The document describes the characteristics and performance of Compact NSX circuit breakers ranging from 100 to 630 amps. It lists the common characteristics such as rated voltages, insulation voltage, impulse withstand voltage, operational voltage, and suitability for isolation. It also provides the electrical characteristics for each breaker model including rated current, number of poles, and breaking and service breaking capacities at different voltage levels. The durability of the breakers ranges from 15,000 to 50,000 mechanical C-O cycles depending on the model.

Uploaded by

Ochena Ami Ek
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
114 views2 pages

MCCB NSX

The document describes the characteristics and performance of Compact NSX circuit breakers ranging from 100 to 630 amps. It lists the common characteristics such as rated voltages, insulation voltage, impulse withstand voltage, operational voltage, and suitability for isolation. It also provides the electrical characteristics for each breaker model including rated current, number of poles, and breaking and service breaking capacities at different voltage levels. The durability of the breakers ranges from 15,000 to 50,000 mechanical C-O cycles depending on the model.

Uploaded by

Ochena Ami Ek
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Compact NSX Characteristics Compact NSX Characteristics

and performance of and performance of


Compact NSX circuit breakers Compact NSX circuit breakers
from 100 to 630 A from 100 to 630 A
Common characteristics Common characteristics
PB103354-40

Rated voltages Control


Insulation voltage (V) Ui 800 Manual With toggle b
Impulse withstand voltage Uimp 8 With direct or extended rotary handle b
(kV) Electrical With remote control b
Operational voltage (V) Ue AC 50/60 Hz 690 Versions
Suitability for isolation IEC/EN 60947-2 yes Fixed b
Utilisation category A Withdrawable Plug-in base b
Pollution degree IEC 60664-1 3 Chassis b

Circuit breakers NSX100 NSX160 NSX250 NSX400 NSX630


Breaking capacity levels B F N H S L B F N H S L B F N H S L F N H S L F N H S L
Electrical characteristics as per IEC 60947-2
Rated current (A) In 40 °C 100 160 250 400 630
Number of poles 2 (3), 3, 4 2 (3), 3, 4 2 (3), 3, 4 3, 4 3, 4
Compact NSX100/160/250. Breaking capacity (kA rms)
lcu AC 50/60 Hz 220/240 V 40 85 90 100 120 150 40 85 90 100 120 150 40 85 90 100 120 150 40 85 100 120 150 40 85 100 120 150
380/415 V 25 36 50 70 100 150 25 36 50 70 100 150 25 36 50 70 100 150 36 50 70 100 150 36 50 70 100 150
440 V 20 35 50 65 90 130 20 35 50 65 90 130 20 35 50 65 90 130 30 42 65 90 130 30 42 65 90 130
500 V 15 25 36 50 65 70 15 30 36 50 65 70 15 30 36 50 65 70 25 30 50 65 70 25 30 50 65 70
PB103279-44

