OSM
PRODUCT GUIDE
OSM AUTOMATIC
CIRCUIT RECLOSER
15kV, 27kV & 38kV Models
1. Product Guide OSM Automatic Circuit Recloser 15kV 27kV 38kV Models Introduction

INTRODUCTION

The OSM15, OSM27 and OSM38 automatic


circuit reclosers are designed for use on overhead
distribution lines as well as distribution substation
applications for all voltage classes up to 15kV,
27kV and 38kV respectively.

The OSM tanks are manufactured from stainless


steel and powder coated a light grey colour.

The product is supplied complete with an RC


control and communications cubicle. The RC
control cubicle provides all the protection, data
logging and communications functions in a single
device. The OSM has been designed for use as
a stand alone device that is easily integrated into
distribution automation and remote control schemes
using the in-built communications capability.

The product has been extensively type tested


by independent laboratories to ensure long life
and reliability under the harshest environmental
conditions. The OSM automatic circuit recloser
is the only solid di-electric insulated recloser
to provide controlled arc fault venting and the
independent testing provides verification of this
important safety feature.
OSM recloser and RC Control and Communications Cubicle
The product uses technology developed and refined
over the last decade.

The in-built user configurable distribution a communications system and will reduce outage time
automation functionality can be used with or without and increase profitability in your network.

OSM15 Autorecloser OSM27 Autorecloser OSM38 Autorecloser OSM38 Single Phase Autorecloser
Introduction Product Guide OSM Automatic Circuit Recloser 15kV 27kV 38kV Models 2. 1.

OVERVIEW

The OSM15, OSM27 and OSM38 automatic circuit The status of the recloser is also reflected by
reclosers incorporate vacuum interrupters inside microswitches connected to the control electronics.
solid dielectric insulated poles which are housed The electronic circuit board where the microswitch
within the arc fault venting designed, stainless steel is fitted has no active elements which dramatically
tank. This ensures maximum life and reliability with improves impulse immunity.
a fully insulated arrangement inside the long life
housing. The main circuit bushings are manufactured
from UV stable silicone rubber, providing a high
Voltage is measured on all six (6) bushings for the creepage distance silicone bushing extension,
three phase devices or on two (2) bushings for which is completed with optional termination
the single phase device. Current is measured on accessories.
all three (3) phases or single phase using current
transformers.
The magnetic actuators are operated from stored
Each phase of the recloser mechanism is operated energy charged capacitors located in the RC10
by an individual magnetic actuator. In three phase control cubicle. There is a rating plate located
operation the magnetic actuators are mechanically in the base of the tank that provides tank rating
interlocked to guarantee correct operation The details in accordance with the requirements of
device is latched in the closed position by magnetic ANSI C37.60. There is an earthing point on the
latching and each magnetic actuator uses a single side of the tank.
coil.
The OSM is supplied with tin plated brass cable
The recloser can be mechanically tripped using connectors on each bushing. The cable connectors
the yellow mechanical hook stick operated lever can be supplied in the form of tunnel terminals to
in the base of the tank. The device Open/Close suit cable up to 260mm2 or 2 hole NEMA cable
indication, also located in the base of the tank, palms.
uses a green ‘0’ to designate contacts are open
and a red ‘I’ to designate contacts closed. The cross sectional diagrams below detail the OSM
tank configuration and main components.

1. Vacuum Interrupter 9. Current Transformer (position varies with model)


2. Insulated Drive Rod 10 . Capacitively Coupled Voltage Sensor
3. Magnetic Actuator 11. Opening spring
4. Aromatic Epoxy Resin Housing 12 . Ceramic Breather
5. Silicone Rubber Bushing Boot 13. Mechanical Trip Ring
6. Cable Connector
7. Stainless Steel Tank
8. Auxiliary Switches

OSM Cross Sectional Diagram


3. Product Guide OSM Automatic Circuit Recloser 15kV 27kV 38kV Models Introduction

RC10 CONTROL &


COMMUNICATIONS CUBICLE
The RC10 control and communications cubicle
provides directional overcurrent, earth fault and
sensitive earth fault relay, auto reclosing relay,
instantaneous metering, event log, demand logger
and remote terminal unit (RTU) for remote control
in a single package.
The operator control panel is provided with a large
backlit LCD display and keypad to provide fast
navigation and local control.

