Calculation According To en 13384-1

This document provides a calculation and sizing for a chimney system according to EN 13384-1. It summarizes data for a natural gas boiler including heat output, efficiency, and flue gas temperatures. It then calculates pressure and temperature requirements and shows the chimney system fulfills these. The connecting flue pipe and chimney are specified as Dinak SW systems with 350mm inner diameter designed to T600 N1 W V2 G. Average velocities, temperatures and sizing are shown to meet requirements at nominal and minimum operating conditions.

Uploaded by

SADJI Rachid
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
2K views

Calculation According To en 13384-1

This document provides a calculation and sizing for a chimney system according to EN 13384-1. It summarizes data for a natural gas boiler including heat output, efficiency, and flue gas temperatures. It then calculates pressure and temperature requirements and shows the chimney system fulfills these. The connecting flue pipe and chimney are specified as Dinak SW systems with 350mm inner diameter designed to T600 N1 W V2 G. Average velocities, temperatures and sizing are shown to meet requirements at nominal and minimum operating conditions.

Uploaded by

SADJI Rachid
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Customer: RS

Project: GST
No. Document: 001
Date: 17/09/2017

CALCULATION ACCORDING TO EN 13384-1, CHIMNEY WITH NEGATIVE


PRESSURE
HEATING APPLIANCE DATA

Fuel: Natural gas


Appliance type: Over pressured boiler
Condensation: NO
Working conditions: Modulating
Nominal Minimum
Heat output: kW 750 250
Efficiency: % 90 90
Flue gas temperature: ºC 180 120
Minimum draught: Pa 0 0
Mass flow: g/s 348.92 116.31

ENVIRONMENT DATA

Altitude: m 50
Maximum ambient
ºC 15
temperature:
Minimum temperature at the
ºC 0
chimney outlet:
Inside
Installation
building
Wind velocity pressure: NO

CONNECTING FLUE PIPE DATA

Total length (m): 1


Route:
Total height (m): 1
Chimney system: Dinak SW

CHIMNEY DATA

Total length (m): 5


Route: 5 m in the boiler room
Total height (m): 5
Chimney system: Dinak SW
Connection: 90º Tee: 1
Chimney outlet: Open terminal
Elements total zeta
1.2
value:

Calculation according to EN 13384-1 Page 1 of 3


Customer: RS
Project: GST
No. Document: 001
Date: 17/09/2017
COMBUSTION AIR SUPPLY DATA

Boiler room ventilation: Ventilated


Pressure losses (Pa): 0

CALCULATIONS AND CHECKINGS

PRESSURE REQUIREMENTS
Flow safety coefficient SE 1.2
Nominal Minimum
+ Thermal draught in the connection point: PH 19.91 14.02 Pa
- Chimney pressure losses: PR 15.25 1.53 Pa
- Wind velocity pressure: PL 0 0 Pa
Available draught in the connection point: PZ 4.66 12.49 Pa

+ Minimum draught of the heating appliance: PW 0 0 Pa


+ Connecting flue pipe pressure losses: PFV -3.6 -2.96 Pa
+ Combustion air supply pressure losses: PB 0 0 Pa
Required draught in the connection point: PZe -3.6 -2.96 Pa

Fulfills
First pressure requirement: PZ ≥ PZe requireme
nts
At nominal heat output: 4.66 > -3.6 YES
At minimum heat output: 12.49 > -2.96 YES
Fulfills
Second pressure requirement: PZ ≥ PB requireme
nts
At nominal heat output: 4.66 > 0 YES
At minimum heat output: 12.49 > 0 YES
Draught in the installation: PZ - PZe
At nominal heat output: 8.26 Pa
At minimum heat output: 15.45 Pa

Calculation according to EN 13384-1 Page 2 of 3


Customer: RS
Project: GST
No. Document: 001
Date: 17/09/2017
TEMPERATURE REQUIREMENTS Nominal Minimum
Inner wall temperature at chimney outlet: Tiob 104.1 41.2 ºC
Inner wall limit temperature: Tg 0 0 ºC

Fulfills
First temperature requirement: Tiob ≥ Tg requireme
nts
At nominal heat output: 104.1 > 0 YES
At minimum heat output: 41.2 > 0 YES

SIZING

CONNECTING FLUE PIPE


Chimney system: Dinak SW
Inner diameter: mm 350
Outer diameter: mm ---
Designation according to EN 1856-1: T600 N1 W V2 G

Nom Min
Average flue gas velocity: m/s 4.9 1.4
Average flue gas temperature: ºC 178 118
Average outer wall temperature: ºC 127 62

CHIMNEY
Chimney system: Dinak SW
Inner diameter: mm 350
Outer diameter: mm ---
Designation according to EN 1856-1: T600 N1 W V2 G
Nom Min
Average flue gas velocity: m/s 4.8 1.4
Average flue gas temperature: ºC 168 108
Average outer wall temperature: ºC 113 53

CHIMNEY OUTLET
Nom
Flue gas velocity: m/s 4.7
Flue gas temperature: ºC 161
Outer wall temperature: ºC 110

Calculation according to EN 13384-1 Page 3 of 3