OperatingInstructions RPS Modular VEC621R0
OperatingInstructions RPS Modular VEC621R0
Operating Instructions
Photovoltaic Inverter
280 kWp ... 1460 kWp
RPS TL
Table of contents
This document............................................................................................................................. 9
Warranty and liability ................................................................................................................. 9
Obligation ................................................................................................................................... 9
Copyright .................................................................................................................................... 9
Storage........................................................................................................................................ 9
1 General safety instructions and information on use ............................................................ 10
1.1 Terminology .................................................................................................................... 10
1.2 Designated use ................................................................................................................ 10
1.3 Misuse ............................................................................................................................. 11
1.3.1 Explosion protection ........................................................................................................ 11
1.4 Residual risks .................................................................................................................. 11
1.5 Safety and warning signs at solar inverter ..................................................................... 11
1.6 Warning information and symbols used in the user manual .......................................... 12
1.6.1 Hazard classes ................................................................................................................ 12
1.6.2 Hazard symbols ............................................................................................................... 12
1.6.3 Prohibition signs .............................................................................................................. 12
1.6.4 Personal safety equipment ............................................................................................... 13
1.6.5 Recycling ........................................................................................................................ 13
1.6.6 Grounding symbol ........................................................................................................... 13
1.6.7 ESD symbol .................................................................................................................... 13
1.6.8 Information signs ............................................................................................................ 13
1.7 Marking of text passages ................................................................................................ 13
1.8 Conformity....................................................................................................................... 13
1.9 Directives and guidelines to be adhered to by the operator ........................................... 14
1.10 Operator's general plant documentation ..................................................................... 14
1.11 Operator's/operating staff's responsibilities ............................................................... 14
1.11.1 Selection and qualification of staff..................................................................................... 14
1.11.2 General work safety......................................................................................................... 14
1.12 Organizational measures ............................................................................................. 15
1.12.1 General .......................................................................................................................... 15
1.13 Handling and installation ............................................................................................. 15
1.14 Electrical connections .................................................................................................. 15
1.14.1 The five safety rules ........................................................................................................ 15
1.15 Safe operation .............................................................................................................. 16
1.16 Maintenance and service/troubleshooting .................................................................. 16
1.17 Utilities and operating materials ................................................................................. 16
2 Transport .............................................................................................................................. 17
2.1 Special safety instructions .............................................................................................. 17
2.2 Dimensions/weight ......................................................................................................... 17
2.3 Marking of center of gravity ............................................................................................ 17
2.4 Crane transport ............................................................................................................... 18
2.4.1 Transport by means of crane fork ..................................................................................... 18
2.4.2 Transport by means of load frame .................................................................................... 18
08/2010 RPS TL 3
2.4.3 Transport without load frame ........................................................................................... 19
2.5 Storage ............................................................................................................................ 20
3 Scope of supply ..................................................................................................................... 21
3.1 Communication ............................................................................................................... 21
3.2 Arrangement of electrical cabinet modules and transport units .................................... 21
4 Technical data ....................................................................................................................... 24
4.1 Multiple String application .............................................................................................. 24
4.1.1 Multiple String connected to 270 V mains .......................................................................... 24
4.1.2 Multiple String connected to 300 V mains .......................................................................... 25
4.1.3 Multiple String connected to 330 V mains .......................................................................... 26
4.2 Master-Slave application ................................................................................................. 27
4.2.1 Master-Slave connected to 270 V mains ............................................................................ 27
4.2.2 Master-Slave connected to 300 V mains ............................................................................ 28
4.2.3 Master-Slave connected to 330 V mains ............................................................................ 29
4.3 Device identification ....................................................................................................... 30
5 Product overview / Description of function ......................................................................... 31
5.1 Multiple String application .............................................................................................. 31
5.2 Master-Slave application ................................................................................................. 32
5.3 Product variants .............................................................................................................. 33
5.3.1 AC distributor .................................................................................................................. 34
5.3.2 Inverter module .............................................................................................................. 37
5.3.3 DC distributor ................................................................................................................. 39
5.3.4 Rating plate .................................................................................................................... 41
5.4 Function........................................................................................................................... 43
5.5 Monitoring and protective functions ............................................................................... 48
5.5.1 Grid monitoring ............................................................................................................... 48
5.5.2 Insulation monitoring....................................................................................................... 48
5.5.3 EFC (Earth Fault Control) ................................................................................................. 48
5.5.4 Temperature monitoring .................................................................................................. 50
5.5.5 Surge arrester ................................................................................................................. 50
6 Installation ........................................................................................................................... 51
6.1 Place of installation/environmental conditions .............................................................. 51
6.2 Cooling ............................................................................................................................ 52
6.3 Distance to ceiling ........................................................................................................... 53
6.4 Mechanical connection of joined modules ...................................................................... 54
7 Electrical connections ........................................................................................................... 55
7.1 Special safety instructions .............................................................................................. 55
7.2 Internal wiring ................................................................................................................ 56
7.2.1 Control voltage connection ............................................................................................... 57
7.2.2 Connection of overvoltage protection ................................................................................ 58
7.2.3 Connection of insulation monitoring .................................................................................. 59
7.2.4 Connection of system bus ................................................................................................ 60
7.2.5 RS485 connection............................................................................................................ 62
7.2.6 Connection of AC busbars ................................................................................................ 65
7.2.7 Connection of Multiple String DC distributor ....................................................................... 67
7.2.8 Connection of Master-Slave DC distributor ......................................................................... 68
7.2.9 Connection of current transformer .................................................................................... 69
7.3 Mains connection ............................................................................................................ 70
4 RPS TL 08/2010
7.3.1 Connection to main switch ............................................................................................... 70
7.3.2 Connection to busbars ..................................................................................................... 72
7.4 Control voltage connection ............................................................................................. 75
7.5 Generator connection ...................................................................................................... 77
7.5.1 Variant with 4 fuse-protected inputs.................................................................................. 77
7.5.2 Variant with DC switch and fuse-protected DC input ........................................................... 78
7.5.3 Variant with DC switch and terminal blocks ........................................................................ 80
7.6 Connection to DC distributor........................................................................................... 80
8 Operation .............................................................................................................................. 82
8.1 Special safety instructions .............................................................................................. 82
8.2 Control elements ............................................................................................................. 83
8.2.1 Inverter module .............................................................................................................. 83
8.2.2 AC distributor .................................................................................................................. 84
8.3 Control unit KP500 .......................................................................................................... 85
8.3.1 Menu structure................................................................................................................ 86
8.4 First commissioning ........................................................................................................ 87
8.5 Commissioning ................................................................................................................ 87
8.5.1 Start .............................................................................................................................. 87
8.6 Measuring the DC and AC voltage ................................................................................... 89
8.7 Decommissioning ............................................................................................................ 90
8.7.1 Stopping ......................................................................................................................... 90
8.8 Emergency shutdown ...................................................................................................... 90
8.9 Final decommissioning/disassembly/disposal/recycling ............................................... 91
9 Parameterization .................................................................................................................. 92
9.1 Selecting the language.................................................................................................... 92
9.2 Set password ................................................................................................................... 92
9.3 Display parameters ......................................................................................................... 93
9.3.1 Inverter data .................................................................................................................. 93
9.3.2 Installed optional modules ............................................................................................... 93
9.3.3 Software version ............................................................................................................. 93
9.4 Operating behavior ......................................................................................................... 93
9.4.1 Multiple String ................................................................................................................. 93
9.4.2 Master-Slave ................................................................................................................... 94
9.5 Operating statuses .......................................................................................................... 97
9.6 Voltage controller ............................................................................................................ 98
9.7 Power limitation .............................................................................................................. 99
9.8 Communication interface for system monitoring ........................................................... 99
9.8.1 Setting the Baud Rate ...................................................................................................... 99
9.8.2 Set up node addresses..................................................................................................... 99
9.8.3 Protocol ........................................................................................................................ 100
9.9 Feed-in management .................................................................................................... 100
9.9.1 Power limitation by setpoint ........................................................................................... 100
9.9.2 Power limitation in case of overfrequency ........................................................................ 101
9.10 Mains frequency monitoring ...................................................................................... 102
9.11 System synchronization ............................................................................................. 102
9.11.1 Node address ................................................................................................................ 103
9.11.2 Baud rate ..................................................................................................................... 103
08/2010 RPS TL 5
9.11.3 Identifier ...................................................................................................................... 103
9.11.4 Synchronization time ..................................................................................................... 104
9.11.5 Timeout monitoring ....................................................................................................... 104
9.11.6 Synchronization operation mode ..................................................................................... 104
9.11.7 Master-Slave operation mode ......................................................................................... 105
9.12 Master-Slave configuration ........................................................................................ 105
9.12.1 Function ....................................................................................................................... 105
9.12.2 Preconditions for Master-Slave........................................................................................ 106
9.12.3 Master-Slave operation mode ......................................................................................... 106
9.12.4 Actual current value....................................................................................................... 106
9.12.5 Release of slave inverter modules ................................................................................... 106
9.12.6 Process data settings ..................................................................................................... 107
9.12.7 Control ......................................................................................................................... 108
9.12.8 Behavior of system in faults ........................................................................................... 109
9.13 Electrical cabinet fan.................................................................................................. 109
9.14 Error/warning behavior ............................................................................................. 110
9.14.1 Automatic acknowledgement of errors/faults ................................................................... 110
9.14.2 Operation mode overvoltage protection ........................................................................... 110
9.14.3 Operation mode Insulation monitoring ............................................................................ 110
9.15 Intelligent current limits ............................................................................................ 111
9.16 Status ......................................................................................................................... 112
9.17 Actual values of solar inverter ................................................................................... 112
9.18 Actual values of frequency inverter ........................................................................... 113
9.19 Mains actual values .................................................................................................... 113
9.20 Actual value memory ................................................................................................. 114
9.21 Parameters ................................................................................................................. 115
10 Maintenance and service .................................................................................................... 118
10.1 Special safety instructions ......................................................................................... 118
10.2 Service intervals/preventive maintenance ................................................................ 119
10.3 Test/inspections ........................................................................................................ 120
11 Error diagnosis .................................................................................................................... 121
11.1 List of errors ............................................................................................................... 121
11.2 Error messages........................................................................................................... 121
11.3 Warning Messages ..................................................................................................... 123
12 Plant monitoring ................................................................................................................. 124
12.1 Plant monitoring by means of data logger ................................................................ 124
Index ......................................................................................................................................... 125
6 RPS TL 08/2010
List of illustrations
Figure 2-1: Marking of center of gravity ................................................................................................ 17
Figure 22: Transport by means of crane fork ......................................................................................... 18
Figure 2-3: Transport by means of load frame ....................................................................................... 19
Figure 2-4: Crane transport ................................................................................................................. 19
Figure 3-1: Transport units door hinge right .......................................................................................... 22
Figure 3-2: Transport units door hinge left ............................................................................................ 23
Figure 4-1: Code description ................................................................................................................ 30
Figure 5-1: Product overview - Multiple String application ....................................................................... 32
Figure 5-2: Product overview - Master-Slave application ......................................................................... 33
Figure 5-3: Connection of solar inverter to IT grid.................................................................................. 33
Figure 5-4: AC distributor, outside view ................................................................................................ 34
Figure 5-5: AC distributor, inside view, connection to main switch, systems ≤ RPS 620 TL ........................ 35
Figure 5-6: AC distributor, inside view, connection with busbars, systems ≥ RPS 680 TL ........................... 36
Figure 5-7: Inverter module, outside view ............................................................................................. 37
Figure 5-8: Inverter module, inside view ............................................................................................... 38
Figure 5-9: DC distributor, outside view ................................................................................................ 39
Figure 5-10: DC distributor, inside view................................................................................................. 40
Figure 5-11: Inverter module rating plate.............................................................................................. 41
Figure 5-12: Solar inverter rating plate ................................................................................................. 42
Figure 5-13: Inverter module block diagram .......................................................................................... 44
Figure 5-14: AC distributor block diagram ............................................................................................. 45
Figure 5-15: Multiple String DC distributor block diagram ....................................................................... 46
Figure 5-16: Master-Slave DC distributor block diagram .......................................................................... 47
Figure 5-17: Earth fault control with grounding at negative pole of PV generator ...................................... 49
Figure 6-1: Air flow ............................................................................................................................. 52
Figure 6-2: Distance to ceiling .............................................................................................................. 53
Figure 6-3: Joining by means of connector and bracket .......................................................................... 54
Figure 7-1: Control voltage connection.................................................................................................. 57
Figure 7-2: Connection of overvoltage protection ................................................................................... 58
Figure 7-3: Connection of insulation monitoring ..................................................................................... 59
Figure 7-4: Connection of system bus ................................................................................................... 60
Figure 7-5: System bus termination example ......................................................................................... 61
Figure 7-6: Connection of shield ........................................................................................................... 61
Figure 7-7: RS485 connection .............................................................................................................. 62
Figure 7-8: RS485 module ................................................................................................................... 63
Figure 7-9: Communication wiring example ........................................................................................... 64
Figure 7-10: Connection of shield ......................................................................................................... 65
Figure 7-11: Connection of AC busbars ................................................................................................. 66
Figure 7-12: Assembly of AC busbars .................................................................................................... 66
Figure 7-13: Connection of Multiple String DC distributor ........................................................................ 67
Figure 7-14: Connection of Master-Slave DC distributor .......................................................................... 68
Figure 7-15: Connection of transformer ................................................................................................ 69
Figure 7-16: Disassembly of bottom plate ............................................................................................. 70
Figure 7-17: Disassembly of base sheet ................................................................................................ 70
Figure 7-18: Connection of cables ........................................................................................................ 71
Figure 7-19: Connection to main switch ................................................................................................ 72
Figure 7-20: Disassembly of bottom plate ............................................................................................. 72
Figure 7-21: Disassembly of base sheet ................................................................................................ 73
Figure 7-22: Connection of cables ........................................................................................................ 73
Figure 7-23: AC connection .................................................................................................................. 74
Figure 7-24: AC distributor, connection of control voltage ....................................................................... 76
Figure 7-25: DC connection 4 string groups ........................................................................................... 77
Figure 7-26: Connection with DC switch and fuses ................................................................................. 78
Figure 7-27: DC connection cable lug sizes/distances ............................................................................. 79
Figure 7-28: DC connection with two cables per pole ............................................................................. 79
Figure 7-29: Connection with DC switch and terminal blocks ................................................................... 80
Figure 7-30: Connection of DC distributor ............................................................................................. 81
08/2010 RPS TL 7
Figure 8-1: Control elements ................................................................................................................ 83
Figure 8-2: AC distributor control elements ........................................................................................... 84
Figure 8-3: Control unit ....................................................................................................................... 85
Figure 8-4: Menu Structure .................................................................................................................. 86
Figure 8-5: DC and AC measurement terminals...................................................................................... 89
Figure 9-1: Operating behavior Master-Slave ......................................................................................... 96
Figure 9-2: I=f(U), insolation const. ..................................................................................................... 98
Figure 9-3: I=f(U), cell temp. const. ..................................................................................................... 98
Figure 9-4: I=f(U), P=f(U) ................................................................................................................... 98
Figure 12-1: Plant monitoring with data logger RPSlog1000 .................................................................. 124
8 RPS TL 08/2010
This document
Dear customer,
This user manual describes the solar inverter type RPS TL by BONFIGLIOLI VECTRON GmbH (in the follow-
ing referred to as solar inverter) in the applications Master-Slave and Multiple String as well as how to use it
in the intended field of application.