525 V - 22 35 35 40 50 - 22 35 35 40 50 - 22 35 35 40 50 20 22 35 40 50 20 22 35 40 50
660/690 V - 8 10 10 15 20 - 8 10 10 15 20 - 8 10 10 15 20 10 10 20 25 35 10 10 20 25 35
Service breaking capacity (kA rms)
lcs AC 50/60 Hz 220/240 V 40 85 90 100 120 150 40 85 90 100 120 150 40 85 90 100 120 150 40 85 100 120 150 40 85 100 120 150
380/415 V 25 36 50 70 100 150 25 36 50 70 100 150 25 36 50 70 100 150 36 50 70 100 150 36 50 70 100 150
440 V 20 35 50 65 90 130 20 35 50 65 90 130 20 35 50 65 90 130 30 42 65 90 130 30 42 65 90 130
500 V 7.5 12.5 36 50 65 70 15 30 36 50 65 70 15 30 36 50 65 70 25 30 50 65 70 25 30 50 65 70
525 V - 11 35 35 40 50 - 22 35 35 40 50 - 22 35 35 40 50 10 11 11 12 12 10 11 11 12 12
660/690 V - 4 10 10 15 20 - 8 10 10 15 20 - 8 10 10 15 20 10 10 10 12 12 10 10 10 12 12
Durability (C-O cycles) Mechanical 50000 40000 20000 15000 15000
Electrical 440 V In/2 50000 20000 20000 12000 8000
In 30000 10000 10000 6000 4000
690 V In/2 20000 15000 10000 6000 6000
In 10000 7500 5000 3000 2000
Characteristics as per Nema AB1
Breaking capacity (kA rms) AC 50/60 Hz 240 V 40 85 90 100 120 150 40 85 90 100 120 150 40 85 90 100 120 150 40 85 100 120 150 40 85 100 120 150
480 V 20 35 50 65 90 130 20 35 50 65 90 130 20 35 50 65 90 130 30 42 65 90 130 30 42 65 90 130
600 V - 8 20 35 40 50 - 20 20 35 40 50 - 20 20 35 40 50 - 20 35 40 50 - 20 35 40 50
Characteristics as per UL 508
Breaking capacity (kA rms) AC 50/60 Hz 240 V - 85 85 85 - - - 85 85 85 - - - 85 85 85 - - 85 85 85 - - 85 85 85 - -
480 V - 25 50 65 - - - 35 50 65 - - - 35 50 65 - - 35 50 65 - - 35 50 65 - -
Compact NSX400/630.
600 V - 10 10 10 - - - 10 10 10 - - - 15 15 15 - - 20 20 20 - - 20 20 20 - -
Protection and measurements
Short-circuit protection Magnetic only b b b b b
Overload / short-circuit protection Thermal magnetic b b b - -
Electronic b b b b b
with neutral protection (Off-0.5-1-OSN) (1) b b b b b
with ground-fault protection b b b b b
with zone selective b b b b b
interlocking (ZSI) (2)
Display / I, U, f, P, E, THD measurements / interrupted-current measurement b b b b b
Options Power Meter display on door b b b b b
Operating assistance b b b b b
Counters b b b b b
Histories and alarms b b b b b
Metering Com b b b b b
Device status/control Com b b b b b
Earth-leakage protection By Vigi module b b b b b
By Vigirex relay b b b b b
Installation / connections
Dimensions and weights
Dimensions (mm) Fixed, front connections 2/3P 105 x 161 x 86 105 x 161 x 86 105 x 161 x 86 140 x 255 x 110 140 x 255 x 110
WxHxD 4P 140 x 161 x 86 140 x 161 x 86 140 x 161 x 86 185 x 255 x 110 185 x 255 x 110
Weight (kg) Fixed, front connections 2/3P 2.05 2.2 2.4 6.05 6.2
4P 2.4 2.6 2.8 7.90 8.13
(1) OSN: Over Sized Neutral protection for neutrals carrying Connections
high currents (e.g. 3rd harmonics). Connection terminals Pitch With/without spreaders 35/45 mm 35/45 mm 35/45 mm 45/52.5 mm 45/52.5 mm
(2) ZSI: Zone Selective Interlocking using pilot wires. 45/70 mm 45/70 mm
(3) 2P circuit breaker in 3P case for B and F types, only with Large Cu or Al cables Cross-section mm² 300 300 300 4 x 240 4 x 240
thermal-magnetic trip unit.

A-10 A-11
Compact NS Protection of distribution Compact NS Protection of distribution
systems systems
Compact NS circuit breakers Compact NS circuit breakers
from 630 up to 3200 A from 630 up to 3200 A
DB112530

Compact circuit breakers NS630b NS800 NS1000 NS1250 NS1600 NS1600b NS2000 NS2500 NS3200
Number of poles 3, 4 3, 4 3, 4 3, 4 3, 4
Control manual toggle b b b b b
direct or extended rotary handle b b b b -
electric b (except LB) b b b -
Type of circuit breaker N H L LB N H L N H N H N H
Connections fixed front connection b b b - b b b b b b b b b
rear connection b b b b b b b b b b b - -
front connection with bare cables b b - - b b - b b - - - -
withdrawable (on chassis) front connection b b b b b b b b b b b - -
rear connection b b b b b b b b b b b - -
Electrical characteristics as per IEC 60947-2 and EN 60947-2
Rated current (A) In 50 °C 630 800 1000 1250 1600 1600 2000 2500 3200
65 °C (1) 630 800 1000 1250 1510 1550 1900 2500 2970
Rated insulation voltage (V) Ui 800 800 800 800 800
Rated impulse withstand voltage (kV) Uimp 8 8 8 8 8
Rated operational voltage (V) Ue AC 50/60 Hz 690 690 690 690 690
Compact NS800L Type of circuit breaker N H L LB N H L N H N H N H
Ultimate breaking capacity (kA rms) lcu AC 220/240 V 50 70 150 200 50 70 150 50 70 50 70 85 125
50/60 Hz 380/415 V 50 70 150 200 50 70 150 50 70 50 70 70 85
E45178R_68

