Different Types of Line Protection: Reasons For Faults
Different Types of Line Protection: Reasons For Faults
LP5p02b2300-Rev 0. 2b:1
2001-11-15
ABB Automation Technology Products AB
Different types of line protections
Västerås Sweden
LP5p02b2300-Rev 0. 2b:2
2001-11-15
ABB Automation Technology Products AB
Different types of line protections
Västerås Sweden
LP5p02b2300-Rev 0. 2b:3
2001-11-15
ABB Automation Technology Products AB
Different types of line protections
Västerås Sweden
Distance protection
The distance protection is the most commonly used protection
for meshed sub-transmission and transmission networks. The
protection is connected to the three phase current and voltage
transformers of the line to be protected. An alternative is to use
the busbar voltage transformers. The distance relay makes a
decision if the impedance from the terminal to the fault point is
within a characteristic area of the complex impedance plane. The
impedance can be defined as the ration between voltage and
LP5p02b2300-Rev 0. 2b:4
2001-11-15
ABB Automation Technology Products AB
Different types of line protections
Västerås Sweden
V
current. Z = The choice of voltage (phase-phase or phase-
I
earth) is dependent of the fault type to be detected.
The design and ability of a distance protection relay vary
between different types. The hardware of the distance relay can
be of the following types:
• Electromechanical relays. This is the oldest type of distance
relay and the function is based on magnetic forces in balance
relays. Electromechanical relays have very complicated
mechanical design.
• Static electronic relays. This type of distance relays uses
analogue electronics. The phase comparison principle is
mostly used. The technique is based on time measurement
between zero-crossings of sinusoidal quantities.
• Digital computer based relays. In this type of relay the input
quantities (voltage and current) are sampled. The sampled
values are processed in the relay to check the locus of the
apparent impedance to the fault point.
For correct judgement of the apparent impedance different faults
loops are available, depending on the fault type. The impedance
to be studied by the protection can be defined as:
V faultloop
Z apparent =
I faultloop
We have the following fault loops for the different fault types:
LP5p02b2300-Rev 0. 2b:5
2001-11-15
ABB Automation Technology Products AB
Different types of line protections
Västerås Sweden
T–R VT - VR IT - IR
R-S–T Any phase- Corresponding phase current
earth voltage Corresponding phase-phase
any phase- current
phase voltage
R-S-T– Any phase- Corresponding phase current
Earth earth voltage Corresponding phase-phase
any phase- current
phase voltage
LP5p02b2300-Rev 0. 2b:6
2001-11-15
ABB Automation Technology Products AB
Different types of line protections
Västerås Sweden
line impedance). Normally the trip from zone 2 has a short delay
(about 0.4 s).
Zone 3: The impedance reach is set to cover a remote back-up
zone (for example adjacent lines) with some margin. Normally
the trip from zone 3 has a short delay (about 0.8 s).
Zones 4 and 5: The impedance reach is set to cover a remote
back-up zone (for example adjacent lines) with some margin.
Normally the trip from zone 4 and 5 has a longer delay than zone
3. Zones 4 and 5 can also be used for special functions such as
reverse looking zones in blocking communication schemes.
The characteristics of the impedance zones of the distance relays
differ between the distance protections. The most common
characteristics are:
• The mho circle
• Any type of polygon
As the distance protection is a non-unit protection it can be used
as a back-up for other types of protections, for example unit
protections such as differential protections.
The distance protection is also very commonly used in protection
schemes using communication such as blocking schemes and
permissive under- and overreach schemes.
An advantage with the distance protection is that the reach is
almost independent of the fault current level.
Differential protection
The differential protection is the often used as protection for
short lines in meshed distribution, sub-transmission and
transmission networks.
The principal function of the differential protection is very
simple. All current flowing into the protected zone is put into the
protection. In normal operation and in case of an external fault
the instantaneous sum of all currents into the protected object
will be zero. In case of an internal fault there will be a
differential current, which is a criterion for operation of the
differential protection.
The line differential protection must have exchange of data with
the remote terminal (terminals) of the line. The instantaneous
current values are sent to one (master-slave system) or to all
terminals (master-master system). The requirements on the
communication media are therefor quit hard. For line differential
protections the following communications are used:
• Galvanic wire: Applicable for relatively short distances only
• Optic fibre communication
The line differential protection can be described as follows:
• The protection is an absolutely selective unit protection. This
means that it will only detect and give trip for faults within
Substation Automation & Protection Training
LP5p02b2300-Rev 0. 2b:7
2001-11-15
ABB Automation Technology Products AB
Different types of line protections
Västerås Sweden
LP5p02b2300-Rev 0. 2b:8
2001-11-15
ABB Automation Technology Products AB
Different types of line protections
Västerås Sweden
External fault
I1 I2
I1
I2
LP5p02b2300-Rev 0. 2b:9
2001-11-15
ABB Automation Technology Products AB
Different types of line protections
Västerås Sweden
Internal fault
I1 I2
I1
I2
LP5p02b2300-Rev 0. 2b:10
2001-11-15
ABB Automation Technology Products AB
Different types of line protections
Västerås Sweden
Wave Wave
velocity v velocity v
LP5p02b2300-Rev 0. 2b:11
2001-11-15
ABB Automation Technology Products AB
Different types of line protections
Västerås Sweden
LP5p02b2300-Rev 0. 2b:12
2001-11-15
ABB Automation Technology Products AB
Different types of line protections
Västerås Sweden
LP5p02b2300-Rev 0. 2b:13
2001-11-15