The user manual contains important information on how the solar inverter can be used safely, properly and
efficiently. Compliance with this user manual contributes to avoiding risks, minimizing repair cost and down-
times and increasing the reliability and service life of the solar inverter. For this reason, make sure you read
the user manual carefully.
In case any problems occur which are not covered by this user manual sufficiently, please
contact the manufacturer.
In addition to that, BONFIGLIOLI VECTRON GmbH excludes any warranty/liability claims for any personal
and/or material damage if such damage is due to one or more of the following causes:
- inappropriate use of the solar inverter,
- non-compliance with the instructions, warnings and prohibitions contained in this user manual,
- unauthorized modifications of the solar inverter,
- insufficient monitoring of parts which are subject to wear,
- maintenance work not carried out properly or not carried out in due time,
- catastrophes by external impact and Force Majeure.
Obligation
This user manual must be read before commissioning. Anybody entrusted with tasks in connection with the
- transport and/or unloading,
- assembly,
- installation of the solar inverter and
- operation of the solar inverter
must have read and understood the user manual and, in particular, the safety instructions in order to protect
himself/herself and prevent the solar inverter from being damaged.
Copyright
This user manual is protected by copyright. It is solely intended for use by operating staff and must not be
copied nor disclosed to third parties.
Storage
This user manual is an integral component of the solar inverter. It must be stored such that it is accessible
to operating staff at all times. In case the solar inverter is sold to other users, this user manual must also be
handed over.
08/2010 RPS TL 9
1 General safety instructions and information on use
The chapter "General safety instructions and information on use" contains general safety instructions for the
Operator and the Operating Staff. At the beginning of certain main chapters, some safety instructions are
included which apply to all work described in the relevant chapter. Special work-specific safety instructions
are provided before each safety-relevant work step.
1.1 Terminology
Operator
This is the entrepreneur/company who/which operates the solar inverter and uses it as per the specifications
or has it operated by qualified and instructed staff.
Operating Staff
The term Operating Staff covers persons instructed by the Operator of the solar inverter and assigned the
task of operating it.
Qualified staff
The term Qualified Staff covers staff who is assigned special tasks by the Operator of the solar inverter , e.g.
transport, installation, maintenance and service/repair and troubleshooting. Based on their qualification
and/or know-how, qualified staff must be capable of identifying defects and assessing functions.
Qualified electrician
The term Qualified Electrician covers qualified and trained staff who has special technical know-how and
experience with electrical installations. In addition, Qualified Electricians must be familiar with the applicable
standards and regulations, they must be able to assess the assigned tasks properly and identify and elimi-
nate potential hazards.
Instructed person
The term Instructed Person" covers staff who was instructed and trained about/in the assigned tasks and
the potential hazards that might result from inappropriate behavior. In addition, instructed persons must
have been instructed in the required protection provisions, protective measures, the applicable directives,
accident prevention regulations as well as the operating conditions and verified their qualification.
Expert
The term Expert covers qualified and trained staff who has special technical know-how and experience relat-
ing to solar inverter. Experts must be familiar with the applicable government work safety directives, acci-
dent prevention regulations, guidelines and generally accepted rules of technology in order to assess the
operationally safe condition of the solar inverter.
10 RPS TL 08/2010
For the performance limits of the solar inverters of applications Master-Slave and Multiple String, refer to
chapter 4 "Technical Data".
1.3 Misuse
Any use other than that described in "Designated use" shall not be permissible and shall be considered as
misuse.
The following is not permitted:
- use by uninstructed staff,
- use of the device while it is not in perfect condition,
- without protection enclosure (e.g. doors, covers),
- without safety equipment or with safety equipment deactivated.
The manufacturer shall not be held liable for any damage resulting from such misuse. The sole risk shall be
borne by the operator.
08/2010 RPS TL 11
1.6 Warning information and symbols used in the user manual
DANGER
Identification of immediate threat holding a high risk of death or serious injury if not avoided.
WARNING
Identification of immediate threat holding a medium risk of death or serious injury if not
avoided.
CAUTION
Identification of immediate threat holding a low risk of minor or moderate physical injury if
not avoided.
NOTE
12 RPS TL 08/2010
1.6.4 Personal safety equipment
Symbol Meaning
Wear body protection.
1.6.5 Recycling
Symbol Meaning
Recycling, to avoid waste, collect all
materials for reuse.
1.8 Conformity
The declaration of conformity will be supplied by the manufacturer upon request.
08/2010 RPS TL 13
1.9 Directives and guidelines to be adhered to by the operator
The operator must follow the following directives and regulations:
• Ensure that the applicable workplace-related accident prevention regulations as well as other applicable
national regulation are accessible to the staff.
• An authorized person must ensure, before using the solar inverter, that the device is used in compliance
with its designated use and that all safety requirements are met.
• Additionally, comply with the applicable laws, regulations and directives of the country in which the solar
inverter is used.
14 RPS TL 08/2010
1.12 Organizational measures
1.12.1 General
• Train your staff in the handling and use of the solar inverter as well as the risks involved.
• Use of any individual parts or components of the solar inverter in other parts of the operator's plant is
prohibited.
08/2010 RPS TL 15
1.15 Safe operation
• During operation of the solar inverter, always comply with the applicable national and international regu-
lations/laws on work on electrical equipment/plants.
• Before commissioning and the start of the operation, make sure to fix all covers and check the terminals.
Check the additional monitoring and protective devices according to the applicable national and interna-
tional safety directives.
• Never open the solar inverter during operation, nor perform any connection work.
• Solar inverters hold high voltage levels during operation, are equipped with rotating parts (fan) and have
hot surfaces. Any unauthorized removal of covers, improper use, wrong installation or operation may re-
sult in serious injuries or material damage.
• Even some time after shutdown of the solar inverter, certain components, e.g. heat sink, transformer,
fuse, filter may have a high temperature. Don't touch any surfaces directly after shutdown. Wear safety
gloves where necessary.
• In order to avoid accidents or damage, only qualified staff and electricians may carry out the work such
as installation, commissioning or setup.
• In the case of a defect of terminals and/or cables, etc., immediately disconnect the solar inverter from
mains supply and the PV generator.
• Persons not familiar with the operation of solar inverter as well as children must not have access to the
solar inverter. Do not bypass nor decommission any protective facilities.
16 RPS TL 08/2010
2 Transport
WARNING
High weight and unusual center of gravity!
Tilting the solar inverter may result in death or serious injuries. Due to the size and weight of
the solar inverter, there is the risk of accidents during transport. Center of gravity is not the
middle of the solar inverter.
• Take utmost care during transport in order to prevent damage and deformation. Trans-
port, attachment and lifting of loads may only be carried out by specially instructed staff
who are familiar with the work.
• Only use suitable transport and lifting equipment with sufficient carrying capacity. The
lifting cables/chains used must be able to carry the weight of the solar inverter. Check
the ropes or chains for damage.
• Wear appropriate safety clothing.
• When lifting the solar inverter up ensure that it does not fall over, is displaced, swings
out or falls down.
• Before the solar inverter is lifted up, everybody must have left the work area.
• Before transport, make sure the transport path has sufficient carrying capacity.
• Tilting the solar inverter is prohibited. Transport may only be effected in upright position.
• Do not step under suspended loads.
2.2 Dimensions/weight
For information on the weight and dimensions of the solar inverter, refer to chapter "Technical
data".
08/2010 RPS TL 17
2.4 Crane transport
Possible transport variants (see chapter 3.2 "Arrangement of electrical cabinet modules and transport
units"):
- 1 x 1 unit
- 1 x 2 units connected to one another
- 1 x 3 units connected to one another.
• Unscrew the base sheets on the front and rear side.
• Move the crane fork below the plant.
• Lift the plant up carefully. Avoid putting it down abruptly.
After installation, screw on the base sheets again.
WARNING
High weight and unusual center of gravity!
Center of gravity is not the middle of the solar inverter.
• The center of gravity of the AC distributor is in the upper area of the electrical cabinet.
• The center of gravity of the inverter modules is in the bottom rear area of the electrical
cabinet.
18 RPS TL 08/2010
Figure 2-3: Transport by means of load frame
Possible transport variants (see chapter 3.2 "Arrangement of electrical cabinet modules and transport
units"):
- 1 x 1 unit
- 1 x 2 units connected to one another
- 1 x 3 units connected to one another.
• Remove the screws from the upper side of the solar inverter.
• Screw in the supplied eyes.
• Lift the solar inverter up carefully. Avoid putting it down abruptly.
• For weight specifications, refer to chapter 4 "Technical data".
08/2010 RPS TL 19
2.5 Storage
NOTE
Damaging of solar inverter
• Wrong or inappropriate storage may result in damage, e.g. due to moisture and dirt.
Avoid major temperature variations and high air humidity.
• During storage, protect the solar inverter against moisture and dirt.
Ensure that all packaging materials are disposed of in an environmentally compatible manner.
20 RPS TL 08/2010
3 Scope of supply
Immediately after delivery, check that the contents are undamaged (transport damage) and corresponds to
the scope of the order.
Check if the specifications on the shipping not match the specification on the rating plate. Also check the
type and completeness of any supplied accessories. Report any transport damage and missing articles to the
forwarding agent immediately.
3.1 Communication
The standard variant features the communication modules CM-485 and CM-CAN for plant monitoring and
configuration via PC/notebook. This module can be replaced by an optional communication module for
RS232, Profibus DP or CANopen.
For more information on the solar inverter types, refer to chapter 4 "Technical data".
