STULZ Quick Select Guide 1113 en

The document discusses CyberCool2, an upcoming cooling solution. It provides information on different types of cooling systems such as air-cooled, water-cooled, chilled-water. It also discusses the product range, available options, and specifications for the CyberAir 3 and MiniSpace EC units.

Uploaded by

hansi1
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
777 views

STULZ Quick Select Guide 1113 en

The document discusses CyberCool2, an upcoming cooling solution. It provides information on different types of cooling systems such as air-cooled, water-cooled, chilled-water. It also discusses the product range, available options, and specifications for the CyberAir 3 and MiniSpace EC units.

Uploaded by

hansi1
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 16

Coming soon: CyberCool2

QUICK SELECT
The next big cooling solution
GUIDE
cooling
solutions

air-cooled (a) water-cooled (G) chilled-water (CW) row based


›D
 irect expansion type compressor ›D
 irect expansion type compressor › Increased energy efficiency levels (a, G, GE, CW)
cooling system with heat rejection cooling system with heat rejection can be achieved via Chilled Water › Row based cooling with
via air cooled condensers. via cooling tower or dry coolers. Fan Management or Raised Floor air-cooled, water-cooled, chilled
Pressure Management. water or free cooling type systems.

air-cooled & Water-cooled & Dual chilled-water Dynamic free


Chilled-water (aCW) Chilled-water (GCW) (CW2) cooling/ dfc (ge)
›D
 ual Fluid Hybrid DX ›D
 ual Fluid Hybrid DX › Dual coil Chilled Water type › Dynamic Free Cooling system.
(air cooled) + Chilled Water type (air cooled) + Chilled Water type system. For superior redundancy Water cooled with optimised free
system for redundancy. system for redundancy. or Chilled Water Dynamic Free cooling system using dynamically
Cooling. floating condenser water
temperature.
NOMENCLATURE

PRODUCT RANGE
› ➢AS: CyberAir Standard (EC Direct Drive Fans)
› ➢AM: CyberAir with Movable Coil (EC Direct Drive Fans)
› ➢AL: CyberAir Low Noise (EC Direct Drive Fans)
› ➢CC: MiniSpace (EC Direct Drive Fans)

AIR FLOW DIRECTION


› ➢D: Downflow
› ➢U: Upflow

a s d 45 2 a COOLING METHOD
› ➢A: Air-Cooled
› ➢ACW: Air-Cooled and Chilled Water
› ➢CW: Chilled Water
› ➢CW2: Dual Chilled Water
› ➢G: Water-Cooled
› ➢GCW: Water-Cooled and Chilled Water
› ➢GE: Dynamic Free Cooling (DFC)
› ➢AS: Air-Cooled and EC Compressor
› ➢GS: Water-Cooled and EC Compressor
› ➢GES: DFC and EC Compressor

NUMBER OF REFRIGERATION CIRCUITS


› ➢0 (i.e. Chilled Water), 1, 2

Nominal kW OUTPUT OF UNIT


› ➢4 to 200

AVAILABLE OPTIONS

› ➢Dual Fluid (ACW, GCW, CW2)


› ➢Free Cooling (GE)
› ➢Raised Floor Stands➢
› ➢Dampers
› ➢Flexible Duct Connections
› ➢High Efficiency Filter (F5/F6)
› ➢Discharge Plenums➢
› ➢Return Air Plenums
› ➢Sound Attenuators
› ➢Refrigerant R407C / R134A / R410A
› ➢Phase Monitoring
› ➢Hot Gas Reheat
› ➢Dual or Triple Power Supplies with
Automatic or Manual Changeover
› ➢Capacity Control
› ➢Other options available on request

www.stulz.com.au
cyberair 3 &
minispace ec WITH
standard scroll COMPRESSORS

direct expansion (DX):


air & water cooled
(ec direct drive fans)

)5
ER
cooling capacity1

(kW
r) 5
AT

/h
TS

S) 3 W

heat
S) 2

(kg
m)
UI

x H NS
(L/ ER
)
(kW

)4
(L/

(m
RC

W ENS

fier
x D SIO

(kg
.

re
)
no

(kW
CI

W
ble

electric
W MEN

HT

(A) 6
FLO ND

midi
FLO
del

. OF

tal

sensi

IG
CO
mo

fla
DI
aiR

hu
WE
no

to

CCD/U51A/G 1 6.4 6.4 694 0.33 600 x 600 x 1850 150 2 2 14.4
CCD/U71A/G 1 7.5 7.5 694 0.39 600 x 600 x 1850 150 2 2 15.3
minispace

