Project Guide 170-200 Letter 08 99
Project Guide 170-200 Letter 08 99
Foreword
This project guide includes the electric power description and auxiliaries data sheets may
generation applications of CW170 and CW200 be reproduced and given to client.
diesel engine series. The content of this handbook is based on the
The project guide is intented for use in most current information at the time of
presales activities, and also as support for publication, and is subject to change without
final design of power plants from 1 to 20MW. notice. Please contact your sale support before
closing contracts.
It does not contain confidential information,
but distribution should be limited to sales We hope this handbook will help your daily
organization and engineering partners. Parts job, don’t hesitate to give us your comments,
of this document, such as equipment complementary information or needs for next
revision.
CUMMINS WÄRTSILÄ,
1 RUE DE LA FONDERIE,
Contents
1. General
1.4 STANDARDS
The following standards are used for our machines con-
struction (if applicable) and advised for power plants
design.
Prime movers Electrical Equipment
ISO 3046 (BS 5514 ) - Specification for reciprocating
IEC 4391(BS EN 60439)(EN 604392) Specification for
internal combustion engines, parts 1 to 6.
low-voltage switchgear and control gear assemblies.
ISO 8528 Reciprocating internal combustion engine driven
IEC 9471(BS EN 60947)(EN 609472) Specification for
alternating current generating sets, parts 1 to 10.
low voltage switchgear and control gear.
EEC Directive 84/536/EEC - Noise from construction
IEC 3641(BS 7671) Requirements for electrical instal-
equipment - power generators.
lations. IEE Wiring Regulations (sixteenth edition).
BS 2869 1970 - Fuel Oils for Oil Engines and Burners
EC 439(BS 5486) Factory Built assemblies of Low Volt-
for non- marine use.
age Switchgear and Control Gear.
ASTM D 975 Standard specification for diesel fuel oils
EC 479 Effects of Current Passing through the Human Body.
and associated testing ASTM standards.
BS3950 Electrical Protective Systems for A.C Plant.
The engine and its auxiliaries are manufactured and/
or controlled under a registered quality control sys- BS 159 1957 Busbars and Busbar Connections.
tem approved to ISO 9001. BS 162 1661 Electrical Power Switchgear and Associ-
Generators ated Apparatus.
IEC 34-1 Rotating electrical machines BS 2757 Insulation.
BS2615 The Electrical Performance of Rotating Electri- BS 5424 Part 1 1977 - Contactors.
cal Machinery.
BS 4999(IEC 341) General requirements for rotating
electrical machines.
BS 5000(IEC 341)Rotating electrical machines of par-
ticular types or for particular applications.
NEMA MG 1 Motors and generators.
EN 50081(BS EN 500812)Electromagnetic compatibil-
ity. Generic emission standard.
EN 50082(BS EN 500822)Electromagnetic compatibil-
ity. Generic immunity standard.
The generator set and its control system are manufac-
tured under a registered quality control system ap-
proved to ISO 9001.
2. Generating sets
2.1 REFERENCE CONDITIONS
Service is defined from ISO 8528/1 :
COP, for “continuous power”, applies to baseload combustion of fuel-oil. Also, global combustion tem-
plants, or industrial plants operated continuously. No perature increase leads to abnormal heating of cylin-
overload is allowed. der heads and pistons, which might result in engine
problems.
PRP, for “prime power” applies to generating sets
used under variable load, without time limitation, PRP To determine true ambient conditions, be aware of true
rating being the maximal available power. application indications. Altitude indication is easy to
verify, but temperature range is mostly dependant on
LTP for “Limited time running output”, applies to
local weather, and true temperatures may cause power
standby diesel generators, operated less than 500 hours
loss, operating problems, or damage to engines. If an
per year with a maximum of 300 hours of continuous
engine is taking combustion air in the generator set
operation. No overload is allowed on indicated power.
room, don’t forget to include in the calculation the
This LTP service is mainly dedicated to Standby ap- temperature rise caused by alternator and engine. It
plications. is not necessary to apply a specific derating factor for
alternator cooling, because diesel derating is higher.
In these operating figures, there is no time limitation
between the stated maintenance intervals. The performance of the generator set will be effective
Reference conditions are from ISO if exhaust backpressure is in the specified range, if
cooling water return temperature is lower than indi-
3046/1
cated limit, and if fuel feeding temperature is below
Reference conditions are not strictly the same for CW the indicated limit.To fulfill these conditions, auxilia-
170 and CW 200 engines. Alternative temperature and ries choice, implementation and piping shall be per-
altitude combinations are proposed for hot climates, formed following the enclosed information.
near sea level, and at higher altitudes.
Exhaust gases emissions
If intake temperature is lower than reference, engine The exhaust gas contains hazardous compounds which
output increase can not be authorised. are detrimental to the environment and therefore
For applications where ambient temperature condi- comprehensive legislation has been introduced. Un-
tions or altitude of the installation are above the ref- fortunately a legal harmonization of levels and how to
erence conditions defined in data sheets, the genera- estimate these emissions have not been achieved. For
tor set output has to be derated following these the 50 Hz market in Europe the German TA-Luft rules
data sheets. have become a guide line while the 60 Hz market is
guided by the US legislation.The standard NOx emis-
Derating factors versus site ambient
sion rates are indicated in generating set data sheets.
conditions Lower NOx adjustment is available on request.Values
Derating purpose : Derating of the diesel engine ver- are expressed in metric units. (TA-luft methods with
sus the altitude and the temperature is mandatory, 5% dry O2, applicable for internal combustion engines).
because altitude increase and air temperature increase To convert NOx rate in g/kWh, in g/bhph, please ap-
results in reduction of oxygen mass entering the ply 0.746 factor.
cylinders. Diesel engine power is reduced, and smoke
increases due to lack of air, necessary for complete
Please refer to technical data sheet of generator set for pending values
2.2.1 ENGINE DESIGN There is one camshaft for each of the two cylinder
banks bearing both valve cams and injection cams. The
bearing housings are fully integrated into the engine
The CW 170 and 200 series engines are four stroke
block and located on the outside of the cylinders. There
high speed diesel engines. Banks are disposed in V
are large crankcase openings as well as openings
formation. Direct high pressure injection increases per-
for the camshafts on both sides of the engine block.
formance and reduces emissions. All main auxiliaries
and ducts are integrated, allowing easy maintenance Cylinder head
by large inspection doors. Vibration level is lowered to The cylinder head is made of special cast iron. The
permit simple resting of generator sets on the floor, thermally loaded flame plate is efficiently water cooled.
without sealing features. The intermediate deck improves the cylinder head cool-
CW 170 is a 170 mm bore high speed engine, ing as well as absorbing the mechanical loads on the
cylinder head. The high and stiff design of the cylin-
CW 200 is a 200 mm bore high speed engine. der head allows it to be fixed by only four hydrauli-
Engine block cally tightened studs.
The engine block is cast in one piece in modular cast The cylinder head features two inlet and two exhaust
iron. It has a stiff and durable design to absorb inter- valves per cylinder. The exhaust valve seat is water
nal forces and to enable resilient mounting. cooled. The valves have stellite-coated seat faces and
The engine has an underslung crankshaft held in place chromium-plated stems.
by main bearing caps. The main bearing caps are nodular Crankshaft
cast iron and guided laterally by the engine block and The crankshaft is forged in one piece in a high tensile
axially by a locating pin. They are fixed by two hy- steel. All the crankshaft surface is nitrided. Journals
draulically tightened studs and secured by lateral and crankpins ends on recessed fillets.
screws.
The crankshaft fulfills all classification societie’s re-
The supercharge air duct is integrated between the quirements. The two counterweights per crankthrow
cylinder banks disposed in a V angle of 60°. The jacket are each bolted on by three screws. They are posi-
cooling water supply to the cylinder heads and the tioned by locating pins which prevent any fretting-
return are integrated in the engine block. corrosion.
The lubricating oil supply to the bearings and the pis-
ton cooling occurs through a drilled channel in the
middle of the engine block.
