3.non Conformance Report For Schneider LV SWGR

1) Schneider Electric France was issued a non-conformance report for not fully complying with electrical bus bar sheathing specifications on recently manufactured switchboards. 2) The specification required green or green with yellow insulating sheathing along the entire length of earth bus bars, but Schneider used sheathing with only yellow marker intervals instead of the entire length. 3) An investigation and corrective actions are required to address the non-compliance and ensure future switchboards meet specifications.

Uploaded by

Sayee Krishnan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
151 views

3.non Conformance Report For Schneider LV SWGR

1) Schneider Electric France was issued a non-conformance report for not fully complying with electrical bus bar sheathing specifications on recently manufactured switchboards. 2) The specification required green or green with yellow insulating sheathing along the entire length of earth bus bars, but Schneider used sheathing with only yellow marker intervals instead of the entire length. 3) An investigation and corrective actions are required to address the non-compliance and ensure future switchboards meet specifications.

Uploaded by

Sayee Krishnan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 2

Attachment 1

EPIC OF RAS LAFFAN COMMON COOLING SEAWATER


SYSTEM PHASE-II FOR ONCE THROUGH
CONSUMERS

Non-Conformance Report Format No.: DOD-QAC-FM 005-C R(0)


Initiator

Client Internal Dodsal Internal Audit External Audit Other…Dodsal Pte Ltd
Issued to : Schneider Electric France(SEF) NCR Ref : DOD-SCHNEIDER/NCR13
Plant M4
F-38050 Grenoble Cedex 9 France
Location : France Date :
Description of Non conformance:
As per QP Engineering Standard ES.2.14.0015 Rev.A, clause # 9.9, Earth bus bars shall be sheathed with green,
or green with yellow, insulating material along its entire length, except at connection points for internal and
external cables or straps. Schneider used tinned copper earth bus with green color sheath and with yellow
marker on earth bus at regular interval instead of entire length. Hence manufactured Switchboards do not comply
with the requirement of specification.

Signature by Originator Signature by Receiver


Root Cause Analysis Schedule Impact Yes / No
Possible causes:

Conclusion : Completed By :

Proposed Correction:

Date:
Proposed By: Date: Accepted by: Date:

Proposed Completion Date : Actual Completion Date :


Proposed Corrective Action :

Proposed Completion Date: Actual Completion Date:


Preventive Action (To be filled in by HOD/Auditee)

Proposed completion Date: Actual Completion Date:


Proposed By: Date: Accepted by: Date:

Verification of Effectiveness of Implementation :

Close Out On:


Actions Verified and NCR Closed out by: COMPANY Representative

Name:

Signature:
Date:

Doc. No. RLCSF21-0-25-0005 Rev. A


Attachment 1