CCD/U91A/G 1 9.1 9.1 694 0.50 600 x 600 x 1850 150 2 2 17.0
CCD/U131A/G 1 11.9 11.9 972 0.64 600 x 600 x 1850 150 2 2 18.1
CCD/U181A/G 1 18.1 18.1 1,944 0.94 1000 x 810 x 1850 286 4 6 22.8
CCD/U221A/G 1 21.9 21.9 1,944 1.11 1000 x 810 x 1850 286 4 6 26.0
CCD/U251A/G 1 25.7 25.7 2,222 1.11 1000 x 810 x 1850 289 4 6 27.6

ASD/U191A/G 1 18.1 18.1 1,639 0.94 950 x 890 x 1980 334 8 9 37.4
ASD/U221A/G 1 20.6 20.6 1,806 1.08 950 x 890 x 1980 335 8 9 38.6
ASD/U251A/G 1 26.3 26.3 1,944 1.39 950 x 890 x 1980 355 8 9 42.2
ASD/U281A/G 1 29.0 26.6 1,944 1.53 950 x 890 x 1980 360 8 9 43.7
ASD/U321A/G 1 31.5 31.5 2,639 1.64 1400 x 890 x 1980 475 8 9 43.7
ASD/U371A/G 1 35.7 35.7 2,917 1.86 1400 x 890 x 1980 475 8 9 46.2
ASD/U391A/G 1 39.2 39.2 3,000 2.06 1400 x 890 x 1980 476 8 9 47.9
ASD/U412A/G 2 40.0 40.0 3,194 2.08 1750 x 890 x 1980 588 8 9 53.3
ASD/U421A/G 1 40.9 40.9 3,194 2.11 1750 x 890 x 1980 560 8 9 52.4
cyberair

ASD/U461A/G 1 46.0 46.0 3,889 2.39 1750 x 890 x 1980 562 8 9 55.5
ASD/U462A/G 2 45.3 45.3 3,750 2.39 1750 x 890 x 1980 589 8 9 57.3
ASD/U522A/G 2 52.3 52.3 4,028 2.75 1750 x 890 x 1980 623 8 9 60.5
ASD/U541A/G 1 51.0 51.0 4,167 2.69 1750 x 890 x 1980 563 8 9 61.7
ASD/U562A/G 2 56.0 56.0 4,583 2.92 2200 x 890 x 1980 745 8 9 60.5
ASD/U622A/G 2 62.5 62.5 5,278 3.25 2200 x 890 x 1980 747 8 9 63.5
ASD/U712A/G 2 70.1 70.1 5,556 3.67 2200 x 890 x 1980 748 8 9 68.5
ASD/U812A/G 2 81.4 81.4 5,972 4.22 2550 x 890 x 1980 853 8 9 76.3
ASD/U872A/G 2 88.9 88.9 6,389 4.69 2550 x 890 x 1980 855 8 9 82.5
ASD/U1072A/G 2 99.4 93.8 6,806 5.33 2550 x 890 x 1980 857 8 9 94.9

1
 ll unit cooling capacities are gross and selected at return air conditions 24°C DB, 45%RH
A
2
Airflows are at nominal ESP ratings of 20Pa for downflow units and 50Pa for upflow units; higher external static pressures available
3
Condenser water temperatures for the water cooled DX type units (G) are 29.5ºC and 35.0ºC
4
Unit weights are valid for water-cooled units
5
Heating and humidification capacities are a guide only; other options are available upon request
6
FLA is not inclusive of external air cooled condensers. Please contact your local Stulz office for more information
cyberair 3
WITH HIGH EFFICIENCY
EC COMPRESSORS

direct expansion (DX):


air & water cooled
(EC direct drive fans)

)5
ER
cooling capacity1

(kW
r) 5
AT

/h
TS

S) 3 W

heat
S) 2

(kg
m)
UI

x H NS
(L/ ER
)
(kW

)4
(L/

(m
RC

W ENS

fier
x D SIO

(kg
.