Starting system
The gear-drive air starter, delivered as standard, is Each cooling circuit is controlled by thermostatic valve
motorized by a turbine, operating under low pressure elements with wax sensors.
of 10 bar. Manual and remote electrical starts may be
The thermostatic valves for both circuits are in the
performed .
same casing, cooling water control unit, assembled on
Engine fuel-oil system the rear side of the free end cover.
The fuel-oil system is based on one cylinder (individual) The CW 200 engine has basically only one inlet and outlet
injection pumps with built-in tappets in the to the external cooler and an internal heat sharing cir-
“multihousing” (common casted piece for injection cuit. The CW 170 engines have basically two inlets/out-
pump and valve tappets). The fuel feeding line is fully lets for the separate HT and LT circuits.
integrated in the injection pump bodies, and surround-
ing ducts. An aluminium cover encloses the system to Optional electrical pre-heating is built-in engine, in-
safeguard against fire hazards. cluding an electrically driven circulating pump.
Water content max 0.3% volume - 3733 Sulfur in fuel ensures the fuel lubricity in
regard with injection equipment. Fuel pro-
Ash content maxi 0.01 weight D 482 6245 ducer mix some additives in low sulfur fu-
Sediment by extraction maxi 0.1% weight D 2276 3735 els to protect injection equipment against
seizing. We advise the purchaser to get a
Water and sediment maxi 0.05 % volume D1796 - fuel lubricity test result, to prevent injec-
Carbon residue, ramsbottom 4262 section tion equipment damage.
maxi 0.35 % D 524
% on 10% residue 3.3
It is mandatory to respect at all times the
Copper corrosion up to 3 index D130 - fuel-oil/lube oil adequacy to prevent pis-
ton rings and bearings damages. See fol-
lowing chapter for lubricants definition.
The table above gives most current test methods. Italic Fuels conforming to the specifications below can be
printed testing methods may be used as alternative. used without prior restriction. If fuel specification is
Lower Heating Value (LHV) of fuel is defined in diesel not included in this list, please compare its analysis
generator data sheets.Copper strip corrosion is not im- results with limits in table above.
portant, because our circuits are made of steel and - U.S. standard ASTM D975-1994 N°1-D and N°2-D.
cast iron
- ISO fuel-oil F-DX, ISO 8217 marine fuel-oil F-DMX,
When output power guarantees are required, we require F-DMA and F-DMB.
a complete analysis of fuel-oil from the forecasted fuel
seller. If analized fuel has some characteristics out of - British standard BS 2 869 A1, A2 and B1.
above specifications, please ask Cummins Wärtsilä for - French syndical specs.CSR.09 and CSR.10 Q,
further information. Some characteristics may be en- FOD N°1 and FOD N°2.
hanced with special features: excessive water content
can be removed using a water trap or a centrifugal sepa- Be aware of the fact that, generally, the quality of
rator, as well as sediment. Excessive sediment and ash fuel-oils continues to decrease due to changing refin-
content reduces fuel filter exchange interval. ery techniques.
Fuel-oil/lube-oil adequacy
Lube oil quality is defined by used fuel-oil properties and
lube-oil grade is defined by service & ambient temperature.
If fuel sulfur content is high (0.2 to 1%) use of API- Gadinia SL0391
SHELL ( SAE 40) 12
CDII, and API CE, or MIL-L 2104E class are adequate.
TBN should be between 10 and 15. LO with TBN over CASTROL TLX 154 15
15 may be used to increase oil change intervals.
EXXMAR CM
If fuel sulfur content is very high (1 to 2%) use of EXXON super 40 15
API-CDII, CE, and MIL L 2104 E, with very high TBN ( SAE 40)
over 15, is adequate. TBN over 20 is preferred. Engines operated with fuel which sulfur content is
between 1 and 2%
As basic principle, TBN value should be as a minimum15
Sirius X 40
Myrina X
times the sulfur content in percent.If they are not, oil SHELL ( SAE 40)
15W40 17
change intervals shall be reduced. (former Myrina)
Rubia FP 40
Lube oil grade (weight) TOTAL (SAE 40) 17
Lube oil grade is defined by the cold starting requirement.
CASTROL TLX 204 20
Use of SAE 30 or lower weight lubricant is forbidden
- For continuous duty or power management diesel ELF
Aurelia 4020
20
( SAE 40)
generators, SAE 40 grade is always recommended.
220 MXD
- For emergency diesel a monograde SAE40 is recom- CASTROL ( SAE 40) 22
mended if preheating is effective before the starting
is performed.
2.2.5.2COOLANT TREATMENT
General Rules of the art :
The purpose of water treatment is to prevent: - Use of distillated water or rain-water without treat-
- Furring of heat exchange surfaces due to mineral ment is strictly forbidden, even for short duration tests.
content of water, - Life-time of antifreezed coolant of grade 1 is about
- Corrosion of metals due to dissolved oxygen and 3 years in air-tight circuits.
carbon dioxide, - An analysis of coolant quality is recommended ev-
- Cavitation due to boiling points, pump impeller ery three months, whatever its nature. Quick-check
vacuum effect or vibrations, sets are proposed by the chemicals manufacturers.
- Freezing if coolant is exposed to frost. - If new products are installed in existant circuitry, it
is advised to clean the former product layer and/or
We have defined for our diesel engines, a set of water treatment remove bottom deposits, and rinse carefully.
products, having given satisfactory results in use. They are depicted
in table right. It is mandatory to use one of these selected products Particularities
during warranty period.
LT water and HT water in engine shall be protected
Water for coolant & inhibitors preparation using the same chemical. These circuits are in contact
inside the engine.
If concentrated products are used, you have to use
demineralized water for coolant preparation or good Use of other products
quality drinking water.
During warranty period, use of recommended products
The minimum quality requirements allowing our anti- is mandatory. After warranty period, other products
corrosion products efficiency are : may be tested following Cummins Wärtsilä procedures.
Consult our service department.
- Water totally clean and limpid.
- Total Hardness < 5.6 °dH(1) (100 ppm as CaCo3) . Particular recommendations for ecology
- Acidity 6.5 < pH < 7.5. Water treatments are chemicals which may cause pol-
lutions ,or which are containing non-degradable sub-
- Chlorides contents < 60 mg/liter of NaCl. stances, such as monoethylene glycol based formulas.
- Sulphates contents < 40 mg / liter of SO4Ca The antifreezes shall be recycled, and never drained
in a sewage. The producer may take it back for recy-
Above these figures, use softened or demineralized cling process.In any cases, handling shall be performed
water, or ready-to use coolants. Another solution is to with usual protective wear, even if product is not toxic.
demineralize water using chemicals which causes pre-
cipitates of calcium carbonates and silicates. After Producer Tradenam e Type of product
chemical demineralizing, water can be used after fil-
tering to remove deposits Coolef W ith antifreeze, m inus
supra 25°C ,ready to use
Coolant preparation E LF
Glacelf W ith antifreeze, u p to
For antifreeze based coolant preparation a maintenance supra m inus 50°C, to be d iluted
tank where water and treatment chemicals are mixed W ith antifreeze, u p to
Diagel-6N
together is proposed. A pump and a set of flexible m inus 50°C, to be d iluted
hose is included, to connect pump, tank, with circuit ROHM & W ith antifreeze , m inu s
filling orifice and antifreeze drum. This tank is trans- Diamigel-6N
H AAS 35°C, ready to use
portable using a fork lift truck.
W ith antifreeze , m inu s
Triagel-6N
20°C, ready to use
(1)
corresponding to 10°f (french degrees ). A total Glycol Shell W ith antifreeze rea dy to
S HELL
hardness up to 250 ppm as CaCO3 may be tolerated, but type D use, m inu s 25°C
top-up with this kind of water, to compensate evapora- ROHM & Anticorrosion without
H AAS
RD 25 antifreeze, to be dilute d
tion in service, would cause deposits or saturate the
furring inhibitors.
2.3 ALTERNATOR
Terminal Boxes
Instrument and control connections are in segregated
compartments, with external access for safety.
Vibration Limits
All alternator rotors are dynamically balanced to bet-
ter than BS6861: Part 1 Grade 2.5 for minimum vibra-
tion in operation. Two bearing alternators are balanced
with a half key.