440 V 50 65 130 200 50 65 130 50 65 50 65 65 85


500/525 V 40 50 100 100 40 50 100 40 50 40 50 65 -
660/690 V 30 42 - 75 30 42 - 30 42 30 42 65 -
Service breaking capacity (kA rms) lcs Value or % Icu manual operation 100 % 75 % 100 % 100 % 100 % 75 % 100 % 100 % 75 % 75 % 50 % 100 % (2) 75 %
electrical operation 75 % 50 % 100 % - 75 % 50 % 100 % 75 % 50 % 75 % 50 % 100 % (2) 75 %
Short-time withstand current (kA rms) lcw AC 50/60 Hz 1 s 19.2 19.2 - - 19.2 19.2 - 19.2 19.2 19.2 19.2 - -
3s - - - - - - - - - - - 32 32
Integrated instantaneous protection kA peak ±10 % 40 40 - - 40 40 - 40 40 40 40 130 130
Suitability for isolation b b b b b
Utilisation category B B A A B B A B B B B B B
Durability (C-O cycles) mechanical 10000 10000 10000 10000 5000
electrical 440 V In/2 6000 6000 4000 4000 6000 6000 4000 5000 5000 3000
In 5000 5000 3000 3000 5000 5000 3000 4000 2000 2000
690 V In/2 4000 4000 3000 3000 4000 4000 3000 3000 2000 2000
In 2000 2000 2000 2000 2000 2000 2000 2000 1000 1000
Pollution degree 3 3 3 3 3
Electrical characteristics as per Nema AB1 N H L LB N H L N H N H N H
Breaking capacity at 60 Hz (kA) 240 V 50 65 125 200 50 65 125 50 65 50 65 85 125
Compact NS2000H 480 V 35 50 100 200 35 50 100 35 50 35 50 65 85
600 V 25 50 - 100 25 50 - 25 50 25 50 50 -
Protection and measurements
Interchangeable control units Micrologic 2.0 Micrologic 5.0 Micrologic 2.0 A Micrologic 5.0 A Micrologic 6.0 A Micrologic 7.0 A Micrologic 5.0 P (3) Micrologic 6.0 P (3) Micrologic 7.0 P (3)
Overload protection long time Ir (In x …) b b b b b b b b b
Short-circuit protection short time Isd (Ir x …) - b - b b b b b b
instantaneous Ii (In x …) b b b b b b b b b
Earth-fault protection lg (In x …) - - - - b - - b -
Residual earth-leakage protection I∆n - - - - - b b b b
Zone selective interlocking ZSI - - b b b b b b b
Protection of the fourth pole b b b b b b b b b
Current measurements - - b b b b b b b
Power measurements - - - b b b b b b
Advanced protection - - - b b b b b b
Remote communication by bus
Device-status indication b b b b b b b b b
Device remote operation b b b b - - b b b
Transmission of settings - - b b b b b b b
Indication and identification of protection devices and alarms - - b b b b - - -
Transmission of measured current values - - b b b b b b b
Additional indication and control auxiliaries
Indication contacts b b
Voltage releases MX shunt release/MN undervoltage release b b
Installation
Accessories terminal extensions and spreaders b -
terminal shields and interphase barriers b b
escutcheons b b
Dimensions fixed devices, front connections (mm) 3P 327 x 210 x 147 350 x 420 x 160
HxWxD 4P 327 x 280 x 147 350 x 535 x 160
Weight fixed devices, front connections (kg) 3P 14 24
4P 18 36
Source changeover system (see section on "source changeover systems")
Manual, remote-operated and automatic source changeover b -
systems
(1) 65 °C with vertical connections. See the temperature derating
tables for other types of connections.
(2) Ics: 100 % Icu for breaking capacity 440V/500V/660V
Ics: 75 % Icu for breaking capacity 220V/380V.
(3) Except 1600b-3200.

A-14 A-15