Loft Conversion 1
Loft Conversion 1
STAAC
1A FAIRLIGHT ROAD
EASTBOURNE
EAST SUSSEX
BN22 7NY
Phone: 01323325354
Email: [email protected]
Page 1
Domestic clients
The domestic client is to appoint a principal designer and a principal contractor when there is more
than one contractor, if not your duties will automatically transferred to the contractor or principal
contractor.
The designer can take on the duties, provided there is a written agreement between you and the
designer to do so.
The Health and Safety Executive is to be notified as soon as possible before construction work
starts if the works:
(a) Last longer than 30 working days and has more than 20 workers working simultaneously at any
point in the project.
Or:
(b) Exceeds 500 person days.
PLANNING NOTE
A loft conversion for your house is considered to be permitted development and not requiring an
application for planning permission, subject to the following limits and conditions:
A volume allowance of 40 cubic metres additional roof space for terraced houses*
A volume allowance of 50 cubic metres additional roof space for detached and semi-detached
houses*
No extension beyond the plane of the existing roof slope of the principal elevation that fronts the
highway
No extension to be higher than the highest part of the roof
THERMAL BRIDGING
Care shall be taken to limit the occurrence of thermal bridging in the insulation layers caused by
gaps within the thermal element, (i.e. around windows and door openings).
marking.
EXISTING STRUCTURE
Existing structure including foundations, floor, beams, walls, roof and lintels are to be exposed and
checked for adequacy prior to commencement of work and as required by the Building Control
Officer.
DORMER CONSTRUCTION
To achieve minimum U Value of 0.28W/m²K
Structure to engineer's details and calculations. Tiles hung vertically on 25 x 38mm preservative
treated battens (vertical counter battens to be provided to ensure vented and drained cavity if
required) fixed to breathable membrane (having a vapour resistance of not more than 0.6 MNs/g)
and 12mm thick W.B.P external quality plywood sheathing (or other approved). Ply fixed to treated
timber frame studs constructed using: 100mm x 50mm head and sole plates and vertical studs
(with noggins) at 400mm centres or to structural engineer's details and calculations. Insulation to
be 100mm Celotex GA4000 between studs plus 37.5mm Celotex PL4000 over. Provide a vapour
control layer fixed to internal face of insulation and finish with 3mm skim coat of finishing plaster.
All junctions to have water tight construction, seal all perimeter joints with tape internally and with
silicon sealant externally. Dormer walls built off existing masonry walls to have galvanised mild
steel straps placed at 900 centres. Dormer cheeks within 1m of the boundary to be lined externally
with 12.5mm Supalux and 12.5mm Gyproc FireLine board internally to achieve 1/2 hour fire
resistance from both sides.
Fig. 5 Upgrading cavity party wall (cold adjoining space) (Not to Scale)
Fig. 6 Upgrading existing single skin party wall (cold adjoining space) (Not to Scale)
NEW STAIRCASE
Dimensions to be checked and measured on site prior to fabrication of stairs. Timber stairs to
comply with BS585 and with Part K of the Building Regulations. Max rise 220mm, min going
220mm. Two risers plus one going should be between 550 and 700mm. Tapered treads to have
going in centre of tread at least the same as the going on the straight. Min 50mm going of tapered
treads measured at narrow end. Pitch not to exceed 42 degrees. The width and length of every
landing should be at least as great as the smallest width of the flight. Doors which swing across a
landing at the bottom of a flight should leave a clear space of at least 400mm across the full width
of the flight. Min 2.0m headroom measured vertically above pitch line of stairs and landings.
However, if there is not enough space to achieve this height the headroom will be satisfactory if the
height measured at the centre of the stair width is l.9 m reducing to 1.8m at one side of the stair.
Handrail on staircase to be 900mm above the pitchline, handrail to be at least one side if stairs are
less than 1m wide and on both sides if they are wider. Ensure a clear width between handrails of
minimum 600mm. Balustrading designed to be unclimbable and should contain no space through
which a 100mm sphere could pass. Allow for all structure as designed by a Structural Engineer.