Insulation/Impregnation of windings
Standard insulation classes for the alternators are
class H for low voltage (400 - 480V), and F for medium
& high voltage (4.160 - 13.800 V) .Please refer to data
sheet for actual specifications. (built-in version)
The 3 phase RMS voltage sensing AVR provides very
All wound components are impregnated with materi-
accurate vc!tage regulation, from no load to full load
als and processes designed specifically to provide pro-
including cold to hot variations for any power factor
tection against the harsh environments encountered
between 0.8 lagging and unity allowing for 4% en-
in generator applications. Resins are selected and de-
gine speed variations. It is particularly suitable for
veloped to provide the high build required for static
non linear load applications.
windings and the high mechanical strength required
for rotating components. Three Phase Sensing
An Hybrid System using the best features of Global Three phase sensing centres any voltage imbalance,
VPI, and Resin Rich Technology is used, to give a su- caused by load imbalance, around the nominal volt-
perior product, optimising insulation life in the slot age, and helps to ensure trouble-free operation under
section, with the advantages of VPI epoxy in the the most demanding loads.
outhangs for strength, electrical properties and opti- Parallel Operation
mum protection. 5kV machines and above, have Co- All alternators are well-suited for parallel operation
rona Protection tapes applied. (optional droop kit fitted) with the mains utility or
PMG excitation with other generators. A fully interconnected damper
Permanent Magnet Generator (PMG) excitation system, (amortisseur) winding reduces oscillations around the
performing in regard with reliability, response and sta- synchronisation point during paralleling.
bility, is delivered as standard feature. The PMG pro- Advanced regulation features
vides power via the AVR to the main exciter, giving a PMG alternators may be operated directly with the
source of constant excitiation power independent of PowerCommand™ system, including its own voltage
generator output. The exciter output is then fed to regulator. See enclosed PowerCommand™ description
the main rotor, through a full wave bridge rectifier, for more information.
protected by a surge suppressor. The AVR has in-built
protection against sustained over-excitation, caused
by internal or external faults. This de-excites the al-
ternator after a preset period.
Over voltage protection is built-in and short circuit
current level adjustment is an optional facility.
Voltage Regulator
Low voltage coils are wound with round enameled Terminal box - Connection
wires. Impregnation is done with polyester based var- A large-sized and easily accessible terminal box is lo-
nish impregnated under vacuum. Medium voltage coils cated at the alternator top. Inside, the six windings
are built with fiberglass-lapped flattened enameled ends are wired to connecting bars (for low voltage)
wires, the sections are isolated using mica products. or to insulators (for medium and high voltage), thus
allowing easy connection.
Thermal protection
PT 100 thermal sensors (100 ohms at 0°C) are enclosed
in the stator winding and implanted in the bearings.
Output is used either for temperature measurement
or alarm and tripping.
Brushless excitation
Field flashing is ensured by residual magnetism, de-
livering minimal field to enable voltage regulator
operation. Excitation alternating current is drawn off
an inverted alternator keyed on rotor shaft. Inverted
means that armature is rotating, and field poles are
fixed. The excitation current is rectified through Graetz
bridge of silicon diodes properly sized and protected
by resistors connected in parallel on the alternator ro-
tor windings. Rectifier is fixed on alternator rotor, and
so named “rotating rectifier”. If out of control, exciting
system trends to minimal voltage output.
Shunt regulator
Special precautions are taken to ensure perfect The regulator (6) is supplied by the generator output
wedging of the sections and connections using insu- (1) and controls the excitation in the exciter field (5).
lating rings and inserts. The excitation current from the exciter armature (4)
Global impregnation with solventless polyester resin is rectified by the rectifier bridge (3) and supplies the
under vacuum and pressure provides the unit with a alternator pole wheel (2). A three phase current
remarkable mechanical strength, a very high degree booster is supplied, and a current transformer (dot-
of insulation impervious to humidity, oil, fuel-oil, die- ted line on diagram) is allowed for parallel operation
sel fumes and industrial chemicals. reactive power control.
Standard insulation classes for the alternators are A potentiometer allows adjustment of the nominal
class H for low voltage (400 - 480 V), and F for me- voltage over a ± 5 % range.
dium & high voltage (4.160 - 13.800 V).
PC Based
HMI 3-Phase AC Supply
by Customer Alternator Engine
PLC
RS-485 Supply to prelube, wtr circ, CENSE
AC sensors Woodward
RS-422
I/O Terminal clean fuel spill pumps, (Level 1) Actuator
Box eng & alt heaters
RS-232
DC sensors sensors
Power Command Control
Terminal
Box
MAIN SCREEN :
The main screen is designed to enable the operator to
determine the current genset status. It further allows
access to the data embedded in the layered screens.Data
Includes voltage per phase, Current per phase, kW, MW/
hr, Frequency, Power factor, Oil pressure, Speed and
Engine hours.
Touchscreen activities allow the following access:
· Engine Data,
· Alternator Data, · Low oil pressure (shutdown)
· AC Auxiliaries mimic, · High coolant temperature (shutdown)
· Alarm Activities, · Fail to crank (shutdown, indicates failure of en
· GCP Configuration, gine to rotate on start command)
· Related Plant Data · Overcrank (shutdown, indicates cranking time
The main screen is designed to include an alarm capa- exceeds 75 seconds or failed to start after all cycle
bility so that the operator is immediately advised of cranking attempts)
all alarm and shutdown conditions. · Magnetic pick up failure (shutdown)
The digital display provides status of the following criti- · Overspeed (shutdown, engine speed >= 115% of nominal)
cal engine functions : · Emergency stop (shutdown)
· Oil temperature (oF or oC) The control has provisions for four programmable fault
· Coolant temperature (oF or oC) conditions. These may be either warning or shutdown
· Oil pressure (PSI or kPA) conditions. Labels for customer faults can be pro-
· Battery voltage grammed into the control.
· Engine operating hours
Historical data
· Number of engine starts
· Speed The control maintains an historical data log of the lat-
est alarm and status conditions on the genset. On an
ENGINE WARNING AND SHUTDOWN MESSAGES. alarm or shutdown condition the control logs the na-
On sensing a warning or shutdown condition the con- ture of the fault and the engine operating time that
trol displays the warning or shutdown message, and a the fault occurred. The control displays the last 20
code to be cross-referenced using the genset manual. alarm and/or shutdown messages.
Functions provided include:
· Low oil pressure (warning)
· Low coolant temperature (warning)
· High coolant temperature (warning)
· Low coolant level (programmable warning or shutdown)
· Low fuel day-tank (warning, external input signal)
· Oil pressure sender (warning, indicates a sender or
wiring failure in the oil pressure monitoring system)
· Engine temperature sender (warning, indicates a
sender or wiring failure in the engine temperature
monitoring equipment)
POWERCOMMAND™ SUPERVISOR
PowerCommand Control
This unit is a microprocessor based genset monitoring,
metering and control system. It is integrated into the
GCP and incorporates the following key features;
• Voltage Regulator
• Synchronizer (Freq, Phase & Volts)
• Iso-Bus kW and kVAR load sharing
• Utility Paralleling kW Load Control
• Utility Paralleling pF Control
• AmpSentryTM Alternator Protection
• Overload,
• Overcurrent [51],
• Short circuit [50],
• High AC Volts [59],
• Low AC Volts [27], OPERATOR’S CONTROLS
• Underfrequency [81u], Operator may choice the operating display screens:
• Sync Check, Fail to Sync, Generator set monitoring, engine warning and shut-
• CB Fail to Close, down messages, the fault occurence historic, and can
• Reverse Power [32], reset faults from front face controls. Some parameters
• Loss of Excitation [40], or set points may be adjusted under access code pro-
• Phase Rotation tection, from front face controls.