re
)
no

(kW
CI

W
ble

electric
W MEN

HT

(A) 6
FLO D

midi
FLO
del

. OF

N
tal

sensi

IG
CO
mo

fla
DI
aiR

hu
WE
no

to

ASD/U321AS/GS 1 30.5 30.5 2,222 1.69 1400 x 890 x 1980 481 8 9 56.4
ASD/U371AS/GS 1 35.5 35.5 2,778 1.94 1400 x 890 1980 481 8 9 56.4
ASD/U391AS/GS 1 38.4 38.4 3,056 2.22 1400 x 890 x 1980 481 8 9 56.4
ASD/U412AS/GS 2 41.4 41.4 3,056 2.27 1750 x 890 x 1980 595 8 9 71.6

cYBERAIR
ASD/U462AS/GS 2 46.3 45.1 3,333 2.53 1750 x 890 x 1980 596 8 9 73.9
ASD/U522AS/GS 2 51.2 51.2 3,889 2.81 1750 x 890 x 1980 630 8 9 74.7
ASD/U562AS/GS 2 54.6 54.6 4,167 3.03 2200 x 890 x 1980 754 8 9 74.7
ASD/U622AS/GS 2 61.3 61.3 4,722 3.39 2200 x 890 x 1980 755 8 9 75.9
ASD/U712AS/GS 2 69.6 69.6 5,556 3.81 2200 x 890 x 1980 756 8 9 79.4
ASD/U812AS/GS 2 78.2 78.2 5,556 4.25 2550 x 890 x 1980 860 8 9 86.2

1
 ll unit cooling capacities are gross and selected at return air conditions 24°C DB, 45%RH
A
2
Airflows are at nominal ESP ratings of 20Pa for downflow units and 50Pa for upflow units; higher external static pressures available
3
Condenser water temperatures for the water cooled DX type units (G) are 29.5ºC and 35.0ºC
4
Unit weights are valid for water-cooled units
5
Heating and humidification capacities are a guide only; other options are available upon request
6
FLA is not inclusive of external air cooled condensers. Please contact your local Stulz office for more information
www.stulz.com.au
cyberair 3 &
minispace ec

chilled water
(ec direct drive fans)

)4
cooling capacity1

(kW
)4
/h
S) 3 ER
S) 2

heat
(kg
m)
)

(L/ AT

x H NS
(kW

(L/
(ºC ir

(m
W DW

)
)

x D SIO

fier
(kg
.

yA

re
(kW
no

W
ble

electric
FLO
ppl

(A) 6
FLO ILLE

W MEN

HT

midi
Temps
del

tal

sensi

IG
Su

CH
aiR
to

fla
mo

DI

hu
WE
CCD/U 100 CW 11.2 11.2 13 555 0.53 600 x 600 x 1850 142 2 2 10.9
minispace

CCD/U 150 CW 18.9 18.9 15 1,000 0.92 600 x 600 x 1850 142 2 2 10.9
CCD/U 190 CW 30.3 30.3 14 1,528 1.44 1000 x 810 x 1850 255 4 6 13.8
CCD/U 250 CW 43.5 43.5 14 2,222 2.08 1000 x 810 x 1850 255 4 6 13.8

ASD/U 320 CW 35.3 35.3 15 1,944 1.69 950 x 890 x 1980 282 8 9 18.6
ASD/U 420 CW 44.2 44.2 15 2,500 2.11 950 x 890 x 1980 282 8 9 18.6
ASD/U 550 CW 54.2 54.2 14 2,778 2.61 1400 x 890 x 1980 351 8 9 18.6
ASD/U 650 CW 68.4 68.4 14 3,611 3.28 1400 x 890 x 1980 351 8 9 18.6
single circuit

ASD/U 800 CW 85.7 85.7 14 4,444 4.11 1750 x 890 x 1980 514 8 9 23.1
ASD/U 950 CW 100.6 100.6 14 5,278 4.83 1750 x 890 x 1980 514 8 9 23.1
ASD/U 1000 CW 103.0 103.0 14 5,278 4.94 2200 x 890 x 1980 605 8 9 23.1
ASD/U 1180 CW 117.9 117.9 14 6,111 5.67 2200 x 890 x 1980 605 8 9 23.1
ASD/U 1250 CW 130.3 130.3 14 6,667 6.25 2550 x 890 x 1980 721 8 9 27.6
ASD/U 1550 CW 155.1 155.1 14 8,056 7.44 2550 x 890 x 1980 721 8 9 27.6
ASD 1800 CW 181.1 181.1 14 9,167 8.69 3110 x 890 x 1980 870 8 9 32.1
ASD 2100 CW 210.8 210.8 14 10,833 10.11 3110 x 890 x 1980 870 8 9 32.1
cyberair