The panel menus are presented in descriptive text


this provides ease of use for operators and reduces
the learning curve.
The control cubicle has three (3) main modules:
■■ The operator panel module which provides the
Human machine interface (HMI) .
■■ The Switchgear Interface Module (SIM) which
provides the power supply battery charger and RC10 Control &
incorporates the capacitors that provide the Communications Cubicle
tripping and closing energy to the OSM tank.
IP66/NEMA 4 Vandal
■■ The Relay module which provides the main proof cable housing
microprocessor and DSP functionality.
Temperature compensated float charging is
provided to the sealed lead acid batteries located stainless steel for a long, maintenance free lifetime.
in the RC10 control cubicle. The roof features a ceramic based insulating
coating that provides a 16°C reduction in internal
There is space provided inside the control cubicle temperature when the cubicle is exposed to 1.1kW
to install any communications equipment to be of solar radiation.
connected to the inbuilt RTU or I/O module.
The entry point for the control cable is housed
The equipment has been designed for the RC10 within a vandal-proof enclosure and the cubicle
control cubicle to operate over a temperature range door has a three point handle locking mechanism
of -40 to +55°C inside the IP66 sealed enclosure. making it extremely difficult to break into.
The cubicle is constructed out of powder coated
Introduction Product Guide OSM Automatic Circuit Recloser 15kV 27kV 38kV Models 4.

PROTECTION

■■ 4 Independent Protection Groups


(Each group contains independent protection
settings for each direction)
■■ Directional over current and earth fault protection
• Current Setting Range 3-1280A
• Setting Resolution 1A
■■ Inverse Time Protection
• Independent Curve Selection for Forward &
Reverse Direction
• 4 x IEC255 Curves
• 8 x ANSI Curves
• User Defined Curves
• 42 x Custom Curves
■■ Definite Time Protection
• 0-120 seconds
• Time Resolution 0.01 seconds
■■ High set Instantaneous element
■■ Directional Sensitive Earth Fault Protection
• Current Setting Range 1-80A
• 1-80A option available
• Setting Resolution 1A
• Definite Time 0-120 seconds
• Time Resolution 0.01 seconds
■■ Voltage Protection Element Local Control Panel
• Phase undervoltage balanced element (UV1)
• 3 phase load shedding
• Multiplier setting range: 0.6-1 of ■■ Zone Sequence Co-ordination
system voltage ■■ Cold Load Pickup
• Multiplier setting resolution: 0.01 • Cold load time ramp up: 1-400 min
• Trip time range: 0-180 sec • Cold load time ramp down: 0-60 min
• Trip time setting resolution: 0.01 sec • Cold load time resolution: 1 min
• Phase-to-Phase Undervoltage Element (UV2) • Cold load multiplier: 1-5 times pickup current
• Multiplier setting range: 0.6-1 • Cold load multiplier resolution: 0.1
of system voltage
• Multiplier setting resolution: 0.01 ■■ Inrush Restraint
• Trip time range: 0-180 sec • Inrush time: 0.01-10 sec
• Trip time setting resolution: 0.01 sec • Inrush time resolution: 0.01 sec
• Loss of Supply (UV3) • Inrush multiplier: 1-20
• Trip time range: 0-180 sec • Inrush multiplier resolution: 0.1
• Trip time setting resolution: 0.01 sec ■■ Temporary Time Addition
• Reclose time: 0-180 sec • Provides a stepped time delay to automatically
• Reclose time resolution: 0.01 sec isolate faulted sections in a feeder or correct
• Voltage Sag Protection (UV4 Sag) grading of devices in series.
• Trip time range: 1-180 sec ■■ Duty Cycle
• Trip time setting resolution: 0.01 sec • O-0.1sec-CO-1sec-CO-1sec-CO-60sec
• Min Multiplier: 0.01 - 0.8 recovery time
• Max Multiplier: 0.5 - 1.0
• Mid Multiplier: 05-1.0 ■■ Reclosing Times
• Phase (OV1) & Line-to-Line (OV2) Over Voltage • 1st reclosing time range 0.1 - 180 seconds
• Trip time range: 0-180 sec • 2nd reclosing time range 1 - 180 seconds
• Multiplier Setting Range: 1.00 -1.20 • 3rd reclosing time range 1 - 180 seconds
• Setting resolution 0.01 seconds
■■ Frequency Protection Element
• Under Frequency (UF) Pickup Range: 46-50Hz ■■ Auto Reclose
(50Hz system), 55-60Hz (60Hz system) • User configurable 1-4 trips to lockout,
• Over Frequency (OF) Pickup Range: 50-55Hz independently settable for overcurrent earth
(50Hz system), 60-65Hz (60Hz system) fault, sensitive earth fault and voltage
• Frequency settings resolution: 0.01Hz protection.
• Trip time range: 0-120 sec ■■ Live Line Function & Hot Line Tag Function
• Trip time setting resolution: 0.01 sec ■■ Negative Phase Sequence
■■ Voltage reclose control with automatic back ■■ Harmonic Protection
feed restoration provides loop automation ■■ Advanced Automation
functionality. ■■ Programmable Logic
5. Product Guide OSM Automatic Circuit Recloser 15kV 27kV 38kV Models Introduction