• Alternator Metering
Upper face of PowerCommand™ bears the indicators
ENCLOSURE ENVIRONMENTAL HARDENING. for AC output metering: kW meter, Frequency meter,
AC voltmeter and Ammeter switchable on each of the
The front face is impervious to water spray, dust and
Three phases.
oil/exhaust residue. Switches for control are incorpo-
rated into the door which is gasketted with a dual Digital metering of alternator is available on screen
moisture and RFI/EMI gasket to protect internal com- for accurate indication and energy counting
ponents from airborne contaminants. AC GENERATOR VOLTAGE REGULATOR , SYN-
CONTROLS AND ADJUSTMENT SWITCHES. CHRONIZING AND LOAD SHARING FEATURES
An oil tight, three position switch starts and stops the PMG Generator digital voltage regulator is built-in PCC.
generator set locally or enables start/stop control from It controls the isolated generator set voltage, ensures
a remote position. matching of voltage and frequency for synchronizing,
and controls the load and reactive power when paral-
It provides the following functions:
leled. Genset breaker is controlled abnd secured for
. The ‘OFF’ position de-energises all primary DC cir- closure and opening on dead or live bus.
cuits. When the switch is in this position, the non-
automatic indicator will flash continuously. SMART STARTING CONTROL SYSTEM
. The ‘RUN’ position energises the control and initiates Starting parameters are controlled to minimize over-
the genset starting operation. shoots, take in account temperature, avoid alternator
overexcitation. Start attempts are automatically con-
Note : the non-automatic indicator will flash when the trolled, and cranking sequence may be programmed.
switch is in the ‘run’ position. Starting battery is checked during starting sequence.
. The ‘AUTO’ position enables the control to receive a
start signal from a remote location. AMPSENTRY PROTECTION
PARALLELING DEVICES
Synchronizing equipment is implanted for operating - A synchronizing indicator allows the operator to check
genset in parallel. phases rotation.
- An automatic synchronizer ensures speed and volt- Functions listed in table below are available in stan-
age matching for synchronizing. It changes speed set dard control panels. Some additional alarms may be
point of electronic governor and changes voltage set added if needed or replaced by others (for example,
point of alternator through logic signals from control- radiator fans alarm replaced by raw water pump flow
ler or operator. detection).
- A live busbar phasing detector enables or disables the INDICATORS AND PROTECTIONS
synchronizer action on paralleling breaker,
see table below
Two bearings
AC generator
Coupling housing
Step reloading
t1 = minimum time for start and rated frequency & Px = Largest single load (active power value) which
voltage build-up. can be instantly applied, causing a speed drop of
10% or less. Load is percentage of nominal out
(*)For emergency generating set, the value could be
put COP.
reduced to 10 s with special booster equipment.
Sudden unloading
t2 = time elapsing before the speed has recovered
steady state (settling time). t3 = time for speed to recover steady state.
t4 = minimum delay between two load steps. n1 = overshoot at sudden unloading.
CW 170 series
CW 200 series
16V170 18V170
connection dimension X Y Z X Y Z
408 HT water inlet 3" - 197.50 - 140 + 680 - 197.50 - 140 + 680
402 HT water outlet 3" - 48.50 - 191 + 680 - 48.50 - 191 + 680
451 LT water inlet 3" - 48.50 - 400 + 680 - 48.50 - 400 + 680
456 LT water outlet 3" - 197.50 - 423 + 680 - 197.50 - 423 + 680
101 fuel inlet 1" - 540 - 195 - 490 - 610 - 195 - 490
102 fuel outlet 1" - 540 - 350 - 490 - 610 - 350 - 490
105 fuel prim ing pump NA - 560 + 460 - 630 - 560 + 460 - 630
215 oil filling dia 60 - 200 + 240 - 580 - 200 + 240 - 580
216 oil drainage 1" + 140 - 605 - 60 + 140 - 605 - 60
301 starting air inlet 1" +1120 -790 -380 +1370 -790 -380
404 HT water perm anent venting 3/4" -625 -430 +1575 -625 -430 +1575
454 LT water permanent venting 3/4" -625 +450 +1575 -625 +450 +1575
+ 279 + 279
501 exhaust gas outlet ND 250 + 1050 + 1375 + 1194 + 1375
- 279 - 279
blind
according to alternator model
TB01 generator term inal box glandplate
* Framed gensets, delivered actually have the same connecting arrangement. Refer to enclosed genset drawings or
contractual drawing for crankshaft altitude from floor.
12V200 18V200
Connection Dimension X Y Z X Y Z
Units mm mm mm mm mm mm
701 Crankcase breathing Ø 4" 1945 - 520 1020 2845 - 520 1020
501-1 Exhaust gas outlet ND 250 - 200 520 1600 - 200 520 1600
501-2 Exhaust gas outlet ND 250 - 200 -520 1600 - 200 -520 1600
451 Cooling water inlet Ø 5" - 210 770 - 10 - 210 770 - 90
402 Cooling water outlet Ø 5" - 210 770 - 395 - 210 770 - 395
480 Cooling water prim. pump Ø 2" connected on inlet pipe, plant side
404 Cooling water outgasing Ø 1/2" - 110 465 1580 - 110 465 1580
301 Starting air inlet Ø 1" 2125 - 700 - 100 3025 - 700 - 100
215-1 Lub oil manual filling (std) Ø 61 - 255 750 335 - 255 750 335
215-2 Lub oil automatic filling (opt) Ø 1/2" - 445 - 655 - 465 - 445 - 655 - 465
216-1 Lub oil sump draining Ø 1" 0 - 180 - 650 0 - 180 - 650
101 Fuel oil inlet Ø 1" - 820 - 470 - 250 - 820 - 470 - 250
102 Fuel oil outlet Ø 1" - 820 - 600 - 250 - 820 - 600 - 250
103 Clean fuel oil leakage Ø 1" 1935 - 680 - 610 2835 - 680 - 610
104-1 Dirty fuel oil leakage Ø 1" 1935 -650 - 610 2835 -650 - 610
104-2 Dirty fuel oil leakage Ø 1" 1935 650 - 610 2835 650 - 610
blind
according to alternator model
TB01 Alternator terminal box glandplate
TB02 Display unit connector
TB03 Engine terminal box connector
Slings B
Distancers
Shacles A
Slings A
Shacles B
Shacles A
Handling system
16 to 30 tons 30 to 40 tons
weight capacity
2 (for CW
Shacle B narrow NA 15 tons 2 narrow NA 20 tons
200&220 only)
metal or metal or
Sling B 4 2.5 to 5 m 15 tons 4 2.5 to 5 m 20 tons
textile textile
CW SMO CW SMO
Distancer 2 2 meters 20 tons 2 2 meters 20 tons
188 200 188 200
Sling B
Distancer
Shacles A
Sling A
Shacle B
Shacle A
Containerized power
plants are particu-
larily suitable for min-
ing power stations,
which have to be
moved with working
plant. (Minera Esc-
ondida, Chile)
3.1.0 GENERAL
Building regulations
This section describes the design principles of the Die- Planning and building legislation varies throughout
sel plants buildings. Typical layouts are shown in the the world. However the principles behind such legis-
appendices for various configurations. Due to local lation are almost always the same and have therefore
regulations and clients’ requirements this information been given due consideration. These principles are :
is a guideline only when establishing diesel Power
- Location suitability and environmental friendli-
Plants.
ness
3.1.1 BUILDING LAYOUT The “zoning plan” for a particular area dictates the
function and general appearance (size and height
The building is largely a reflection of the processes etc....) of buildings in the area.
that exists inside it. Not simply mechanical and elec-
trical processes but also processes involving movement - Structural stability
of people and maintenance activities.
The buildings structure must naturally withstand the
The main process movements can be summarized as pressures placed upon it by local conditions. Build-
follows : ing regulations decides the loadings that the build-
Process movements such as fuel, coolant, lubricating ing must be designed with. Other factors include
oil, electricity between the different components in- local weather conditions, inundation possibility, hur-
side and outside the building. ricane, risk for insect attack and, in the event of
People movements and in particular the relationships fire, the buildings ability to remain structurally stable
that exists between periodicity of movement and dis- long enough to allow emergency evacuation.
tance. Codes throughout the world differ in respect to re-
Equipment movements. How, when, where, what and quirements on structural stability and therefore the
why equipment shall be moved into and around the final structural arrangement of the building will dif-
building. This includes giving consideration to required fer. Extreme circumstances, such as risk for earth-
space during installation. quake, storm, require special consideration.