ASD 390 CWE/U 59.3 59.3 16 3,611 2.83 950 x 890 x 2495 365 8 9 18.6
ASD 600 CWE/U 73.5 73.5 14 3,750 3.53 1400 x 890 x 2495 482 8 9 18.6
ASD 1050 CWE/U 123.0 123.0 16 7,222 5.89 1750 x 890 x 2495 559 8 9 23.1
cwe/u

ASD 1350 CWE/U 146.1 146.1 14 7,500 7.00 2200 x 890 x 2495 692 8 9 23.1
ASD 1700 CWE/U 191.4 191.4 15 10,278 9.17 2550 x 890 x 2495 863 8 9 27.6
ASD 2050 CWE/U 254.2 254.2 15 14,167 12.19 3110 x 890 x 2495 1,055 8 9 32.1
ASD 2400 CWE/U 266.8 266.8 15 14,444 12.80 3110 x 890 x 2495 1,133 8 9 32.1

ASD/U 270 CW2 40.3 40.3 17 2,639 1.94 950 x 890 x 2495 293 8 9 18.6
dual circuit

ASD/U 510 CW2 53.9 53.9 16 3,194 2.58 1400 x 890 x 2495 380 8 9 18.6
ASD/U 670 CW2 83.9 83.9 17 5,389 4.03 1750 x 890 x 2495 461 8 9 23.1
ASD/U 810 CW2 100.6 100.6 17 6,306 4.83 2200 x 890 x 2495 553 8 9 23.1
ASD/U 1070 CW2 134.7 134.7 17 8,528 6.47 2550 x 890 x 2495 644 8 9 27.6
cyberair 3 &
minispace ec

chilled water
(ec direct drive fans)

CyberAir CWE/CWU

CWU Version
Fan Unit installed under the raised floor
(Power input of fans is up to 30% less
than when installed on the raised floor)

CWE Version
Fan Base installed on raised floor when
raised floor height is less than 525mm

1
 ll unit cooling capacities are gross and selected at return air conditions 30°C DB, 30%RH, chilled water 10ºC in and 15ºC out
A
2
Airflows are at nominal ESP ratings of 20Pa for downflow units and 50Pa for upflow units; higher external static pressures available
3
The annotation CWE/CWU denotes a high performance chilled water unit, representing a unit which is comprised of two separate sections (a coil unit and a
fan base unit) that result in market leading cooling capacities for its footprint (refer to images above)
4
Heating and humidification capacities are a guide only; other options are available upon request

www.stulz.com.au
AIR MODULATOR
INTELLIGENT RAISED FLOOR TILES
& BOOSTERS

Providing automated air flow management in low and variable load


applications. Ability to cool hot spots and high density areas
STULZ AIRMODULATOR

AIRFLOW (M3/H)
4650
4200
3550
2840
2030

20 40 60 80 100

RAISED FLOOR VOID OVERPRESSURE (PA)

STULZ AirModulator Key benefits


› ➢Suitable for raised floor installation in data centres with homogenous pressure conditions
› Suitable for cold aisle containment
› Temperature measurement via two sensors
› Optional pressure control (PTM)
› Precisely designed for standard raised floor panels
› Easy installation, operational in minimal time

TECHNICAL DATA APPLICATION LIMITS

Model No. SAM Operating Temp 10-55±5ºC


Torque range 0-8 Nm Humidity Range 0-90% RH
Current consumption 1.5 A Nominal Voltage 230 VAC
Power consumption 6.5VA Frequency 50/60 Hz
Dimensions 600 x 230 x 600 UDL on the grid 2780 kg/m2
Weight 16 kg Point load 250 kg
AIR MODULATOR
INTELLIGENT RAISED FLOOR TILES
& BOOSTERS

STULZ AIRBOOSTER STULZ AIRBOOSTER PRO

STULZ AirBooster & AirBooster Pro key benefits


› ➢Suitable for data centres with raised floor
› ➢Suited to cooling localised high density zones
› ➢Air flow up to 2650m3/h (2500m3/h for AirBooster Pro)
› ➢EC Fan for precise air flow supply
› ➢Temperature measurement via two sensors
› ➢Optional pressure control (PTM)
› ➢Precisely designed for standard raised floor panels
› ➢High level interface-modbus connection

