short-circuited.
TYPICAL APPLICATION OF THE ERMLG01 TEST SOCKET AND ERMLB01 TEST PLUG
Figure 3
OUTLINE AND DRILLING FOR ERMLG TEST SOCKET IN EPSILON E2 CASE
Figure 4
The policy of EASUN REYROLLE is one of continuous improvement and development. The company therefore reserves the right to supply equipment which may differ slightly
from that described and illustrated in the publication.
FACT/ERMLG/10-10/REV1.0
Global Manufacturing Centers
India, Canada & Germany
Mumbai Noida
Tel: +91 22 2285 54415/ 2202 2270 Tel: +91 120 2405 741/42/43
Fax: +91 22 2285 5703
Email: [email protected]
Fax: +91 120 2405 744
Email: [email protected]
Secunderabad
Tel: +91 40 2781 7847
Email: [email protected] ERL