ELECTRICAL WORKS
All electrical work required to meet the requirements of Part P (electrical safety) must be designed,
installed, inspected and tested by a competent person registered under a competent person self
certification scheme such as BRE certification Ltd, BSI, NICEIC Certification Services or Zurich Ltd.
An appropriate BS7671 Electrical Installation Certificate is to be issued for the work by a person
competent to do so. A copy of a certificate will be given to the Council.
INTERNAL LIGHTING
Install low energy light fittings that only take lamps having a luminous efficiency greater than 45
lumens per circuit watt and a total output greater than 400 lamp lumens. Not less than three
energy efficient light fittings per four of all the light fittings in the main dwelling spaces to comply
with Part L of the current Building Regulations.
HEATING
Extend all heating and hot water services from existing and provide new TVRs to radiators. Heating
system to be designed, installed, tested and fully certified by a GAS SAFE registered specialist. All
work to be in accordance with the Local Water Authorities by laws, Gas safety requirements and
IEEE regulations.
EXTRACT TO BATHROOM
Bathroom to have mechanical vent ducted to external air to provide min 15 litres / sec extraction.
Vent to be connected to light switch and to have 15 minute over run if no window in room. Internal
doors should be provided with a 10mm gap below the door to aid air circulation. Ventilation
provision in accordance with the Domestic Ventilation Compliance Guide. Intermittent extract fans
to BS EN 13141-4. All fixed mechanical ventilation systems, where they can be tested and adjusted,
shall be commissioned and a commissioning notice given to the Building Control Body.
EXTRACT TO W/C
W/C to have mechanical ventilation ducted to external air with an extract rating of 15l/s operated
via the light switch. Vent to have a 15min overrun if no window in room. Internal doors should be
provided with a 10mm gap below the door to aid air circulation. Ventilation provision in accordance
with the Domestic Ventilation Compliance Guide. Intermittent extract fans to BS EN 13141-4. All
fixed mechanical ventilation systems, where they can be tested and adjusted, shall be
commissioned and a commissioning notice given to the Building Control Body.
RAINWATER DRAINAGE
New rainwater goods to be new 110mm upvc half round gutters taken to and connected into 68mm
dia upvc downpipes
Size of wastes pipes and max length of branch connections (if max length is exceeded then anti
vacuum traps to be used)
Wash basin - 1.7m for 32mm pipe 4m for 40mm pipe
Bath/shower - 3m for 40mm pipe 4m for 50mm pipe
W/c - 6m for 100mm pipe for single WC
All branch pipes to connect to 110mm soil and vent pipe terminating min 900mm above any
openings within 3m.
Or to 110mm upvc soil pipe with accessible internal air admittance valve complying with BS EN
12380, placed at a height so that the outlet is above the trap of the highest fitting.
Waste pipes not to connect within 200mm of the WC connection. Supply hot and cold water to all
fittings as appropriate.
ROOF LIGHTS
Min U-value of 1.6 W/m²K.
Roof-lights to be double glazed with 16mm argon gap and soft low-E glass. Window Energy Rating
to be Band C or better. Roof lights to be fitted in accordance with manufactures instructions with
rafters doubled up to sides and suitable flashings etc.
SAFETY GLAZING
All glazing in critical locations to be toughened or laminated safety glass to BS 6206, BS EN 14179
or BS EN ISO 12543-1:2011 and Part K (Part N in Wales) of the current building regulations. i.e.
within 1500mm above floor level in doors and side panels within 300mm of door opening and within
800mm above floor level in windows.
NEW WINDOWS
New windows to be double glazed with 16mm argon gap and soft coat low-E glass. Window Energy
Rating to be Band C or better and to achieve U-value of 1.6 W/m²K.
GLASS BALUSTRADING
All balcony balustrades to be min 1.1m height. Balustrades to be in toughened glass in accordance
with Part K (Part N in Wales) of the Building Regulations and designed to resist the horizontal force
given in BS 6180:2011. No openings in any balustrading should allow the passage of a 100mm
sphere and children should not readily be able to climb the guarding.
TRADITIONAL BALUSTRADES
Provide balustrades to balcony min 1100mm in height and capable of resisting at least the
horizontal force given in BS 6180:2011. No openings in any balustrading should allow the passage
of a 100mm sphere and children should not readily be able to climb the guarding.