Piping, Ducting, and Cabling Fire Protection
In conjunction with process movements, consid-
The following questions are those most commonly
eration should also given to the media in which the
posed by fire authorities and have been taken into
movement takes place, i.e. piping and cabling. The
closer components are to each other the smaller the account when designing the building :
amounts of piping and cabling will be required and the I. What is the risk that the building will catch fire
cheaper the installations will be. Priority is given to ?
more expensive mediums such as exhaust gas piping
and power cabling. 2. What are the consequences of the building catch-
ing fire in terms of risk to persons ?
Processes are much more effective if pipes, ducts, and
cable runs are as straight as possible. Back pressure 3. How can the outbreak of fire be avoided ?
will be minimized in piping systems and disturbance
will be minimized in cable systems. 4. How can the spread of fire from one area of the
plant to others be avoided ?
When process arrangements are finalized and piping
and cable runs are decided upon an even distribution 5. Do persons inside the building have adequate time
of piping and cabling exists throughout the process to escape from the building before it collapses af-
related parts of the power plant. ter they have detected a fire ?
6. Does the building design ensure the safety of fire may be called by automatic system (optionally). Gen-
fighting personnel ? erator set and auxiliaries of power plant are
immediatly stopped by an emergency shutdown or-
7. Should the building collapse, will surrounding build-
der, equivalent to local emergency pushbutton. We
ings and/or installations be damaged?
recommend to provide a dump line for the fuel and
oil service tanks, if it is possible(earthed storage
3.1.2 FIRE DETECTION SYSTEMS tanks), this draining is controlled by a remote puller,
placed outside. To limit oxygen entering air louvres(if
Fire detection systems are strongly advised to ensure motorized) shall be automatically closed.
personnel and equipment protection. Diesel generator
fire hazards are at the higher level, due to fuel and 3.1.3 NOISE LEVEL
high temperature presence. A good fire detection sys-
tem allows rapid fire fighting, by automatic or human
Local authorities are placing higher requirements on
means.
industries and thereby industrial processes we live
The core of fire detection systems is constituted by a in. The future promises further increases in require-
control unit, which receives fire information from sen- ments for environmental pollution control.
sors placed in critical locations. If a sensor is tripped, a
One form of environmental pollution is noise. The
fire alarm is given locally (and remotely on option), to
“technic” plant has been specifically designed to meet
ensure personnel evacuation and fire fighting action.
the residual noise level of today.
Fume sensors are to be placed away from fresh air inlet
A study of noise level requirements in European coun-
ways, to prevent fumes dilution. Air exhaust places are
tries showed that there are substantial differences
suitable. Temperature sensors are to be placed at high
between east and west and even differences between
locations, taking care that settings will not cause trip
regions within countries.
during hot seasons, or directly near the parts to be
protected, particularily in enclosures where fire takes “Technic” power plant has been designed with a double
place out of operator view. Emergency pushbuttons shall enclosure system. Sound is first attenuated by genset
be accessible any time, from all directions. They shall enclosure, and then by soundproofed building. Ven-
be positioned at a suitable height to allow operators to tilation, intake and exhaust systems are soundproofed.
localize them in seconds.
The detection center is to be supplied with a non-inter-
ruptible power supply. Internal batteries must operate
it for one month without reloading in the case of power
supply failure.
The fire alarm is given by a land audible alarm. Firemen
3.1.4 GENERATOR SET FOUNDATION On the table below, the dimensions “A” and “B” of the
foundation are indicated for vell resting of generator
on top surface. They can be increased if block weight
The Cummins Wärtsilä generating sets are mounted on
is to be augmented, resulting in undergroung pressure
resilient elements and do not need special anchorage. The
reduction. Depth “C” is to be determined by civil engi-
standard rubber elements have a vibration filtration
neer according to concrete specific weight, including
efficiency of 95 %. For higher efficiency or special
re-bars. As indicative value, ferro-concrete regular den-
applications, other types of mounts can also be used.
sity is 2,4 t/m3 (150 lb/cu ft), taken in reference for
The foundation slab should be able to support the static calculation of “C” in table below. Basement shape is to
weight of the generating set. Usually, the weight of be designed according to soil resistance to maintain
the foundation should be at a minimum the weight of any time rated pressure.Building contractor shall pre-
the generating set. If, for any reason, elastic mounts pare ground to prevent foundation tilting.
are not used, block weight should be 125% of genset
If plant is built on a floating slab, it should have a
weight. Dynamic forces can be disregarded for iloted
400 mm thickness as a minimum and bear on a well
and paralleled operation(start, step loading, sudden
compacted soil, permanently drained and out of freez-
unloading) using our standard control equipment,
ing depth.
which prevents out of phase coupling .
3.1.5 MAINTENANCE FACILITIES
To prevent further operation costs, a power plant shall
be designed to allow maintenance tasks to be performed
with sufficient space to avoid use of special lifting
equipment, stopping and removal of adjacent units, or
partial building demolition. Each cylinder bank of die-
sel engine shall be provided with an overhead crane,
to ensure fast and easy maintenance.
The surrounding of a building shall allow cranes to
safety support the loads. When turning the crane, at-
tention is drawn to the fact that it can reach the ex-
haust stack; arrangement of handling area shall avoid
that. Trenches shall be stepped to allow a generator
set to be passed over, installing H profile irons for pas-
sage with skates or rolling bars. Pipes shall not pre-
vent bridge installation.
Trenches shall be well drained, and metallic mesh fit-
ted to prevent rodent intrusion.
Storehouses shall be protected from
large temperature variation, be free
Engine Weight of the Dimensions of the foundation(mm) of dust, humidity and ultraviolet
type genset (kg) (concrete spec. weight = 2,4) rays penetration ( windows are blue
in operation A B C painted and lighting is with incan-
16V170 20,500 6,500 1,900 700 descent bulbs).
18V170 22,000 6,500 2,000 700
12V200 28,000 7,000 2,000 830
18V200 37,500 8,000 2,400 810
Main features
This power plant is designed for cost ef-
fective installation, allowing short time
commissioning and simplified servicing.
The whole building is erected on elevated
slab to prevent flooding. Structure of
building is made of steel, wall filling may
be corrugated steel or masonry. Blowers
are disposed on façades of building and
push air toward engine, transformer and
generator. Room ventilation is by natu-
ral convection effect, through large inlet
and outlet duct, when machines are
stopped.
The mechanical auxiliaries are positioned
near free end of engine to reduce piping
length.
The oil bath filter, placed outdoor takes
air at middle altitude to prevent dust
and exhaust hot air aspiration. Radia-
tors are grouped together to prevent hot
air recirculating. It is recommended to
place them 10 metres (30 ft) from the power sta-
tion.
genset number
Electrical room should be built in masonry to pre- with W P E H of
engine gensets
vent temperature changes and effects of condensa-
MV-HV
tion. It is placed in middle of the building to shorten 16V170
15.0 m 6.5m
18V170 2 to 8
power and control lines. Power cables may be routed 12V200
49 ft
5.0m
21 ft
5.5m
in trenches or on cable trays, overhead. 16' 5"
LV
18 ft
16.5 m 7.0 m
18V200 2 to 10
This arrangement includes an optional workshop 54 ft 23 ft
Main features, with sound proofing Power cables may be routed in trenches or on cable
This power plant is designed for temperate climate or trays, overhead.
hot climate countries, enhanced for sound attenua- Main features, without sound proofing
tion capacity and auxiliary equipment quality.The re- Generator set cells are to be removed,and a single
sidual noise level is 50 dB A @ 50 metres. exhaust silencer is suitable. We can design any kind
The basic principle is to build closed generator set cells, of power plant, adapting civil engineering to surround-
providing a first step of sound attenuation, and place ings and client requests.
them in a sound proofed building to obtain forecasted
sound attenuation. Generator sets can be operated
without necessity for an operator to enter the engine
rooms. Maintenance areas are reserved around
the generator set cells, providing the ability to
repair each generator set individually without
noise increase out of building.
