Industrial DC Systems IBB: High Efficiency Industrial Power Solutions
Industrial DC Systems IBB: High Efficiency Industrial Power Solutions
Power Solutions
Eltek IBB Power systems and building blocks are built around our
Flatpack2 High Efficiency (HE) rectifiers and designed for a number
of power-critical Industrial applications, including Power Generation
& Distribution, Rail, Marine & Offshore, Oil & Gas and other
demanding industries.
Railway & Metro infrastructure ü Overall size and footprint; 50% less
• Control & protection than thyristor systems
• Power conversion
ü Graphical 3.2” TFT high contrast, high
• Signaling
resolution color display for easy
• GSM-R
navigation in user menu
• Safety Systems Flatpack2 HE rectifier
• Communication systems ü Optional built in VRLA batteries (up to
125VDC)
Eltek HQ: Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway. Phone: +47 32 20 32 00 - Eltek © 2015 – www.eltek.com
Building blocks for IBB Systems
FPC Cabinets
FPC is a family of high-end indoor cabinets, designed for flexibility.
With its robust design, removable side panels and variety of
options, the FPC cabinet can be used in a wide range of
applications.
FPC Cabinets
IBF-SP2 Power Core
A complete 19” & 23” Power core pre-engineered and designed for:
24, 30, 48, 60, 110, 125 and 220 VDC with the following features:
Distribution Unit
A complete 23” Distribution unit designed for: 24, 30, 48, 60, 110,
125 and 220 VDC with the following features:
Eltek HQ: Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway. Phone: +47 32 20 32 00 - Eltek © 2015 – www.eltek.com
24V/30V Systems
Applications
The 24V/30V rectifiers are suitable for parallel operation with all
types of stationary batteries, including lead acid or nickel
cadmium types, and can also operate without batteries.
Typical applications:
- Alarm systems
- Diesel start float application
- PABX systems
- Emergency lightning
- Industrial control systems
48V/60V Systems
Applications
The 48V rectifiers are deigned to meet international telecom
standards for safe and reliable operation in telecom
environments or any industrial communication system.
Typical applications:
110V/125V Systems
Applications
The 110V rectifiers are designed for demanding environments
and comply with IEC61000-6.5 (Immunity Power Stations and
Substations) for reliable operation in critical applications.
Typical applications:
Eltek HQ: Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway. Phone: +47 32 20 32 00 - Eltek © 2015 – www.eltek.com
220V Systems
Applications
The 220V rectifiers are designed for demanding environments
and also comply with IEC61000-6.5 (Immunity Power Stations
and Substations) for reliable operation in critical applications.
Typical applications:
INPUT DATA
Voltage (range) 115 - 400 VAC (∆) or (Y), Derating <185VAC, 45-66Hz
Input protection MCBs and SPD ( OVP Class 2)
Rectifier protection Individual fuse in rectifier modules
Connection Terminals 10mm2
OUTPUT DATA
Voltage (nominal) 24VDC, 30VDC, 48VDC, 60VDC, 110VDC, 125VDC &220VDC
Power (maximum) @ nominal input 16kW
Current (maximum) @ nominal input See previous page or applicable Flatpack2 rectifier datasheet
Protected battery output 1 x 2 pole NH00/NH1 Fuses (63 - 250A) or MCCB Circuit Breaker(63 - 250A) with or
without fuse trip alarm
Protected load outputs 1-24 x 2 pole (6 - 40A) MCB:s with or without fuse trip alarm
Integrated battery shunt 100/300A
Load connection Terminal, max 16mm2
Output Protection in rectifiers Blocking OR-ing FET or fuse, Short circuit proof & High temperature protection
CONTROL AND MONITORING
Monitoring Unit Smartpack2 or UPC4
Local Operation Display and keys, WEB interface via standard browser using WebPower
Remote Operation WebPower (WEB Interface, SNMP protocol and email)
Alarm Relays (Connection: clamp ≤ 1.5 mm ) 2
6 x Potential free change over contacts (NO, NC, C) [Max 75V/2A/60W]
Optional; 3 x Potential free change over contacts (NO, NC, C) [Max 430VDC/0,1A]
Inputs 6 x Configurable (digital, analog max 75V) and 3 temperature
Current measurements Rectifier current and, if battery shunt is used, battery current and load current
Alarms Low & high output voltage alarms (Minor and major levels), Earth fault alarm,
Temperature alarm, Mains outage alarm, Battery remaining capacity/low quality
alarms, Battery/load breaker tripped alarm and much more
OTHER SPECIFICATIONS
Isolation 3.0 kVAC - input to output
1.5 kVAC - input to earth
0.5 kVDC - output to earth1)
Operating temperature -40 to +45°C (-40 to +113°F), humidity 5 - 95% RH non-condensing
Output power de-rates at high temperature, see datasheet for applicable rectifier
Storage temperature -40 to +85°C (-40 to +185°F), humidity 0 - 99% RH non-condensing
Dimensions[WxHxD] 600 x 1800/2000 x 600mm
DESIGN STANDARDS
Electrical safety UL 60950-1-3rd edition, EN 60950-1-3rd edition
EMC ETSI EN 300 386 V.1.4.1
EN 61000-6-1 / -2 / -3 / -4 / -5
Environment ETSI EN 300 019, ETSI EN 300 132 - 2
1) 1.5kVAC for IBB with 110V & 220V Flatpack2 rectifiers
Eltek HQ: Gråterudveien 8, PB 2340 Strømsø, 3003 Drammen, Norway. Phone: +47 32 20 32 00 - Eltek © 2015 – www.eltek.com