MEASUREMENT
Voltage is measured on each bushing and current provides a full log of all operational history including
is measured on each phase of the OSM recloser setting changes, operations and fault history. The fault
using capacitively coupled voltage sensors and history logs include 50 cycles of pre-trip history to allow
current transformers. analysis of the fault propagation.
Phase to Earth Voltage: REMOTE CONTROL
Range 0.3 - 22.0kV, Accuracy ± 1% or ± 0.1kV
Phase to Phase Voltage: A USB front panel interface is provided for a PC to connect
Range 0.5 - 38.0kV, Accuracy ± 2% or ± 0.1kV directly to the RC10 to provide engineering access. In addition
Phase Current: remote control systems can connect to the RC10 using
Range 0 - 800A, Accuracy ± 1% or ± 4A a number of interfaces which include: RS232, USB and
Residual Current: Ethernet. Serial connections offer 300-115200bps and both
Range 0 - 100A, Accuracy ± 5% or ± 0.5A full and half duplex modes. USB ports can be configured for
Active, Reactive and Total Power: Serial, Wi-fi and LAN. The Ethernet port provides connection
Range 40 - 800A, 4.5 - 38kV, Accuracy ± 2% to 10/100BaseT networks.
Active, Reactive and Energy: NOJA Power application is available for download from the
Range 40 - 800A, 4.5 - 38kV, Accuracy ± 2% Apple app store, it will run on Apple iPhones and iPads to
Frequency: provide full local and remote control of all products connected
Range 46-55Hz, 55-65Hz to the RC10 control and communication cubicle.
Accuracy at dF/dT < 0.2Hz/s: ± 0.025Hz
Range 46-55Hz, 55-65Hz DNP3, IEC60870-5-101 and 104 communications protocols
Accuracy at dF/dT < 0.5Hz/s: ± 0.05Hz are provided in the standard product combined with our
Power Factor: ability to engineer new protocols to meet specified customer
Range 0-1, Accuracy ± 0.02 requests.
The control cubicle has space to mount a radio or modem.
POWER QUALITY The onboard radio power supply is rated at 12V 20W on
average over a rolling 60 seconds window.
Oscillography
Multiple channel wave capture of voltage and current. I/O modules with eight (8) user configurable inputs and eight
1600 samples per second. Event triggered data (8) user configurable outputs can be ordered as options in the
memory storage. RC10 control. Up to two I/O modules can be fitted extending
this to sixteen inputs and sixteen outputs.
Harmonics
15th Harmonic (750Hz) capable. Current measurement User Constructed Logic Expressions provide custom user
up to 1000A. Harmonic data is averaged over 64 functions. Evaluated (true/false) logic expressions initiate
cycles and is made available every 32 cycles. actions, activates SCADA points, turns on or off I/O output
relays and/or turns on other additional expressions.
Interruption
Collects long and short interruption information for Three (3) user configurable relay digital inputs are included
calculating SAIDI, SAIFI and MAIFI. as standard.
Sag and Swell
Sag and Swell Information of voltage outside user LOAD PROFILE LOG
configured range and set time period. The Load Profile is logged with a user configured
Captured data can be stored on internal flash memory integration period of either 1, 2, 5, 10, 15, 30, 60 and
or external USB drive. 120 minutes.
The captured Oscillography files are saved in the file Up to 10000 events can be stored in the memory
system in the IEEE Std C37.111-1999 Comtrade binary. which corresponds to a 417 day, 60 minute, integration
Harmonic data, long and short duration interruptions period.
and sag/swell logs can be transferred to a USB in CMS can be used to upload and plot the data.
IEEE P1159.3 PQDIF.