FAN EC

Number of fans per unit 1


Maximum air flow 1
2650m3/h
Distributed load 1000 kg/m2
Dimensions (W x H x D)2 600 x 210 x 600mm
Sensors 2

1
Maximum air flow is 2650m3/h for AirBooster and 2500m3/h for AirBooster Pro
2
Dimensions are 600 x 210 x 600mm for AirBooster and 600 x 202 x 600mm for AirBooster Pro

www.stulz.com.au
cyber ROW ROW BASED COOLING – DX, condenser
water, chilled water & free cooling

Four air discharge configurations

Left right

both sides front

STANDARD INCLUSIONS/OPTIONS

› DC Brushless Inverter Driven Compressor, allowing continuous capacity control from 30%-100%
› The choice of four airflow configurations
› ➢Refrigerant R410A
› ➢3 x EC fans with proportional control
› ➢Microprocessor Controller
› ➢Maintenance access from front and back
› ➢Dual Power Supply
› ➢Humidification
› ➢Other options available on request
cyber ROW ROW BASED COOLING – DX, condenser
water, chilled water & free cooling

cooling capacity1

ER
AT

ER
S) 3 W
S) 2

m)
)

AT

x H NS
(kW

(L/ ER
(L/
(ºC ir

(m
W DW

)
)

W ENS
)

x D SIO

(kg
.

yA
(kW
no

W
ble

FLO
ppl

(A) 6
FLO ILLE

W MEN

HT
FLO ND
Temps
del

tal

sensi

IG
Su

CO

CH
aiR
to

fla
mo

DI

WE
CRS251AS2/GS2/GES2 24.0 24.0 20 1,333 1.11 - 400 x 1175 x 1950 270 20.1

cYBERROW
CRS361AS /GS /GES
2 2 2
36.4 36.4 21 2,139 1.67 - 600 x 1175 x 1950 330 28.3
CRS210CW 20.9 20.9 21 1 ,250 - 1.00 300 x 1175 x 1950 170 -
CRS320CW 32.2 30.3 21 1,778 - 1.56 400 x 1175 x 1950 197 4.1
CRS560CW 56.0 54.8 20 3,111 - 2.69 600 x 1175 x 1950 254 6.3

1
At nominal conditions 35°C DB, 30%RH, condensing temperature 45ºC (air-cooled only)
2
Free cooling models

NOMENCLATURE (MODEL No.)

Products Range

Airflow Discharge
Output of Unit in kW

Number of Refrigeration Circuits

COOLING SYSTEM
› ➢AS: Air-Cooled & EC Compressor
› ➢GS: Water-Cooled & EC Compressor
C R S 25 1 AS › ➢GES: Glycol-Cooled & Free Cooling
› ➢CW: Chilled Water Cooling (Directly)

AS, GS, GES, CW


0,1

25, 36 (CW: 21, 32, 56)

S: Sideflow

CR: CyberRow

www.stulz.com.au
STULZ DATA CENTRE
OPTIMISATION
PLATFORM

Assess Instrument Optimise Control Sustain

Stulz Australia is focused on the most critical


components of Data Centre Infrastructure
Management (DCIM): power and cooling
infrastructure via mesh-wireless sensing
technology. The Data Centre Optimisation
Platform saves up to 50% of cooling
energy while delivering tangible ROI for
our customers.

Prior to wireless sensing technology, deployment of high


density sensing within the Data Centre was simply not
cost effective; not only from a physical infrastructure
perspective but also the solution lacked the versatility
and adaptability to easily respond to frequent changes
in load profile and room configuration.

Mesh wireless technology puts an end to those problems. It is a self-discovery, self-healing network that adheres to the Safe,
Affordable, Flexible and Easy (SAFE) principles of environmental monitoring. Any device within the mesh wireless network
(sensor or gateway) can communicate with any other device on the network. As a result, increasing the number of sensors
within the network increases the resiliency and redundancy of the system while offering superior data accuracy.

As well as ease of deployment and network management, the non-IP addressable system offers security against passive and
active IP-based attacks. Low power transmission, low duty cycle and channel adaptation are just a few of the design features
which allow the Stulz environmental monitoring system to co-exist with other wireless devices within the Data Centre.

