Catalogue OSM Recloser - NOJA
Catalogue OSM Recloser - NOJA
OSM
PRODUCT GUIDE
OSM AUTOMATIC
CIRCUIT RECLOSER
15kV, 27kV & 38kV Models
1. Product Guide OSM Automatic Circuit Recloser 15kV 27kV 38kV Models Introduction
INTRODUCTION
The in-built user configurable distribution a communications system and will reduce outage time
automation functionality can be used with or without and increase profitability in your network.
OSM15 Autorecloser OSM27 Autorecloser OSM38 Autorecloser OSM38 Single Phase Autorecloser
Introduction Product Guide OSM Automatic Circuit Recloser 15kV 27kV 38kV Models 2. 1.
OVERVIEW
The OSM15, OSM27 and OSM38 automatic circuit The status of the recloser is also reflected by
reclosers incorporate vacuum interrupters inside microswitches connected to the control electronics.
solid dielectric insulated poles which are housed The electronic circuit board where the microswitch
within the arc fault venting designed, stainless steel is fitted has no active elements which dramatically
tank. This ensures maximum life and reliability with improves impulse immunity.
a fully insulated arrangement inside the long life
housing. The main circuit bushings are manufactured
from UV stable silicone rubber, providing a high
Voltage is measured on all six (6) bushings for the creepage distance silicone bushing extension,
three phase devices or on two (2) bushings for which is completed with optional termination
the single phase device. Current is measured on accessories.
all three (3) phases or single phase using current
transformers.
The magnetic actuators are operated from stored
Each phase of the recloser mechanism is operated energy charged capacitors located in the RC10
by an individual magnetic actuator. In three phase control cubicle. There is a rating plate located
operation the magnetic actuators are mechanically in the base of the tank that provides tank rating
interlocked to guarantee correct operation The details in accordance with the requirements of
device is latched in the closed position by magnetic ANSI C37.60. There is an earthing point on the
latching and each magnetic actuator uses a single side of the tank.
coil.
The OSM is supplied with tin plated brass cable
The recloser can be mechanically tripped using connectors on each bushing. The cable connectors
the yellow mechanical hook stick operated lever can be supplied in the form of tunnel terminals to
in the base of the tank. The device Open/Close suit cable up to 260mm2 or 2 hole NEMA cable
indication, also located in the base of the tank, palms.
uses a green ‘0’ to designate contacts are open
and a red ‘I’ to designate contacts closed. The cross sectional diagrams below detail the OSM
tank configuration and main components.
PROTECTION
MEASUREMENT
Voltage is measured on each bushing and current provides a full log of all operational history including
is measured on each phase of the OSM recloser setting changes, operations and fault history. The fault
using capacitively coupled voltage sensors and history logs include 50 cycles of pre-trip history to allow
current transformers. analysis of the fault propagation.
Phase to Earth Voltage: REMOTE CONTROL
Range 0.3 - 22.0kV, Accuracy ± 1% or ± 0.1kV
Phase to Phase Voltage: A USB front panel interface is provided for a PC to connect
Range 0.5 - 38.0kV, Accuracy ± 2% or ± 0.1kV directly to the RC10 to provide engineering access. In addition
Phase Current: remote control systems can connect to the RC10 using
Range 0 - 800A, Accuracy ± 1% or ± 4A a number of interfaces which include: RS232, USB and
Residual Current: Ethernet. Serial connections offer 300-115200bps and both
Range 0 - 100A, Accuracy ± 5% or ± 0.5A full and half duplex modes. USB ports can be configured for
Active, Reactive and Total Power: Serial, Wi-fi and LAN. The Ethernet port provides connection
Range 40 - 800A, 4.5 - 38kV, Accuracy ± 2% to 10/100BaseT networks.
Active, Reactive and Energy: NOJA Power application is available for download from the
Range 40 - 800A, 4.5 - 38kV, Accuracy ± 2% Apple app store, it will run on Apple iPhones and iPads to
Frequency: provide full local and remote control of all products connected
Range 46-55Hz, 55-65Hz to the RC10 control and communication cubicle.
Accuracy at dF/dT < 0.2Hz/s: ± 0.025Hz
Range 46-55Hz, 55-65Hz DNP3, IEC60870-5-101 and 104 communications protocols
Accuracy at dF/dT < 0.5Hz/s: ± 0.05Hz are provided in the standard product combined with our
Power Factor: ability to engineer new protocols to meet specified customer
Range 0-1, Accuracy ± 0.02 requests.
The control cubicle has space to mount a radio or modem.
POWER QUALITY The onboard radio power supply is rated at 12V 20W on
average over a rolling 60 seconds window.
Oscillography
Multiple channel wave capture of voltage and current. I/O modules with eight (8) user configurable inputs and eight
1600 samples per second. Event triggered data (8) user configurable outputs can be ordered as options in the
memory storage. RC10 control. Up to two I/O modules can be fitted extending
this to sixteen inputs and sixteen outputs.
Harmonics
15th Harmonic (750Hz) capable. Current measurement User Constructed Logic Expressions provide custom user
up to 1000A. Harmonic data is averaged over 64 functions. Evaluated (true/false) logic expressions initiate
cycles and is made available every 32 cycles. actions, activates SCADA points, turns on or off I/O output
relays and/or turns on other additional expressions.
Interruption
Collects long and short interruption information for Three (3) user configurable relay digital inputs are included
calculating SAIDI, SAIFI and MAIFI. as standard.
Sag and Swell
Sag and Swell Information of voltage outside user LOAD PROFILE LOG
configured range and set time period. The Load Profile is logged with a user configured
Captured data can be stored on internal flash memory integration period of either 1, 2, 5, 10, 15, 30, 60 and
or external USB drive. 120 minutes.