EVENT LOG
The RC10 control provides two methods to access the
event logs which time and date stamped to a 0.001 sec
resolution.
The first method is from the RC LCD display, it provides
critical operations data for the linesman and includes
close/open operations, fault types, phase and peak level
of fault current.
The second method is by PC upload using CMS. It
Introduction Product Guide OSM Automatic Circuit Recloser 15kV 27kV 38kV Models 6.

Single Phase Pole Mounting Arrangement Terminal Connectors Three Phase Pole Mounting Arrangement

■■ Earthing should be in accordance with the


technical manual. Earthing required is a main
earth bond from the tank to ground and a
tee-off to the RC10 control cubicle from this
main earth bond. Minimum 35mm2 earth cable
should be used. Tunnel Connector Two Hole NEMA
Pad Option

■■ Each HV terminal on the OSM has a tin-plated


brass connector at the end with options for cable
connection as follows:
• A Tunnel terminal arrangement suitable
for cable sizes from 40mm2 to 260mm2.
Cables are secured in the connector with
two hexagon socket screws.
• Two hole cable palms with NEMA spacing.
The cable palms are supplied with two (2)
M12x25mm stainless steel bolts together
OSM38 Single Phase Recloser
with flat and spring washers.

■■ Pole mounting brackets and surge arrester


mounting brackets are provided as standard.

■■ Full installation details are provided in the


technical manual, this diagram is provided to
show a typical arrangement only.

OSM38
7. Product Guide OSM Automatic Circuit Recloser 15kV 27kV 38kV Models Introduction

Arc Fault Containment

NOJA Power Automatic recloser complies with arc fault


containment and venting standards. If failure occurs, internal
arcing is contained and any gases generated are safely
vented.

NOJA Power’s Patent Arc fault contained and vented design


is in accordance with the requirements of IEC62271-200
Clause 6.106 and Annex A.

The NOJA Power OSM range of reclosers offers solid


dielectric installation have been designed and type tested to
provide this important safety feature.

The NOJA Power OSM range of reclosers have successfully


Arc fault containment VENTED Design
passed the arc fault containment type test and have complied
with the specifications. Finite Element Analysis (FEA) on
insulation systems is conducted using ANSYS to optimise
and minimise electrical stresses inside solid dielectric material
on the surface of insulators in the air.

FEA analysis addresses the following issues:


• Partial discharge
• Impulse withstand
• Longevity due to surface degradation

Arc fault containment testing

Finite Element Analysis


Quality & Environmental CertifIED

NOJA Power is unique among comparable companies


in attaining AS/NZS ISO 14001 and AS/NZS 4801
accreditation. NOJA Power’s SF6-free Automatic
Recloser is a key environmental initiative using solid
dielectric insulation to reduce environmental footprint. SF6
Load-break switches gas has a potent global warming
potential of 23,900 times that of CO2 so by selecting
KEma Type Test Certificate NOJA Power’s SF6-free ACRs, would allow utilities to
reduce environmental footprint.

NOJA Power’s OSM reclosers have been subjected to


full type testing by independent test consultants DNV
KEMA. The OSM38 recloser, for example, was tested
for electrical performance including interruption duty cycle
at 12.5 kA, load switching at 630 A, cable charging, line
charging, dielectric withstand capability including 170 kV
BIL across the open gap and 195 kV BIL phase-to-phase
and phase-to-ground, wet and dry power frequency,
KEMA High Current Test Laboratory temperature rise and mechanical operations testing.
Introduction Product Guide OSM Automatic Circuit Recloser 15kV 27kV 38kV Models 8.

FIELD Safety

NOJA Power Automatic recloser comes with a free


software app which enhances electrical utility field
engineers job safety by enabling wireless remote
control.

NOJA Power Recloser App, available free from Apple


App Store runs on Apple’s handheld devices including
iPhone and iPad. It communicates via a Wi-Fi link with
the Automatic Circuit Recloser allowing field engineers
to control and interrogate the device without having to
climb the pole.

Use of the app improves safety because field engineers


no longer have to undertake a hazardous climb that is
often attempted in poor weather, high off the ground
and close to cables that carry tens of thousands of
volts.

Running on an Apple iPhone®, iPod touch®, iPad® or


iPad mini®, the Recloser App communicates with the
NOJA Power RC10 control and communications cubicle
via a TCP/IP connection.