WIRELESS SENSOR NETWORK (ONLY TWO IP ADDRESSES)


STULZ DATA CENTRE
OPTIMISATION LIVEIMAGING™ & ACTIVE CONTROL™
PLATFORM

LIVEIMAGING™

LiveImaging™ provides maps and movies detailing


the environmental and power conditions of
the data centre. They include temperature,
humidity, pressure differential and rack power
using real-time data at multiple levels of your data
centre. Customers can literally see hot spots and
direct airflow to avoid overheating or air mixing.

Real-time visualisations can not only be used by the facilities team


for day-to-day diagnostics and planning but, more importantly, for
real-time manual optimisation of cooling infrastructure to ensure
your Data Centre is operating at its most energy efficient.

ACTIVE CONTROL™

Active Control™ has a proven track record of achieving tangible ROI for customers, with payback timeframes consistently
less than 3 years and unprecedented energy savings. The Stulz Power Suite optimises power, enhances ROI, and enables
customers to stay within their current data centre footprint.

Step 1: Step 2: Step 3:


Baseline Performance AIRFLOW OPTIMISATION ACTIVECONTROL™

Including environmental conditions, Using industry best practice, Stulz Allows your cooling infrastructure to
IT load, cooling capacity and Professional Services use real-time intelligently evolve with changes in
mechanical infrastructure energy data and a metrics based approach room load, controlling to maintain
consumption. to airflow management and raised acceptable server inlet conditions
floor remediation. within ASHRAE standards while
The end result is savings on energy minimising fan power consumption.
and cost and a measurable ROI.

www.stulz.com.au
free cOoling Free cooling is the principle of using
favourable ambient air conditions to
systems cool your critical space

Direct Free Cooling draws outside air directly into the


critical space to achieve lowest power usage effectiveness (PUE).

mixing box
(with bag filters and dampers)
hot exhaust air

cold outside air

PCUs

underfloor plenum

Direct Free Cooling


with optional Movable Coil (AMD)

In free cooling mode, the heat exchanger automatically moves away from
the supply air path to allow unimpeded flow of filtered ambient air into
critical space, thus reducing the pressure drop and lowering fan energy
consumption to further improve PUE.

Direct Free Cooling is available on both the CyberAir range (DFC2, Eco-cool2) and
MiniSpace range (Eco-cool).
free cOoling Free cooling is the principle of using
favourable ambient air conditions to
systems cool your critical space

Indirect Free Cooling monitors external ambient air


conditions and internal loads to select the most economical mode
of operation (DX, Mixed, Extended Free Cooling or Free Cooling) to
DRYCOOLER
achieve excellent power usage effectiveness (PUE).

Cyber Air DX with Free Cooling Coil

CHILLER DRYCOOLER

Cyber Air CW2 with Free Cooling Coil

DRYCOOLER

Cyber rOW with Free Cooling Coil

Indirect Free Cooling is available on the CyberAir DX range


(GE/DFC), CyberRow DX range (GE/DFC), Indoor Data Chiller range
(GE/DFC), and CyberAir Dual Coil Chilled Water Units (CW2).

www.stulz.com.au
STZ0066
Stulz offices

NSW/ACT
Phone › +61 2 9674 4700
Fax › +61 2 9674 6722
Email › [email protected]

QLD/NT
Phone › +61 7 3890 5755
Fax › +61 7 3890 3799
Email › [email protected]

VIC/TAS/SA
Phone › +61 3 9562 6333
Fax › +61 3 9562 6444
Email › [email protected]

Wa
Phone › +61 8 9202 6846
Fax › +61 8 9202 6801
Email › [email protected]

NZ
Phone › +64 9 360 3232
Fax › +64 9 360 2180
Email › [email protected]

DISCLAIMER
© No part of this document may be copied without express written permission from STULZ Australia Pty. Ltd.
The information presented in this document is of a general nature and while every precaution has been taken to
ensure accuracy and completeness of information, STULZ Australia Pty. Ltd. assumes no responsibility and disclaims
all liability for any damages resulting from the use of information contained herein or any errors of omissions. STULZ
Australia Pty. Ltd. reserves the right to change model specifications and performance without any prior notification.
For confirmation of any data or information presented in this document please contact your local STULZ sales office.

www.stulz.com.au