08/2010 RPS TL 21
The following transport units are defined:
Standard door hinge right Standard door hinge right
without DC distributor with DC distributor
22 RPS TL 08/2010
Standard door hinge left Standard door hinge left
without DC distributor with DC distributor
Figure 3-2: Transport units door hinge left Connected transport units
08/2010 RPS TL 23
4 Technical data
The RPS TL inverter system is designed for connection to three voltage levels. Minimum MPP voltage de-
pends on the mains voltage.
24 RPS TL 08/2010
4.1.2 Multiple String connected to 300 V mains
08/2010 RPS TL 25
4.1.3 Multiple String connected to 330 V mains
26 RPS TL 08/2010
4.2 Master-Slave application
08/2010 RPS TL 27
4.2.2 Master-Slave connected to 300 V mains
Type RPS 310 TL RPS 380 TL RPS 470 TL RPS 570 TL RPS 760TL
DC side input
Recommended maximum
kip 315 378 470 567 756
connected generator power
Max. input current A 600 700 900 1050 1400
Max. DC input voltage V 900*
MPP area V 460 … 875
AC side output
Mains voltage V 300 (IT mains)
Mains frequency Hz 50 - 60
Rated power kW 280 333 420 500 667
Rated current A 540 640 810 960 1280
Power factor - adjustable, > 0.99 at rated power
Distortion factor % < 3 at rated power
Control voltage, external 230 V, 50 Hz
Efficiency
Maximum efficiency % 98,6
European efficiency % 98,4
Consumption at night W <40 <60 <80
Mechanical
Dimensions (W x H x D)
2400 x 2400 x 3000 x 3000 x 3800 x
mm
2100 x 800 2100 x 800 2100 x 800 2100 x 800 2100 x 800
Weight approx. kg 1400 1550 1860 2100 2700
Degree of protection - IP 20
Environment
Ambient temperature °C -10 … 40
Rel. air humidity % 15...85 not condensing
Rate of coolant air required m3/h 3000 4500 6000
Protection and monitoring
Insulation monitor Adjustable response value,
Tripping value 30 kΩ,
- max. leakage capacitance
max. leakage capacitance 30 µF
999.9 µF
Grid monitoring - adjustable voltage and frequency range
Overvoltage protection - EN Type 2, IEC Class 2 on mains and generator side
Communication
Communication interface RS485
* 1000 V upon request
28 RPS TL 08/2010
4.2.3 Master-Slave connected to 330 V mains
08/2010 RPS TL 29
4.3 Device identification
RPS 0280 DE 0 1 1 0
Door arrester
0 right
1 left
DC-Input construction *
Multi String
Inverter module 2x unfused inputs per pole (see chapter 7.5.3)
0
DC distribution none, generator connection to inverter module
Inverter module 2x fuse covered inputs per pole (see chapter 7.5.2)
1 DC distribution none, generator connection to inverter module
Inverter module 2x unfused inputs per pole (see chapter 7.5.3)
2
DC distribution Gen. connection to DC distribution (see chapter 7.6)
Inverter module 4x fused inputs per pole, (see chapter 7.5.1)
3
DC distribution none, generator connection to inverter module
Master Slave
Generator construction Insulated generator (see chapter 5.5.2)
6 Inverter module 2x fused inputs per pole, (see chapter 7.5.2)
DC distribution Gen. connection to DC distribution (see chapter 7.6)
Generator construction Gen. grounded in negative pole (see chapter 5.5.3)
7 Inverter Module 2x fused inputs per pole (see chapter 7.5.2)
DC distribution Gen. connection to DC distribution (see chapter 7.6)
Generator construction Gen. grounded in positive pole (see chapter 5.5.3)
8 Inverter Module 2x fused inputs per pole (see chapter 7.5.2)
DC distribution Gen. connection to DC distribution (see chapter 7.6)
Country selection *
DE Germany
ES Spain
IT Italy
FR France
30 RPS TL 08/2010
5 Product overview / Description of function
The devices of the RPS TL series are grid-coupled solar inverters used for feeding the power generated by
PV modules to the medium voltage grid.
The grid-connected solar inverters of the RPS TL series are available both for Multiple String and Master-
Slave application.
The solar inverters are of a modular design and comprise an AC distributor and at least 2 inverter modules.
In the case of the Master-Slave application, an additional DC distributor is used, in the case of the Multiple-
String application, this distributor is available as an option.
The modular design enables perfect adaptation of the individual inverter module to the solar generator and
results in an increased availability of the whole plant.
The RPS TL works fully automatically, i.e. no manual intervention is required for feed-in operation.
NOTE
• The voltage levels of the sub-generators must not deviate from one another by more than
50 V, i.e. the string configuration must be identical for all inverter modules. Each solar in-
verter should only be equipped with modules of the same type.
• Connection of grounded generators is not permissible.
08/2010 RPS TL 31
Figure 5-1: Product overview - Multiple String application
Product overview
1 Inverter module 2 AC distributor 3 Solar generator
NOTE
• Connection of grounded generators is permissible. To that end, a suitable solar inverter
design, including earth fault controller in DC distributor, must be used.
32 RPS TL 08/2010
Figure 5-2: Product overview - Master-Slave application
Product overview
1 Inverter module 3 Solar generator
2 AC distributor 4 DC distributor
In the case of the Master-Slave application, the sub-generators must be connected to the DC distributor.
The solar inverter systems of type RPS TL are exclusively designed for connection to an IT grid.
08/2010 RPS TL 33
The solar inverter systems must not be coupled galvanically on the AC side. This means that if more than
one system is used, these systems must be connected to separate transformers or transformer windings.
5.3.1 AC distributor
AC distributor
1 AC main switch rotary drive 2 Lock
The AC can be protected against unintentional reactivation by means of up to three padlocks. Shackle di-
ameter = 7 mm.
34 RPS TL 08/2010
5.3.1.1 AC distributor with connection to main switch for systems ≤ RPS 620 TL
Figure 5-5: AC distributor, inside view, connection to main switch, systems ≤ RPS 620 TL
AC distributor
1 AC busbar 7 Control voltage connection
2 Insulation monitoring 8 Overvoltage protection - control voltage
3 Grid monitoring 9 Overvoltage protection - grid
4 AC main switch 10 AC main switch
5 Mains connection 11 Terminal blocks
6 Connection terminals for internal wiring 12 Terminal cover
08/2010 RPS TL 35
5.3.1.2 AC distributor with busbars for systems ≥ RPS 680 TL
Figure 5-6: AC distributor, inside view, connection with busbars, systems ≥ RPS 680 TL
AC distributor
1 AC busbar 6 Connection terminals for internal wiring
2 Insulation monitoring 7 Control voltage connection
3 Grid monitoring 8 Overvoltage protection - control voltage
4 AC main switch 9 Overvoltage protection - grid
5 Busbars
36 RPS TL 08/2010
5.3.2 Inverter module
Inverter module
1 Control unit "KP 500" 4 Lock
2 Control switch "Start/Stop" 5 Air inlet filter
3 Illuminated "Reset" button 6 DC switch (only in connection variants 6B and
6C, see Figure 5-8)
08/2010 RPS TL 37
For connection to the generator, three different connection variants are available. Depending on the applica-
tion and generator, choose the matching connection variant.
Inverter module
1 AC Fuse disconnector 6 DC connection variants
2 AC main contactor 6A Connection of 4 string groups
3 Grid monitoring 6B Connection with DC switch and fuses
4 24 V power supply unit 6C Connection with DC switch and terminal blocks
5 Frequency inverter AEC
38 RPS TL 08/2010
5.3.3 DC distributor
DC distributor
1 Lock
08/2010 RPS TL 39
1
1A 1B
2A 2B
Figure 5-10: DC distributor, inside view
DC distributor
1 Fuse holder for generator connection 2 Terminal blocks
1A Fuse holder for generator connection 2A Terminal blocks, positive
Positive pole, 4x
1B Fuse holder for generator connection 2B Terminal blocks, negative
Negative pole, 4x
In the case of the Master-Slave application, the sub-generators are connected to the DC distributor. The
sub-generators are connected to the fuse holders by means of tubular cable lugs. The inverter modules are
connected via the terminal blocks. The DC distributor can also be used in the Multiple String application.
40 RPS TL 08/2010
5.3.4 Rating plate
/ /
Identifications
Type identification 7 Order number
AC rated power 8 Date of delivery
AC rated voltage 9 Circuit diagram number
AC mains frequency 10 Article number
DC operating voltage range 11 Serial number
Maximum DC current
The inverter type is identified by the rating plate. You will find rating plates on the inside of the door and on
the outside on the side wall.
RPS 450-170TL refers to the maximum DC connected generator power (peak power) [kWp].
A system is composed of x inverter modules, an AC distributor and possibly a DC distributor.
A RPS 340 TL solar inverter is composed of 2 x inverter modules RPS450-170TL and 1 x AC distributor RPS
450-375AC.
08/2010 RPS TL 41
Bonfiglioli Vectron GmbH
D- 47 07 Krefeld
Tel. +49 2151/8396-0
Identifications
1 Type identification 5 Order number
2 Rated power of solar inverter 6 Date of delivery
3 Rated voltage of solar inverter 7 Circuit diagram number
4 Rated frequency of solar inverter 8 Article number
9 Serial number
The solar inverter is identified by the rating plate. You will find rating plates on the inside of the door and on
the outside on the side wall.
RPS0340DE0110 is the type identification of the solar inverter. For a description of the code, refer to chapter
4.3 “Device identification”.
42 RPS TL 08/2010
5.4 Function
If the disconnecting device is closed, the energy coming from the PV field reaches the frequency inverter via
the DC EMC filter. Surge arresters in the DC input protect the frequency inverter against destructive overvol-
tage coupling from the PV field. In the case of an earth fault in the plant, either the insulation monitor in the
AC distributor or the earth fault control (in the case of the Master-Slave application variant with earth fault
control) is tripped
The frequency inverter controls the system. As from a DC voltage of 300 V, grid monitoring as well as insula-
tion monitoring are activated.
If the plant was enabled via the control switch and no fault is present, the main contactor will be switched
on as soon as the voltage limit set in parameter U DC Start 830 is reached.
The frequency inverter is now connected to the AC distributor via the sine filter and the line choke and thus
to the grid. One auxiliary contact of the main contactor activates feed-in mode and the MPP controller in the
frequency inverter. The MPP controller adjusts the DC voltage such that a power optimum is obtained. In the
case of the Master-Slave application, the master will start first and activate/deactivate the slaves, depending
on the irradiation. In the case of the Multiple-String application, the inverter modules work independent from
one another and start feed-in mode, depending on the connected sub-generator. Although the same photo-
voltaic modules are connected to each inverter module, the inverter modules of a solar inverter will not start
operation at the same time but with a slight offset due to manufacturing tolerances and different conditions
at the place of installation (shadowing).
If the insolation becomes so weak that the power of the PV field is no longer enough for economical opera-
tion of the plant the inverter modules are disconnected from the AC distributor and thus the grid again. In
the case of the Master-Slave application, the master will be the last to stop operation. In the case of the
Multiple-String application, the inverter modules are not all disconnected at the same time, but with a slight
offset.
In the evening, supply of the monitoring systems is interrupted, only the frequency inverter is supplied with
power via the AC mains. This ensures that communication with the inverter is possible at night, too.
08/2010 RPS TL 43
Inverter module
5 6 7 8
AEC
4 9
U/f 10
12
RUN STOP
11
PARA CPY WARN REM F
-1
h min
%mVA
kHz/s
2
ESC FUN
ENT
+ 1 13
L1 L2 L3
Identifications
1 Connection Generator 8 Line choke
2 Disconnecting device 9 Mains contactor
3 Surge arrester 10 Mains monitoring
4 Current transformer 11 Operating unit
5 DC EMC Filter 12 Fuses
6 Frequency inverter 13 Connection AC Distribution
7 Sine filter
44 RPS TL 08/2010
AC distributor
L1 L2 L3
1
2 RIT
3
6 U / fRIT
7
L1 L2 L3
Identifications
1 Connection inverter module 5 Mains switch
2 Insulation monitoring 6 Mains monitoring
3 Control power transformer 7 Connection transformer
4 Surge arrester
08/2010 RPS TL 45
DC distributor
+ -
3 4
+ -
5 6
+ -
7 8
+ -
9 10
+ -
1 2
Figure 5-15: Multiple String DC distributor block diagram
Identifications
1 Four connections to inverter module 6 Four inputs to inverter module 2
2 Four connections to inverter module 7 Four inputs to inverter module 3
3 Four inputs to inverter module 1 8 Four inputs to inverter module 3
4 Four inputs to inverter module 1 9 Four inputs to inverter module 4
5 Four inputs to inverter module 2 10 Four inputs to inverter module 4
46 RPS TL 08/2010
+ -
4 5
+ -
6 7
+ -
8 9
2
+ -
10 11
+ -
1 3
Figure 5-16: Master-Slave DC distributor block diagram
Identifications
1 Four connections to inverter module 7 Four inputs to inverter module 2
2 Current transformer 8 Four inputs to inverter module 3
3 Four connections to inverter module 9 Four inputs to inverter module 3
4 Four inputs to inverter module 1 10 Four inputs to inverter module 4
5 Four inputs to inverter module 1 11 Four inputs to inverter module 4
6 Four inputs to inverter module 2
08/2010 RPS TL 47
5.5 Monitoring and protective functions
DANGER
Live components - Risk of electric shock!