The external structure of building may be made
of steel with insulating material or of concrete,
generator set enclosure is made of steel and
insulating material. Maintenance doors are pro-
vided for the generator set removal from the
building.
Combustion air is taken from the generator set
room. This fresh air is obtained from outside
by a fan through a sound trap. Air outlet is
also soundproofed. The exhaust line is equipped
with two high efficiency silencers.
genset A B C D
16V170
12V200
Main features
This power plant is designed for cold climate coun- through a sound trap. For winter, inlet air can be pre-
tries, with sound attenuation and equipped with air heated. Air outlet is also soundproofed. Exhaust line
preheaters. is equipped with two high efficiency silencers.
The basic principle is to build closed generator set cells, Power cables may be routed in trenches or on cable
providing a first step of sound attenuation, and place trays, overhead.
them in a sound proofed building to obtain forecasted
sound attenuation. Gensets can be operated
without necessity for operator to enter the
engine rooms. Maintenance areas are reserved
around the cells, providing ability to repair
individually each generator set without out-
door noise increase.
The external structure of building may be
made of steel with insulating material or of
concrete, generator set enclosure is made of
steel and insulating material.
the roof is made of corrugated steel, with a
slope for snow melting water easy flowing
down
Facade removable panels are provided for genera-
tor set exit from building, following a right way.
Combustion air is routed in a separated duct,
and cell is fed with fresh air by fans operated
genset A B C D
16V170
12V200
18V200 11.0m (36') 5.9m (19.4') 3.6 (11.8') 15.5m (60')
There is no need to seal the containers, only the radia- A paved or gravelled area shall be layed under radia-
tor and electricals container are to be fixed by bolts tors, to prevent dust clogging.
against the effects of storm.
Local scope of supply is mainly the storage tank for
the power plant, the fuel oil piping between storage
and container, the electrical distribution system and/
or switchboard.
container overview
L1 L2 W1 W2 H1 H H2
(meca) (elec) (meca) (elec) (meca) (meca) (elec)
The figure below shows the installation of a container ing an external oil bath filter. Care must be taken to
based power plant with a single diesel generator. Slab place it at distance from the container to prevent the
dimension of this example is adapted for equipment hot air exiting ventilation to be reaspirated.
placing. Square arrangement reduces the operator’s
The fuel oil storage tank may be grounded or be in-
walking during production and cables/pipes lengths
stalled near the slab. If step-up transformeris provided,
are shortened. The advised thickness of slab is 25 to 30
it should be placed near electrical container, with ad-
cm of concrete, on stabilized soil.
equate fences.
If cables are routed on external trays, an electrical
Every time, area facing the compressor end of con-
container is to be installed on an elevated foundation
tainer shall be maintained free to allow the genset to
(out of our scope of supply) to allow bending radius of
be handled out of the container for maintenance pur-
power cables entering down the cubicles. If cables are
poses. Free area shall be reserved for cranes and load-
routed in trenches, or in ducts, the electrical container
ing truck to operate at short distance.
is rested directly on the floor. Installation shown be-
low is for hot climate and dusty atmosphere, requir-
TO BUS OR GRID
auxiliaries
transformer
Plant auxiliaries
Optional
Step-up transformer
If voltage > 13.8 kV
Neutral
grounding
option B
32851 32826 32826 32851 32826 item
To local bus
Neutral
grounding
option A
To grid
To grid
N.E.T. N.G.R.
.
Ie>100A
e < 100A
very good
lowers the fault very important due
neutral directly low level is selectivity, dangerous while
overvoltage to high fault
grounded. needed. 1st step trips fault is pending.
occurences. current.
generator.
equipment is not
simple protections
permanent fault heavely damaged,
neutral grounded may be used with
current is limited, regular insulation good protection by power is dissipated
through low good selectivity. 1st
and internal surge system is suitable. voltage limitation. in impedance. (fault
impedance. step trips
is limited. current is betwen 3
generator.
and 50 amps)
Fault current is
limited as soon as selectivity is large voltage surge
neutral grounded
it appears. (suitable regular insulation ensured if IL>>Ic may be caused equipment may be
through a
for extended system is suitable. network. 1st step when fault is damaged by surge.
reactance system
distribution trips generator. eliminated.
networks)
START
GCP
NO YES
n > 1 Genset
ACPx required
NO YES
n > 2 Genset
ACP0 to be added
to:
PSCPx or GCPx
CACP (1)
NO YES
n > 6 Gensets
Select
Select ACP1 + ACP4 or
ACP1, ACP2 or ACP3 ACP2 + ACP4 or
ACP3 + ACP4
CACP (1)
CACP (1)
AUXILIARIES SEQUENCES
Stand-by Starting Operation Shut down
Control system UNINTERRUPTED 24V SOURCE
Fuel-oil transfer pump X X
Water pre-heat. pump + pre-heater
Pre-lubricating pump
Fan coolers / Water cooling pump X X
Room fan X X
Air electro-compressor
Battery loaders
Lubricating oil transfer pump X X
Clean fuel-oil draining pump X X X
Generator space heater X
Auxiliaries consumptions
Installed power of auxiliaries are indicated here as in- ing. Please note true power of auxiliaries for final defi-
formation base for transformer and ACP pre-dimension- nition, particularily for fan radiators.
Electric motors power for 50 HZ - 400 V for 60 HZ - 440 V, please add 15 %; for resistors add 10 %
Example of SCADA arrangement for an eight CW200 power plant, with eight local bus outputs
3.4.0 GENERAL
The diesel engine installation depends on the auxi- 4) Circuit filling point must be indicated at the low
liary system in order to operate properly. The environ- points, and the high parts must be fitted with manual
mental conditions must be considered at an early stage, or automatic degasing systems.
and it is of utmost importance that all auxiliary sys- 5) If required by the raw water quality, circuits
tems are considered and optimized for their intended should be made of rust-proofed material : PVC or bronze.
purposes at the project design stage.
6) The connections between the installation and the
Piping complies with the following rules : generator set are flexible, so as to absorb the vibra-
1) All tubes must be installed with a slope of tions and misalignments resulting from relative mo-
1 cm/m in order to facilitate fluid-emptying or strai- tions or expansion.
ning. 7) The inside of lubricating oil pipes and fuel-oil
2) Low points are fitted with valves or drainplugs, pipes must be pickled when situated downstream of
both on fluid circuits and gas circuits. the filters.
3) Tubular exchangers are also inclined by 1 cm/m. Indications to be followed when perfoming installa-
In case of frost, the bundle can be emptied by blo- tion are enclosed in our Power Plant installation hand-
wing through a hole. book.
Air sto
rage u
nit
Air pro
ductio
n unit
Air prod
uction u
nit
filling in
tercon
nectio
n
Water/fuel
heat exchange
r
fuel s
er vic
e tan
k
Fue
ls
tank torage
(bul
k
tank
fuel )
s
tank pillage
Lube
oil
servic
e
tank
Lube Opt
stora oil i
was onal
ge ta te lu
nk
oil ta be
nk
Litres per pipe metres Water expansion with maximum T°C and glycol part (0, 30, 50) Tank volume calculation
DN Ø l/m tank 1 2
0,08 50 %
30 %
25 1" 0,7 0,06
engine litres
0%
40 1"½ 1,5 piping litres
50 2" 2,3 0,04 miscellaneous litres
65 2" ½ 3,9 radiator litres
0,02
80 3" 5,4 total volume litres
100 4" 9,0 0 % expansion %
125 5" 14 0°C 20°C 40°C 60°C 80°C 100°C
150 6" 20 litres
The above table is intended to determine the expansion and antifreeze concentration. Expansion tank capacity
rate versus the temperature, the circuit internal volume should be three times the expansion volume.
RADIATOR SYSTEM
Cooling systems using radiators are operated sealed. engine through a pressure resistant heat exchanger. This
Radiators are built in complete modules, ready to in- principle is known under “remote radiator”name.
stall on anchors, over paved or stoned areas. Fans are Expansion tank
used to suck air through a finned tube bundle.