The app is able to configure and retain the fixed IP


address and port number for each recloser, which is
then stored in a device list that identifies each unit
with a name or code. The engineers can then select,
configure, control and interrogate any recloser from the
list providing connections via a fixed line, GPRS, WiMax
or Wi-Fi. NOJA Power Recloser Remote App

The enginners will be able to read three phase-current In addition, the app also allows the field engineers to
and phase-voltage (voltage on all six bushings), frequency, control Recloser functionality such as Trip/Close, Local/
power, power factor, power flow direction and energy Remote, Active Protection Group, Protection On/Off, Auto
measurements. Reclose On/Off, Live Line On/Off and Earth Fault On/
Off among others.

NOJA Power Recloser Remote App NOJA Power Recloser Remote App SCREENS
9. Product Guide OSM Automatic Circuit Recloser 15kV 27kV 38kV Models Introduction

Interoperable

NOJA Power’s RC10 Control cubilce provides flexible


communication options. The OSM recloser is supplied
with an RC10 Control Cubicle. The Relay module inside
the RC10 has 3 USB ports and one RS232 port available
for communication connections.

The USB ports can be used with NOJA Power approved


communications accessories. The accessories can be used
to provide a wide range of port interfaces such as RS485,
RS232, Ethernet, WiFi, GSM and GPRS modems.

The USB communications accessories can also be used


to remotely connect the CMS configuration software for
engineering access across serial, modem and Ethernet links.

The accessories provide a wide range of flexible options for 2 x OPTIONAL


SCADA and engineering access to the RC10 control cubicle. IO MOdule
All approved USB accessories are designed to work within
the RC10 specified temperature range of - 40°C to + 55°C.

Up to two General Purpose Input Output (GPIO) modules


can be supplied with the RC cubicle as an option. Each
I/O module has eight opto–coupled inputs and eight
voltage free contact outputs with normally open and
normally closed contacts. The modules can be used to
control or monitor external equipment, implement custom
automation functionality and provide remote I/O when
not using the built in SCADA functionality.

The CMS configuration software is used to program


the modules. Any available control signal can be
programmed for each input and any combination of
available indications can be programmed for each output. 2 x OPTIONAL IO MOdule

Local Panel

RC10
RELAY MODULE

Remote Panel
(maximum length 120m)

CMS on Computer
Radio Module

RS485 Blue Tooth Wireless GSM GPRS Ethernet


Module Module Module Module Module
Introduction Product Guide OSM Automatic Circuit Recloser 15kV 27kV 38kV Models 10.

Power Quality Software

NOJA Power’s Power Quality Software (PQS)


automates the analysis of data captured by NOJA
Power’s OSM range Automatic Circuit Reclosers
(ACR) and associated RC10 controllers allowing
engineers to quickly react to problems in the network.

PQS allows Engineers to monitor harmonics caused


from:
• Microgeneration systems such as domestic roof-
mounted photovoltaic (PV) panels
• Charging of electric vehicles PQS Harmonic Log
• Electric motors
• Semiconductor-based consumer products

PQS allows utilities to monitor Power Quality and


meet regulation standards avoiding penalties and
protects infrastructure in the event of a harmonics
exceeding a predetermined threshold. The software is
also a valuable tool for companies that want to check
that internal operations are not injecting harmonics
back into the grid from their spur nor risking damage
through harmonics to their own electrical assets. PQS Over Current Graph

Oscillography Data
The RC-10 can capture an oscillogram of the
waveform when a specific event occurs such as a
trip or a close. The amount of waveform captured
prior to the trigger can be configured by the user.
This ranges from 0 to 80% of the capture prior to the
trigger point. The data can be used to analyse power
quality fluctuations.

Harmonics
Harmonics are waves which have frequency multiples
of the fundamental frequency. The RC-10 measures PQS Harmonic Current Graph
Total Harmonic Distortion (THD), Total Demand
Distortion (TDD) and Harmonics Voltages and Sag and Swell
Currents up to the 15th Harmonic. The RC-10 records voltage variations (sags & swells)
occurring outside a user set period of time. Sags &
15th Harmonic (750Hz) capable. Current measurement Swell voltages are based on the phase to ground
up to 1000A. Harmonic data is averaged over 64 voltages.
cycles and is made available every 32 cycles.
Captured data can be stored on internal flash memory
Long and Short Duration Interruption or external USB drive.
The RC-10 stores information relating to long and
short duration interruptions. This information is used The captured Oscillography files are saved in the file
to calculate SAIDI (System Average Duration Index), system in the IEEE Std C37.111-1999 Comtrade binary.
SAIFI (System Average Interruption Frequency
Index) and MAIFI (Momentary Average Interruption Harmonic data, long and short duration interruptions
Frequency Index). Both long and short interruptions and sag/swell logs can be transferred to a USB in
are based on the Loss of Supply Detection (LSD). IEEE P1159.3 PQDIF.