• Only qualified electrical staff may inspect the monitoring equipment.
• High mains voltage and high DC voltage from solar modules.
• Using suitable protective equipment, secure live components in the work area to prevent
contact.
NOTE
The earth fault control is installed in the DC distributor and can only be used in the case of the
Master-Salve application.
The use of certain module types requires earthing of the PV generator at the negative or positive pole. The
solar inverters designed for this application, are provided with high-performance circuit breakers with ad-
justable trip current. The insulation monitor required for IT systems is not required in this case. The high-
performance circuit breaker signals earth faults at the non-grounded pole. In the case of an earth fault at
the non-grounded pole, a current will flow between the defective area and the earth fault controller. This
results in a tripping of the high-performance circuit breaker. Grounding of the grounded pole is stopped as
soon as the earth fault control has tripped.
48 RPS TL 08/2010
1 2
Figure 5-17: Earth fault control with grounding at negative pole of PV generator
Under certain circumstances, it may take a long time until an earth fault in the non-grounded pole results in
the earth fault control being tripped. It might not even be tripped at all. Irradiation and the earth resistance
influence the fault current. In the case of high earth resistance or low irradiation, particularly with low-power
inverters, an earth fault in the non-grounded pole will not result in tripping of the earth fault control imme-
diately.
NOTE
Requirements to be met by the plant
The following instructions must be followed:
• Ensure short-circuit and earth fault safe installation of the DC cables
• Ensure good reference to grounding of solar inverter
• The insulation monitor of the solar inverter does not exist in the case of grounded posi-
tive or negative pole. Both poles must be protected against direct contact.
• Grounding may only be effected in the solar inverter, additional earthing in the PV gene-
rator or the connection boxes is not permissible.
The tripping of the earth fault control results in error message F0404 "Insulation". Before the inverter can be
commissioned again, the insulation fault must be repaired. Operation of the solar inverter with the earth
fault control tripped is not permissible.
DANGER
Live components - Risk of electric shock!
• EFC protects the equipment only, it does not protect persons. Grounded PV plants may
only be accessed by qualified and instructed electricians. If the plant is to be accessed by
non-instructed staff, the grounding must be undone.
In the case of an earth fault at the grounded pole, part of the total current will flow through the earth fault
controller during operation and can result in the EFC being tripped.
In the case of an earth fault at both poles, earth fault control will have no effect. The fault current will not
flow through the earth fault controller and the circuit cannot be opened for this reason. This might damage
the plant.
08/2010 RPS TL 49
NOTE
Maintenance work
The following instructions must be followed:
• The generator grounding is undone when the DC disconnector in the solar inverter is
opened. Insulation measurements may only be carried out on the PV generator when the
solar inverter DC disconnector is open.
Setup values
Setting range Factory settings
3,8 A to 5,8 A 3,8 A
50 RPS TL 08/2010
6 Installation
EMC and noise emission of the inverter are designed for operation an industrial environment.
08/2010 RPS TL 51
6.2 Cooling
NOTE
Damaging of solar inverter
For the minimum and maximum ambient temperature and relative moisture, refer to the
tables in chapter 4"Technical data".
For the cooling air requirements, refer to the tables in chapter 4 "Technical data".
If the specified cooling air values cannot be reached, the operator must install additional ven-
tilation equipment at the place of installation.
If the cooling air is very dirt-loaded, the operator must install additional filters (e.g. in build-
ing).
When the unit leaves the factory, the overtemperature cut-off and the parameters for control
of the electrical cabinet fans are set to suitable values.
For the cleaning intervals of the air filters and exhaust air grilles, refer to the table in chapter 10.2 "Service
intervals/preventive maintenance".
The fans must not be covered. Do not place any objects on the plant.
Insufficient cooling can reduce the feed-in power.
Discharge the hot exhaust air of the inverter from the plant if possible.
The equipment room must not be heated up by the discharged air.
Do not exceed the maximum ambient temperature.
The base strips must be mounted to the solar inverter. All cable entries must be sealed tightly
(dust-proof) in order to prevent intake of unfiltered air.
52 RPS TL 08/2010
6.3 Distance to ceiling
NOTE
Damaging of solar inverter
• All solar inverters must keep a distance to the ceiling of at least 250 mm.
08/2010 RPS TL 53
6.4 Mechanical connection of joined modules
NOTE
• Install the supplied junction seal between the connection rails of the modules (between joined electrical
cabinets).
• Fix the modules to one another using connector 1 and bracket 2.
6 pcs.
Turn in screws, drive in connector using a hammer and secure it.
1
4 pcs.
Fix bracket.
2 Either:
- horizontally and vertically using 8 sheet metal screws
- horizontally using 2 bolts and M8 nuts, vertically using 4 sheet metal screws
54 RPS TL 08/2010
7 Electrical connections
Depending on the power class, details of the electrical connection may differ from the layout
described below.
Lightning protection
The DC and AC side of the solar inverters are protected by type 2 surge arresters against overvoltage.
In order to achieve lightning protection as per DIN VDE 0185-4, additional lightning arresters must be in-
stalled on the building or in the plant.
Tools
For electrical connection provide the following tools:
- Stripping tool
- Crosshead screw driver
- Torx screw driver
- Allen wrench
- Torque wrench
Cable installation
The cables must be prepared properly by the operator before connection, i.e. sufficient length and cross-
section.
08/2010 RPS TL 55
7.2 Internal wiring
The transport units, i.e. connected systems, have already been pre-wired in the factory.
In the case of two or more transport units, they must be wired internally.
The cables in the modules have already been prepared and provided with sleeves and identifications. The
inscription on the sleeves indicates the terminals to which the cable wires must be connected.
Equipotential bonding is to be ensured via the PE busbars provided in the electrical cabinet modules.
In the transport units, the PE busbars are already pre-wired.
Wiring of the PE busbars is only required between the transport units.
NOTE
• Before connecting external voltage, the internal wiring must be done.
• The representations in the instructions may deviate from the specifications in the circuit
diagrams. Note the information provided in the circuit diagrams. You will find the relevant
circuit diagrams in the bags in the electrical cabinets. These circuit diagrams contain in-
formation on connection of the terminals.
In the following (chapter 7.2.1 through 7.2.9), the connections of the internal wiring are shown using an
example, consisting of:
1 x AC distributor (AC) and 4 inverter modules (WR) split up in two transport units:
Transport unit 1: AC + WR1 + WR2
Transport unit 2: WR3 + WR4
56 RPS TL 08/2010
7.2.1 Control voltage connection
Transport unit 1 (AC + WR1 + WR2) has already been pre-wired (full lines):
1. Terminal 1, 2 and PE of terminal strip X1.2 of the AC distributor and terminal L10, L0 and PE of terminal
strip X2 of inverter module 1 have been pre-wired.
2. Terminal 3, 4 and PE of terminal strip X1.2 of the AC distributor and terminal L10, L0 and PE of terminal
strip X2 of inverter module 2 have been pre-wired.
Wiring of transport unit 1 and transport unit 2 is required (broken lines):
3. Wire terminal 5, 6 and PE of terminal strip X1.2 of the AC distributor and terminal L10, L0 and PE of
terminal strip X2 of inverter module 3.
4. Wire terminal 7, 8 and PE of terminal strip X1.2 of the AC distributor and terminal L10, L0 and PE of
terminal strip X2 of inverter module 4.
NOTE
The number of terminals at terminal strip X1.2 in the AC distributor depends on the number of
connected inverter modules.
08/2010 RPS TL 57
7.2.2 Connection of overvoltage protection
You will find the relevant circuit diagrams in the bags in the electrical cabinets. These circuit
diagrams contain information on connection of the terminals.
Transport unit 1 (AC + WR1 + WR2) has already been pre-wired (full lines):
1. Terminal 1 and 2 of terminal strip X3.3 of the AC distributor and terminal 1 and 2 of terminal strip X3 of
inverter module 1 have been pre-wired.
2. Terminal 3 and 4 of terminal strip X3.3 of the AC distributor and terminal 1 and 2 of terminal strip X3 of
inverter module 2 have been pre-wired.
Wiring of transport unit 1 and transport unit 2 is required (broken lines):
3. Wire terminal 5 and 6 of terminal strip X3.3 of the AC distributor and terminal 1 and 2 of terminal strip
X3 of inverter module 3.
4. Wire terminal 7 and 8 of terminal strip X3.3 of the AC distributor and terminal 1 and 2 of terminal strip
X3 of inverter module 4
NOTE
The number of terminals at terminal strip X3.3 in the AC distributor depends on the number of
connected inverter modules.
58 RPS TL 08/2010
7.2.3 Connection of insulation monitoring
Transport unit 1 (AC + WR1 + WR2) has already been pre-wired (full lines):
1. Terminal 1 and 2 of terminal strip X3.1 of the AC distributor and terminal 4 and 5 of terminal strip X3 of
inverter module 1 have been pre-wired.
2. Terminal 3 and 4 of terminal strip X3.1 of the AC distributor and terminal 4 and 5 of terminal strip X3 of
inverter module 2 have been pre-wired.
Wiring of transport unit 1 and transport unit 2 is required (broken lines):
4. Wire terminal 5 and 6 of terminal strip X3.1 of the AC distributor and terminal 4 and 5 of terminal strip X3
of inverter module 3.
5. Wire terminal 7 and 8 of terminal strip X3.1 of the AC distributor and terminal 4 and 5 of terminal strip X3
of inverter module 4.
NOTE
• Grounded generators can only be connected to the Master-Slave system. To that end, the
insulation monitoring in the AC distributor is removed and connected to the EFC in the DC
distributor. In this case, the earth fault control is wired like the insulation monitor. Addi-
tionally, the signal contact of the earth fault control must be connected to the AC dis-
tributor.
The number of terminals at terminal strip X3.1 in the AC distributor depends on the number of
connected inverter modules.
08/2010 RPS TL 59
7.2.4 Connection of system bus
Transport unit 1 (AC + WR1 + WR2) has already been pre-wired (full lines):
1. Terminal 1 and 2 of terminal strip X4.1 of inverter module 1 and terminal 1 and 2 of terminal strip 4.1 of
inverter module 2 have been pre-wired.
Transport unit 2 (WR3 + WR4) has already been pre-wired (full lines):
2. Terminal 1 and 2 of terminal strip X4.1 of inverter module 3 and terminal 1 and 2 of terminal strip 4.1 of
inverter module 4 have been pre-wired.
Wiring of transport unit 1 and transport unit 2 is required (broken lines):
3. Wire terminal 1 and 2 of terminal strip X4.1 of inverter module 2 to terminal 1 and 2 of terminal strip
X4.1 of inverter module 3.
The bus termination required in a string in the physically first and last client (see example in Figure 7-4:
Inverter 1 and Inverter 4) can be activated via the two DIP switches S1 and S2 on extension module EM-IO-
01. In all other clients, the bus termination must remain deactivated (DIP switches S1 and S2 OFF).
You will find the extension module on the AEC frequency inverter
The bus termination switches in the inverter modules were set correctly in the factory.
For termination, set DIP switch S1 to ON and S2 to OFF.
60 RPS TL 08/2010
Figure 7-5: System bus termination example
The connection to the system bus is done via terminal strip X4.1.
For details on the pin assignment of terminal strip X4.1, refer to the following table
08/2010 RPS TL 61
7.2.5 RS485 connection
Transport unit 1 (AC + WR1 + WR2) has already been pre-wired (full lines):
1. Terminal 1 and 3 of terminal strip X4.2 of inverter module 1 and terminal 2 and 4 of terminal strip 4.2 of
inverter module 2 have been pre-wired.
Transport unit 2 (WR3 + WR4) has already been pre-wired (full lines):
2. Terminal 1 and 3 of terminal strip X4.2 of inverter module 3 and terminal 2 and 4 of terminal strip 4.2 of
inverter module 4 have been pre-wired.