The captured Oscillography files are saved in the file Up to 10000 events can be stored in the memory
system in the IEEE Std C37.111-1999 Comtrade binary. which corresponds to a 417 day, 60 minute, integration
Harmonic data, long and short duration interruptions period.
and sag/swell logs can be transferred to a USB in CMS can be used to upload and plot the data.
IEEE P1159.3 PQDIF.
EVENT LOG
The RC10 control provides two methods to access the
event logs which time and date stamped to a 0.001 sec
resolution.
The first method is from the RC LCD display, it provides
critical operations data for the linesman and includes
close/open operations, fault types, phase and peak level
of fault current.
The second method is by PC upload using CMS. It
Introduction Product Guide OSM Automatic Circuit Recloser 15kV 27kV 38kV Models 6.
Single Phase Pole Mounting Arrangement Terminal Connectors Three Phase Pole Mounting Arrangement
OSM38
7. Product Guide OSM Automatic Circuit Recloser 15kV 27kV 38kV Models Introduction
FIELD Safety
The enginners will be able to read three phase-current In addition, the app also allows the field engineers to
and phase-voltage (voltage on all six bushings), frequency, control Recloser functionality such as Trip/Close, Local/
power, power factor, power flow direction and energy Remote, Active Protection Group, Protection On/Off, Auto
measurements. Reclose On/Off, Live Line On/Off and Earth Fault On/
Off among others.
NOJA Power Recloser Remote App NOJA Power Recloser Remote App SCREENS
9. Product Guide OSM Automatic Circuit Recloser 15kV 27kV 38kV Models Introduction
Interoperable
Local Panel
RC10
RELAY MODULE
Remote Panel
(maximum length 120m)
CMS on Computer
Radio Module
Oscillography Data
The RC-10 can capture an oscillogram of the
waveform when a specific event occurs such as a
trip or a close. The amount of waveform captured
prior to the trigger can be configured by the user.
This ranges from 0 to 80% of the capture prior to the
trigger point. The data can be used to analyse power
quality fluctuations.
Harmonics
Harmonics are waves which have frequency multiples
of the fundamental frequency. The RC-10 measures PQS Harmonic Current Graph
Total Harmonic Distortion (THD), Total Demand
Distortion (TDD) and Harmonics Voltages and Sag and Swell
Currents up to the 15th Harmonic. The RC-10 records voltage variations (sags & swells)
occurring outside a user set period of time. Sags &
15th Harmonic (750Hz) capable. Current measurement Swell voltages are based on the phase to ground
up to 1000A. Harmonic data is averaged over 64 voltages.
cycles and is made available every 32 cycles.
Captured data can be stored on internal flash memory
Long and Short Duration Interruption or external USB drive.
The RC-10 stores information relating to long and
short duration interruptions. This information is used The captured Oscillography files are saved in the file
to calculate SAIDI (System Average Duration Index), system in the IEEE Std C37.111-1999 Comtrade binary.
SAIFI (System Average Interruption Frequency
Index) and MAIFI (Momentary Average Interruption Harmonic data, long and short duration interruptions
Frequency Index). Both long and short interruptions and sag/swell logs can be transferred to a USB in
are based on the Loss of Supply Detection (LSD). IEEE P1159.3 PQDIF.
Collects long and short interruption information for The PQS is available to all NOJA Power OSM range
calculating SAIDI, SAIFI and MAIFI. ACR customers, free of charge.
®
NOJA Power AustrAlia NOJA Power BRAZIL NOJA Power CHILE NOJA Power UK NOJA Power USA
Corporate Office & Factory Office & Factory Sales Office Sales Office Sales Office
NOJA Power Switchgear Pty Ltd NOJA Power do Brasil Ltda NOJA Power SpA NOJA Power Limited NOJA Power, LLC
16 Archimedes Place, Murarrie Avenida Pierre Simon de Laplace, 764 Av 11 de septiembre 1881, Of 1415 4 Stalyhill Drive, Stalybridge 3611 SW Humphrey Blvd
Brisbane Qld 4172, Australia Techno Park – Campinas – SP Providencia, Santiago Cheshire SK 15 2TR Portland OR 97221
CEP 13069-301, Brasil Chile United Kingdom United States of America
Phone: +61 (7) 3907 8777 Phone: +55 (19) 3283 0041 Phone: +56 (2) 8979649 Phone: +44 (01865) 58 9499 Mobile: +1 (971) 404-9039
Fax: +61 (7) 3399 6777 Fax: +55 (19) 3283 0041 Email: [email protected] Fax: +44 (01865) 58 9400 Email: [email protected]
Email: [email protected] Email: [email protected] Web: w w w.nojapower.cl Email: [email protected] Web: www.nojapower.com
Web: www.nojapower.com.au Web: www.nojapower.com.br Web: www.nojapower.co.uk
Scan to view
NOJA Power
website
NOJA Power® is a registered trademarks of NOJA Power Switchgear Pty Ltd. This document is copyright and is intended for users and distributors of NOJA Power Switchgear product. It contains information that is the intellectual
property of NOJA Power Switchgear and the document, or any part thereof, should not be copied or reproduced in any form without written permission from NOJA Power Switchgear.
NOJA Power Switchgear applies a policy of continued fundamental research and development and reserves the right to change designs and specifications of this product without notice. NOJA Power Switchgear does not accept
any responsibility for loss or damage incurred by anyone as a result of acting or refraining from action based on information in this Product Guide.
NOJA-560-03