Collects long and short interruption information for The PQS is available to all NOJA Power OSM range
calculating SAIDI, SAIFI and MAIFI. ACR customers, free of charge.
®

Part Number OSM15-12-800-310 OSM27-12-800-310 OSM38-12-800-300 OSM38-12-800-301


Current Sensing 3 x Current Transformers 3 x Current Transformers 3 x Current Transformers 1 x Current Transformer
Voltage Sensing 6 x Voltage Screens 6 x Voltage Screens 6 x Voltage Screens 2 x Voltage Sensors
Control Type RC10 RC10 RC10 RC10
Rated Maximum Voltage 15.5kV 27kV 38kV 38kV
Rated Continuous Current 800A 800A 800A 800A
Fault Make Capacity RMS 12.5kA 12.5kA 12.5kA 12.5kA
Fault Make Capacity Peak 31.5kA 31.5kA 31.5kA 31.5kA
Fault Break Capacity 12.5kA 12.5kA 12.5kA 12.5kA
Mechanical Operations 30,000 30,000 30,000 30,000
Full Load Operations 30,000 30,000 30,000 30,000
Fault Break Capacity Operations 70 70 70 70
Short Time Current Withstand 12.5kA/3 secs 12.5kA/3 secs 12.5kA/3 secs 12.5kA/3secs
Mainly Active Breaking Capacity 800A 800A 800A 800A
Cable Charging Current 25A 25A 40A 40A
Line Charging Current 10A 5A 5A 5A
Impulse Withstand Phase to Earth & Phase to Phase 110kV 150kV 195kV 195kV
Impulse Across the Interrupter 110kV 150kV 170kV 170kV
Power Frequency Withstand Phase to Earth (Dry) 50kV 60kV 70kV 70kV
Power Frequency Across the Interrupter 50kV 60kV 70kV 70kV
Ambient Temperature -40°C to +55°C -40°C to +55°C -40°C to +55°C -40 C to +55 C
Humidity 0-100% 0-100% 0-100% 0-100%
Altitude § 3000M 3000M 3000M 3000M
Weight of the Tank 105kg 112kg 140kg 75kg

§ Altitudes above 1000m should be corrected in accordance with ANSI C37.60-2012

NOJA Power AustrAlia NOJA Power BRAZIL NOJA Power CHILE NOJA Power UK NOJA Power USA
Corporate Office & Factory Office & Factory Sales Office Sales Office Sales Office

NOJA Power Switchgear Pty Ltd NOJA Power do Brasil Ltda NOJA Power SpA NOJA Power Limited NOJA Power, LLC
16 Archimedes Place, Murarrie Avenida Pierre Simon de Laplace, 764 Av 11 de septiembre 1881, Of 1415 4 Stalyhill Drive, Stalybridge 3611 SW Humphrey Blvd
Brisbane Qld 4172, Australia Techno Park – Campinas – SP Providencia, Santiago Cheshire SK 15 2TR Portland OR 97221
CEP 13069-301, Brasil Chile United Kingdom United States of America

Phone: +61 (7) 3907 8777 Phone: +55 (19) 3283 0041 Phone: +56 (2) 8979649 Phone: +44 (01865) 58 9499 Mobile: +1 (971) 404-9039
Fax: +61 (7) 3399 6777 Fax: +55 (19) 3283 0041 Email: [email protected] Fax: +44 (01865) 58 9400 Email: [email protected]
Email: [email protected] Email: [email protected] Web: w w w.nojapower.cl Email: [email protected] Web: www.nojapower.com
Web: www.nojapower.com.au Web: www.nojapower.com.br Web: www.nojapower.co.uk

Scan to view
NOJA Power
website

NOJA Power® is a registered trademarks of NOJA Power Switchgear Pty Ltd. This document is copyright and is intended for users and distributors of NOJA Power Switchgear product. It contains information that is the intellectual
property of NOJA Power Switchgear and the document, or any part thereof, should not be copied or reproduced in any form without written permission from NOJA Power Switchgear.
NOJA Power Switchgear applies a policy of continued fundamental research and development and reserves the right to change designs and specifications of this product without notice. NOJA Power Switchgear does not accept
any responsibility for loss or damage incurred by anyone as a result of acting or refraining from action based on information in this Product Guide.
NOJA-560-03