Wiring of transport unit 1 and transport unit 2 is required (broken lines):
3. Wire terminal 1 and 2 of terminal strip X4.2 of inverter module 2 to terminal 2 and 4 of terminal strip X4.2
of inverter module 3.
62 RPS TL 08/2010
Figure 7-8: RS485 module
The RS485 assembly can be found on the frequency inverter AEC.
The RS485 interface is connected via terminal strip X4.2.
For details on the pin assignment of terminal strip X4.2, refer to the following table.
NOTE
• Ensure proper bus termination. Otherwise, communication via the RS485 interface is not
possible.
• Active termination is permissible only once per network. Termination via an external cir-
cuit and the DIP switch at the same time is not permissible.
• Ensure that the GND is not interrupted. In practice, this result in a better fault behavior.
• The terminals for signals A and B are parallel. This enables wiring of several inverter
modules.
08/2010 RPS TL 63
Solar inverter 1 Solar inverter 2 Solar inverter 20
Termination OFF Termination OFF Termination OFF
A B A B A B
1 2 3 4 1 2 3 4 1 2 3 4
Data logger
Termination ON
A B
-X4.2
-X4.2
-X4.2
1 2 3 4
RS485-A
max. 1000 m
NOTE
• Via a data logger RPSlog1000, the data of up to twenty solar inverters can be recorded.
For details of the data logger, refer to the separate RPSlog1000 user manual.
64 RPS TL 08/2010
The cable shield must be connected to PE.
NOTE
• For connection of further inverter modules or data loggers, a twisted cable with braided
shield (no foil shield) must be used.
• Control and communication cables must be kept physically separate from the power
cables. The braided shield of the communication cable is to be connected to ground (PE)
on both sides on a large area and with good conductivity.
NOTE
During transport of the connected systems, the screws of the busbar connectors may loosen.
For this reason, make sure to re-tighten the screws and check the connectors for tight fit be-
fore commissioning in any case.
08/2010 RPS TL 65
Figure 7-11: Connection of AC busbars
In the case of transport units (in example transport unit 1: AC + WR1 + WR2 and transport unit 2: (WR3 +
WR4), the AC busbars were already connected in the factory (see marks 1, 2 and 3).
In order to connect transport unit 1 and transport unit 2 to one another, the busbar connectors of inverter
module 2 must be connected to the busbar connectors of inverter module 3 (see mark 4).
• Place the busbar connectors (1) on the busbars (2). Tighten screws M8.
1
M8
Tightening torque: 18-22 Nm
66 RPS TL 08/2010
7.2.7 Connection of Multiple String DC distributor
+ - + - + - + -
+ -
In the case of the Multiple String application the DC distributor is connected to inverter connection variant
6C (see Figure 5-8, chapter 5.3.2 "Inverter module" and chapter 7.5.3 "Variant with DC switch and terminal
blocks")
The DC distributor and the inverter modules of transport unit 2 (DC + WR3 + WR4) have already been pre-
wired (full lines). The cables for connection of the inverter modules of transport unit 2 (WR3 + WR4) are
pre-assembled.
Wiring between transport unit 1 and transport unit 2 is required (broken lines):
The free terminal blocks of the DC distributor are to be connected to the corresponding terminal blocks of
inverter modules 1 and 2.
NOTE
• In any case make sure that the two inverter modules are not coupled galvanically on the
DC-side.
• The positive and negative pole of a sub-generator must be connected to the same inver-
ter module.
08/2010 RPS TL 67
7.2.8 Connection of Master-Slave DC distributor
+- +- +- +-
+ -
In the case of the Master-Slave application, the DC distributor is connected to inverter connection variant 6B
(see Figure 5-8, chapter 5.3.2 "Inverter module" and chapter 7.5.2 "Variant with DC switch and fuse-
protected DC input")
The DC distributor and the inverter modules of transport unit 2 (DC + WR3 + WR4) have already been pre-
wired (full lines). The cables for connection of the inverter modules of transport unit 2 (WR3 + WR4) are
pre-assembled.
Wiring between transport unit 1 and transport unit 2 is required (broken lines):
The free terminal blocks of the DC distributor are to be connected to the corresponding DC switch terminals
of inverter modules 1 and 2.
68 RPS TL 08/2010
7.2.9 Connection of current transformer
In the case of the Master-Slave application, it is necessary to pass the actual total current value from the DC
distributor on to the inverter modules.
The current transformer of the DC distributor and the inverter modules in transport unit 2 (DC + WR3 +
WR4) have already been pre-wired (full lines).
Wiring between transport unit 1 and transport unit 2 is required (broken lines):
1. Connect terminal 3 of terminal strip X4.3 of the DC distributor to terminal 1 of terminal strip X4.3 of
inverter module 2.
2. Connect terminal 4 of terminal strip X4.3 of the DC distributor to terminal 1 of terminal strip X4.3 of
inverter module 1.
3. Connect terminal 7 of terminal strip X4.3 of the DC distributor to terminal 2 of terminal strip X4.3 of
inverter module 2.
4. Connect terminal 8 of terminal strip X4.3 of the DC distributor to terminal 2 of terminal strip X4.3 of
inverter module 1.
Internal wiring is not required in the case of the Multiple String application as this application is not equipped
with a current transformer.
08/2010 RPS TL 69
7.3 Mains connection
Depending on the inverter system, mains connection is done either at the main switch or the busbars.
2. For cable entry, unscrew a base sheet. This is only required if no cable conduit is provided in the founda-
tion for guiding the cables into the solar inverter from below.
If cables are to enter from the back side, remove the base sheet in the rear part of the solar inverter. If
cables are to enter from the side, the base sheet on the relevant side of the solar inverter must be re-
moved.
70 RPS TL 08/2010
3. If the cables enter from the side/rear, cut suitable holes in the base sheet for the cable glands.
4. Pull the connecting cables into the solar inverter.
5. To provide for strain relief, fix the supply cables to the cable clamping rail using cable clamps. Use alumi-
num cable clamps.
6. Using the supplied foamed material seal, to seal the open area in the solar inverter. All cable entries must
be sealed tightly in order to prevent intake of unfiltered air.
7. Fix the base sheets again.
8. Fix acrylic glass again.
For mains connection, use bare copper or aluminum cables, solid aluminum conductors cannot be used.
08/2010 RPS TL 71
2
AC distributor
1 Main switch 4 Terminal cover
2 Main switch 5 Busbars for PE connection
3 Terminal blocks
72 RPS TL 08/2010
1 Bottom plate 4 Busbar for phase 3
2 Busbar for phase 1 5 Busbar for PE connection
3 Busbar for phase 2
2. For cable entry, unscrew any base sheet. This is only required if no cable conduit is provided in the foun-
dation for guiding the cables into the solar inverter from below.
If cables are to enter from the back side, remove the base sheet in the rear part of the solar inverter. If
cables are to enter from the side, the base sheet on the relevant side of the solar inverter must be re-
moved.
3. If the cables enter from the side/rear, cut suitable holes in the base sheet for the cable glands.
4. Pull the connecting cables into the solar inverter.
5. To provide for strain relief, fix the supply cables to the cable clamping rail using cable clamps. Use alumi-
num cable clamps.
6. Using the supplied foamed material seal, to seal the open area in the solar inverter. All cable entries must
be sealed tightly in order to prevent intake of unfiltered air.
7. Fix the base sheets again.
08/2010 RPS TL 73
7.3.2.1 Mains connection of AC distributor
The solar inverter is designed for connection to an IT grid.
Use tubular cable lugs for connection.
Ensure that the cross-section and voltage resistance of the cables is sufficient.
Note that the cross-section of PE is sufficient.
• Remove the acrylic glass cover installed in front of the AC connection busbars.
• Connect PE conductor to PE busbar. To provide for equipotential bonding, connect all the electrical cabi-
nets with one another to PE.
• Connect L1, L2 and L3 to the AC busbars. Note the marks provided on the AC busbars.
L1
L2
L3
PE
M16x30, max. tightening torque: 25 Nm
74 RPS TL 08/2010
7.4 Control voltage connection
Depending on the design of the solar inverter, the 230 V power supply for the solar inverter controller can
be generated internally or supplied via a connected external power source.
If an internal 230 V power supply is available, no external power supply may be connected.
An external 230 V power supply must be connected to the terminal provided for this purpose. Power must
be supplied from a source designed for this purpose. The operator must ensure that the 230 V power supply
is protected by means of a 16 A back-up fuse.
Connection
Max. cable cross section mm2 2,5
Recommended back-up fuse A 16
08/2010 RPS TL 75
L10 L0 PE
X2
AC distributor
1 Control voltage connection
76 RPS TL 08/2010
7.5 Generator connection
NOTE
Damaging of solar inverter
• The values specified in "Technical data" for maximum DC input voltage and maximum DC
input current must not be exceeded. Otherwise the unit may be damaged.
• When connecting the DC cables ensure that the polarity of the solar modules matches
the polarity of the connecting terminals of the DC main switch. Prevent short circuits be-
tween DC+ and DC-.
Before connecting the solar modules, verify if the voltage value of the solar modules as specified by the
manufacturer match the actual values. When measuring the voltage, note that solar modules supply a higher
DC voltage if the insolation remains the same while temperatures drop.
Ensure that the cross-section and voltage resistance of the cables is sufficient.
Note the maximum cable cross-sections.
Do not exceed the specified tightening torques.
Do not divide the connections of a sub-generator plus and minus pole to several inverter modules (only ap-
plies to Multiple String).
Generator connection can be done directly to the inverter modules (Multiple String) or the DC distributor
(Master-Slave). Connection to the DC distributor is also possible in the case of the Multiple-String applica-
tion.
Three connection variants are available for connecting a generator to inverter modules
08/2010 RPS TL 77
Due to the limited rated current of the fuses, at least two string groups must be connected.
The rated fuse current depends on the cable size used by the customer.
The fuses are not included in scope of supply.
DC connection
Technical data
Size NH 1
Rated voltage 1000 V DC
Fixture Bolt M10 x 40
Tightening torque 32 Nm
Rated current 50 A, 63 A, 80 A, 100 A, 125 A, 160 A, 200 A
NOTE
• This variant is obligatory in the case of the Master-Slave system.
In this variant, you can connect up to two string groups to one inverter module. Connection is done to the
DC main switch using tubular cable lugs.
78 RPS TL 08/2010
1. Pull off the covers of the DC main switch.
2. Connect the positive pole and the negative pole of the PV field to the terminals of the DC main switch.
Q10
+ -
3. After installation, the covers of the DC main switch must be fixed again.
4. Between the fixed tubular cable lugs at the positive and negative pole, the specified minimum distance
dmin must be kept.
5. Do not exceed the maximum width wmax of the tubular cable lugs.
DC connection
Technical data
Fixture Bolt M10 x 30
Minimum distance between tubular cable 10 mm
lugs dmin
Max. width of tubular cable lugs wmax 34 mm
Tightening torque 30…44 Nm
08/2010 RPS TL 79
7.5.3 Variant with DC switch and terminal blocks
In this variant, you can connect up to two string groups to one inverter module.
DC connection
Connecting specifications
Wire cross section, inflexible least 70 mm2
Wire cross section, inflexible max. 240 mm2
Wire cross section, flexible least 70 mm2
Wire cross section, flexible max. 240 mm2
Wire cross section, flexible with ferrule without plastic sleeve at least 70 mm2
Wire cross section, flexible with ferrule without plastic sleeve max. 185 mm2
Wire cross section, flexible with ferrule with plastic sleeve at least 50 mm2
Wire cross section, flexible with ferrule with plastic sleeve max. 185 mm2
Type of connection Screw connection
Tightening torque min. 25 Nm
Tightening torque max. 30 Nm
80 RPS TL 08/2010
Figure 7-30: Connection of DC distributor
DC distributor
1 Fuse holder for generator connection
1A Fuse holder for generator connection plus
1B Fuse holder for generator connection minus
The rated fuse current depends on the cable size used by the customer.
The fuses are not included in scope of supply.
DC connection
Technical data
Size NH 1
Rated voltage 1000 V DC
Fixture Bolt M10 x 40
Tightening torque 32 Nm
Rated current 50 A, 63 A, 80 A, 100 A, 125 A, 160 A, 200 A
08/2010 RPS TL 81
8 Operation
82 RPS TL 08/2010
8.2 Control elements
Control elements
1 Control unit KP500, parameterization and display device for:
- Setting of parameters for operating behavior
- Display of measured values
- Error diagnosis
2 Illuminated selector switch "Start/Stop" (green=run signal)
08/2010 RPS TL 83
8.2.2 AC distributor
Control elements
1 AC main switch
84 RPS TL 08/2010
8.3 Control unit KP500
B C
D E
F
G
J
Figure 8-3: Control unit
Buttons
A RUN Acknowledge fault.