The expansion tank is delivered mounted on the radia-
The radiator module is of copper tube/aluminium fins tor and equipped with a low level switch and a valve,
type as standard. In maritime climate, acid polluted which limits circuit internal pressure and allows air
areas, and coal power plants, it is necessary to use entry if necessary ( as for automotive radiators). The
copper or heavy protected aluminium fins. If cotton expansion tank has to be placed above the higher part
fibres are present in radiator area, it is preferable to of the circuit, usually between 5 and 10 metres above
replace it by a cooling tower with special air filtering generator set floor. When the radiators are placed re-
system. mote from power plant, install it in generator set room.
Radiator installation When the radiators are installed on the roof, expan-
sion tank remains on the radiator. The priming pipe
Radiators should be installed at a five ( 170 series) to must be connected close to the engine pump inlet,
ten (200 series) metres distance of power plant, to port 451. It must have a sufficient diameter to avoid
prevent exhaust gases recirculating through radiator cavitation effects (DN 50). To limit recirculating, the
bundles. Radiators should be installed at a ten metres degasing connections must be throttled to ID 6 max.
distance of mechanical containers, to prevent exhaust If higher part(s) of the circuit can’t be connected to
gases recirculating through the radiator bundles. If mul- the expansion tank, they must be equipped with a
tiple radiators are installed, it is recommended to group degasing handvalve.
them, ensuring that the lateral air inlet section is equal
or more than the top surface of the bundle This ar- It is mandatory to provide a permanent degasing of the
rangement ensures that hot air recirculating through engine, connecting a ascendant sloping pipe between
the radiator is minimized. Degasing points are equipped port 404 and expansion tank.
with venting cocks. Draining points shall be provided Maintenance water tank
on lower section of lines.
The maintenance water tank is used to store treated
If a radiator is placed on the roof of a high building, or water for the engine cooling systems. It is made of a
skyscraper, total static head shall be limited to 20 metres kit including a polyethylene tank, a portable electric
(2 bar - 29 psi). If this criteria is overpassed, the radia- pump and a set of flexible hoses. Clean water and chemi-
tor circuit shall be separated and interfaced with the cals can be added and mixed in the 1000 liters tank
(by circulating the tank content). The unit can also
retrieve and save the water when the engine needs to
Expansion tank be emptied during maintenance or repair work. Addi-
tional tanks are available on request.
g
asin
deg
g
in
im
pr
Radiator
Main
te
Wate nance
r tan
k
TOWER SYSTEM
The system makes it possible to use treated water in tower water. The evaporation losses must be compen-
the engine circuit while using fresh water in the cool- sated for by adding new water. To prevent the accumu-
ing tower circuit. The engine cooling loop is running lation of salts and minerals in the cooling media, a per-
in an exchanger as final cooler, and an expansion tank centage of the evaporation losses must be drained off.
is installed on this circuit.
Particular attention shall be paid to the raw water added
Cooling tower in tower circuit. If it contains earth, oxydes in sus-
The cooling water delivered by the circulating pump pension, installing a plates exchanger, engine side is
passes through exchanger, takes heat, and then is the wrong choice, because of rapid clogging of the tower
sprayed into the tower’s internal cooling plates. Water water side. A tubular exchanger is more suitable be-
is collected in a basin at the bottom of the cooling cause it is easily cleaned.
tower, where a pump recirculates it. A fan provides a Raw water used in the tower should be filtered and
forced draft through the cooling tower, which, in con- treated to prevent algal formation, calcareous depos-
junction with the forced evaporation of the water, cools its and excessive salinity. A dosing pump shall be in-
the liquid and the internal plates. stalled on top-up water circuit, for treatment product
An advantage with using the cooling tower is that the addition. If chlorides are used as biocid, circuits and
coolant can reach a temperature lower than the ambi- exchanger must be of stainless manufacture.The tower
ent temperature due to a forced evaporation of the may be painted with strong water resistant paint.
From this table, you can determine the temperature of Some worldwide temperatures are given here for weath-
“wet bulb”of thermometer, from both the ambient tem- ering evaluation, according to country. Be aware that
perature and the relative humidity. Practical tempera- some days in the year, this temperature may be ex-
ture of water exiting tower will be 10°C over the wet ceeded. (don’t accept stringent contractual guarantees
bulb temperature.You can see,that the drier is the air, of result).
the more the evaporation is intense, and the cooling tower
efficiency increases. For a tropical climate, where humid-
ity is any time near 100%, a cooling tower will not be
efficient: choose oversized radiator or raw water if avail- Country Max dry Associat.
(station) bulb wet bulb
Units °C °C
Relative
Associated wet bulb temp. °C Algeria (Alger) 35 25
humid. Australia (Alice Springs) 40 25
(%) Air temperature °C Brazil (Rio Janeiro) 34 27
30 35 40 45 50 China (Shangaï) 34 27
Congo (Brazaville) 34 27
10 13.0 15.5 18.5 21.0 23.0
Egypt (Cairo) 39 24
20 15.5 18.5 22.0 25.0 28.0
France (Paris) 32 21
30 17.9 21.5 25.0 28.5 32.0 Hong Kong (Hong Kong) 33 27
40 19.9 24.0 27.5 31.5 India (Calcutta) 37 28
50 21.9 26.0 30.0 Indonesia (Djakarta) 32 27
60 23.8 28.0 32.5 Pakistan (Karachi) 38 28
70 25.5 30.0 Saudi Arabia (Dharhan) 44 30
80 27.2 32.0 Singapore (Singapore) 33 28
90 28.8 Russia (Moscow) 30 21
100 30.0 Vietnam (Da Nang) 36 30
Expa
nsion
tank
coolin
g towe
r
ng
Degasi
top-u
p
ing treatm water
im ent
Pr
Plate
s hea Deco
t exch n
ange
r valve centrati
o n
r
ilte
shf
Me
Main
te
wate nance
r tan
k
t
uni
mp
Pu
Expansion ta
nk
sing
Dega
From th
e river
ing
im
Pr
Sand
sepa
rator
Main
te
ate
r wate nance
r tan
ww k
Ra p
pum
To the
river
4.Partnership
4.1 ENGINEERING 4.2 MAINTENANCE
Engineering of LFO Power Plants is performed by The Group is well represented world wide and can there-
Cummins Wärtsilä project team supported by local rep- fore commit itself to long lasting relations with its
resentatives. Some information given in this handbook clients. The Cummins Wärtsilä service organization will
may be used for pre-configuration studies. At any time, not only participate in start up of plant but also en-
up-to-date information is available for Cummins gages itself to help the user for the operation and
Wärtsilä representatives, in Cummins Wärtsilä offices, maintenance of the plant during commercial op-
for a final design. eration.
Commissioning Preventive maintenance
Commissioning of the equipment delivered by Cummins In order to maintain a sustainable operation it is of
Wärtsilä is normally included in the main contract. importance that the maintenance of the power plant
Documentation is performed continuously.
The contents of the final documentation depends on Such a maintenance program is established in the Pre-
the extent of delivery. In principle, the following docu- ventive Maintenance Guidelines included in contrac-
ments are included in each delivery from Cummins tual documentation, which is a comprehensive instruc-
Wärtsilä : tion describing when certain activities will take place.
Some of them can easily be performed by the plant
- Installation drawings and diagrams, operation personnel but certain activities need exter-
- Installation handbook, nal assistance from Cummins Wärtsilä network person-
nel.
- Operator’s manual,
- Operation and maintenance manuals for components,
4.3 OPERATION OF THE POWER PLANT
- Parts list. Cummins Wärtsilä can when appropriate enter into
operational agreements which implies that when a cus-
A basic operator training session at the factory or on
tomers so requires Cummins Wärtsilä can on his behalf
site is available on request. This training may be ori-
operate the plant. All consumables such as filter, and
ented to mechanical and diesel engines, or to power
lube oil can be arranged by Cummins-Wärtsilä.
plant and electrical systems.
The plant will be interconnected to the service main
office where all operational parameters can be studied
and measures recommended for adjustment of the plant.
5. Units,Formulae
5.1 CURRENT EQUIVALENTS
Power imperial measurements
Energy measurements
Air conditioning
To convert from Unit_1 to Unit_2, use the two conversion lines Unit_1 to Ref_Unit and
Unit_2 to Ref_Unit as described hereafter:
Factor _ 1
Unit_1 .............................................................................. ......................... Unit_2
Factor _ 2
Scientific notation
Prefix
Length
Area
Square inch ............................................. in2 ........................ 6.452 E-4 ......... m2 ............... Square meter
Square foot .............................................. ft2 ......................... 9.290 E-2 ......... m2 ............... Square meter
Square yard ............................................. yd2 ....................... 8.361 E-1 ......... m2 ............... Square meter
Acre ......................................................... acre ................ 4.047 E+3 ........ m2 ............... Square meter
Volume
Cubic inch ................................................ in3 ........................ 1.639 E-5 ......... m3 ............... Cubic meter
Cubic foot ................................................ ft3 ......................... 2.832 E-2 ......... m3 ............... Cubic meter
Cubic yard ............................................... yd3 ....................... 7.646 E-1 ......... m3 ............... Cubic meter
US gallon ................................................. gal ................... 3.785 E-3 ......... m3 ............... Cubic meter
Acre.inch ................................................. acre.in ............. 1.028 E+2 ........ m3 ............... Cubic meter
Acre.foot .................................................. acre.ft ............. 1.233 E+3 ........ m3 ............... Cubic meter
Mass
Force
Force
Pressure
Pressure,, stress
Hectopascal, millibar ............................... hPa, mbar ....... 1.000 E+2 ........ Pa, N/m2 ...... Pascal
Kilopascal, Pieze ..................................... Pz, kPa, kN/m2 . 1.000 E+3 ........ Pa, N/m2 ...... Pascal
Newton per square centimeter ................. N/cm2 ................. 1.000 E+4 ........ Pa, N/m2 ...... Pascal
Bar ........................................................... bar .................. 1.000 E+5 ........ Pa, N/m2 ...... Pascal
Megapascal ............................................. MPa, N/mm2 .... 1.000 E+6 ........ Pa, N/m2 ...... Pascal
Meter of water ......................................... mW mW, mH20, mCE . 9.807 E+3 ........ Pa, N/m2 ...... Pascal
Kilogramforce per square mm .................. kgf/mm2 ............. 9.807 E+6 ........ Pa, N/m2 ...... Pascal
Atmosphere (technical) ............................ kgf/cm2, At ..... 9.807 E+4 ........ Pa, N/m2 ...... Pascal
Atmosphere (standard) ............................ atm ................. 1.013 E+5 ........ Pa, N/m2 ...... Pascal
pressure
pressure,, stress (contin uation)
(continuation)
Millimeter of mercury, Torricelli ................. mmHg, Torr ..... 1.333 E+2 ........ Pa, N/m2 ...... Pascal
Centimeter of mercury ............................. cmHg .............. 1.333 E+3 ........ Pa, N/m2 ...... Pascal
Inch of water ............................................ inH2O, inW ...... 2.491 E+2 ........ Pa, N/m2 ...... Pascal
Foot of water............................................ ftH2O, ftW ....... 2.989 E+3 ........ Pa, N/m2 ...... Pascal
Inch of mercury ....................................... inHg ................ 3.386 E+3 ........ Pa, N/m2 ...... Pascal
Foot of mercury ....................................... ftHg ................. 4.064 E+4 ........ Pa, N/m2 ...... Pascal
Pound.force per square inch .................... psi psi, lbf/in2 ......... 6.895 E+3 ........ Pa, N/m2 ...... Pascal
Pound.force per square foot ..................... lbf/ft2 ................... 4.788 E+1 ........ Pa, N/m2 ...... Pascal
Temperature
Power
Energy
Energy
Kilowatt·hour per kilogram ....................... kWh/kg ........... 3.600 E+6 ........ J/kg ......... Joule per kg
Kilowatt·hour per pound ........................... kWh/lb ............ 7.937 E+6 ........ J/kg ......... Joule per kg
Kilocalorie per kilogram ........................... CHU/lb, kcal/kg .. 4.187 E+3 ........ J/kg ......... Joule per kg
Kilocalorie per pound ............................... kcal/lb ............. 9.230 E+3 ........ J/kg ......... Joule per kg
British thermal unit per pound .................. Btu/lb .............. 2.326 E+3 ........ J/kg ......... Joule per kg
Watt·hour per cubic meter ....................... Wh/m3 ................ 3.600 E+3 ........ J/m3 ........... J per cubic meter
Watt·hour per cubic inch .......................... Wh/in3 ................ 5.900 E-2 ......... J/m3 ........... J per cubic meter
Watt·hour per cubic foot ........................... Wh/ft3 ................. 1.020 E+2 ........ J/m3 ........... J per cubic meter
Kilocalorie per cubic meter ...................... kcal/m3 ............... 4.187 E+3 ........ J/m3 ........... J per cubic meter
Kilocalorie per cubic inch ......................... kcal/in3 ............... 6.862 E-2 ......... J/m3 ........... J per cubic meter
Kilocalorie per cubic foot .......................... kcalft3 ................. 1.186 E+2 ........ J/m3 ........... J per cubic meter
Btu per cubic foot ..................................... Btu/ft 3 ................. 3.726 E+4 ........ J/m3 ........... J per cubic meter
Btu per US Gallon .................................... Btu/USgal ....... 2.787 E+5 ........ J/m3 ........... J per cubic meter
CHU per cubic foot .................................. Pcu/ft3, CHU/ft3 . 6.707 E+4 ........ J/m3 ........... J per cubic meter
Therm per US Gallon .............................. Therm/USgal .. 2.787 E+10 ...... J/m3 ........... J per cubic meter
Kilowatt·hour per (kilogram·Kelvin) .......... kWh/(kg·K) ...... 3.600 E+6 ........ J/(kg·K) ... Joule per kg.K
Kilocalorie per (kilogram·Kelvin) .............. kcal/(kg·K) ...... 4.187 E+3 ........ J/(kg·K) ... Joule per kg.K
Btu per (pound·degree Fahrenheit) .......... Btu/(lb·°F) ....... 4.187 E+3 ........ J/(kg·K) ... Joule per kg.K
Kilowatt·hour/(cubic meter·Kelvin) ............ kWh/(m3·K) ..... 3.600 E+6 ........ J/(m3·K) ... Joule / m3.K
Kilocalorie per (cubic meter·Kelvin) ......... kcal/(m3·K) ...... 4.187 E+3 ........ J/(m3·K) ... Joule / m3.K
Btu per (cubic inch·degree Fahr.) ............. Btu/(in3·°F) ...... 1.159 E+8 ........ J/(m3·K) ... Joule / m3.K
Btu per (cubic foot·degree Fahr.) ............. Btu/(ft3·°F) ...... 6.707 E+4 ........ J/(m3·K) ... Joule / m3.K
Water hardness
hardness
German degree ....................................... °dH ................. 1.790 E+1 ... ppm(wt) ... Parts / million CaO3
French degree ......................................... °Fr ................... 1.000 E+1 ... ppm(wt) ... Parts / million CaO3
Clark degree ............................................ °Ck ................. 1.425 E+1 ... ppm(wt) ... Parts / million CaO3
Millival per liter ......................................... mval/l .............. 5.000 E+1 ... ppm(wt) ... Parts / million CaO3
Grain of CaO3 per US Gallon of water ..... GPG ............... 1.712 E+1 ... ppm(wt) ... Parts / million CaO3
Miscellaneous
5.3 FORMULAE
kW mechanical output
BMEP (bar) = 1.528 x —————————————————————————— (for 4-cycle engine)
(rated r.p.m.) x (stroke in m)x (bore in m)2 x (nb of cylinders)
Temperature
(oF - 32)
o o
Temp. ( C) = ———————— F = (oC x 1.8) + 32
1.8
kW kW
PF = ——— kVA = ——
kVA PF
V x A x PF kVA x PF VxA
kWe = ————— ———
1000 1000
V x A x PF kVA x PF
engine meca. kW = —————— ——————
1000 x gen. eff. gen. eff.
VxA V x A x 1.732
kVA = ——— ———————
1000 1000
generator frequency