STOP Acknowledge fault.
J ▲ ▼ Navigate in menu structure and select parameters.
Increasing or reducing parameter values.
ENT Open parameters or switch within the menu structure.
Confirm the selected function or parameter.
ESC Used for aborting parameters or switching back to the previous menu within the menu
structure. Canceling the function or resetting the parameter value.
FUN FUN , ▲ (pressed one after the other): Display of last parameter (highest number),
FUN , ▼ (pressed one after the other): Display of first parameter (lowest number).
Display
B Three-digit 7-segment display to show the parameter number.
C One-digit 7-segment display, e.g. display of the active data set.
D Display selected menu branch:
VAL Show actual values.
PARA Select parameters and adjust parameter values.
CTRL No function.
CPY Copy parameters via the control unit:
ALL All the parameter values are copied.
Act Active parameter values are copied only.
FOr Control unit memory is formatted and deleted.
E Status and operating messages:
WARN Warning about a critical operating behavior.
FAULT Message indicating that the unit was switched off due to a fault.
RUN Flashing: signals readiness for operation.
Lights up: signals that the unit is operating and the output stage is enabled.
REM Active remote control via interface connection.
F Function switch-over with the FUN key.
F Five-digit 7-segment display for display of parameter value and sign.
G Physical unit of the parameter value displayed.
08/2010 RPS TL 85
8.3.1 Menu structure
86 RPS TL 08/2010
8.4 First commissioning
Before first commissioning after connection of the solar inverter, the following must be checked/carried out:
• Electrical installation was carried out according to chapter 7 "Electrical connections" and the supplied
circuit diagrams.
• The AC main switch on the door of the AC distributor is turned off.
• The control switch of all inverter modules is in "Stop" position".
• All fuses and circuit breakers are switched on.
• Rated values for mains voltage and mains frequency are kept. See chapter 4 "Technical data".
• The maximum values for DC input voltage and DC input current are kept. See chapter 4 "Technical da-
ta".
• The poles of the PV field are connected to the correct poles of the DC connection in the inverter module.
Positive and negative pole are not exchanged.
• In an insulation test, it was verified that the PV field does not have an earth fault. The measurements of
the insulation resistance between the positive pole of the PV generator and PE as well as between the
negative pole of the PV generator and PE must result in a value > 30 kΩ.
NOTE
The plant is equipped with overvoltage protection devices. For insulation measurements, un-
plug connectors and/or disconnect protection devices.
• The inverter module is connected to the equipotential bonding system at the place of installation or in
the equipment room.
• All cables are connected to the terminals. The screws of the terminals must be checked for tight fit.
• After transport from a cold environment to an equipment room, condensation water can form. Before
commissioning, the plant must be dry.
• There may be no objects on the plant, e.g. tools.
• Close the doors of the plant.
• Close external disconnecting devices.
8.5 Commissioning
8.5.1 Start
NOTE
Damaging of solar inverter
• The DC voltage must not exceed the maximum input voltage of 900 V (1000V optional).
The solar inverter may be damaged.
• In any case, follow the right order when switching the solar inverter on.
08/2010 RPS TL 87
If an error is displayed on the control unit after start of the inverter, correct the error follow-
ing the instructions in chapter 11.2 "Error messages".
If the DC disconnecting device (or, if installed, the DC main switch) is switched on before the
AC main switch is closed, the error F0405 "Grid failure" is displayed.
If the inverter works properly, the green signal lamp in the plant door will be on and the control unit, in de-
fault settings) will display the parameter Active power 213.
Additional actual values can be displayed on the control unit. The actual value parameters are described in
chapter 9.19 "Mains actual values".
88 RPS TL 08/2010
8.6 Measuring the DC and AC voltage
For measurement of the DC voltage and AC mains voltage, measurement terminals are provided in the
plant, each of these terminals is fuse-protected (6A).
- Measurement terminals X01 for DC voltage, X01.1 = +, X01.2 = –
- Measurement terminal X1.1 for AC mains voltage
08/2010 RPS TL 89
8.7 Decommissioning
8.7.1 Stopping
DANGER
Live components - Risk of electric shock!
Even with main switches switched off, dangerous voltage is present in the solar inverter.
• When shutting down the plant, note that an active power source is connected. Depend-
ing on the operating status, voltage from the PV generator or the solar inverter may be
present.
• The control switch is no disconnecting device. By turning the plant off via the control
switch, the solar inverter is not disconnected from power supply of the PV field. For full
disconnection, all main switches and external disconnecting devices must be opened.
If you must shut the plant down, follow the following instructions:
NOTE
Damaging of solar inverter
If you must shut the solar inverter down, follow the following instructions:
• Only actuate the main switches without load.
• In any case, follow the right order when switching the solar inverter off.
Only actuate the disconnecting devices without load. Before turning off the disconnecting device, turn off the
inverter modules via the control switches on the plant doors of the inverter modules ("Stop" position).
1. Turn the plant off via the control switch ("Stop" position).
2. Switch DC disconnecting device off.
3. Switch AC main switch off.
Doors can only be opened with the main switches turned off.
CAUTION
Danger of burns due to hot surfaces!
Even some time after shutdown of the solar inverter, certain components, e.g. heat sink, fuse,
sine filter may have a high temperature.
• Do not touch the surfaces directly after shutdown. Wear safety gloves where necessary.
90 RPS TL 08/2010
8.9 Final decommissioning/disassembly/disposal/recycling
08/2010 RPS TL 91
9 Parameterization
NOTE
• The solar inverters were parameterized in the factory such that configuration by the
customer is not required.
• If a data logger is used, the Node-ID and the bus termination must be parameterized.
As an alternative to the control unit, you can also use the optional PC user software VPlus for parameteriza-
tion, monitoring and maintenance of the solar inverter.
The parameters are divided in 3 control levels.
The parameter Control level 28 defines the relevant control level.
- Control level 1 provides inverter information, actual values, an error list and contains parameters with
which the operating behavior can be influenced.
- Control level 2 contains additional parameters, actual values and functions.
- Control level 3 contains additional error information, functions and actual values. Additionally, it enables
fundamental changes of the operating behavior. Setting of parameters in this control level is not re-
quired and will not be fully covered by this user manual.
Parameter Setting
No. Description Min. Max. Factory setting Control level
28 Control level 1 3 1 1
Parameter Setting
No. Description Setting Factory setting Control level
0 - German
1 - English
33 Language 1 1
2 - Italian
3 - Spanish
Parameter Setting
No. Description Min. Max. Factory setting Control level
27 Set password 0 999 0 1
92 RPS TL 08/2010
9.3 Display parameters
In menu PARA of the control unit, several actual values and statuses are available in addition to various
parameters.
The available display parameters can be read via the control unit or the PC user software. Write access is
only possible via parameter User name 29.
Parameter Setting
No. Description Min. Max. Factory setting Control level
Depending on
830 V DC Start 450,0 V 800,0 V 1
min. UMPP
08/2010 RPS TL 93
The optimum shutdown point can be determined more precisely via the DC power. For this reason Switch-off
limit AC 838 = 0.0 should be turned off.
In order to prevent actuation of the main contactor during short power drops, you can set up a shut down
delay via parameter Off time 839. The power must drop below the limits set via parameters 834, 837 or
838 for this time before operation is stopped. Restarting can be delayed by an adjustable time via the Turn
on delay time 840.
Parameter Setting
No. Description Min Max. Factory setting Control level
834 P switch off limit DC 0,00 kW 20.00 kW 1,00 kW 2
Depending on
837 V DC switch off limit 405,0 V 650,0 V 1
min. UMPP
838 P switch off limit AC 0,00 KW 20.00 kW 1,00 kW 2
839 Off time 1 min 20 min 5 min 2
840 Turn on delay 1 min 30 min 10 min 2
9.4.2 Master-Slave
In the case of the Master-Slave application, the master performs the MPP control of the plant. The slaves are
activated/deactivated by the master in steps, depending on the available power. The startup and shutdown
behavior can only be parameterized on the master inverter module. The behavior set on the slave inverter
modules does not have any effect.
The power values of the activation points defined for the slave inverter modules depend on the rated power
(Pn) of the inverter modules used. For the factory settings of the activation points, refer to the table below.
94 RPS TL 08/2010
Parameter Setting
No. Description Min. Max. Factory setting
1136 Start1 50% * Pn 100% * Pn 80% * Pn
1138 Start2 150% * Pn 200% * Pn 180% * Pn
1148 Start3 250% * Pn 300% * Pn 280% * Pn
The power values of the shutdown points defined for the slave inverter modules depend on the rated power
(Pn) of the inverter modules used. For the factory settings of the shutdown points, refer to the table below.
Parameter Setting
No. Description Min. Max. Factory setting
1137 Stop1 50% * Pn 100% * Pn 70% * Pn
1139 Stop2 150% * Pn 200% * Pn 170% * Pn
1141 Stop3 250% * Pn 300% * Pn 270% * Pn
08/2010 RPS TL 95
9.4.2.3 Operating behavior of the system
Based on an example, the operating behavior of an RPS with a total power of 680 kWp, consisting of four
inverter module (each with 170kWp) is to be explained.
P
680 kW
510 kW
4 5
340 kW
3 6
170 kW
2 7
1 8
96 RPS TL 08/2010
9.5 Operating statuses
Switch-on behaviour Switch-off behaviour
Standby
Enabled by no
control switch?
Main Contactor off
ja
Udc > no
U DC Start 830 ? For at least the Off Time 839
the power of voltage falls below:
ja
- P Switch off Limit DC 834
- P Switch off Limit AC 838
- U DC Switch off Limit 837
no
Start of timer
yes
for Off Time 839 yes
Main Contactor on no
Start feed
MPP Tracking
In the case of an error, feed-in is stopped and the error is displayed on the control unit.
The operating behavior can be set up separately for each inverter module.
The operating statuses shown here apply to inverter modules of the Multiple String application and the mas-
ter inverter module of the Master-Slave application. The slave inverter modules are started and stopped
according to the description in chapter 9.4.2 “Master-Slave”.
08/2010 RPS TL 97
9.6 Voltage controller
NOTE
Damaging of solar inverter
• The voltage controller may only be set up by qualified staff. Wrong setup can result in
plant parts being damaged.
The following characteristics of a PV module show the DC output current (module current) as a function of
the DC voltage (module voltage). Since the current remains fairly constant at first and drops in the area of
the graph with higher voltage, there is a maximum power operating point. The operating point at which the
modules produce maximum power is also referred to as MPP (Maximum Power Point).
By proper setting of the DC voltage it is tried to operate the PV modules at MPP. The DC voltage is adjusted
by means of the solar inverter.
If insolation changes or the temperature of the PV modules changes, the DC voltage at which power output
is at its maximum will also change.
Cell temperature: 25 °C
2 MPP
Module current [A]
1000 W/m
Module current [A]
20 °C
2
30 °C 800 W/m
40 °C 2
600 W/m
50 °C
2
60 °C 400 W/m
Solar radiation: 2
1000 W/m² 200 W/m
Current-voltage-characteristic PMPP
IMPP
MPP
Module power [W]
Module current [A]
tic
eris
t
ac
har
- c
ge
ta
vol
-
er
w
Po
The solar inverter contains a voltage controller which sets the DC voltage automatically such that the mod-
ules are operated at MPP.
98 RPS TL 08/2010
9.7 Power limitation
Parameters Max. output current 803 and Max. active power 812 are used for power limitation. The smaller
of the two values is used. The max. current or power which may be fed to the grid are entered. If the out-
put value or current reach the adjusted value in strong insolation, MPP control is deactivated. The operating
point is changed such the limits set with parameters Max. output current 803 and Max. active power 812
are not exceeded. MPP is activated again if the values drop below the configured limits.
Parameter Setting
No. Description Min. Max. Factory setting Control level
803 Max. output current depending on type 2
812 Max. active power depending on type 2
Parameter Setting
No. Description Factory setting
10 Baud rate 5 - 57600 Baud
For operation with the RS485 bus, each client must be assigned an address.
Bus addresses may only be assigned once, i.e. no double assignments. Identical NodeIDs
result in a communication fault!
An address change is effective immediately, i.e. without a restart of the frequency inverter.
When using a data logger RPSlog1000, note that not more than 20 inverter modules may be
connected to it.
9.8.3 Protocol
The VABus protocol is the standard protocol of BONFIGLIOLI VECTRON. It defines and describes the com-
munication via the serial interfaces RS232/RS485. When they leave the factory, the frequency inverters are
set to VABus protocol. Communication with the data logger RPSlog1000 is only possible via the VABus proto-
col. If data capturing and monitoring is to be realized by means of an external product, other protocol types
can be used for this. The protocol types are described in detail in the communication module user manual.
Via parameter Protocol 395 you can view and set the protocol type:
Parameter Setting
No. Description Factory setting
395 Protocol 0 - VABus
Changes of the parameter Protocol type 395 take effect immediately, i.e. without a restart of
the frequency inverter.
If the wrong protocol is selected, communication via CM-232/CM-485 is not possible.
In this case correct the protocol type using the control unit KP500.
If you select 0="Off", there will not be any additional power reduction.
If you select 1="Reduction via RS232/485", there will be additional power reduction. The setpoint for reduc-
tion is specified in % via Power reduction reference value 1020 and refers to the AC Nominal power 1096.
The data logger RPSlog1000 PM is connected directly with the ripple control transmitter of the utility compa-
ny and transmits the current power reduction to the solar inverter while reading the solar inverter data. For
more information, refer to the RPSlog1000 PM user manual.
If you select 2="Setpoint via system bus", there will be additional power reduction. The setpoint for reduc-
tion is specified in % via S. power reduction systembus 1027 and refers to the AC Nominal power 1096.
Via Power reduction timeout 1026, you can configure the time which may pass between two write accesses
to parameter Power reduction reference value 1020 before the solar inverter resets the internal setpoint to
100 % automatically.
Parameter Setting
No. Description Min. Max. Factory setting Control level
Power reduction reference
1020 0% 100% 100 % 3
value
0
1026 Power reduction timeout 1000 min 0 min 3
min
S. power reduction system- 66-Reference percen-
1027 Selection 3
bus tage
In case of a power reduction ordered by the feed-in management system, the Feed-in power management
power reduction warning is set.
For setting of the warning, the following conditions must be met.
- the required power defined by the feed-in management is lower than the Max. active power 812
the solar inverter could feed more power into the grid than the set power of the feed-in management.
Parameter Setting
No. Description Setting Factory setting Control level
Mode lower-/upper frequency 0 - OFF
1029 1 3
monitoring 1 - ON
If the current mains frequency drops below the set frequency threshold for Lower frequency limit 1032, the
solar inverter is disconnected from the grid, and error message F0421=Mains underfrequency is displayed.
If the current mains frequency exceeds the set frequency threshold for Upper frequency limit 1033, the
solar inverter is disconnected from the grid, and error message F0421=Mains overfrequency is displayed.
Parameter Setting
No. Description Min. Max. Factory setting Control level
1031 Rated mains frequency 35,00 Hz 65,00 Hz 50,00 Hz 3
1032 Lower frequency limit 30,00 Hz 70,00 Hz 47,50 Hz. 3
1033 Upper frequency limit 30,00 Hz 70,00 Hz 51,50 Hz 3
Parameter Setting
Factory set-
No. Description Inverter module Control level
ting
Synchronization master 0 3
900 Node-ID Synchronization slave 1 1 3
Synchronization slave x x 3
Parameter Setting
Factory set-
No. Description Inverter module Control level
ting
Synchronization master 3
903 Baud rate 8 to 1000kBit/s
Synchronization slaves 3
9.11.3 Identifier
The identifier of the SYNC telegram must be set identically in all clients on the system bus. The setting of
the identifier of the SYNC telegram is done via parameter SYNC-Identifier 918. The identifier range
129...191 may not be used as the emergency telegrams can be found there. It is recommended to use the
identifier 128.
Parameter Setting
No. Description Min. Max. Factory setting
918 SYNC identifier 0 2047 128
Parameter Setting
Factory set-
No. Description Inverter module Control level
ting
Synchronization master 128 3
918 SYNC identifier Synchronization slave 1 128 3
Synchronization slave x 128 3
Parameter Setting
Factory set-
No. Description Inverter module Control level
ting
Synchronization master 1 ms 3
919 SYNC-Time Synchronization slave 1 0 ms 3
Synchronization slave x 0 ms 3
Parameter Setting
Factory set-
No. Description Inverter module Control level
ting
Synchronization master 0 ms 3
939 SYNC-Timeout Synchronization slave 1 100 ms 3
Synchronization slave x 100 ms 3
Setting 0 for this function means that there is no timeout monitoring and must be deactivated in the case of
the synchronization master.
Parameter Setting
Factory set-
No. Description Inverter module Control level
ting
Synchronization master 0 - OFF 3
1180 Operation mode Synchronization slave 1 10 - SYNC 3
Synchronization slave x 10 - SYNC 3
Master-Slave application
Parameter Setting
No. Description Inverter module Factory setting Control level
Synchronization master 1 - Master 3
Master/Slave operation
1091 Synchronization slave 1 2- Slave_Adr1 3
mode
Synchronization slave x x- Slave_Adrx 3
9.12.1 Function
In the Master-Slave function in the solar inverters of the RPS TL series, all inverter modules are networked in
the DC link. The individual string groups of the solar generator are connected to the common DC link.
In the Master-Slave application, the inverter modules are always operated at their optimum efficiency. The
number of slave inverter modules turned on is always adjusted to the available generator power; thus the
service life of the slave inverter modules is increased.
Attention!
Identifiers may only be assigned once, i.e. no double assignments.
The identifier range 129...191 may not be used as the emergency telegrams can be found there.
All unused TxPDOx and RxPDOx are turned off with 0 – not active. The RxPDO functions must be set to 0-
controlled by time.
On the TXPDO2, the mains phase position and the mains frequency are transmitted.
Parameter Setting
No. Description Inverter module Factory setting
962 TxPDO2 Word 3 Master 503 - AEC Phi low
963 TxPDO2 Word 4 Master 504 - AEC Phi high
964 TxPDO2 Long 1 Master 505 - AEC PLL mains frequency
After connection to the supply grid and synchronization, the slave inverter modules report back to the
TxPDO1.
Parameter Setting
No. Description Inverter module Factory setting
946 TxPDO1 Boolean1 Slave 184 - Flux formation complete
9.12.7 Control
In operation, various quantities must be transmitted from the master inverter module to the slave inverter
modules. This is done via the system bus.
The sources of the reference current values (active, reactive current) for the current controllers of the slave
inverter modules are set via parameters S. Isq controller 150 and S. Isd controller 152.
Parameter Setting
No. Description Inverter module Factory setting
Master 500 - AEC_Udreg_Isq
150 S. Isq controller
Slave 704 - RxPDO1 Word1
Master 501 - AEC_Udreg_Isd
152 S. Isd controller
Slave 705 - RxPDO1 Word2
Upon start of a slave inverter module, the mains frequency and the current phase angle must be transmitted
from the master inverter module to the slave inverter module. The source of the mains frequency for the
slave inverter modules is set via parameter S. Stator frequency start 1092. The phase angle is transmitted
via two quantities, the sources are entered in parameter S. Phi low start 1093 and S. Phi high start 1094.
Parameter Setting
No. Description Factory setting Control level
532 Op. mode digital output 3 44- Electrical cabinet fan 2
If function "100-On" is selected for Operation mode digital output 3 532, the fans will be on permanently
independent of the temperature.
Parameter Setting
No. Description Min. Max. Factory setting Control level
Switching Limit Heat Sink
825 -35 0 -15 °C 2
Temp.
826 Switching limit Inside Temp. -30 0 -15 °C 2
Tk: Heat sink temperature of frequency inverter Tk 255
Ti: Inside temperature of frequency inverter Ti 256
Setting of these parameters does not affect the frequency inverter fans.
Parameter Setting
No. Description Min. Max. Factory setting Control level
836 Delay Auto-Acknowl. 1 min 20 min 5 min 2
The maximum number of errors which can be acknowledged automatically per day is set with parameter
Allowed. No. of Auto-Acknowl. 835. If a setting is made for this parameter, the set number of error ac-
knowledgements will be available again on this day, even if one or more errors have already been acknowl-
edged automatically.
Parameter Setting
No. Description Min. Max. Factory setting Control level
Allowed No. of Auto-
835 0 20 15 2
Acknowl.
Parameter Setting
No. Description Selection Factory setting Control level
0 – Off
Op. Mode overvoltage
828 1 – Warning 1 – Warning 2
protection
2 – Error Switch-Off
Thanks to the visual signaling at the surge arresters, you can identify the component which is defective and
must be replaced.
Parameter Setting
No. Description Selection Factory setting Control level
0 – Off
Op. Mode isolation
829 1 – Daily 2 – Permanent 2
monitoring
2 – Permanent
NOTE
• If an earth fault controller is installed, monitoring will be done in a similar way.
Parameter Setting
No. Description Min. Max. Factory setting
574 Power limit 40,00% 95,00% 80,00%
575 Limitation time 5 min 300 min 15 min
In the operation modes with overload reserve (Ixt), the output current will be reduced if the threshold is
exceeded. A distinction is made in this context between long-time and short-time overload reserve. After the
short-term overload (1s) has been used up, the output current is reduced to the long-term overload current
matching the present switching frequency. After the long-term overload current has been used up (60s), the
output current is reduced to the rated current which also depends on the switching frequency.
If the output current has already been reduced due to the fact that the long-term overload has used up, the
short-term overload is no longer available even if it has not been used up beforehand. The defined overload
reserve (Ixt) of the frequency inverter is available again after 10 minutes of operation at reduced power.
The following table shows the values for Solar Status 1089.
No. 1089 State
1 Init Solar inverter is initializing
2 Wait for Init Solar inverter is waiting for release of initialization, e.g. delay
after MPP minimum shutdown.
3 Wait for mains management Solar inverter is waiting for release by grid management.
4 Ready DC voltage OK but no release.
5 Ready+warning DC voltage OK but no release, a warning is reported.
6 Undervoltage DC voltage too low.
8 Synchronization Not valid for modular system
9 MPP-tracking Tracking of optimum MPP point.
10 MPP-Tracking+Warning Tracking of optimum MPP point, a warning is reported.
11 MPP-maximum Power limitation, MPP point cannot be approached.
12 MPP-minimum MPP point below shutdown threshold.
13 MPP-FastSearch Quick MPP tracking, e.g. after grid failure
14 Fault A fault has occurred
15 Fault+Warning A fault has occurred, a warning is reported.
16 AutoQuit There was a fault, but the fault is no longer present and is ac-
knowledged automatically.
Due to error tolerances it is possible that the displayed active values are not plausible, especially
in the case of low power.
The working hours can be read via parameter Working Hours Counter 244.
CAUTION
Danger of burns due to hot surfaces!
Even some time after shutdown of the solar inverter, certain components, e.g. heat sink, fuse,
sine filter may have a high temperature.
• Do not touch the surfaces directly after shutdown. Wear safety gloves where necessary.
CAUTION
Danger of crushing due to rotating fan!
Fans are installed in the upper area of the inverter. These fans might start suddenly without
warning.
• Always ensure that the unit is isolated from power supply.
• In the case of the solar inverters, the external control voltage supply must be discon-
nected.
Service
Monthly
Subject Maintenance Reason
work
Filter mats can get clogged by pollen, dust, etc. and prevent
Air inlet filter, Clean, replace if proper cooling as a result. Dirty filter mats can result in over-
Filter mats necessary temperature and consequently failures. The filter mat covers can
be removed from the outside of the door.
Frequent errors or errors which are present over extended pe-
riods may be a sign of hardware defects. In order to prevent
Error protocol Check
unplanned outages, the relevant component(s) should be re-
placed in due time.
Ageing and frequent failures reduce the yield. Compare the ex-
Yield Check
pected yield with the actual yield.
Yearly
Subject Maintenance Reason
work
The exterior components of the solar inverter (handles, con-
Exterior Visual inspection
tacts, filter grilles, etc.) may be damaged by improper handling.
Moisture, insects, dirt or dust may enter the solar inverter. In
Visual inspection,
Interior the case of significant moisture, insect, dirt/dust load, eliminate
clean if necessary
the cause.
Insulation of the cable, particularly power cables, may change
Visual check, its color due to temperature or ageing, change its structure or
Cabling and terminal
replace if neces- be damaged by animals. Replace damaged cables.
connections
sary Terminal connections may loosen in the course of time and must
be checked for tight fit.
Warning labels and signs may loosen in the course of time due
Warning information, Check, replace if
to environmental impact. Replace damaged or missing warnings
signs necessary
and signs.
Unusual operating noise is a possible sign of a fan failing soon.
Defective filters can result in overtemperature and consequently
Fan Functional test
failures. Visual inspection and check for unusual noise during
operation.
Insulation, Possibly, the signal contacts or the electronics of the monitoring
voltage, earth fault Functional test equipment don't work properly and defects will not be recog-
frequency monitoring nized. Check signaling. Check changeover contacts.
In the case of RPS solar inverters with earth fault control, an
PV generator Insulation test insulation check for earth faults must be carried out at the
grounded and the non-grounded pole.
Visual inspection The optical detector should be checked, especially after thun-
or reading of derstorms. After a defect, the solar inverter remains ready for
Overvoltage protection
warning messag- operation, but the overvoltage protection must be replaced as
es soon as possible.
The switches are hardly ever actuated. Nevertheless, there may
Visual inspection/ be defects. Sparks may form in switching operations under load.
Switches, contactors
functional test These may change the color of the switching device. Replace
the switches, contactors in case of significant discoloration.
List of errors
No. Description Function
310 last error hhhhh:mm ; FXXXX error message.
311 second to last error hhhhh:mm ; FXXXX error message.
312 to 325 Error 3 to error 16.
Number of errors occurred after the initial commissioning of the
362 No. of Errors
frequency inverter.
The error and warning behavior of the frequency inverter can be set in various ways. Automatic error ac-
knowledgment enables acknowledgement without intervention by an overriding controller or the user. No. of
self acknowledged Errors 363 shows the total number of automatic error acknowledgments.
List of errors
No. Description Function
363 No. of self acknowledged Errors Total number of automatic error acknowledgments with syn-
chronization.
* Overtemperature errors can be acknowledged only when the Temperature has dropped by 5 °C.
F0420 Mains upper frequency limit Mains frequency exceeds the limit set in parameter P1033.
F0420 Mains lower frequency limit Mains frequency is below the limit set in parameter P1032.
Example:
A8040 Lim WARN2
A0040 + A8000 = A8040
The warnings initialization and surge arrester are reported.
USB
LAN RS232
°C °C km/h
RS485
Module Ambient Wind
Connection of up to temperature temperature speed
20 inverter modules
Nearby plant
RS232 VPlus Telephone line
Analogue modem
Internet
Mobile
GPRS Modem network
Telephone line
DSL-Router
Figure 12-1: Plant monitoring with data logger RPSlog1000
Features of optional data logger RPSlog1000:
- Graphical touch screen display
- Relay for external alarming
- LAN interface (10/100 MBit/s)
- Web control
- Email/SMS/Homepage messaging
- Remote inquiry
- S0 input for digital power meters
- USB port for data transfer via USB stick
- 512 MByte memory for yield data
- Monitoring/recording for up to 20 inverters
Index
A L
AC distributor 84 Language 92
Actual values 93 Lightning protection 55
actual value memory 114
of mains 113 M
Measurement terminal
C
AC 89
Cables DC 89
cross-sections 77 Measurement terminals 89
Commissioning 87 Menu
Connection 55 Actual values 86
AC 74 Parameters 86
DC 77 Monitoring
Control functions Grid 48
intelligent current limits 111 Insulation 48
Control unit 85 temperature 50
MPP 98
D
O
Displays 93
Operating statuses 97
E Options 93
F R
Fan RPS
Electrical cabinet 109 Function 43
Start temperature 109
S
G
Service 118
Grid monitoring 48 Software version 93
Surge arrester 50
I
T
Installation 15, 51
Insulation monitor 48 Temperature monitoring 50
Intelligent current limits 111 Transport 17
Internal power supply 75
Inverter module 83 V
Voltage controller 98
K
KP500 85
AUSTRALIA INDONESIA
BONFIGLIOLI TRANSMISSION (Aust) Pty Ltd. PT. ANEKAMAKMUR TEKNIK NUSAJAYA
2, Cox Place Glendenning NSW 2761 ( Australia) Pertokoan Glodok Makmur No. 32 - Jakarta Barat
Locked Bag 1000 Plumpton NSW 2761 Tel. (+62) 21 624 8828 - Fax (+62) 21 624 2405
Tel. (+ 61) 2 8811 8000 - Fax (+ 61) 2 9675 6605 www.anekamakmur.com - [email protected]
www.bonfiglioli.com.au - [email protected]
AUSTRIA ITALY
BONFIGLIOLI ÖSTERREIC( GmbH BONFIGLIOLI ITALIA S.p.A.
Molkereistr 4 - A-2700 Wiener Neustadt Via Sandro Pertini lotto 7b - 20080 Carpiano (Milano)
Tel. (+43) 02622 22400 - Fax (+43) 02622 22386
Tel. (+39) 02 985081 - Fax (+39) 02 985085817
www.bonfiglioli.at - [email protected]
www.bonfiglioli.it - [email protected]
MOLL MOTOR GmbH
Industriestrasse 8 - 2000 Stockerau NEW ZEALAND
Tel. (+43) 2266 634210 - Fax (+43) 2266 6342180
SAECO BEARINGS TRANSMISSION
www.mollmotor.at - [email protected]
36 Hastie Avenue, Mangere Po Box 22256, Otahuhu - Auckland
BELGIUM Tel. (+64) 9 634 7540 - Fax (+64) 9 634 7552
ESCO TRANSMISSION N.V./S.A. [email protected]
Culliganlaan 3 - 1831 Machelem Diegem
Tel. (+32) 2 7176460 - Fax (+32) 2 7176461 POLAND
www.esco-transmissions.be - [email protected] POLPACK Sp. z o.o. - Ul. Polna 129 - 87100 Torun
BRASIL Tel. (+48) 56 6559235 to 37 - Fax (+48) 56 6559238
BONFIGLIOLI REDUTORES DO BRASIL INDÚSTRIA E COMÉRCIO LTDA. www.polpack.com.pl - [email protected]
Travessa Cláudio Armando 171 - Bloco 3 - CEP 09861-730
Bairro Assunção - São Bernardo do Campo - São Paulo (Brasil)
Tel. (+55) 11 43 1 - Fax (+55) 11 43 PORTUGAL
www.bonfigliolidobrasil.com.br - [email protected] BT BONFITEC Equipamentos Industriais, Lda.
Largo do Colegio de Ermesinde, 70 - Formiga 4445-382 Ermesinde
CANADA
BONFIGLIOLI CANADA INC. Tel. (+351) 229759634/5/6 - Fax (+351) 229752211
2-7941 Jane Street - Concord, Ontario L4K 4L6 www.bonfitec.pt - [email protected]
Tel. (+1) 905 7384466 - Fax (+1) 905 7389833
www.bonfigliolicanada.com - [email protected] RUSSIA
CHILE FAM
IMATESA S.A. 57, Maly prospekt, V.O. - 199048, St. Petersburg
Santa Rosa 5699 - San Miguel - Santiago Tel. (+7) 812 3319333 - Fax (+7) 812 3271454
Tel. (+56) 2 5264702 - Fax (+56) 2 5265878 www.fam-drive.ru - [email protected]
www.imatesa.cl - [email protected]
CHINA SPAIN
BONFIGLIOLI DRIVES (SHANGHAI) CO. LTD. TECNOTRANS BONFIGLIOLI S.A.
19D, No. 360 Pudong Road (S) Pol. Ind. Zona Franca sector C, calle F, nr6 08040 Barcelona
New Shanghai International Tower - 200120 Shanghai (P.R. China) Tel. (+34) 93 4478400 - Fax (+34) 93 3360402
Tel. (+86) 21 69225500 - Fax (+86) 21 69225511 www.tecnotrans.com - [email protected]
www.bonfiglioli.cn - [email protected]
DENMARK SOUTH AFRICA
BRD. KLEE BONFIGLIOLI POWER TRANSMISSION Pty Ltd.
Gadagervej 11 Denmark - 2620 Albertslund 55 Galaxy Avenue, Linbro Business Park - Sandton
Tel. (+45) 43 868333 - Fax (+45) 868388 Tel. (+27) 11 608 2030 OR - Fax (+27) 11 608 2631
www.brd-klee.dk - [email protected] www.bonfiglioli.co.za - [email protected]
FRANCE
BONFIGLIOLI TRANSMISSIONS S.A. SOUTH KOREA
14 Rue Eugène Pottier BP 19 YOUN HO INDUSTRIAL
Zone Industrielle de Moimont II - 95670 Marly la Ville Room B1, World Plaza Bldg.
Tel. (+33) 1 34474510 - Fax (+33) 1 34688800
1262 Guro-Dong, Gurd-Gu, Seoul
www.bonfiglioli.fr - [email protected]
Tel. (+82) 2 626 43201 - Fax (+82) 2 263 23202
GERMANY www.younho.com - [email protected]
BONFIGLIOLI DEUTSCHLAND Gmbh
Sperberweg 12 - 41468 Neuss
SWEDEN
Tel. (+49) 02131 2988-0 - Fax (+49) 02131 2988-100
www.bonfiglioli.de - [email protected] BONFIGLIOLI SKANDINAVIEN AB
Koppargatan 8 - 234 35 Lomma (Sweden)
GREAT BRITAIN Tel. (+46) 40418230 - Fax (+46) 40414508
BONFIGLIOLI UK Ltd
www.bonfiglioli.se - [email protected]
Industrial Equipment - Unit 7, Colemeadow Road
North Moons Moat - Redditch, Worcestershire B98 9PB
Tel. (+44) 1527 65022 - Fax (+44) 1527 61995 THAILAND
www.bonfiglioli.co.uk - [email protected] K.P.T MACHINERY (1993) CO.LTD.
Mobile Equipment 259/83 Soi Phiboonves, Sukhumvit 71 Rd. Phrakanong-nur,
3 - 7 Grosvenor Grange, Woolston, Warrington - Cheshire WA1 4SF Wattana, Bangkok 10110
Tel. (+44) 1925 852667 - Fax (+44) 1925 852668 Tel. (+66) 2 3913030/7111998
www.bonfiglioli.co.uk - [email protected] Fax (+66) 2 7112852/3811308/3814905
www.kpt-group.com - [email protected]
GREECE
B.E.S.T. HELLAS S.A.
O.T. 48A T.O. 230 - C.P. 570 22, Industrial Area - Thessaloniki TURKEY
Tel. (+30) 2310 796456 - Fax (+30) 2310 795903 BONFIGLIOLI TURKIYE HEADQUARTERS
www.bonfiglioli.gr - [email protected] Atatürk Organíze Sanayi Bölgesi, 10015 Sk. No: 17, Çigli - Izmir BONFIGLIOLI RIDUTTORI S.p.A.
Tel. +90 (0) 232 328 22 77 (pbx) - Fax +90 (0) 232 328 04 14 Via Giovanni XXIII, 7/A
HOLLAND www.bonfiglioli.com.tr - [email protected] 40012 Lippo di Calderara di Reno
ELSTO AANDRIJFTECHNIEK
Bologna (ITALY)
Loosterweg, 7 - 2215 TL Voorhout
Tel. (+31) 252 219 123 - Fax (+31) 252 231 660 USA Tel. (+39) 051 6473111
www.elsto.nl - [email protected] BONFIGLIOLI USA, INC. Fax (+39) 051 6473126
3541 Hargrave Drive Hebron, Kentucky 41048 www.bonfiglioli.com
HUNGARY Tel. (+1) 859 334 3333 - Fax (+1) 859 334 8888 [email protected]
AGISYS AGITATORS & TRANSMISSIONS Ltd www.bonfiglioliusa.com
2045 Törökbálint, Tö u.2. (Hungary) [email protected] - [email protected] SPARE PARTS BONFIGLIOLI
Tel. (+36) 23 50 11 50 - Fax (+36) 23 50 11 59 B.R.T.
www.agisys.hu - [email protected] Via Castagnini, 2-4
VENEZUELA Z.I. Bargellino - 40012
INDIA
BONFIGLIOLI TRANSMISSIONS PVT Ltd. MAICA SOLUCIONES TECNICAS C.A. Calderara di Reno - Bologna (ITALY)
PLOT AC7-AC11 Sidco Industrial Estate - Thirumudivakkam - Chennai 600 044 Calle 3B - Edif. Comindu - Planta Baja Tel. (+39) 051 727844
Tel. +91(0) 44 24781035 / 24781036 / 24781037 Local B - La Urbina - Caracas 1070 Fax (+39) 051 727066
Fax +91(0) 44 24780091 / 24781904 Tel. (+58) 212 2413570 / 2425268 / 2418263 www.brtbonfiglioliricambi.it
wWWBONFIGLIOLIINDIACOM - INFO BONFIGLIOLIIN.com Fax (+58) 212 2424552 - Tlx 24780 Maica V - [email protected] [email protected]
PHOTOVOLTAIC SOLUTIONS
RPS TL
www.bonfiglioli.com